<br />ELECTRICAL SYMBOLS
<br />THIS IS A MASTER LEGEND AND NOT ALL SYMBOLS OR ABBREVIATIONS ARE USED
<br />STANDARD MOUNTING HEIGHTS
<br />AUDIBLE APPLIANCES (CENTERLINE)
<br />84"
<br />ALARMS
<br />48"
<br />ANNUNCIATOR PANELS (DISPLAY)
<br />60"
<br />CONTROLS (TOP OF DEVICE)
<br />48"
<br />EXIT SIGNS (WALL MOUNTED)
<br />80"
<br />FIRE ALARM ANNUNCIATOR PANEL (DISPLAY)
<br />60"
<br />FIRE ALARM BELL (EXTERIOR) (CENTERLINE)
<br />120"
<br />FIRE ALARM CONTROL PANEL/UNIT (DISPLAY)
<br />60"
<br />INTERCOM (AFEA ONLY)
<br />36"
<br />INTERCOMS (TOP OF DEVICE)
<br />48"
<br />PULL STATIONS (TOP OF DEVICE)
<br />48"
<br />PHOTOCELLS
<br />144"
<br />RECEPTACLES
<br />16"
<br />RECEPTACLES (EXTERIOR)
<br />24"
<br />RECEPTACLES(GARAGES)
<br />24"
<br />RECEPTACLES (POOLS)
<br />27"
<br />RECEPTACLES (ABOVE COUNTER) +6" ABOVE BACKSPLASH/COUNTER, 40" MAX
<br />RECEPTACLES IN EQUIPMENT ROOMS
<br />44"
<br />REMOTE INDICATING LIGHT (EQUIPMENT ROOMS)
<br />48"
<br />REMOTE INDICATING LIGHT (FINISHED AREAS)
<br />CEILING
<br />SAFETY SWITCHES (TOP OF DEVICE)
<br />48"
<br />STARTERS (TOP OF DEVICE)
<br />48"
<br />SWITCHES (TOP OF DEVICE)
<br />44"
<br />TELEPHONE, DATA OUTLETS
<br />SAME AS ADJACENT DEVICE, LINO
<br />TELEPHONE TERMINAL BOARD (BOTTOM)
<br />6"
<br />TELEVISION OUTLETS
<br />REFER TO ARCH DRAWINGS
<br />VISIBLE APPLIANCES (CENTERLINE)
<br />84"
<br />INSTALL OUTLET BOXES AT THE MOUNTING HEIGHTS SHOWN ABOVE LINO IN THE
<br />CONSTRUCTION DOCUMENTS. MOUNTING HEIGHTS LISTED ABOVE, OR ELSEWHERE IN THE
<br />CONSTRUCTION DOCUMENTS, ARE AFF OR AFG TO BOTTOM OF OUTLET BOX, UNO. ALL
<br />DEVICES SHALL BE INSTALLED IN COMPLIANCE WITH CURRENT ADA AND LOCAL
<br />REQUIREMENTS.
