CITY OF SANTA ANA <br />a <br />U) <br />U <br />U <br />U) <br />I <br />U <br />c <br />c <br />U) <br />N <br />N <br />ii <br />U <br />0 <br />N <br />O <br />N <br />0 <br />0- <br />ELECTRICAL DEMOLITION GENERAL NOTES (WHEN APPLICABLE): <br />1. REFERENCE ARCHITECTURAL DRAWINGS FOR FULL EXTENT OF DEMOLITION WORK <br />AND PHASING. NOTIFY ARCHITECT, ENGINEER AND OWNER, AS APPLICABLE, OF ANY <br />CONFLICTS OR DISCREPANCIES BETWEEN DRAWINGS AND JOB SITE CONDITIONS <br />PRIOR TO SUBMITTING BID. <br />2. COORDINATE DEMOLITION AND REMOVAL OF EXISTING ELECTRICAL EQUIPMENT AND <br />LIGHTING SYSTEMS WITH ARCHITECTURAL PHASING DRAWING AND OWNER TO <br />ALLOW NECESSARY SYSTEMS TO REMAIN OPERATIONAL DURING CONSTRUCTION. <br />(NOTE: NOT ALL EXISTING/DEMOLISHED EQUIPMENT, LIGHT FIXTURES, DEVICES OR <br />RACEWAYS WILL BE SHOWN ON THE DRAWINGS). COORDINATE ELECTRICAL <br />REQUIREMENTS FOR REMODELED/RENOVATED SPACES WITH THE OWNER. <br />3. AVOID DAMAGING FACILITIES, INCLUDING EQUIPMENT, LIGHT FIXTURES AND DEVICES <br />THAT ARE EXISTING TO REMAIN, NEW OR REUSED. REPAIR ALL DAMAGE CAUSED <br />DURING WORK AT NO EXTRA COST TO THE OWNER. <br />a. DISPOSE OF ALL ELECTRICAL EQUIPMENT, LIGHT FIXTURES, AND DEVICES SHOWN TO <br />BE REMOVED, UNLESS NOTED OTHERWISE. COORDINATE WITH THE OWNER THE <br />ITEMS TO BE SALVAGED, AND THE LOCATION FOR STORAGE. AVOID DAMAGING <br />SALVAGED ITEMS DURING DEMOLITION WORK AND DURING TRANSPORT TO OWNER'S <br />DESIGNATED STORAGE LOCATION. <br />5. WHERE ALTERATION OF ELECTRICAL EQUIPMENT, LIGHT FIXTURES, RACEWAYS OR <br />WIRING DEVICES AFFECTS EXISTING SURFACES/FINISHES: REPAIR/PAINT AFFECTED <br />SURFACE TO MATCH EXISTING ADJACENT SURFACE IN ACCORDANCE WITH OWNER <br />REQUIREMENTS. MAINTAIN FIRE RATING OF ALL FLOORS/WALLS/CEILINGS THAT ARE <br />RATED. <br />6. WHERE DEMOLITION WORK INTERRUPTS ELECTRICAL CONTINUITY OF CIRCUITS THAT <br />ARE TO REMAIN IN USE, PROVIDE NECESSARY DEVICES AND RELATED CIRCUITRY TO <br />MAINTAIN ELECTRICAL CONTINUITY IN ACCORDANCE WITH OWNER REQUIREMENTS. <br />RECIRCUIT REUSED ELECTRICAL EQUIPMENT, LIGHT FIXTURES AND WIRING DEVICES <br />PREVIOUSLY POWERED FROM DEMOLISHED EQUIPMENT TO NEW OR TEMPORARY <br />EQUIPMENT AS NEEDED. <br />7. COORDINATE DISCONNECTION OF POWER TO EQUIPMENT BEING <br />DEMOLISHED/REMOVED/RELOCATED WITH OTHER TRADES PRIOR TO START OF <br />WORK. ALL ELECTRICAL EQUIPMENT, LIGHT FIXTURES, RACEWAYS, WIRING DEVICES <br />AND RELATED CIRCUITRY NOT BEING REUSED SHALL BE REMOVED IN ALL <br />ACCESSIBLE AREAS AND IN FLOORS/WALLS/CEILINGS THAT ARE TO BE REMOVED, <br />UNLESS NOTED OTHERWISE. AS ALLOWED BY OWNER, UNUSED ELECTRICAL <br />EQUIPMENT, RACEWAYS AND RELATED CIRCUITRY THAT ARE INACCESSIBLE MAY BE <br />ABANDONED IN PLACE AND SHALL BE PERMANENTLY DISCONNECTED FROM ALL <br />POWER SOURCES, INSULATED FROM CONTACT WITH OTHER LIVE ELECTRICAL <br />WIRING/DEVICES, AND IDENTIFIED AT THE TERMINATIONS AS NO LONGER BEING IN <br />SERVICE. <br />8. LOW VOLTAGE CABLES/WIRING NOT BEING REUSED SHALL BE REMOVED