SS-1 SERVICE SINK SEE PLANS 3 2 3/4 3/4 3 3 3
<br />TMV-1
<br />MASTER
<br />THERMOSTATIC MIXING
<br />VALVE
<br />ROOF - - - - - - -LEONARD MODEL TM-2020B-3PS-LF. SEE DETAIL-5/ R1-P9.6 FOR DETAIL, SET AT 140 DEG-F OUTLET HW TEMP. PROVIDE WITH APPROVED SEISMIC BRACING.
<br />INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
<br />WC-1 WATER CLOSET SEE PLANS 3 2 3/4 - 3 2.5 -AMERICAN STANDARD AFWALL 3351.511 (IAPMO #0677) WALL-MOUNTED ELONGATED WITH TOP-SPUD INLET, ADA COMPLIANT, 1.1 GPF SELECTRONIC FLUSH VALVE,
<br />BATTERY POWERED SENSOR ACTIVATED, SEAT: OPEN FRONT LESS COVER, CARRIER: JR SMITH 210Y.
<br />WC-2 WATER CLOSET,
<br />PUBLIC, ADA SEE PLANS 4 2 1-1/2 - 4 5 -SAME AS WC-1 EXCEPT INSTALLED PER ADA REQUIREMENTS.
<br />L-1 LAVATORY SEE PLANS 2 2 1/2 1/2 1 1 1
<br />AMERICAN STANDARD LUCERNE 0356.421 (IAPMO #0677), WALL HUNG WITH CONCEALED ARMS SUPPORT, FRONT OVERFLOW, ADA COMPLIANT, FAUCET: SLOAN
<br />OPTIMA "SOLIS" MODEL EAF-275-ISM, SOLAR POWERED BATTERY BACK-UP SENSOR ACTIVATED ELECTRONIC FAUCET WITH INTEGRAL SPOUT TEMP. MIXER, 0.35
<br />GPM FLOW (IAPMO #4567).
<br />L-2 LAVATORY, PUBLIC,
<br />ADA SEE PLANS 2 2 1/2 1/2 1 1 1 SAME AS L-1 EXCEPT INSTALLED PER ADA REQUIREMENTS.
<br />TP-1 TRAP PRIMER SEE PLANS - - - - - - -MIFAB MR-500 UPC LISTED, ACTIVATE AT 3 PSI PRESS. DROP, WITH FILTER SCREEN, BUILT-IN AIR GAP FITTING, PIPE DISTRIBUTION SYSTEM TO 6 DRAIN TRAPS.
<br />PROVIDE WITH ACCESS PANEL TO SERVE ALL FD, FS, AND INDIRECT DRAINS. INSTALL PER MFR'S. RECOMMENDATIONS.
<br />TP-2 TRAP PRIMER SEE PLANS - - - - - - -ZURN Z1020-CW-DU4 IAPMO #4864, FLUSH MOUNTED TO WALL WITH VANDAL-PROOF STAINLESS STEEL COVER. COORDINATE 120V POWER REQUIREMENTS WITH
<br />ELECTRICAL CONTR. INSTALL PER MFR'S. RECOMMENDATIONS. PROVIDE WHA-1 AS REQUIRED.
<br />WHA-A WATER HAMMER
<br />ARRESTER SEE PLANS - - - - - - - PPP SC SERIES, INSTALL SIZES PER MANUFACTURER'S RECOMEMNDATIONS. PROVIDE WITH ACCESS PANEL. COORDINATE LOCATION WITH ARCHITECT.
<br />FD-1 FLOOR DRAIN SEE PLANS 2 2 - - - - - MIFAB F1000-S UPC LISTED, WITH 6"X6" STAINLESS STEEL RECTANGULAR HEAVY-DUTY VANDAL-RESISTANT STRAINER AND TRAP PRIMER CONNECTION.
<br />OD-1 ROOF DRAIN
<br />OVERFLOW SEE PLANS - - - - - - - JR SMITH FIG. 1010, CAST IRON VANDAL PROOF LOW PROFILE DOME WITH WATER DAM 2" HIGHER THAN FINISH ROOF LEVEL, UNDERDECK CLAMP.
