<br />LABEL FACE PLATE
<br />WITH BLACK LETTERS
<br />ON CLEAR VINYL (TYP.)
<br />GREY FACEPLATE
<br />(GAMES FLOOR)
<br />GREEN DEVICE COLOR
<br />(GAMES FLOOR NON
<br />CONTROLLED)
<br />GREY DEVICE COLOR
<br />(GAMES FLOOR
<br />ARCADE CONTROLLED)
<br />FACTORY ETCHED SYMBOL
<br />FOR CONTROLLED
<br />RECEPTACLES (NEC 406.3)
<br />CO
<br />N
<br />T
<br />R
<br />O
<br />L
<br />L
<br />E
<br />D
<br />CO
<br />N
<br />T
<br />R
<br />O
<br />L
<br />L
<br />E
<br />D
<br />QUAD (DOUBLE DUPLEX) WITH 24HR AND CONTROLLED
<br />24
<br />H
<br />R
<br />
<br />-
<br />
<br />H
<br />O
<br />U
<br />S
<br />E
<br />K
<br />E
<br />E
<br />P
<br />I
<br />N
<br />G
<br />LABEL FACE PLATE
<br />WITH BLACK LETTERS
<br />ON CLEAR VINYL (TYP.)
<br />GREY FACEPLATE
<br />(GAMES FLOOR)
<br />GREEN DEVICE COLOR
<br />(GAMES FLOOR NON
<br />CONTROLLED)
<br />DUPLEX 24HR - HOUSEKEEPING
<br />ARCADE
<br />GREY FACEPLATE
<br />(GAMES FLOOR)
<br />GREY DEVICE COLOR
<br />(GAMES FLOOR
<br />ARCADE CONTROLLED)
<br />FACTORY ETCHED SYMBOL
<br />FOR CONTROLLED
<br />RECEPTACLES (NEC 406.3)
<br />CO
<br />N
<br />T
<br />R
<br />O
<br />L
<br />L
<br />E
<br />D
<br />CO
<br />N
<br />T
<br />R
<br />O
<br />L
<br />L
<br />E
<br />D
<br />QUAD (DOUBLE DUPLEX) ALL CONTROLLED
<br />CO
<br />N
<br />T
<br />R
<br />O
<br />L
<br />L
<br />E
<br />D
<br />CO
<br />N
<br />T
<br />R
<br />O
<br />L
<br />L
<br />E
<br />D
<br />LABEL FACE PLATE
<br />WITH BLACK LETTERS
<br />ON CLEAR VINYL (TYP.)
<br />X-XX
<br />CIRCUIT NUMBER
<br />X-XX X-XX
<br />CIRCUIT NUMBER (TYP.)
<br />X-XX
<br />CIRCUIT NUMBER
<br />ELECTRICAL SYMBOL LEGEND
<br />SYMBOL DESCRIPTION NOTESMFG. DATA
<br />AC
<br />WP
<br />EWC
<br />CS
<br />J
<br />S
<br />S
<br />WEATHER PROOF GFI RECEPTACLE SEE SPECS
<br />T
<br />WFS
<br />S
<br />DD
<br />D
<br />S
<br />S
<br />S
<br />SEE PLANS
<br />FUSIBLE DISCONNECT SWITCH SEE PLANS
<br />HOME RUN
<br />SINGLE PHASE MOTOR
<br />THREE PHASE MOTOR
<br />TRANSFORMER
<br />JUNCTION BOX
<br />NONFUSIBLE DISCONNECT SWITCH
<br />PANEL BOARD SURFACE MOUNTED
<br />SEE PLANS
<br />SEE PLANS
<br />SEE PLANS
<br />SEE SPECS
<br />SEE SPECS
<br />SEE SPECS
<br />MT. 18" A.F.F. TO BOTTOM OF BOX, UNLESS NOTED
<br />WATER FLOW SWITCH SEE SPECS
<br />FIRE ALARM SPEAKER/VISUAL DEVICE SEE SPECS
<br />SMOKE DETECTOR
<br />FIRE ALARM CONTROL PANEL
<br />FIRE ALARM VISUAL DEVICE
<br />DUCT SMOKE DETECTOR
<br />SEE SPECS
<br />SEE SPECS
<br />SEE PLANS
<br />SEE SPECS
<br />MT. 88" A.F.F. TO CENTERLINE OF BOX
<br />4 SQUARE BOX WITH SINGLE GANG PLASTER RING AND
<br />3/4" C. TO ACCESSIBLE CEILING.