UNLESS <br />IDENTIFIED FOR FUTURE USE. COORDINATE REQUIREMENTS WITH OWNER. CARE <br />SHOULD BE TAKEN DURING THE REMOVAL PROCESS TO PROTECT THE EXISTING <br />REUSED CABLES/WIRING FROM DAMAGE. <br />VOLTAGE DROP SCHEDULE <br />120V BRANCH CIRCUITS: MAXIMUM CIRCUIT LENGTH; <br />3% MAX VOLTAGE DROP <br />WIRE GAUGE <br />#12 <br />#10 #8 <br />#6 #4 <br />#3 <br />3840 <br />N/A <br />N/A <br />69 <br />110 174 <br />220 <br />3500 <br />N/A <br />N/A <br />76 <br />120 <br />191 <br />242 <br />3250 <br />N/A <br />N/A <br />82 <br />130 <br />206 <br />-- <br />3000 <br />N/A <br />N/A <br />88 <br />140 <br />223 <br />-- <br />2880 <br />N/A <br />58 <br />92 <br />146 <br />233 <br />-- <br />Lu <br />�_ <br />2500 <br />N/A <br />66 <br />106 <br />169 <br />268 <br />-- <br />v <br />2250 <br />N/A <br />74 <br />118 <br />187 <br />298 <br />-- <br />U � <br />z <br />1920 <br />54 <br />87 <br />138 <br />220 <br />-- <br />-- <br />m <br />1800 <br />58 <br />92 <br />148 <br />234 <br />-- <br />-- <br />1500 <br />70 <br />111 <br />177 <br />281 <br />-- <br />i <br />-- <br />1200 <br />87 <br />139 <br />221 <br />-- <br />-- <br />-- <br />1000 <br />105 <br />167 <br />266 <br />-- <br />-- <br />-- <br />700 <br />150 <br />238 -- <br />-- -- <br />-- <br />VOLTAGE DROP SCHEDULE <br />208V/10 BRANCH CIRCUITS: MAXIMUM CIRCUIT LENGTH; <br />3% MAX VOLTAGE DROP <br />WIRE GAUGE <br />#12 <br />#10 #8 #6 #4 #3 <br />8320 <br />N/A <br />N/A <br />96 <br />152 241 <br />-- <br />7488 <br />N/A <br />N/A <br />106 <br />169 <br />269 <br />-- <br />D <br />6656 <br />N/A <br />N/A <br />120 <br />190 <br />302Lu <br />-- <br />�_ <br />5764 <br />N/A <br />N/A <br />138 <br />220 <br />-- <br />- <br />4992 <br />N/A <br />100 <br />160 <br />253 <br />-- <br />-- <br />v <br />4160 <br />N/A <br />120 <br />192 <br />304 <br />m3328 <br />94 <br />150 <br />240 <br />-- <br />-- <br />-- <br />2080 <br />151 <br />251 <br />-- <br />-- <br />-- <br />-- <br />1456 <br />216 <br />-- <br />-- <br />-- <br />-- <br />-- <br />VOLTAGE DROP SCHEDULE <br />208V/30 BRANCH CIRCUITS: MAXIMUM CIRCUIT LENGTH; <br />3% MAX VOLTAGE DROP <br />WIRE GAUGE <br />#12 <br />#10 #8 <br />#6 #4 #3/0 <br />36000 <br />N/A <br />N/A N/A <br />N/A N/A <br />452 <br />14411 <br />N/A <br />N/A 111 <br />176 280 <br />-- <br />F- <br />11528 <br />N/A <br />N/A <br />138 <br />220 <br />-- <br />-- <br />w <br />9727 <br />N/A <br />N/A <br />164 <br />260 <br />-- <br />-- <br />U < <br />8646 <br />N/A <br />116 <br />185 <br />292 <br />-- <br />-- <br />U Q <br />7205 <br />N/A <br />139 <br />222 <br />-- <br />-- <br />-- <br />5764 <br />109 <br />174 <br />277 <br />-- <br />-- <br />-- <br />11 <br />4323 <br />146 <br />232 <br />-- <br />-- <br />-- <br />-- <br />3602 <br />175 <br />279 <br />-- <br />-- <br />-- <br />-- <br />2882 <br />219 <br />-- <br />-- <br />-- <br />-- <br />-- <br />VOLTAGE DROP NOTES <br />A. THE CONDUCTORS FOR FEEDER AND BRANCH <br />CIRCUITS COMBINED SHALL