<br />PD-1 PLANTER DRAINS SEE PLANS 3 - - - - - - JR SMITH 2671 WITH STAINLESS STEEL SCREEN, FLITER FABRIC, 12"x12"x12" GRAVEL AROUND.
<br />TD-1 TRENCH DRAINS SEE PLANS 3 - - - - - - ACO KS100S KLASSIKDRAIN WITH ADA GRATE TYPE 478Q - DUCTILE IRON, HEEL PROOF, CLASS E. SEE PLANS FOR PIPE OUTLET SIZE.
<br />AD-1 AREA DRAINS SEE PLANS - - - - - - - JR SMITH FIG. 1470, VANDAL PROOF GRATE, UNDERDECK CLAMP. COORDINATE COLOR FINISH WITH ARCHITECT. SEE FLOOR PLANS FOR OUTLET SIZE.
<br />FS-1 FLOOR SINK SEE PLANS 2 2 - - - - - JR SMITH 3101 WITH OUTLET SAME AS PIPE SIZE, 1/2 GRATE, SEDIMENT BUCKET.
<br />RR-1 ROOF RECEPTOR SEE PLANS 2 2 - - - - - JR SMITH FIG. 3980, WITH WATER DAM 2" HIGHER THAN FINISH ROOF.
<br />ED-1 EMERGENCY DRAIN SEE PLANS 2 2 - - - - - MIFAB F1000 WITH HEAVY DUTY TRAFFIC RATED 7" DIA. STAINLESS STEEL STRAINER.
<br />RD-1 ROOF DRAIN SEE PLANS - - - - - - - JR SMITH FIG. 1010, CAST IRON VANDAL PROOF LOW PROFILE DOME, UNDERDECK CLAMP.
<br />OAD-1 OVERFLOW AREA
<br />DRAINS SEE PLANS - - - - - - - SAME AS AD-1 EXCEPT PLACED AT HIGHER ELEVATION.
<br />HB-1 HOSE BIB SEE PLANS - - 3/4 - - 2.5/1 - ARROWHEAD 353-LF-BFP-LK. PROVIDE ACCESSIBLE SOV UPSTREAM OF EACH HB.
<br />ES-1 EYEWASH STATION SEE PLANS - - 3/4 - - - - HAWS MODEL 7460, 5 GPM
<br />NOTES:
<br />1. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT FIXTURE SPECS., LOCATIONS, ADDITIONAL INSTRUCTIONS, AND COLOR FINISHES.
<br />2. INSTALL ALL ITEMS PER MANUFACTURER'S RECOMMENDATIONS.
<br />3. PROVIDE ACCESSIBLE WHA-1 TO ALL QUICK CLOSING VALVES, INCLUDING DISHWASHERS, FLUSH VALVES, ETC.
<br />4. COORDINATE ACC (ACCESS CODE COLLABORATION) REQUIREMENTS WITH ARCHITECT.
<br />PLUMBING FIXTURES SCHEDULE (RES. BLDG.)
<br />MARK
<br />NO.DESCRIPTION LOCATION
<br />MIN. ROUGH-IN CONN. (INCHES)
<br />SS (DFU)CW
<br />(WSFU)
<br />HW
<br />(WSFU)REMARKS
<br />SS V CW HW
<br />SP-1,2 SUMP PUMP, DUPLEX
<br />SYSTEM 2 BASEMENT
<br />2 HP (1
<br />HP EACH)- 3450 460 3 50 GPM EACH 61' --WEIL 2442-3450
<br />DUPLEX SUBMERSIBLE TYPE, WITH AUTOCOUPLING GUIDE RAIL CONFIGURATION 2613 REMOVAL, CONTROL PANEL,
<br />ALTERNATOR, CONTROL TRANSFORMER, STARTER, INTRIST. SWITCH RELAY, AUDIO/VISUAL ALARM. COORD. ELECT.
<br />RQMTS. WITH ELECT. CONTR. AND MONITORING WITH BMS CONTR. INSTALL PER MFR'S RECOMMENDATIONS.
<br />NOTES:
<br />1. INSTALL ALL UNITS PER MANUFACTURER'S RECOMMENDATIONS.
<br />2. PROVIDE APPROVED SEISMIC BRACING, 6"H HOUSE-KEEPING PAD.
<br />3. COORDINATE POWER REQUIREMENTS WITH ELECTRICAL CONTRACTOR PRIOR TO START OF WORK.