<br />AF
<br />AMPERE FUSE SIZE
<br />AFC
<br />ABOVE FINISHED CEILING
<br />AFF
<br />ABOVE FINISHED FLOOR
<br />AFG
<br />ABOVE FINISHED GRADE
<br />AHJ
<br />AUTHORITY HAVING
<br />JURISDICTION
<br />AHU
<br />AIR HANDLING UNIT
<br />AIC
<br />AMPERE INTERRUPTING
<br />CAPACITY
<br />AS
<br />AMPERE SWITCH SIZE
<br />AT
<br />AMPERE TRIP SETTING
<br />ATS
<br />AUTOMATIC TRANSFER SWITCH
<br />AV
<br />AUDIO VISUAL
<br />BAS
<br />BUILDING AUTOMATION
<br />SYSTEM
<br />BKR
<br />BREAKER
<br />C
<br />CONDUIT
<br />CAT
<br />CATEGORY
<br />CATV
<br />CABLE TELEVISION SYSTEM
<br />CCTV
<br />CLOSED CIRCUIT TELEVISION
<br />CD
<br />CANDELA
<br />CKT
<br />CIRCUIT
<br />CODE
<br />APPLICABLE CODE ADOPTED BY
<br />JURISDICTION
<br />CT
<br />CURRENT TRANSFORMER
<br />CTR
<br />CENTER
<br />CVD
<br />CUMULATIVE VOLTAGE DROP
<br />D/DEMO
<br />DEMOLITION
<br />DPDT
<br />DOUBLE -POLE,
<br />DOUBLE -THROW
<br />DPST
<br />DOUBLE -POLE,
<br />SINGLE -THROW
<br />E/ETR/EX
<br />EXISTING TO REMAIN
<br />EC
<br />ELECTRICAL CONTRACTOR
<br />EF
<br />EXHAUST FAN
<br />EM
<br />EMERGENCY
<br />EMS
<br />ENERGY MANAGEMENT
<br />SYSTEM
<br />ELV
<br />ELECTRONIC LOW -VOLTAGE
<br />EWC
<br />ELECTRIC WATER COOLER
<br />FAAP
<br />FIRE ALARM ANNUNCIATOR
<br />PANEL
<br />FACP
<br />FIRE ALARM CONTROL PANEL
<br />FCA
<br />FAULT CURRENT AMPS AVAILABLE
<br />FCU
<br />FAN COIL UNIT
<br />FF
<br />FINISHED FLOOR
<br />FLA
<br />FULL LOAD AMPS
<br />FLR
<br />FLOOR
<br />GC
<br />GENERAL CONTRACTOR
<br />GEC
<br />GROUNDING ELECTRODE
<br />CONDUCTOR
<br />GES
<br />GROUNDING ELECTRODE SYSTEM
<br />GFR
<br />GROUND FAULT RELAY
<br />G
<br />GROUND
<br />IG
<br />ISOLATED GROUND
<br />ISC
<br />SHORT CIRCUIT CURRENT
<br />JB/J-BOX
<br />JUNCTION BOX
<br />LF
<br />LINEAR FEET
<br />LRA
<br />LOCKED ROTOR AMPS
<br />LTG/LTS
<br />LIGHTING/LIGHTS
<br />MAU
<br />MAKE-UP AIR UNIT
<br />MAX
<br />MAXIMUM
<br />MCA
<br />MINIMUM CIRCUIT AMPACITY
<br />MCB
<br />MAIN CIRCUIT BREAKER
<br />MCC
<br />MOTOR CONTROL CENTER
<br />MFR
<br />MANUFACTURER
<br />MIN
<br />MINIMUM
<br />MLO
<br />MAIN LUGS ONLY
<br />MLV
<br />MAGNETIC LOW -VOLTAGE
<br />MOCP
<br />MAXIMUM OVERCURRENT
<br />PROTECTION
<br />MTD
<br />MOUNTED
<br />N/A
<br />NOT APPLICABLE
<br />NF
<br />NON -FUSED
<br />NL
<br />NIGHT LIGHT (24HR ON)
<br />NRTL
<br />NATIONALLY RECOGNIZED
<br />TESTING LABORATORY
<br />(CSA,ETL,NSF,UL)
<br />NTS
<br />NOT TO SCALE
<br />OS
<br />OCCUPANCY SENSOR
<br />P
<br />POLE
<br />PART
<br />PARTIAL CIRCUIT
<br />PH/O
<br />PHASE
<br />PNL
<br />PANEL
<br />PNLBD
<br />PANELBOARD
<br />PROVIDE FURNISH AND INSTALL
<br />PT
<br />POTENTIAL TRANSFORMER
<br />QTY
<br />QUANTITY
<br />R/REL
<br />RELOCATE
<br />RCPT
<br />RECEPTACLE
<br />RLA
<br />RUNNING LOAD AMPS
<br />RTU
<br />ROOFTOP UNIT
<br />SCCR
<br />SHORT-CIRCUIT CURRENT
<br />RATING
