CONTACTOR FOR ARCADE EQUIPMENT MANUAL SHUTDOWN FROM <br />CONTROL STATION AND AUTOMATIC SHUT DOWN AND RESET FROM <br />FIRE ALARM SYSTEM. <br />PLUG IN UNITS SHALL HAVE 1P20A BREAKER AND 18' CORD DROP WITH <br />STRAIN RELIEF ON EACH END AND CONNECTED TO A TWO GANG BOX <br />WITH DOUBLE DUPLEX RECEPTACLE. E.C. SHALL INITIALLY INSTALL <br />THESE PLUG IN UNITS AT THE DIRECTION OF THE OWNER FOR INITIAL <br />ARCADE MACHINE LAYOUT. BUSWAY AND DROPS FURNISHED BY <br />OTHERS AND INSTALLED BY E.C. <br />ONE LINE DIAGRAM NOTES <br />1 <br />2 <br />3 <br />4 <br />5 <br />6 E.C. SHALL FURNISH AND INSTALL SURGE SUPPRESSOR FOR THIS <br />PANEL EQUAL SQUARE D HMA TVS2HWA10X. MOUNT AS CLOSE TO <br />PANEL AS POSSIBLE AND UTILIZE (5) #10, 3/4"C FOR CONNECTION TO <br />BREAKER AS SHOWN. (100KA 208V-4W) <br />EXISTING MAIN DISTRIBUTION SWITCHBOARD "MDB" <br />1200A MAIN FUSED SWITCH <br />3P <br />6 <br />0 <br />A <br />PROVIDE CONTACTOR AND WIRE TO RELAY SHOWN FOR CONTROL OF <br />POWER TO MONITOR CIRCUITS. <br />NOTE: ALL EQUIPMENT AND WIRING IS NEW UNLESS SPECIFICALLY <br />NOTED AS EXISTING. <br />PROVIDE BREAKER LOCK FOR TRANSFORMER, PROVIDE LABEL ON <br />TRANSFORMER NOTING LOCATION OF DISCONNECT, (SEE NEC 450.14) <br />3P <br />1 <br />0 <br />0 <br />A <br />EXISTING LANDLOARD <br />SWITCHBOARD <br />480Y/277V-3Ø-4W 4000A <br />EXISTING <br />TO EXISTING UTILITY <br />TRANSFORMER <br />MM <br />3P1200A <br />GFI <br />3P600A <br />3P4000A <br />GFI <br />(ERMS) <br />SUITE 1100 <br />(ROUND 1) <br />SUITE 1140 <br />(ROUND 1- <br />EXPANSION) <br />EXISTING SECTION EXISTING SECTIONEXISTING SECTION <br />EXISTING 45 KVA <br />TRANSFORMER <br />480V-3Ø PRIMARY <br />208Y/120V-3Ø-4W <br />SECONDARY <br />EXISTING <br />PANEL "LP2" <br />EX <br />I <br />S <br />T <br />I <br />N <br />G <br />3P <br />2 <br />0 <br />0 <br />A <br />EXISTING 150 KVA <br />TRANSFORMER <br />480V-3Ø PRIMARY <br />208Y/120V-3Ø-4W <br />SECONDARY <br />EXISTING <br />PANEL <br />"DLP2A" <br />EX <br />I <br />S <br />T <br />I <br />N <br />G <br />EX <br />I <br />S <br />T <br />I <br />N <br />G <br />EX <br />I <br />S <br />T <br />I <br />N <br />G <br />EXISTING <br />PANEL <br />"LP1" <br />EXISTING <br />PANEL <br />"DLP2B" <br />EXISTING <br />PANEL <br />"DLP2C" <br />EXISTING <br />PANEL <br />"DLP2D" <br />EXISTING <br />PANEL <br />"DLP2E" <br />EXISTING <br />PANEL <br />"HL" <br />3P <br />1 <br />0 <br />0 <br />A <br />EXISTING <br />PANEL <br />"HK" <br />3P <br />6 <br />0 <br />A <br />EXISTING 45 KVA <br />TRANSFORMER <br />480V-3Ø PRIMARY <br />208Y/120V-3Ø-4W <br />SECONDARY <br />EXISTING <br />PANEL <br />"BS" <br />EX <br />I <br />S <br />T <br />I <br />N <br />G <br />EX <br />I <br />S <br />T <br />I <br />N <br />G <br />3P <br />2 <br />0 <br />0 <br />A <br />EXISTING 150 KVA <br />TRANSFORMER <br />480V-3Ø PRIMARY <br />208Y/120V-3Ø-4W <br />SECONDARY <br />EXISTING <br />PANEL <br />"DLP1" <br />EX <br />I <br />S <br />T <br />I <br />N <br />G <br />EX <br />I <br />S <br />T <br />I <br />N <br />G <br />EXISTING <br />PANEL <br />"LP4" <br />EXISTING <br />PANEL <br />"LK1" <br />EXISTING <br />PANEL <br />"LP2" <br />3P <br />1 <br />0 <br />0 <br />A <br />EXISTING 75 KVA <br />TRANSFORMER <br />480V-3Ø PRIMARY <br />208Y/120V-3Ø-4W <br />SECONDARY <br />EXISTING <br />PANEL <br />"GS1" <br />EX <br />I <br />S <br />T <br />I <br />N <br />G <br />EX <br />I <br />S <br />T <br />I <br />N <br />G <br />3P <br />6 <br />0 <br />A <br />EXISTING 45 KVA <br />TRANSFORMER <br />480V-3Ø PRIMARY <br />208Y/120V-3Ø-4W <br />SECONDARY <br />EXISTING <br />PANEL <br />"LP3" <br />EX <br />I <br />S <br />T <br />I <br />N <br />G <br />EX <br />I <br />S <br />T <br />I <br />N <br />G <br />3P <br />2 <br />0 <br />0 <br />A <br />EXISTING <br />PANEL <br />"AC" <br />3P <br />1 <br />2 <br />5 <br />A <br />EXISTING <br />RTU-3 <br />3P <br />6 <br />0 <br />A <br />EXISTING 45 KVA <br />TRANSFORMER <br />480V-3Ø PRIMARY <br />208Y/120V-3Ø-4W <br />SECONDARY <br />EXISTING <br />PANEL <br />"GS2" <br />EX <br />I <br />S <br />T <br />I <br />N <br />G <br />EX <br />I <br />S <br />T <br />I <br />N <br />G <br />NEW 30 KVA <br />TRANSFORMER "T-BUS A" <br />480V-3Ø PRIMARY <br />208Y/120V-3Ø-4W <br />SECONDARY <br />NEW (4) #1, <br />(1) #6GND., <br />1-1/2"C. <br />(3 <br />) <br /> <br /># <br />6 <br />, <br /> <br />( <br />1 <br />) <br /> <br /># <br />1 <br />0 <br /> <br />G <br />N <br />D <br />. <br />, <br /> <br />1 <br />- <br />1 <br />/ <br />4 <br />" <br />C <br />. <br />4 <br />NEW 3P100A <br />FUSED <br />DISCONNECT <br />(100A FUSES) <br />C <br />3P100A <br />1 <br />TIE INTO EXISTING <br />ARCADE POWER FOR <br />CONTROL OF NEW <br />CONTACTOR (FIELD <br />VERIFY CONNECTION) <br />NEW (4) #1, <br />(1) #6GND., <br />1-1/2"C. <br />NEW (4) #1, <br />(1) #6GND., <br />1-1/2"C. <br />PO <br />W <br />E <br />R <br /> <br />B <br />U <br />S <br /> <br />" <br />A <br />" <br /> <br />S <br />E <br />C <br />T <br />I <br />O <br />N <br /> <br />1 <br />NE <br />W <br />PO <br />W <br />E <br />R <br /> <br />B <br />U <br />S <br /> <br />" <br />A <br />" <br /> <br />S <br />E <br />C <br />T <br />I <br />O <br />N <br /> <br />2 <br />NE <br />W <br />PO <br />W <br />E <br />R <br /> <br />B <br />U <br />S <br /> <br />" <br />A <br /> <br />S <br />E <br />C <br />T <br />I <br />O <br />N <br /> <br />3 <br />NE <br />W <br />NEW (4) #1, <br />(1) #6GND., <br />1-1/2"C. (TYP. BETWEEN BUS) <br />PO <br />W <br />E <br />R <br /> <br />B <br />U <br />S <br /> <br />" <br />A <br /> <br />S <br />E <br />C <br />T <br />I <br />O <br />N <br /> <br />4 <br />NE <br />W <br />NE <br />W <br /> <br />3 <br />P <br />5 <br />0 <br />A <br />NEW 30 KVA <br />TRANSFORMER "T-BUS B" <br />480V-3Ø PRIMARY <br />208Y/120V-3Ø-4W <br />SECONDARY <br />NEW (4) #1, <br />(1) #6GND., <br />1-1/2"C. <br />(3 <br />) <br /> <br /># <br />6 <br />, <br /> <br />( <br />1 <br />) <br /> <br /># <br />1 <br />0 <br /> <br />G <br />N <br />D <br />. <br />, <br /> <br />1 <br />- <br />1 <br />/ <br />4 <br />" <br />C <br />. <br />4 <br />NEW 3P100A <br />FUSED <br />DISCONNECT <br />(100A FUSES) <br />C <br />3P100A <br />1 <br />TIE INTO EXISTING <br />ARCADE POWER FOR <br />CONTROL OF NEW <br />CONTACTOR (FIELD <br />VERIFY CONNECTION) <br />NEW (4) #1, <br />(1) #6GND., <br />1-1/2"C. <br />NEW (4) #1, <br />(1) #6GND., <br />1-1/2"C. <br />PO <br />W <br />E <br />R <br /> <br />B <br />U <br />S <br /> <br />" <br />B <br />" <br /> <br />S <br />E <br />C <br />T <br />I <br />O <br />N <br /> <br />1 <br />NE <br />W <br />PO <br />W <br />E <br />R <br /> <br />B <br />U <br />S <br /> <br />" <br />B <br />" <br /> <br />S <br />E <br />C <br />T <br />I <br />O <br />N <br /> <br />2 <br />NE <br />W <br />PO <br />W <br />E <br />R <br /> <br />B <br />U <br />S <br /> <br />" <br />B <br />" <br /> <br />S <br />E <br />C <br />T <br />I <br />O <br />N <br /> <br />3 <br />NE <br />W <br />NEW (4) #1, <br />(1) #6GND., <br />1-1/2"C. (TYP. BETWEEN BUS) <br />PO <br />W <br />E <br />R <br /> <br />B <br />U <br />S <br /> <br />" <br />B <br />" <br /> <br />S <br />E <br />C <br />T <br />I <br />O <br />N <br /> <br />4 <br />NE <br />W <br />NE <br />W <br /> <br />3 <br />P <br />5 <br />0 <br />A <br />EXISTING <br />PANEL <br />"H" <br />EXISTING 45 KVA <br />TRANSFORMER <br />480V-3Ø PRIMARY <br />208Y/120V-3Ø-4W <br />SECONDARY <br />EXISTING <br />PANEL "A" <br />EX <br />I <br />S <br />T <br />I <br />N <br />G <br />EXISTING <br />PANEL "B" <br />NEW 30 KVA <br />TRANSFORMER "T-BUS C" <br />480V-3Ø PRIMARY <br />208Y/120V-3Ø-4W <br />SECONDARY <br />NEW (4) #1, <br />(1) #6GND., <br />1-1/2"C. <br />NE <br />W <br />( <br />3 <br />) <br /> <br /># <br />6 <br />, <br /> <br />( <br />1 <br />) <br /> <br /># <br />1 <br />0 <br /> <br />G <br />N <br />D <br />. <br />, <br /> <br />1 <br />- <br />1 <br />/ <br />4 <br />" <br />C <br />. <br />4 <br />NEW 3P100A <br />FUSED <br />DISCONNECT <br />(100A FUSES) <br />C <br />3P100A <br />1 <br />TIE INTO EXISTING <br />ARCADE POWER FOR <br />CONTROL OF NEW <br />CONTACTOR (FIELD <br />VERIFY CONNECTION) <br />NEW (4) #1, <br />(1) #6GND., <br />1-1/2"C. <br />NEW (4) #1, <br />(1) #6GND., <br />1-1/2"C. <br />PO <br />W <br />E <br />R <br /> <br />B <br />U <br />S <br /> <br />" <br />C <br />" <br /> <br />S <br />E <br />C <br />T <br />I <br />O <br />N <br /> <br />1 <br />NE <br />W <br />PO <br />W <br />E <br />R <br /> <br />B <br />U <br />S <br /> <br />" <br />C <br />" <br /> <br />S <br />E <br />C <br />T <br />I <br />O <br />N <br /> <br />2 <br />NE <br />W <br />PO <br />W <br />E <br />R <br /> <br />B <br />U <br />S <br /> <br />" <br />C <br />" <br /> <br />S <br />E <br />C <br />T <br />I <br />O <br />N <br /> <br />3 <br />NE <br />W <br />NEW (4) #1, <br />(1) #6GND., <br />1-1/2"C. (TYP. BETWEEN BUS) <br />PO <br />W <br />E <br />R <br /> <br />B <br />U <br />S <br /> <br />" <br />C <br />" <br /> <br />S <br />E <br />C <br />T <br />I <br />O <br />N <br /> <br />4 <br />NE <br />W <br />PO <br />W <br />E <br />R <br /> <br />B <br />U <br />S <br /> <br />" <br />C <br />" <br /> <br />S <br />E <br />C <br />T <br />I <br />O <br />N <br /> <br />5 <br />NE <br />W <br />SPD <br />2 <br />5 5 5 55555 <br />EXISTING <br />EXISTING <br />PO <br />W <br />E <br />R <br /> <br />B <br />U <br />S <br /> <br />" <br />C <br />" <br /> <br />S <br />E <br />C <br />T <br />I <br />O <br />N <br /> <br />5 <br />NE <br />W <br />PO <br />W <br />E <br />R <br /> <br />B <br />U <br />S <br /> <br />" <br />C <br />" <br /> <br />S <br />E <br />C <br />T <br />I <br />O <br />N <br /> <br />5 <br />NE <br />W <br />C <br />TIE INTO EXISTING ARCADE <br />POWER CONTROLS (FIELD <br />VERIFY CONNECTION) <br />C <br />1 <br />1 <br />12P30A <br />12P30A <br />B-2,4,6,8,10,12,14 <br />,16,18,20,21,22 <br />B-24,26,28,30,32,34, <br />36,38,40,42,1,3 <br />NEW RTU-1 <br />E.C. SHALL FURNISH AND INSTALL SURGE SUPPRESSOR FOR THIS <br />PANEL EQUAL TO SQUARE D HMA TVS4HWA10X. MOUNT AS CLOSE TO <br />PANEL AS POSSIBLE AND UTILIZE (5) #10, 3/4"C FOR CONNECTION TO <br />BREAKER AS SHOWN. (100KA 480V-4W) <br />NEW (3) #4, <br />(1) #10GND., <br />1-1/4"C. <br />4 4 <br />SPD <br />6 <br />GENERAL EQUIPMENT:43,128VA <br />ARCADE EQUIPMENT: 31,281VA <br />KITCHEN/FOOD PREP:0 .65 = 0VA <br />LIGHITNG:2,472VAX 