BE SIZED FOR A <br />MAXIMUM OF (5) PERCENT VOLTAGE DROP TOTAL. <br />B. THE VOLTAGE DROP OF THE SERVICE FEEDERS <br />SHALL NOT EXCEED (2) PERCENT. (CONTRACTOR TO <br />VERIFY FEEDER LENGTH IN FIELD, UPSIZE FEEDER <br />CONDUCTOR SIZE AS NEEDED, KEEP VOLTAGE <br />DROP BELOW (2) PERCENT.) <br />C. THE VOLTAGE DROP OF ANY BRANCH CIRCUIT <br />SHALL NOT EXCEED (3) PERCENT. <br />D. CONTRACTOR TO DETERMINE THE LENGTH OF RUN <br />AND THE CONNECTED LOAD FOR EACH BRANCH <br />CIRCUIT. USING THE VOLTAGE DROP SCHEDULES IN <br />THIS DETAIL, THE CONTRACTOR SHALL DETERMINE <br />THE SIZE OF THE BRANCH CIRCUIT CONDUCTOR IS <br />ADEQUATE FOR A VOLTAGE DROP LESS THAN THE <br />MAXIMUM (3) PERCENT. CONTRACTOR TO UP -SIZE <br />THE BRANCH CIRCUIT CONDUCTORS AS NEEDED <br />TO ADJUST FOR VOLTAGE DROP. <br />(:: <br />.� VOLTAGE DROP SCHEDULE AND NOTE <br />NO SCALE <br />ELECTRICAL GENERAL NOTES: <br />1. EXISTING CONDITIONS WERE TAKEN FROM ORIGINAL DRAWINGS AND SITE VISITS AND <br />MAY NOT REFLECT ACTUAL "AS -BUILT" CONDITIONS. VERIFY EXISTING CONDITIONS <br />PRIOR TO SUBMITTING FINAL BID. COORDINATE NEW AND DEMOLITION WORK WITH ALL <br />OTHER TRADES AND EXISTING CONDITIONS. <br />2. NOTIFY ARCHITECT, ENGINEER AND OWNER, AS APPLICABLE, IF ANY DANGEROUS <br />CONDITIONS EXIST ON JOB SITE BEFORE ANY DEMOLITION OR REMODEL WORK <br />BEGINS. <br />3. COORDINATE ANY NECESSARY POWER OUTAGES WITH THE LANDLORD AND OWNER <br />AND MAKE EVERY ATTEMPT TO SCHEDULE DURING NON -BUSINESS OR OFF-PEAK <br />BUSINESS HOURS TO MINIMIZE DISRUPTION TO BUSINESS OPERATIONS. REQUESTS <br />FOR ELECTRICAL SHUTDOWNS OF THE LANDLORD'S EQUIPMENT SHALL BE BROUGHT <br />IN WRITING TO THE ATTENTION OF THE LANDLORD AT LEAST 7 DAYS IN ADVANCE. <br />SHUTDOWNS SHALL NOT BE PERFORMED WITHOUT WRITTEN APPROVAL FROM THE <br />LANDLORD. <br />4. ALL ROOF PENETRATIONS, FLOOR CHASING OR CORE DRILLING SHALL REQUIRE THE <br />SPECIFIC APPROVAL OF THE LANDLORD AND OWNER. ALL WORK IN COMMON AREAS, <br />SHAFTS OR OTHER OWNER SPACES MUST BE SPECIFICALLY REVIEWED AND <br />APPROVED BY THE LANDLORD PRIOR TO ANY WORK BEING PERFORMED. MINIMIZE <br />DISTURBANCE TO OTHER BUILDING TENANTS. <br />5. FOR AREAS AND EQUIPMENT WITHIN THE SCOPE OF THIS REMODEL: EXISTING <br />ELECTRICAL EQUIPMENT AND CIRCUITRY MAY BE REUSED IF IN GOOD CONDITION AND <br />NEW DESIGN REQUIREMENTS CAN BE MET; OTHERWISE REPLACE. <br />6. FOR AREAS AND EQUIPMENT WITHIN THE SCOPE OF THIS REMODEL: REPAIR OR <br />REPLACE ANY EXISTING DAMAGED OR RECALLED ELECTRICAL EQUIPMENT, LIGHT <br />FIXTURES, WIRING DEVICES AND RELATED CIRCUITRY AND RESTORE ALL ELECTRICAL <br />SYSTEMS TO PROPER WORKING ORDER. THE FINAL ELECTRICAL INSTALLATION SHALL <br />BE FREE FROM ELECTRICAL DEFECTS TO THE SATISFACTION OF THE AHJ, OWNER, <br />ARCHITECT AND ENGINEER. <br />7. FOR AREAS AND EQUIPMENT WITHIN THE SCOPE OF THIS REMODEL: VERIFY <br />CONDITION AND AGE OF EXISTING REUSED ELECTRICAL EQUIPMENT, LIGHT FIXTURES, <br />CIRCUIT BREAKERS, FUSES, CONDUIT, SWITCHES AND RELATED WIRING. NOTIFY <br />OWNER OF ANY ELECTRICAL EQUIPMENT, LIGHT FIXTURES AND WIRING AGED BEYOND <br />ITS USEFUL LIFE AND REPLACE AS DIRECTED. THE MAXIMUM EXPECTED USEFUL LIFE <br />SHALL NOT EXCEED THE FOLLOWING, (AS DATED FROM THE POINT OF MANUFACTURE), <br />UNLESS APPROVED BY THE ENGINEER, MANUFACTURER AND OWNER: 20 YEARS FOR <br />CIRCUIT BREAKERS, GENERATOR/UPS SYSTEMS AND LIGHT FIXTURES, 30 YEARS FOR <br />TRANSFORMERS AND PANELBOARDS, 40 YEARS FOR SWITCHBOARDS AND OTHER <br />ELECTRICAL EQUIPMENT. <br />8. FOR AREAS AND EQUIPMENT WITHIN THE SCOPE OF THIS REMODEL: ELECTRICAL <br />EQUIPMENT SHALL BE LOCATED SO THAT THE CODE REQUIRED MINIMUM WORKING <br />CLEARANCE AND DEDICATED ELECTRICAL SPACE ARE MAINTAINED. EXISTING <br />EQUIPMENT NOT MEETING CURRENT CODE CLEARANCE REQUIREMENTS MAY REMAIN <br />IF ALLOWED TO REMAIN BY THE AHJ, ENGINEER AND OWNER. <br />ELECTRICAL SUPPLEMENTAL SPECIFICATIONS: <br />1. PRIOR TO SUBMITTING BID, VISIT THE JOB SITE AND BECOME FULLY ACQUAINTED WITH <br />THE EXISTING CONDITIONS. AS APPLICABLE, REVIEW THE LANDLORD CRITERIA, <br />GENERAL NOTES, OTHER TRADE DRAWINGS AND SPECIFICATIONS FOR ADDITIONAL <br />REQUIREMENTS THAT MAY NOT BE CALLED OUT IN THIS PORTION OF THE <br />CONSTRUCTION DOCUMENTS. NOTIFY ARCHITECT AND ENGINEER OF ANY CONFLICTS <br />OR DISCREPANCIES PRIOR TO SUBMITTING BID. <br />2. ALL WORK SHALL CONFORM TO ALL LOCAL CODES AND ORDINANCES AS WELL AS <br />APPLICABLE INDUSTRY STANDARDS. ALL EQUIPMENT SHALL BEAR LABELS FOR THE <br />USE INTENDED BY AN AHJ ACCEPTED NATIONALLY RECOGNIZED TESTING <br />LABORATORY (NRTL), SUCH AS UL OR ETL. THE FINAL ELECTRICAL INSTALLATION OF <br />THE FACILITY OCCUPIED BY OWNER SHALL BE FREE FROM ELECTRICAL DEFECTS TO <br />THE SATISFACTION OF THE AHJ, OWNER, ARCHITECT AND ENGINEER. <br />3. COORDINATE FINAL LOCATION AND INSTALLATION REQUIREMENTS OF ALL LIGHT <br />FIXTURES, ELECTRICAL EQUIPMENT AND ELECTRICAL DEVICES WITH ARCHITECTURAL <br />DRAWINGS, EXISTING CONDITIONS AND OTHER TRADES PRIOR TO ROUGH -IN. PROVIDE <br />ALL NECESSARY DEVICES, CORDS, PLUGS, DISCONNECTS AND FINAL CONNECTIONS <br />TO ELECTRICAL EQUIPMENT FOR PROPER OPERATION IN ACCORDANCE WITH CODE, <br />OWNER AND MANUFACTURER REQUIREMENTS. <br />4. ELECTRICAL DRAWINGS ARE DIAGRAMMATIC/SCHEMATIC IN NATURE AND REPRESENT <br />THE GENERAL SCOPE OF WORK. IT IS NOT WITHIN THE SCOPE OF THE ELECTRICAL <br />DRAWINGS TO SHOW ALL NECESSARY RACEWAY ROUTING, BENDS, OFFSETS, PULL <br />BOXES AND OBSTRUCTIONS. CONTRACTOR SHALL COORDINATE THE FINAL LOCATION <br />OF EQUIPMENT AND WIRING DEVICES WITH OTHER TRADES PRIOR TO INSTALLATION <br />AND INSTALL ALL WORK TO CONFORM TO THE OWNER REQUIREMENTS. <br />5. ALL CONDUCTOR AND CONDUIT LENGTHS SHOWN IN THESE DESIGN DOCUMENTS ARE <br />INTENDED SOLELY FOR USE IN THE DESIGN CALCULATIONS BY THE DESIGN <br />PROFESSIONAL, UNLESS NOTED OTHERWISE. LENGTHS SHOWN SHALL NOT BE USED <br />TO ASSIST IN THE BIDDING TAKEOFF PROCESS. THE CONTRACTOR IS SOLELY <br />RESPONSIBLE FOR THE MATERIAL QUANTITIES REQUIRED TO BID AND CONSTRUCT <br />THE COMPLETE PROJECT. <br />6. PROVIDE PROPER FIRE PROOFING AND SEALANT FOR PENETRATIONS THROUGH FIRE <br />RATED ASSEMBLIES. THE FIRE STOPPING METHOD, MATERIAL AND ITS APPLICATION <br />SHALL BE NRTL LISTED, CODE COMPLIANT AND APPROVED BY AHJ. <br />7. FOR CAST -IN -PLACE CONCRETE, TILT -UP WALLS, PRECAST OR SIMILAR <br />PRE-ENGINEERED WALL SYSTEMS: COORDINATE THE FINAL LOCATION OF ALL <br />ELECTRICAL DEVICES, RACEWAYS, LIGHT FIXTURES AND PENETRATIONS WITH <br />ARCHITECT, WALL SUPPLIER AND OTHER TRADES PRIOR TO WALL CONSTRUCTION. <br />CONDUIT/RACEWAY IMBEDDED IN CONCRETE WALLS SHALL BE SCHEDULE 80 PVC OR <br />LFMC; OTHER TYPES MAY BE ALLOWED IF APPROVED BY WALL SYSTEM <br />MANUFACTURER AND ENGINEER. <br />8. ALL APPLICABLE SWITCHES, RECEPTACLES, OUTLETS, AND CONTROLS SHALL BE <br />PLACED AT HEIGHTS THAT ARE IN ACCORDANCE WITH ADA ACCESSIBILITY <br />GUIDELINES. <br />9. WIRING DEVICES ADJACENT TO EACH OTHER SHALL BE INSTALLED UNDER A SINGLE <br />COVER PLATE, UNO. <br />10. WIRING DEVICES SHOWN BACK-TO-BACK ON A COMMON WALL SHALL BE OFFSET A <br />MINIMUM OF 12" HORIZONTALLY TO REDUCE SOUND TRANSMISSION BETWEEN ROOMS, <br />UNO. <br />11. ALL WP OUTLET BOX HOODS SHALL BE "EXTRA -DUTY" AND "WHILE -IN -USE COVER" <br />TYPE. OUTLET BOX HOODS SHALL BE LOW PROFILE WHEREVER PRACTICABLE, UNLESS <br />NOTED OTHERWISE. THE USE OF LARGE BUBBLE COVERS SHALL BE AVOIDED ON THE <br />EXTERIOR OF THE BUILDING OR BEHIND EQUIPMENT IN ORDER TO PREVENT DAMAGE <br />TO THE COVER AND TO ALLOW THE EQUIPMENT TO BE LOCATED CLOSE TO THE WALL. <br />12. ALL SINGLE-PHASE RECEPTACLES RATED 150 VOLTS TO GROUND OR LESS, 50 <br />AMPERES OR LESS AND THREE PHASE RECEPTACLES RATED 150 VOLTS TO GROUND <br />OR LESS, 100 AMPERES OR LESS INSTALLED IN LOCATIONS REQUIRED BY CODE (THIS <br />INCLUDES BATHROOMS, KITCHENS/FOOD PREP AREAS, GARAGES, EXTERIOR <br />LOCATIONS AND RECEPTACLES WITHIN 6 FEET OF A SINK). SHALL BE PROVIDED <br />GROUND -FAULT CIRCUIT -INTERRUPTER PROTECTION FOR PERSONNEL PER N.E.C. <br />210.8 AND INSTALLED IN ACCORDANCE WITH N.E.C. 240,24. ALTERNATIVELY, A GFCI <br />CIRCUIT BREAKER CAN BE INSTALLED.GFCI RECEPTACLES SHALL BE READILY <br />ACCESSIBLE AND SHALL NOT BE LOCATED BEHIND STATIONARY EQUIPMENT. GFCI <br />PROTECTION MAY BE VIA A GFCI CIRCUIT BREAKER OR GFCI RECEPTACLE, UNLESS <br />NOTED OTHERWISE. WHERE NECESSARY, GFCI PROTECTION MAY BE ACHIEVED VIA A <br />BLANK FACE GFCI DEVICE LOCATED IN A READILY ACCESSIBLE LOCATION NEAR <br />RECEPTACLE BEING PROTECTED. FOR DOWNSTREAM WIRING DEVICES LOCATED ON <br />THE SAME BRANCH CIRCUIT, THE GFCI PROTECTION MAY BE PROVIDED FOR BY A <br />SINGLE UPSTREAM DEVICE IF ALL PROTECTED DEVICES ARE LABELED PER CODE.) <br />13. PROVIDE TAMPER -RESISTANT JR) TYPE RECEPTACLES AT ALL CODE REQUIRED <br />LOCATIONS AND AT LOCATIONS WHERE RECEPTACLES ARE MOUNTED LESS THAN 5'-61, <br />AFF AND ARE EASILY ACCESSIBLE BY CHILDREN, UNLESS NOTED OTHERWISE. <br />14. FLEXIBLE CONDUIT IS ONLY PERMITTED WHERE SPECIFICALLY ALLOWED IN THE <br />CONSTRUCTION