<br />4. COORDINATE BMS MONITORING WITH BMS CONTRACTOR PRIOR TO START OF WORK.
<br />5. PROVIDE LISTED MANUFACTURER OR EQUAL.
<br />CP-L06
<br />ZONED INLINE
<br />CIRCULATING PUMP,
<br />FOR EWH-L06
<br />1 LEVEL-06 0.75 - - 115 1 17 GPM 48' - - BELL & GOSSETT ECOCIRCL-XL-65-130
<br />ALL BRONZE LEAD-FREE CONSTRUCTION, UL AND NSF LISTED, RATED AT 230°F, FOR HOT WATER RETURN, 100% BACK-
<br />UP. PROVIDE SEISMIC BRACING, APPROVED AQUASTAT AND 24 HR/7 DAY TIME CLOCK, WEATHER-PROOF ENCLOSURE ON
<br />ROOF.
<br />WS-1 WATER SOFTENER 1 ROOF -SEE
<br />REMARKS - - -
<br />SALT: 1400
<br />LBS; PEAK
<br />FLOW RATE
<br />PER TANK: 94
<br />GPM
<br />- - AREA: 192”W x 31”D CUSTOM H2O CH7224WS2QPS
<br />WITH CH5030BT
<br />8 AMPS, FOUR OUTLETS NECESSARY ON ONE 20A CIRCUIT, WITH 2" CONTROL VALVE AT EACH TANK, ALTERNATING
<br />FLOW, CONTROLS: FULLY AUTOMATIC FACTORY WIRED FACTORY MOUNTED UNIT, HARDNESS MONITOR, 120 V, WITH
<br />CONTROL PANEL AND ALARM SYSTEM, 2 RESIN TANKS, 1 BRINE TANK, PLUS 4-FT CLEAR IN FRONT, 1-FT CLEAR IN HT.
<br />PROVIDE WITH APPROVED VACUUM RELIEF VALVE, SEISMIC RESTRAINT, AND 6"H HOUSEKEEPING PAD. COORD. ELECT.
<br />RQMTS. WITH ELECT. CONTR. AND MONITORING WITH BMS CONTR. INSTALL PER MFR'S RECOMMENDATIONS. CONTACT
<br />CHRIS MACKNIGHT OF CUSTOM H2O AT PHONE: 714-305-9015.
<br />GI-1 GREASE INTERCEPTOR 1 BASEMENT - - - - - 1500 GAL - - 6' x 11' x 6'H JENSEN PRECAST JP1500G
<br />PROVIDE UPC LISTED, TRAFFIC TYPE, CONCRETE PRECAST WITH BIOCRETE TYPE CONCRETE. COORDINATE LOCATION
<br />AND DEPTH WITH STRUCTURAL ENGINEER. PROVIDE WITH TRAFFIC TYPE SAMPLING BOX. INSTALL PER
<br />MANUFACTURER'S INSTRUCTIONS AND RECOMMENDATIONS.
<br />SE-1,2 SEWAGE EJECTOR
<br />DUPLEX SYSTEM 2 BASEMENT
<br />15 HP (7.5
<br />HP EACH)- 1750 460 3 300 GPM EACH 43' - - HOMA AMS434-200/7,5T/C
<br />FM
<br />DUPLEX SUBMERSIBLE TYPE, EXPLOSION PROOF MOTOR, WITH AUTOCOUPLING GUIDE RAIL CONFIGURATION 2613
<br />REMOVAL, CONTROL PANEL, ALTERNATOR, CONTROL TRANSFORMER, STARTER, INTRIST. SWITCH RELAY, AUDIO/VISUAL
<br />ALARM. COORD. ELECT. RQMTS. WITH ELECT. CONTR. AND MONITORING WITH BMS CONTR. INSTALL PER MFR'S
<br />RECOMMENDATIONS.
<br />CWM-1 COLD WATER METER 1
<br />SEE DETAILS
<br />ON R1-P9.4
<br />FOR
<br />LOCATIONS
<br />- - - - - 1" - - - BADGER
<br />E-SERIES G2®
<br />ULTRASONIC INLINE
<br />METERS
<br />WITH BMS REMOTE MONITORING. COORDINATE WITH BMS CONTRACTOR FOR MONITORING PRIOR TO START OF WORK.