<br />SD
<br />SMOKE DUCT DETECTOR
<br />SF
<br />SQUARE FEET
<br />SPDT
<br />SINGLE -POLE,
<br />DOUBLE -THROW
<br />SPST
<br />SINGLE -POLE,
<br />SINGLE -THROW
<br />SSBJ
<br />SUPPLY-SIDE BONDING JUMPER
<br />ST
<br />SHUNT TRIP
<br />SWBD
<br />SWITCHBOARD
<br />SWGR
<br />SWITCHGEAR
<br />TBB
<br />TELECOMMUNICATIONS
<br />BONDING BACKBONE
<br />TBD
<br />TO BE DETERMINED
<br />TGB
<br />TELECOMMUNICATIONS
<br />GROUND BUS BAR
<br />TL
<br />TWISTLOCK
<br />TMGB
<br />TELECOMMUNICATIONS MAIN
<br />GROUND BUS BAR
<br />TX/XFMR TRANSFORMER
<br />TYP
<br />TYPICAL
<br />U/F
<br />UNDERFLOOR
<br />U/G
<br />UNDERGROUND
<br />U/S
<br />UNDERSLAB
<br />UH
<br />UNIT HEATER
<br />LINO
<br />UNLESS NOTED OTHERWISE
<br />UPS
<br />UNINTERRUPTIBLE POWER
<br />SUPPLY
<br />VD
<br />VOLTAGE DROP
<br />VFD
<br />VARIABLE FREQUENCY DRIVE
<br />VS
<br />VACANCY SENSOR
<br />W
<br />WIRE
<br />W/
<br />WITH
<br />WP
<br />WEATHER PROOF
<br />WR
<br />WEATHER RESISTANT
<br />WT
<br />WATERTIGHT
<br />XP
<br />EXPLOSION -PROOF
<br />THROUGHOUT THE DRAWINGS DIFFERENT LINETYPES ARE USED IN COMBINATION WITH
<br />THE SYMBOLS TO INDICATE THE STATUS OF ITEMS AS EXISTING, TO BE DEMOLISHED, TO
<br />BE INCLUDED AS PART OF NEW WORK AND/OR ITEMS WHICH ARE ANTICIPATED TO BE
<br />PROVIDED IN THE FUTURE. THE STATUS OF ITEMS USING THESE LINETYPES ARE RELATIVE
<br />TO THE VIEW IN WHICH THEY APPEAR. PHASING SHOWN IN DRAWINGS IS NOT INTENDED
<br />TO FULLY DESCRIBE ALL NECESSARY CONSTRUCTION PHASING, WHICH IS DETERMINED BY
<br />THE CONTRACTOR AS PART OF THEIR RESPONSIBILITIES. ANY SUCH PHASES DESCRIBED
<br />IN THE CONSTRUCTION DOCUMENTS ARE GENERAL AND ONLY INTENDED TO INDICATE A
<br />BROAD ORDER FOR THE SAKE OF DESCRIBING THE PROJECT. THE FOLLOWING LINETYPES
<br />MAY BE USED ON ANY DEVICE, EQUIPMENT, NOTE, LINE, SHAPE, ETC.
<br />EXISTING I I NEW
<br />DEMOLISH - - - - - - - - - - -- FUTURE — — — — — — — —
<br />ANNOTATION
<br />OMECHANICAL OR FIRE PROTECTION PLAN NOTE CALLOUT
<br />OPLUMBING PLAN NOTE CALLOUT
<br />lflELECTRICAL OR FIRE ALARM PLAN NOTE CALLOUT
<br />OTECHNOLOGY PLAN CALLOUT
<br />PLUMBING EQUIPMENT DESIGNATION. (CONTRACTOR FURNISHED AND
<br />OINSTALLED).
<br />REFER TO PLUMBING FIXTURE OR EQUIPMENT
<br />SCHEDULES
<br />EQUIPMENT DESIGNATION (OWNER FURNISHED, CONTRACTOR
<br />INSTALLED)
<br />CU
<br />MECHANICAL EQUIPMENT DESIGNATION (CONTRACTOR FURNISHED
<br />1
<br />AND INSTALLED UNLESS NOTED OTHERWISE)
<br />CONNECTION POINT OF NEW WORK TO EXISTING
<br />1
<br />DETAIL REFERENCE UPPER NUMBER INDICATES DETAIL NUMBER
<br />E1
<br />LOWER NUMBER INDICATES SHEET NUMBER
<br />1
<br />E1
<br />SECTION CUT DESIGNATION
<br />7 5 HOMERUN TO PANELBOARD. INFORMATION AT ARROWS ARE CIRCUIT
<br />3 NUMBERS AND PANELBOARD FOR TERMINATION. REFER TO
<br />OR [R-#1 P1 PANELBOARD SCHEDULES FOR BRANCH CIRCUIT CONDUCTOR SIZES.