DOCUMENTS, WHERE CONCEALED FROM VIEW OR EXPOSED FINAL <br />CONNECTIONS TO LIGHT FIXTURES AND EQUIPMENT IN LENGTHS OF 6-0" OR LESS. <br />15. ALL EMPTY CONDUIT/RACEWAY SHALL BE INSTALLED WITH PULL STRINGS. TERMINATE <br />CONDUIT STUB -UP WITH A NYLON BUSHING. <br />16. EXPOSED CONDUIT/RACEWAY SHALL BE PAINTED TO MATCH ADJACENT SURFACE, <br />UNLESS NOTED OTHERWISE. COORDINATE REQUIREMENTS WITH ARCHITECT AND <br />OWNER PRIOR TO INSTALLATION. <br />Plannin <br />17. <br />CONDUITS/RACEWAYS SHALL BE CONCEALED FROM VIEW WHEREVER <br />ACTICABLE, <br />UNLESS NOTED OTHERWISE. ROUTE CONDUITS SERVING ROOFTOP EQL <br />IPMENT <br />CONCEALED INSIDE EQUIPMENT CURB AND MINIMIZE ROOF PENETRATIONS <br />AND <br />EXTERIOR CONDUIT RUNS WHERE PRACTICABLE. SUPPORT RACEWAY FROM <br />STRUCTURE, NOT ROOF DECK. MAINTAIN 2" MIN SPACING FROM BOTTOM <br />OF ROOF <br />DECK TO PREVENT ROOFING SCREWS FROM PENETRATING RACEWAY. MO <br />NOT ROUTE <br />CONDUITS ACROSS SKYLIGHTS, ACCESS PANELS, HATCHED TILES, HVA <br />DIFFFSIfS, <br />R P <br />OR EQUIPMENT WORKING CLEARANCE SPACE. ROUTE ALL EXPOSED N <br />N-FL IB�f <br />CONDUITS TIGHT TO STRUCTURE, PARALLEL TO BUILDING LINES AND IN <br />STRUT OR <br />CABLE/PIPE TRAY WHERE PRACTICABLE. INSTALL CONDUITS PLUMB/ LEI <br />IEL WHERE <br />EXPOSED TO VIEW. COORDINATE RACEWAY ROUTING AND INSTALLATI <br />WITH OTHER <br />TRADES PRIOR TO ROUGH -IN. <br />18. <br />WHERE PRACTICABLE, ALL UNDER-FLOOR/UNDER-GROUND CONDUITS/ <br />ACEWAY <br />SHALL BE INSTALLED A MINIMUM OF 24" BELOW BOTTOM OF SLAB/PAVI <br />/GRADE, <br />UNLESS NOTED OTHERWISE. NOTE: THE DESIGN INTENT FOR INSTALLIN <br />ftlgft <br />r <br />I <br />CIRCUITRY AT THIS DEPTH IS TO PROTECT THE ELECTRICAL CIRCUITRY <br />zT <br />L <br />` <br />DUE TO FUTURE WORK. <br />19. <br />PROVIDE LABEL AT EACH RECEPTACLE COVER PLATE WITH THE RESPE <br />T,Qate. <br />"PNLBD-CKT#" DESIGNATION. COORDINATE LABEL REQUIREMENTS WITH <br />THE OWNER <br />PRIOR TO INSTALLATION. REFER TO THE SPECIFICATIONS FOR MORE INFORMATION. <br />20. <br />MULTIWIRE BRANCH CIRCUITS ARE NOT ALLOWED, UNLESS NOTED OTH <br />ERWISE. <br />21. <br />PROVIDE INSULATED EQUIPMENT GROUNDING CONDUCTOR FOR ALL CIRCUITS, <br />UNLESS NOTED OTHERWISE. <br />22. <br />IF CONTRACTOR IS RESPONSIBLE FOR INSTALLING UTILITY TRANSFORMER PAD (FOR <br />NEW UTILITY TRANSFORMER) REFER TO SERVING UTILITY'S GREEN BOOK <br />FOR <br />INSTALLATION REQUIREMENTS AND COORDINATE TRANSFORMER INSTALLATION <br />WITH <br />UTILITY COMPANY. <br />SPECIAL SYSTEMS SUPPLEMENTAL SPECIFICATIONS: <br />1. PROVIDE NECESSARY BOXES, CONDUIT AND MAKE FINAL CONNECTIONS TO <br />TEMPERATURE CONTROL DEVICES PER MANUFACTURER'S RECOMMENDATIONS. THIS <br />INCLUDES BUT IS NOT LIMITED TO: MAIN CONTROL PANELS, THERMOSTATS, <br />HUMIDISTATS, AC SOLENOIDS, HEAT RECLAIM WIRING, AHU CONTROL WIRING, DUCT <br />FURNACE CONTROL WIRING, TIMERS, AND SIMILAR CONTROLS. PROVIDE CONDUIT FOR <br />ALL WIRING WITHIN WALLS. PROVIDE CONTROL AND INTERLOCK WIRING WHEN NOT <br />PROVIDED BY OTHER