1.25= 3,090VA <br />RECEPTACLES:4,920VA <br />25% OF LARGEST MOTOR: 10,182A <br />TOTAL DEMAND:92,601VA, 111.4A x 1.25 = 139.3A <br />SERVICE LOAD CALCULATIONS <br />SERVICE : 480Y/277V-3Ø-4W , 600A <br />SERVICE LOAD CALCULATIONS <br />SERVICE: 480Y/277V-3Ø-4W , 1200A <br />PANEL H PANEL MDB <br />EXISTING CALCULATED DEMAND (ORIGINAL): 701,316VA <br />NEW ARCADE EQUIPMENT: 70,150VA <br />TOTAL REVISED DEMAND:771,466VA, 928.36A x 1.25 = 1160.5A <br />C <br />3 4P30A <br />A-11,13,15 <br />LCPA-8 <br />PO <br />W <br />E <br />R <br /> <br />B <br />U <br />S <br /> <br />" <br />B <br />" <br /> <br />S <br />E <br />C <br />T <br />I <br />O <br />N <br /> <br />5 <br />NE <br />W <br />5 <br />PO <br />W <br />E <br />R <br /> <br />B <br />U <br />S <br /> <br />" <br />B <br />" <br /> <br />S <br />E <br />C <br />T <br />I <br />O <br />N <br /> <br />6 <br />NE <br />W <br />5 <br />R1 <br />480V <br />EQUIPMENT GROUNDING <br />CONDUCTOR <br />480V-3PH PRIMARY <br />208Y/120V-3PH-4W SECONDARY <br />TRANSFORMER <br />PH B <br />PH A PH C <br />NEUTRAL (GROUNDED) <br />BAR <br />TO NEAREST GROUNDING ELECTRODE (STRUCTURAL STEEL) <br />GROUNDING ELECTRODE CONDUCTOR SHALL <br />BE SIZED PER NEC TABLE 250.66 <br />(SEE "GND" CONDUCTOR ON ONE LINE <br />DIAGRAM FOR SUB DISTRIBUTION TRANSFORMER <br />GROUNDING ELECTRODE SIZING) <br />EQUIPMENT GROUND BAR <br />208Y/120V-3PH-4W <br />PANELBOARD <br />EQUIPMENT GROUNDING <br />CONDUCTOR <br />5/21/2025 1:08:51 PM <br />2309147GR <br />ROUND1 <br />BOWLING AND <br />AMUSEMENT <br />2800 N. MAIN ST. SUITE 1100 <br />SANTA ANA, CA 92705 <br />ROUND 1 <br />ENTERTAINMENT <br />3070 SATURN ST. STE. 200 <br />BREA, CA 92821 <br />ELECTRICLAL ONE-LINE <br />DIAGRAM <br />E-501 <br />MAINPLACE <br />MALL <br />REMODEL <br />BUSWAY DETAILS <br />SCALE:1/8" = 1'-0"E-501 <br />PROPOSED ONE-LINE SANTA ANA1 <br />SCALE:3/32" = 1'-0"E-501 <br />TRANSFORMER GROUNDING DETAIL2 <br />1751 Barlow St. <br />Traverse City, MI 49686 <br />T 231-947-1707 <br />F 231-947-1710 <br />4801 Henry St. <br />Muskegon, MI 49441 <br />T 231-798-4328 <br />F 231-798-2981 <br />REC #5001 <br />CLIENT <br />ARCHITECTS <br />PARADIGM <br />415 Leonard Street NW, Suite 200 <br />Grand Rapids, MI 49504 <br />(616) 785-5656 <br />www.paradigmae.com <br />Grand Rapids | Phoenix | Traverse City <br />DESIGN <br />ENGINEERS| <br />DATE DESCRIPTION <br />RELEASE DATE <br />SHEET <br />PROJECT <br />PROJECT <br />12-09-24 Permits <br />R1 5-21-25 PLAN REVIEW <br />COMMENTS <br />PROVIDE NEW ENGRAVED <br />PLAQUE INDICATING <br />"ROUND 1 TENANT" ABOVE <br />EACH SWITCH.