<br />P1-3,5,7
<br />INDICATES RELAY NUMBER
<br />CIRCUIT CONTINUATION OR PARTIAL CIRCUIT
<br />CONDUIT CONCEALED
<br />CONDUIT CONCEALED (EMERGENCY)
<br />CONDUIT IN/UNDER FLOOR/GROUND CONSTRUCTION
<br />EXPOSED CONDUIT
<br />EXPOSED CONDUIT (EMERGENCY)
<br />FLEXIBLE CONDUIT
<br />LOW VOLTAGE CABLE (NOT ROUTED IN CONDUIT)
<br />E) CONDUIT TURNING DOWN
<br />0 CONDUIT TURNING UP
<br />ICONNECTION POINT OR EQUIPMENT TERMINATION
<br />---- N EQUIPMENT TERMINATION
<br />WHERE TICK MARKS ARE SHOWN, THE FOLLOWING SHALL GOVERN:
<br />SWITCHED HOT (PHASE) CONDUCTORS (SHOWN TRAILING
<br />NEUTRAL)
<br />NEUTRAL(GROUNDED)CONDUCTOR
<br />UNSWITCHED HOT (PHASE) CONDUCTORS (SHOWN LEADING
<br />NEUTRAL)
<br />xx
<br />NOTE: HASH MARKS INDICATE QUANTITY OF CONDUCTORS
<br />EQUIPMENT GROUNDING CONDUCTOR IN CONDUIT (GREEN
<br />INSULATION OR BARE)
<br />ISOLATED GROUNDING CONDUCTOR IN CONDUIT (GREEN
<br />INSULATION WITH YELLOW TRACER)
<br />BRANCH CIRCUIT CONDUCTOR TABLE
<br />WHERE TICK MARKS ARE NOT SHOWN, THE FOLLOWING SHALL GOVERN:
<br /># OF POLES HOT (PHASE)* NEUTRAL (GROUNDED)** GROUNDING***
<br />1P (1) (1) UNO (1)
<br />2P (2) (1) LINO (1)
<br />3P (3) (1) UNO (1)
<br />PROVIDE ADDITIONAL CONDUCTORS THROUGH ENTIRE CIRCUIT (SWITCHED,
<br />UNSWITCHED/EM, ETC.) AS INDICATED THROUGHOUT CONSTRUCTION DOCUMENTS
<br />AND AS REQUIRED FOR A COMPLETE AND WORKING SYSTEM.
<br />** REFER TO SPECIFICATIONS FOR LIMITATIONS ON SHARING NEUTRAL (GROUNDED)
<br />CONDUCTORS. DO NOT CIRCUIT AS A MULTI -WIRE BRANCH CIRCUIT, LINO.
<br />*** PROVIDE ADDITIONAL ISOLATED GROUNDING CONDUCTORS WHERE INDICATED.
<br />REFER TO SPECIFICATIONS, PLANS, NOTES, WIRING AND CONTROL DIAGRAMS FOR
<br />ADDITIONAL CIRCUITING REQUIREMENTS.