<br />HWM-1 COLD WATER METER 1
<br />SEE DETAILS
<br />ON R1-P9.4
<br />FOR
<br />LOCATIONS
<br />- - - - - 1" - - - BADGER
<br />E-SERIES G2®
<br />ULTRASONIC INLINE
<br />METERS
<br />WITH BMS REMOTE MONITORING. COORDINATE WITH BMS CONTRACTOR FOR MONITORING PRIOR TO START OF WORK.
<br />FCS-1
<br />DOM. WATER
<br />BACKFLOW
<br />PREVENTER FLOOD
<br />CONTROL
<br />1 LEVEL P1 - - - - - - - - - ZURN FCISAST FLOOD
<br />CONTROL SYSTEM
<br />REFER TO CIVIL DRAWINGS FOR BACKFLOW PREVENTER LOCATION AND SPECIFICATIONS. REFER TO ELECTRICAL
<br />DRAWINGS FOR POWER CONNECTION. CONNECT TO BUILDING AUTOMATION SYSTEM AS REQUIRED.
<br />CP-1,2
<br />CIRCULATING PUMP,
<br />DUPLEX FOR
<br />GWH-1,2,3
<br />2 ROOF 0.75 - - 115 1 17 GPM 48' - - BELL & GOSSETT ECOCIRCL-XL-65-130
<br />ALL BRONZE LEAD-FREE CONSTRUCTION, UL AND NSF LISTED, RATED AT 230°F, FOR HOT WATER RETURN, 100% BACK-
<br />UP. PROVIDE SEISMIC BRACING, APPROVED AQUASTAT AND 24 HR/7 DAY TIME CLOCK, WEATHER-PROOF ENCLOSURE ON
<br />ROOF.
<br />CP-L15
<br />ZONED INLINE
<br />CIRCULATING PUMP,
<br />FOR EWH-L15
<br />1 LEVEL-15 0.75 - - 115 1 17 GPM 48' - - BELL & GOSSETT ECOCIRCL-XL-65-130
<br />ALL BRONZE LEAD-FREE CONSTRUCTION, UL AND NSF LISTED, RATED AT 230°F, FOR HOT WATER RETURN, 100% BACK-
<br />UP. PROVIDE SEISMIC BRACING, APPROVED AQUASTAT AND 24 HR/7 DAY TIME CLOCK, WEATHER-PROOF ENCLOSURE ON
<br />ROOF.
<br />EQUIPMENT SCHEDULE (RES. BLDG.)
<br />MARK NO. DESCRIPTION QTY. LOCATION
<br />MOTOR DATA
<br />CAPACITY HEAD
<br />(FT)
<br />OP. WT.
<br />(LBS)DIMENSIONS MAKE MODEL REMARKS
<br />HP KW RPM VOLTS PHASE
<br />© Gensler
<br />Date Description
<br />Project Name
<br />Project Number
<br />Description
<br />Scale
<br />Seal / Signature
<br />2015
<br />NOT FOR
<br />CONSTRUCTION
<br />Tel 949.863.9434
<br />Fax 949-553-1676
<br />4675 MacArthur Court
<br />Suite 100
<br />Newport Beach, CA
<br />92600
<br />USA
<br />Job No.:
<br />Contact:
<br />www.glumac.com
<br />18200 Von Karman Ave., Suite 100
<br />Irvine, CA 92612
<br />T. 949.833.8190
<br />12" = 1'-0"
<br />6/12/2024 7:39:07 PM
<br />BIM 360://007.3757.000 - Caribou Industries - 3rd & Broadway/3RD-B_MEP_WEST_R20.rvt
<br />R1-P0.2
<br />PLUMBING SCHEDULES
<br />21US00608
<br />3rd & Broadway West
<br />1103 North Broadway
<br />Santa Ana, CA 92701
<br />21US00608
<br />TG
<br />1 9/21/2021 REISSUE FOR PLAN CHECK
<br />2 01/18/2022 REISSUE FOR PLAN CHECK
<br />4 06/17/2024 REVISION TO PERMIT
<br />4
<br />EOR: SEAN AGUON
<br />LIC#: M41274
<br />10/11/2024
|