<br />4 SQUARE BOX WITH SINGLE GANG PLASTER RING AND 3/4" C.
<br />TO ACCESSIBLE CEILING.
<br />DUPLEX RECEPTACLE ISOLATED GROUND
<br />DUPLEX CONVENIENCE OUTLET MTD.
<br />"ABOVE COUNTER"
<br />DATA OUTLET
<br />TELEPHONE OUTLET
<br />SPECIAL RECEPTACLE
<br />SPECIAL CONNECTION (HARDWIRE)
<br />SEE PLANS
<br />SEE PLANS
<br />SEE SPECS
<br />SEE SPECS
<br />OTHERWISE. COORDINATE WITH AV CONTRACTOR
<br />MT. 18" A.F.F. TO BOTTOM OF BOX
<br />OCCUPANCY SENSOR
<br />DUPLEX RECEPTACLE
<br />CONTACTOR
<br />OCCUPANCY SENSOR (WALL MOUNT)
<br />ELECTRIC WATER COOLER RECEPTACLE
<br />GFI PROTECTED DUPLEX RECEPTACLE SEE SPECS
<br />SEE SPECS
<br />SEE SPECS
<br />SEE PLANS
<br />MT. 24" ABOVE FINISH FLOOR
<br />MT. 18" A.F.F. TO BOTTOM OF BOX
<br />LITHONIA #LIRW 120/277 WH
<br />SEE SPECS (FOR SENSORS BELOW)POWER PACK
<br />WALL MOUNTED OCCUPANCY SWITCH
<br />THREE-WAY TOGGLE SWITCH SEE SPECS MT. 46" A.F.F. TO CENTERLINE OF BOX
<br />MT. 46" A.F.F. TO CENTERLINE OF BOX
<br />DUPLEX RECEPTACLE SPLIT WIRED SEE PLANS
<br />MT. 88" A.F.F. TO CENTERLINE OF BOX
<br />MT. 8" ABOVE COUNTER TO BOTTOM OF BOX, UNLESS
<br />NOTED OTHERWISE. SEE CABINET DRAWINGS.
<br />COMBINATION
<br />DATA/TELEPHONE OUTLET
<br />4 SQUARE BOX WITH SINGLE GANG PLASTER RING
<br />AND 3/4" C. TO ACCESSIBLE CEILING.
<br />DOUBLE DUPLEX RECEPTACLE SEE SPECS, NOTE WHERE CONTROLLED THE DEVICE
<br />SHALL HAVE PERMANENT MARKINGS PER NEC 406.3(E)MT. 18" A.F.F. TO BOTTOM OF BOX
<br />FIRE ALARM ANNUNCIATOR PANEL SEE SPECSFAAP
<br />FACP
<br />DIMMER SWITCH SEE 6/E601, COORDINATE TYPE WITH LIGHTING FOR 0-10V MT. 46" A.F.F. TO CENTERLINE OF BOX
<br />PANEL BOARD FLUSH MOUNTED SEE SPECS
<br />TS TAMPER SWITCH (FIRE ALARM)SEE SPECS
<br />NETWORK LIGHITNG CONTROL STATION REFER TO E601 AND CONTROL STATION SCHEDULE
<br />SINGLE POLE TOGGLE SWITCH SEE SPECS MT. 46" A.F.F. TO CENTERLINE OF BOX
<br />SEE SPECS
<br />SEE SPECS
<br />MT. 18" A.F.F. TO BOTTOM OF BOX, UNLESS NOTED
<br />OTHERWISE. COORDINATE WITH AV CONTRACTOR
<br />MT. 18" A.F.F. TO BOTTOM OF BOX, UNLESS NOTED
<br />OTHERWISE. COORDINATE WITH AV CONTRACTOR
<br />WALL MOUNTED SPEAKER SEE PLANS, BY AV CONTRACTOR, E.C. SHALL PROVIDE COORDINATE HEIGHTS WITH AV CONTRACTORSINGLE GANG BOX AND CONDUIT TO ACCESSIBLE CEILING
<br />OR JOIST SPACE
<br />WALL MOUNTED SPEAKER
