Laserfiche WebLink
Round 1 Bowling and Amusement 12/09/2024 Paradigm Design <br />Main Place Mall Expansion Grand Rapids, MI <br />Santa Ana, California <br />Project #2309147GR <br />e.Manufacturer's serial number. <br />f.Unit arrangement and class. <br />g.Discharge arrangement. <br />h.Sheave make, size in inches, and bore. <br />i.Center-to-center dimensions of sheave, and amount of adjustments in inches. <br />j.Number, make, and size of belts. <br />k.Number, type, and size of filters. <br />2.Motor Data: <br />a.Motor make, and frame type and size. <br />b.Horsepower and rpm. <br />c.Volts, phase, and hertz. <br />d.Full-load amperage and service factor. <br />e.Sheave make, size in inches, and bore. <br />f.Center-to-center dimensions of sheave, and amount of adjustments in inches. <br />3.Test Data (Indicated and Actual Values): <br />a.Total air flow rate in cfm. <br />b.Total system static pressure in inches wg. <br />c.Fan rpm. <br />d.Discharge static pressure in inches wg. <br />e.Filter static-pressure differential in inches wg. <br />f.Preheat-coil static-pressure differential in inches wg. <br />g.Cooling-coil static-pressure differential in inches wg. <br />h.Heating-coil static-pressure differential in inches wg. <br />i.Outdoor airflow in cfm. <br />j.Return airflow in cfm. <br />k.Outdoor-air damper position. <br />l.Return-air damper position. <br />m.Vortex damper position. <br />F.Apparatus-Coil Test Reports: <br />1.Coil Data: <br />a.System identification. <br />b.Location. <br />c.Number of rows. <br />d.Make and model number. <br />e.Face area in sq. ft.. <br />f.Tube size in NPS. <br />g.Tube and fin materials. <br />h.Circuiting arrangement. <br />2.Test Data (Indicated and Actual Values): <br />a.Air flow rate in cfm.