TRADES. COORDINATE REQUIREMENTS WITH EQUIPMENT <br />SUPPLIERS AND OTHER TRADES PRIOR TO ROUGH -IN. <br />2. PROVIDE LINE VOLTAGE WIRING AND MAKE FINAL CONNECTIONS TO ALL <br />DUCT -MOUNTED SMOKE DETECTORS, FIRE/SMOKE AND SMOKE DAMPERS WHERE <br />APPLICABLE. COORDINATE REQUIREMENTS WITH OTHER TRADES PRIOR TO <br />INSTALLATION. <br />3. DEVICES MOUNTED ON ACOUSTICAL TILE CEILINGS SHALL BE CENTERED ON THE TILE, <br />UNO. <br />4. PROVIDE BOX AND 3/4" CONDUIT FROM EACH THERMOSTAT LOCATION TO MECHANICAL <br />EQUIPMENT, (FLUSH MOUNT BOX WHEREVER PRACTICABLE). COORDINATE LOCATION <br />OF ALL THERMOSTAT BOXES WITH MECHANICAL/CONTROLS CONTRACTOR AND <br />OWNER PRIOR TO ROUGH -IN. <br />5. PROVIDE BOXES AND CONDUITS FOR THE FIRE PROTECTION SYSTEM LOW VOLTAGE <br />WIRING AS REQUIRED. THIS INCLUDES EXPOSED WIRING LESS THAN 96" AFF. AT A <br />MINIMUM, PROVIDE 3/4" CONDUIT, UNLESS NOTED OTHERWISE. COORDINATE <br />REQUIREMENTS AND LOCATIONS WITH SYSTEM INSTALLER AND FIRE ALARM <br />SPECIFICATIONS. <br />6. AT A MINIMUM, PROVIDE EXTRA DEEP, DOUBLE GANG COMMUNICATION OUTLET <br />BOXES, (FLUSH MOUNTED WHEREVER PRACTICABLE), WITH SINGLE -GANG PLASTER <br />RING AND 1" CONDUIT STUBBED -UP CONCEALED TO ACCESSIBLE CEILING SPACE, <br />UNLESS NOTED OTHERWISE. PROVIDE SURFACE MOUNTED DATA BOXES WITHIN <br />CABINETRY, AND SELECT OTHER LOCATIONS AS INDICATED ON THE DRAWINGS. <br />COORDINATE TELEPHONE/DATA BOX AND CONDUIT LOCATIONS AND SIZES WITH <br />OWNER AND OTHER TRADES PRIOR TO ROUGH -IN. <br />7. PROVIDE NYLON BUSHINGS FOR ALL COMMUNICATIONS AND LOW VOLTAGE WIRING <br />CONDUITS AND SLEEVES, UNLESS NOTED OTHERWISE. <br />8. ALL COMMUNICATIONS AND LOW VOLTAGE WIRING CONDUIT SHALL BE INSTALLED <br />WITH AN ACCESSIBLE PULLBOX BETWEEN EVERY 180 DEGREE CHANGE IN DIRECTION <br />AND AT 100' INTERVALS OF CONTINUOUS RUNS. <br />9. MINIMUM BEND RADIUS FOR COMMUNICATIONS CONDUIT IS 6 TIMES THE INSIDE <br />DIAMETER FOR CONDUITS 2" IN DIAMETER AND SMALLER AND 10 TIMES THE INSIDE <br />DIAMETER FOR CONDUITS GREATER THAN 2" IN DIAMETER, UNLESS NOTED <br />OTHERWISE. <br />10. LOW VOLTAGE COMMUNICATION, ENERGY MANAGEMENT, SOUND SYSTEM, SECURITY <br />AND RELATED WIRING IS TO BE PERFORMED BY OTHERS UNDER A SEPARATE <br />CONTRACT, UNLESS NOTED OTHERWISE. PROVIDE BOXES AND CONDUIT IN FINISHED <br />AND RATED FLOORS/WALLS/CEILINGS TO ACCESSIBLE LOCATIONS FOR ALL LOW <br />VOLTAGE WIRING. PROVIDE ALL LINE VOLTAGE CIRCUITRY (120V AND HIGHER) TO <br />OWNER FURNISHED EQUIPMENT AND LOW VOLTAGE STEP-DOWN TRANSFORMERS AS <br />REQUIRED. COORDINATE ELECTRICAL REQUIREMENTS AND LOCATIONS WITH SYSTEM <br />INSTALLER AND OWNER. <br />11. ALL LOW VOLTAGE CLASS 2 OR 3 WIRING NOT IN CONDUIT SHALL BE PLENUM RATED <br />WHERE APPLICABLE. <br />12. LOW VOLTAGE CABLE SHEATH LABELS AND RELATED MANUFACTURER INFO SHALL <br />REMAIN APPARENT IN ALL EXPOSED APPLICATIONS. PROTECT ALL EXPOSED CABLING <br />FROM PAINTING AND OVERSPRAY (INCLUDES CABLE NOT ROUTED IN CONDUIT AND <br />THAT IS IN CABLE TRAY). <br />13. CABLES SHALL BE