Laserfiche WebLink
Round 1 Bowling and Amusement 12/09/2024 Paradigm Design <br />Main Place Mall Expansion Grand Rapids, MI <br />Santa Ana, California <br />Project #2309147GR <br />n.Motor amperage for each phase. <br />o.Heating value of fuel in Btu/h. <br />H.Fan Test Reports: For supply, return, and exhaust fans, include the following: <br />1.Fan Data: <br />a.System identification. <br />b.Location. <br />c.Make and type. <br />d.Model number and size. <br />e.Manufacturer's serial number. <br />f.Arrangement and class. <br />g.Sheave make, size in inches, and bore. <br />h.Center-to-center dimensions of sheave, and amount of adjustments in inches. <br />2.Motor Data: <br />a.Motor make, and frame type and size. <br />b.Horsepower and rpm. <br />c.Volts, phase, and hertz. <br />d.Full-load amperage and service factor. <br />e.Sheave make, size in inches, and bore. <br />f.Center-to-center dimensions of sheave, and amount of adjustments in inches. <br />g.Number, make, and size of belts. <br />3.Test Data (Indicated and Actual Values): <br />a.Total airflow rate in cfm. <br />b.Total system static pressure in inches wg. <br />c.Fan rpm. <br />d.Discharge static pressure in inches wg. <br />e.Suction static pressure in inches wg. <br />I.Round, Flat-Oval, and Rectangular Duct Traverse Reports: Include a diagram with a grid <br />representing the duct cross-section and record the following: <br />1.Report Data: <br />a.System and air-handling-unit number. <br />b.Location and zone. <br />c.Traverse air temperature in deg F. <br />d.Duct static pressure in inches wg. <br />e.Duct size in inches. <br />f.Duct area in sq. ft.. <br />g.Indicated air flow rate in cfm. <br />h.Indicated velocity in fpm. <br />i.Actual air flow rate in cfm.