<br />SEE PLANS, BY AV CONTRACTOR, E.C. SHALL PROVIDE COORDINATE HEIGHTS WITH AV CONTRACTOR
<br />SINGLE GANG BOX AND CONDUIT TO ACCESSIBLE CEILING
<br />OR JOIST SPACE
<br />CEILING MOUNTEDC
<br />AUDIO/VIDEO CONTRACTORAV
<br />PLUMBING CONTRACTORPC
<br />GENERAL CONTRACTORGC
<br />MECHANICAL CONTRACTORMC
<br />ELECTRICAL CONTRACTOREC
<br />OS
<br />OS
<br />PP
<br />X
<br />OS
<br />3
<br />D
<br />PROVIDE COMPLETE WITH POWER PACK RELAYS AS NEEDED
<br />PROVIDE COMPLETE WITH POWER PACK RELAYS AS NEEDED
<br />S FIRE ALARM SPEAKER/VISUAL DEVICE SEE SPECS
<br />LOW VOLTAGE SWITCH SEE 7/E601 MT. 46" A.F.F. TO CENTERLINE OF BOXL
<br />F FIRE ALARM PULL STATION SEE SPECS
<br />FIRE ALARM HEAT DETECTOR SEE SPECSH
<br />GFI BY BREAKER WHERE NOT ACCESSIBLE
<br />C
<br />FLOOR MOUNTEDF
<br />TAMPER RESISTANTTR
<br />AREA DEVICE PLATE
<br />ARCADE/GAME AREA GREY GREY
<br />REDEMPTION SLAT WALLS WHITE WHITE
<br />REDEMPTION GENERAL WHITE WHITE
<br />REDEMPTION CEILING WHITE WHITE
<br />KITCHEN WHITE WHITE
<br />BAR GREY GREY
<br />SNACK BAR WHITE WHITE
<br />GUEST COUNTER WHITE WHITE
<br />ALCOVE GREY GREY
<br />FAMILY TOILET WHITE WHITE
<br />JANITOR WHITE WHITE
<br />WOMEN'S RESTROOM WHITE WHITE
<br />MEN'S RESTROOM GREY GREY
<br />OFFICE GREY GREY
<br />EMPLOYEE LOUNGE GREY GREY
<br />SAFE ROOM GREY GREY
<br />KAROKE/PARTY ROOMS GREY GREY
<br />BILLIARDS AREA GREY GREY
<br />VESTIBULE GREY GREY
<br />STORAGE ROOMS GREY GREY
<br />MECHANICS ROOM GREY GREY
<br />WITHIN STRUCTURAL CEILING BLACK BLACK
<br />BUS CORD DROP BLACK BLACK
<br />OUTLETS IN TOE KICK BLACK BLACK
<br />A. ELECTRICAL ORDINANCES: ALL ELECTRICAL WORK SHALL BE INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF THE LATEST
<br />EDITION OF THE NATIONAL ELECTRICAL CODE AND FEDERAL LAWS OR ORDINANCES GOVERNING THE PROJECT. IF, IN ANY INSTANCE, THE
<br />PLANS AND SPECIFICATIONS ARE IN DIRECT CONFLICT WITH SUCH CODES, LAWS OR ORDINANCES, THE CODE, LAWS AND ORDINANCES
<br />SHALL HAVE JURISDICTION AND THE WORK IN QUESTION SHALL BE INSTALLED ACCORDING TO THE CODES, LAWS AND ORDINANCES. ALL
<br />WORK SHALL BE INSTALLED UNDER THE SUPERVISION OF A LICENSED MASTER ELECTRICIAN.
<br />B. BRING ALL DISCREPANCIES SHOWN ON DIFFERENT DRAWINGS AND BETWEEN DRAWINGS AND SPECIFICATIONS OR BETWEEN
<br />DOCUMENTS AND FIELD CONDITIONS TO THE IMMEDIATE ATTENTION OF THE ARCHITECT.