ROUTED THROUGH THE BUILDING CABLE TRAY/RACEWAY SYSTEM, <br />UNLESS NOTED OTHERWISE. EXPOSED CABLING SHALL NOT BE ROUTED IN AREAS <br />EXPOSED TO STRUCTURE UNLESS SPECIFICALLY PERMITTED BY THE OWNER. IN <br />AREAS WHERE EXPOSED CABLES ARE ALLOWED, IT SHALL BE INSTALLED IN A NEAT <br />AND WORKMAN LIKE MANNER IN ACCORDANCE WITH THE OWNER'S REQUIREMENTS. <br />WHERE REQUIRED, PROVIDE CONDUIT TO ROUTE LOW VOLTAGE CABLING TO THE <br />CABLE TRAY OR NEAREST ACCESSIBLE CEILING SPACE. <br />14. CONDUITS FOR COMMUNICATIONS OUTLETS SERVING ELEVATOR EQUIPMENT ROOMS, <br />FACP, AND SIMILAR CRITICAL EQUIPMENT AS DESIGNATED BY THE OWNER SHALL BE <br />CONTINUOUS ("HOMERUN") FROM OUTLET TO SERVING COMMUNICATIONS ROOM. <br />SHEET INDEX <br />CLICCT nC CrE:)I E)TIIIKI <br />E0.1 <br />ELECTRICAL GENERAL NOTES <br />E0.2 <br />ELECTRICAL SYMBOLS AND ABBREVIATIONS <br />E0.3 <br />ELECTRICAL SPECIFICATIONS <br />E2.1 <br />ELECTRICAL SITE POWER PLAN <br />E2.2 <br />ELECTRICAL SITE LIGHTING PLAN <br />E4.1 <br />ELECTRICAL SINGLE LINE AND PANEL SCHEDULE <br />E5.1 <br />TITLE-24 ENERGY COMPLIANCE FORMS <br />APPLICABLE ELECTRICAL CODES: <br />NOTE: PROJECT IS DESIGNED IN COMPLIANCE WITH THE <br />FOLLOWING CODES. THIS IS NOT AN EXHAUSTIVE LIST. <br />PROJECT SHALL COMPLY WITH ALL APPLICABLE <br />CODES, STANDARDS AND LOCAL REQUIREMENTS. <br />2022 CALIFORNIA BUILDING CODE (CBC) <br />2022 CALIFORNIA ENERGY CONSERVATION CODE (CECC) <br />2022 CALIFORNIA ELECTRIC CODE (CEC) <br />2022 CALIFORNIA GREEN BUILDING CODE <br />r <br />Arch i t e c t u ra I <br />Corporation <br />9431 HAVEN AVENUE, SUITE 212 <br />RANCHO CUCAMONGA, CA 91730 <br />P. 909.259.9971 1 F. 909.944.8409 <br />www.AmorArch.com <br />BRISTOL CENTER <br />PROPERTIES LLC <br />714 S PLYMOUTH BLVD <br />LOS ANGELES, CA 90005 <br />AMIR HOURIANI <br />aihouriani@gmail.com <br />Nz r.16Y1i111111r_sLNN <br />cv i <br />E <br />MECHANICAL I ELECTRICAL I PLUMBING <br />CARLOS RIVAS <br />carlos@rivasdesignconsultants.com <br />Z <br />Lu <br />G <br />O <br />J <br />W <br />W <br />W <br />m <br />Qo <br />F_� O <br />W <br />N <br />J <br />OU <br />E Q <br />z <br />z Q <br />CD ~ <br />�z <br />U) <br />w <br />J <br />F <br />F <br />H <br />w <br />w <br />U) <br />U) <br />Lu <br />O <br />z <br />J <br />Q <br />z <br />Lu <br />Q <br />U <br />Lu <br />J <br />Lu <br />STAMP <br />V <br />C - 24421 <br />8/31 /2025 <br />* RENEWAL <br />cSj DATE <br />�TFOF CA1-�FO� <br />DATE SIGNED: 08/13/2024 <br />SHEETS BEARING THIS SEAL AND WET SIGNATURE <br />ARE AUTHENTICATED. RESPONSIBILITY FOR ALL <br />OLDER PLANS, SPECIFICATIONS OR INSTRUMENTS <br />ARE DISCLAIMED. <br />REVISIONS <br />0 <br />0 <br />0 <br />0 <br />0 <br />DATE <br />2024.08.15 <br />PROJECT NUMBER <br />A2641 <br />SHEET NUMBER <br />001 <br />COPYRIGHT 2024 - DESIGNS, DRAWINGS AND SPECIFICATIONS ARE INSTRUMENTS OF SERVICE AND ARE THE PROPERTY OF THE DESIGN PROFESSIONAL. REPRODUCTION PROHIBITED WITHOUT THE EXPRESSED WRITTEN CONSENT OF THE DESIGN PROFESSIONAL. <br />