<br />LIGHTING
<br />A a
<br />LIGHT FIXTURE
<br />a = LOWER CASE LETTER IS SWITCH IDENTIFIER
<br />0
<br />A = UPPER CASE LETTER INDICATES LIGHT FIXTURE TYPE
<br />0 k
<br />J_ = WALL MOUNT
<br />O ®)
<br />> = ARROW INDICATES AIMING DIRECTION
<br />®
<br />LIGHT FIXTURE CIRCUITED AS A NIGHT LIGHT (NL)
<br />®EMERGENCY
<br />LIGHT FIXTURE WITH EMERGENCY LIGHTING BATTERY
<br />TO
<br />PACK OR CONNECTED EMERGENCY SOURCE
<br />NIGHT LIGHT/EMERGENCY LIGHT FIXTURE WITH EMERGENCY BATTERY
<br />PACK OR CONNECTED TO EMERGENCY SOURCE
<br />p
<br />LIGHT FIXTURE WITH DUAL BALLASTS CIRCUITED SEPARATELY
<br />(SHADING IMPLIES EMERGENCY LIGHT FIXTURE)
<br />V '7 '7 #1
<br />LIGHTING TRACK (# INDICATES RELAY NUMBER)
<br />0 0 0 o
<br />MIRROR LIGHTS
<br />0--0 0-1--1
<br />EXTERIOR PARKING LOT LIGHT FIXTURE
<br />OO
<br />EXTERIOR PEDESTRIAN POST TOP LIGHT FIXTURE
<br />O
<br />EXTERIOR LIT BOLLARD LIGHT FIXTURE
<br />EXIT SIGN - CEILING / WALL MOUNTED, ARROWS AS INDICATED, FACE
<br />HATCHED
<br />LJ
<br />EMERGENCY LIGHTING UNIT EQUIPMENT WITH BATTERY PACK -
<br />CEILING/WALL MOUNTED
<br />®
<br />AFEA (AREA FOR EVACUATION ASSISTANCE) SIGN - CEILING/WALL
<br />MOUNTED, ARROWS AS INDICATED
<br />REFER TO LIGHT FIXTURE SCHEDULE FOR MORE INFORMATION.
<br />=
<br />ELECTRICAL PANELBOARD (SURFACE OR FLUSH MOUNT)
<br />0
<br />ELECTRICAL CABINET (SURFACE OR FLUSH MOUNT), TYPE AS NOTED
<br />PLYWOOD TERMINAL BOARD FOR TELEPHONE SYSTEM, LINO. SIZE AS
<br />NOTED
<br />®
<br />SWITCHBOARD OR MOTOR CONTROL CENTER ON HOUSEKEEPING PAD
<br />®
<br />ELECTRICAL DISTRIBUTION PANELBOARD
<br />TRANSFORMER
<br />DISCONNECT SWITCH - "200/3/150/3R" DENOTES
<br />200/3/150/3R
<br />AMPERES/POLE/FUSE/NEMA ENCLOSURE RATING, NF= NON -FUSED,
<br />CB= CIRCUIT BREAKER (200/3/CB), NO VALUE (200/3/150) FOR NEMA
<br />ENCLOSURE MEANS STANDARD NEMA 1 RATING
<br />COMBINATION DISCONNECT (SAFETY) SWITCH AND MOTOR STARTER
<br />30/3/15/1/3R
<br />"30/3/15/1/3R" DENOTES AMPERES/POLE/FUSE/NEMA STARTER
<br />L®
<br />SIZE/NEMA ENCLOSURE RATING. NF= NON -FUSED, CB= CIRCUIT
<br />BREAKER (30/3/CB/1), NO VALUE (200/3/150/1) FOR NEMA ENCLOSURE
<br />MEANS STANDARD NEMA 1 ENCLOSURE RATING
<br />® 2
<br />MAGNETIC MOTOR STARTER, NEMA SIZE AS NOTED. 3-POLE, LINO
<br />VFD
<br />VARIABLE FREQUENCY DRIVE
<br />INDICATING LIGHT
<br />EMERGENCY POWER OFF BUTTON
<br />• •
<br />STOP -START PUSH BUTTON CONTROL STATION
<br />•••
<br />HAND -OFF -AUTO PUSH BUTTON CONTROL STATION
<br />MUSHROOM -TYPE PUSH BUTTON
<br />OVERHEAD PADDLE FAN