<br />C. COORDINATE ELECTRICAL INSTALLATION WITH ALL OTHER CONTRACTORS AND OWNER FOR THE LOCATION AND SIZES OF ALL
<br />EQUIPMENT PRIOR TO ROUGH-IN. SHOULD ELECTRICAL WORK BE INSTALLED WHICH INTERFERES WITH THE WORK OF OTHER
<br />CONTRACTORS OR OWNER, SUCH WORK SHALL BE CHANGED WITH NO ADDITIONAL COST TO OWNER.
<br />D. MOUNT EQUIPMENT AT NOMINAL MOUNTING HEIGHT INDICATED IN ELECTRICAL SYMBOL SCHEDULE UNLESS NOTED OTHERWISE ON THE
<br />FLOOR PLANS OR DETAILED IN ARCHITECTURAL ELEVATIONS. DIMENSION SHOWN IS TO CENTER LINE OF BOX. SEE ARCHITECTURAL
<br />INTERIOR AND EXTERIOR ELEVATIONS FOR EXACT LOCATION OF WALL MOUNTED DEVICES AND LIGHT FIXTURES.
<br />E. ALL CONDUCTORS SHALL BE COPPER, UNLESS SPECIFIED OTHERWISE. BUILDING POWER WIRING SHALL HAVE THHN/THWN INSULATION.
<br />CONDUCTOR AMPACITY SHALL BE BASED ON TABLE 310-16 OF THE NEC. USE 60-DEGREE C RATING FOR CIRCUITS TERMINATING ON
<br />DEVICES RATED 100A AND BELOW. USE 75-DEGREE RATING FOR CIRCUITS TERMINATING ON DEVICES AND IN ENCLOSURES RATED OVER
<br />100a.
<br />F. INSTALL INSULATED GREEN EQUIPMENT GROUNDING CONDUCTOR WITH ALL BRANCH CIRCUIT AND FEEDER CONDUCTORS, SIZED IN
<br />ACCORDANCE WITH NEC ARTICLE 250.
<br />G. DRAWINGS INDICATE DESIGN LOADS, VOLTAGES, CORRESPONDING CONTROL EQUIPMENT, FEEDERS AND OVER CURRENT DEVICES. IF
<br />EQUIPMENT ACTUALLY FURNISHED HAVE LOADS OTHER THAN THOSE INDICATED ON THE DRAWINGS OR SPECIFIED HEREIN, CONTROL
<br />EQUIPMENT, FEEDERS AND OVER CURRENT DEVICES SHALL BE ADJUSTED IN SIZE ACCORDINGLY AT NO ADDITIONAL COST TO THE OWNER.
<br />SUCH ADJUSTMENT SHALL BE SUBJECT TO THE REVIEW OF THE ARCHITECT PRIOR TO ACCEPTANCE OR PURCHASE.
<br />H. IN GENERAL, BRANCH CIRCUIT CONDUIT AND WIRE IS NOT SHOWN. PROVIDE CONDUIT AND WIRE TO CONNECT DEVICES TO CIRCUITS
<br />SHOWN. WIRE FILL AND CONDUCTOR SIZE SHALL BE AS SPECIFIED. PROVIDE A MAXIMUM OF THREE PHASE CONDUCTORS IN A SINGLE
<br />HOME RUN. PROVIDE A DEDICATED NEUTRAL FOR EACH PHASE CONDUCTOR UNLESS OTHERWISE NOTED. INSTALL PULL BOXES AND
<br />JUNCTION BOXES AS REQUIRED TO AID IN THE INSTALLATION OF CABLES AND CONDUCTORS. LABEL LOCATION OF POWER CIRCUITS ON
<br />COVER OF ALL RECEPTACLES AND ON COVER OF JUNCTION BOXES AND BOXES ASSOCIATED WITH EQUIPMENT. INCLUDE PANEL AND
<br />CIRCUIT IDENTIFICATION. LABEL LOCATION OF POWER CIRCUITS ON COVER OF ALL LIGHT SWITCHES. INCLUDE PANEL AND CIRCUIT
<br />IDENTIFICATION.
<br />I. PROVIDE MINIMUM #12 AWG CONDUCTORS FOR HOMERUNS, #10 AWG CONDUCTORS FOR HOMERUNS THAT EXCEED 100 FEET FOR 120
<br />VOLT CIRCUITS AND 250 FEET FOR 277 VOLT CIRCUITS. HOMERUNS SHALL BE CONSIDERED TO ORIGINATE FROM THE POWER SOURCE TO
<br />THE FIRST PIECE OF EQUIPMENT OR DEVICE.
<br />J. SEE ARCHITECTURAL REFLECTED CEILING PLANS FOR FINAL LOCATION OF CEILING MOUNTED EQUIPMENT. MOUNT RECESSED CEILING
<br />FIXTURES WITH FLEXIBLE METAL CONDUIT OF LENGTH REQUIRED TO MEET MOUNTING LOCATION AND NEC REQUIREMENTS. MAXIMUM
<br />FLEXIBLE CONDUIT LENGTH SHALL BE (6') SIX FEET.
<br />K. NOT USED
<br />L. THE ELECTRICAL CONTRACTOR SHALL INSTALL ALL ITEMS NECESSARY TO COMPLETE THE INSTALLATION. THIS CONTRACTOR SHALL
<br />TOUCH-UP OR REFINISH THE FACTORY FINISH OF EQUIPMENT MARRED DURING SHIPMENT, DEMOLITION OR INSTALLATION.
<br />M. ELECTRICAL WORK SHALL NOT INTERFERE WITH CLEARANCES REQUIRED FOR GENERAL AND MECHANICAL CONSTRUCTION.
<br />N. ELECTRICAL CONTRACTOR SHALL SUBMIT SHOP DRAWINGS OF ALL NEW EQUIPMENT, DEVICES, FIXTURES AND CABLES/CONDUCTORS
<br />TO BE INSTALLED IN SYSTEM FOR WRITTEN APPROVAL FROM ENGINEER PRIOR TO INSTALLATION. REFER TO SPECIFICATIONS FOR
<br />ADDITIONAL SUBMITTAL REQUIREMENTS.
<br />O. ALL WORK SHALL BE GUARANTEED FREE FROM DEFECTS FOR A PERIOD OF ONE YEAR FROM DATE OF FINAL ACCEPTANCE.
<br />P. UNLESS NOTED OTHERWISE WITHIN THE DOCUMENTS MOUNTING HEIGHTS FOR ITEMS IN THE ARCADE/OPEN STRUCTURE AREA SHALL
<br />BE AS FOLLOWS TO BOTTOM.
<br />CABLE TRAY: 12'-6" A.F.F.(IN AREAS OF CONFLICT TRAY SHALL BE ROUTED UP OR DOWN AND PAST OBSTRUCTION IN LOCATION OF
<br />OBSTRUCTION ONLY)
<br />POWER BUS: 12'-0" A.F.F.
<br />GENERAL LIGHTING: 12'-0" A.F.F.
<br />ELECTRICAL DEVICE
<br />COLOR SCHEDULE
<br />GENERAL ELECTRICAL NOTES
<br />WALL MOUNTED OCCUPANCY/VACANCY SWITCH
<br />WITH 0-10V DIMMINGOSD SENSOR SWITCH WSX-D-SA MT. 46" A.F.F. TO CENTERLINE OF BOX
<br />1. EMT (ELECTRIC METALIC TUBING) SHALL BE USED IN ALL DEMISING WALLS, HOME RUNS, AND BETWEEN JUNCTION BOXES AND PULL
<br />BOXES. MC CABLE MAY BE USED IN OTHER APPLICATIONS AS ALLOWED BY THE AHJ. ALL EXPOSED CONDUIT, RIDID, OR MC CABLE, SHALL
<br />BE INSTALLED IN TIGHT STRAIGHT LINES, PARALLEL OR IN RIGHT ANGLES TO BUILDING STRUCTURE. DO NOT LOOP EXCESS MC CABLE IN
<br />CEILING SPACE OR WALL CAVITY.
<br />2. UPON COMPLETION E.C. SHALL MEASURE PHASE LOADS AND ADUST TO BE BALLANCE WITHIN 10%. UPDATE ALL CIRCUIT DIRECTORIES,
<br />AS BUILTS AND LABELING AS A RESULT OF THIS PROCESS.
<br />3. NOTHING IS PERMITTED TO BE ATTACHED TO, SUSPENDED FROM, OR PENETRATE LANDLORDS STRUCTURE, FLOOR DECK, OR ROOF
<br />DECK. YOU MAY ATTACH, NON-DESTRUCTIVELY, TO OR SUSPEND FROM THE TOP CHORD OF THE JOISTS OR THE STRUCTURAL STEEL WHICH
<br />EXISTS ABOVE THE TENANT SPACE. WHEN ATTACHING TO LANDLORD'S STRUCTURE, DO NOT DRILL, WELD, SCREW, OR SHOOT INTO
<br />STRUCTURE. ALTERNTIVE METHODS OF ATTACHEMENT ONLY, NOTHING TO DAMAGE LANDLORD'S BASE BUILDING STRUCTURE. TENANT
<br />SHALL PROVIDE SIGNED SEALED STRUCTURAL DRAWINGS BY A STRUCTURAL ENGINEER WITH LEGALLY ACTIVE REGISTRATION AS
<br />INDICATED BY ALL JURISDICTIONAL REQUIREMENTS, FOR ALL STRUCTURAL MODIFICATIONS FOR LANDLORD RECORDS.
<br />4. ELEVATED SLABS: TENANT'S GENERAL CONTRACTOR SHALL ADVISE THE OPERATIONS TEAM PRIOR TO ANY SLAB MODIFICATION OR
<br />REMOVAL. IF ANY ELEVATED SLAB IS TO BE MODIFIED IN ANYWAY (DRILLED, CORED, OR PENETRATED), TENANT SHALL PROVIDE STAMPED
<br />AND CERTIFIED DRAWINGS BY A LICENSED STRUCTURAL ENGINEER CERTIFIED IN THE LOCAL JURISDICTION. ALL PENETRATIONS SHALL BE
<br />CORE BORED ONLY. SAW CUTTING, JACK HAMMERING, AND TRENCHING IS STRICTLY PROHIBITED. ALL PENETRATIONS SHALL BE SLEEVED,
<br />SEALED, FIRE STOPPED AND WATERPROOFED. THE PENETRATION SLEEVE SHALL EXTEND A MINIMUM OF 4" ON EITHER SIDE OF THE SLAB
<br />AND BE LABELED WIT HTHE REQURED NFPA RATING. TENANT GC SHALL VERIFY THAT WORKS SHALL NOT CONFLICT WITH ANY EXISTING
<br />STRUCTURAL, UTILITY, OR OTHER UNDER-SLAB CONDITION. (NONDESTRUCTIVE VERIFICATION MAYBE REQURED.) ANY DAMAGE OF
<br />DOWNTIME CAUSED BY TENANT'S WORK SHALL BE REPAIRED AND REIMBURSED AT CONTRACTOR'S EXPENSE.
<br />ADDITIONAL GENERAL LANDLORD REQURIREMENTS
<br />12/9/2024 4:08:53 PM
<br />2309147GR
<br />ROUND1
<br />BOWLING AND
<br />AMUSEMENT
<br />2800 N. MAIN ST. SUITE 1100
<br />SANTA ANA, CA 92705
<br />ROUND 1
<br />ENTERTAINMENT
<br />3070 SATURN ST. STE. 200
<br />BREA, CA 92821
<br />ELECTRICAL GENERAL
<br />INFORMATION
<br />E-001
<br />MAINPLACE
<br />MALL
<br />REMODEL
<br />CLIENT
<br />ARCHITECTS
<br />PARADIGM
<br />415 Leonard Street NW, Suite 200
<br />Grand Rapids, MI 49504
<br />(616) 785-5656
<br />www.paradigmae.com
<br />Grand Rapids | Phoenix | Traverse City
<br />DESIGN
<br />ENGINEERS|
<br />DATE DESCRIPTION
<br />RELEASE DATE
<br />SHEET
<br />PROJECT
<br />PROJECT
<br />12-09-24 Permits
<br />SCALE:1/4" = 1'-0"E-001
<br />GAME FLOOR CONTROLLED/NON-CONTROLLED RECEPTACLES1
|