<br />BOXES, LIGHTING CONTROL & WIRING DEVICES
<br />SWITCH LETTER DESIGNATIONS AS FOLLOWS:
<br />BLANK = SINGLE POLE
<br />2 = TWO POLE
<br />3 = THREE-WAY
<br />4 = FOUR-WAY
<br />D = DIMMER
<br /># F = FAN SPEED CONTROL
<br />FH = FRACTIONAL HORSEPOWER MANUAL CONTROLLER
<br />IH = INTEGRAL HORSEPOWER MANUAL CONTROLLER
<br />K = KEYED
<br />LV# = LOW VOLTAGE / DIGITAL
<br />M = MANUAL MOTOR STARTER DISCONNECT
<br />OS# = OCCUPANCY SENSOR
<br />WP = WEATHER PROOF
<br />#, OS-MW, P2, P2RL, P4, P4S OR P4RL = REFER TO LIGHTING CONTROL
<br />DEVICE SCHEDULE
<br />VC# = VACANCY SENSOR
<br />ALC AUTOMATIC LOAD CONTROL RELAY
<br />BTS BRANCH CIRCUIT TRANSFER SWITCH
<br />C# CONTACTOR (SIZE, COIL VOLTAGE AND NUMBER OF POLES AS INDICATED)
<br />© TRACK -MOUNTED CURRENT LIMITER (## INDICATES AMPERAGE)
<br />PHOTOELECTRIC SWITCH
<br />TS# TIME SWITCH
<br />LC LIGHTING CONTROLS PROCESSOR AND/OR EQUIPMENT
<br />HUB VIVE HUB (SEE VIVE HUB DEVICE SCHEDULE FOR HUB TYPE & LIGHTING
<br />CONTROL DEVICE SCHEDULE FOR MODEL INFORMATION.)
<br />PP POWER PACK (SEE LIGHTING CONTROL SCHEDULE FOR POWPAK SELECTION &
<br />LIGHTING CONTROL DEVICE SCHEDULE FOR POWPAK MODEL INFORMATION.)
<br />DL DAYLIGHT SENSOR (SEE LIGHTING CONTROL DEVICE SCHEDULE FOR MODEL
<br />INFORMATION.)
<br />OC CEILING MOUNTED OCCUPANCY SENSOR (SEE LIGHTING CONTROL DEVICE
<br />SCHEDULE FOR MODEL INFORMATION.)
<br />SIMPLEX RECEPTACLE - NEMA 5-20R, LINO
<br />DUPLEX RECEPTACLE - NEMA 5-20R, LINO
<br />DOUBLE DUPLEX RECEPTACLE - NEMA 5-20R, LINO
<br />SPECIAL RECEPTACLE - NEMA TYPE AS NOTED
<br />TWIST -LOCK TYPE RECEPTACLE
<br />©
<br />BLANK FACE GFCI FEED THROUGH DEVICE
<br />OR (BGFCI
<br />VVVVYYYY
<br />GFCI TYPE RECEPTACLE'
<br />a OR
<br />(BIG
<br />ISOLATED GROUND TYPE RECEPTACLE"`
<br />4 OR f M
<br />EMERGENCY RECEPTACLE`
<br />RECEPTACLE INSTALLED ABOVE COUNTER OR BACKSPLASH*
<br />RECEPTACLE INSTALLED IN CEILING*
<br />®
<br />RECEPTACLE INSTALLED IN FLOOR*
<br />RECEPTACLE INSTALLED VIA DROP CORD*
<br />ADDITIONAL RECEPTACLE LETTER DESIGNATIONS AS FOLLOWS:
<br />C = AUTOMATICALLY CONTROLLED
<br />CH = CLOCK HANGER TYPE
<br />G = RCPT PROTECTED BY GFCI CIRCUIT BREAKER OR UPSTREAM
<br />GFCI DEVICE
<br />H = HORIZONTALLY MOUNTED
<br />�#
<br />S = MANUALLY SWITCHED
<br />SP / TVSS = SURGE PROTECTION
<br />TR = TAMPER RESISTANT
<br />TV = TELEVISION
<br />USB = USB/DUPLEX
<br />WP = WEATHER PROOF COVER
<br />WR = WEATHER RESISTANT
<br />• • • •
<br />MULTI -OUTLET ASSEMBLY
<br />-
<br />TELEPHONE OUTLET
<br />®
<br />DATA OUTLET
<br />MULTI -SERVICE OUTLET; TELEPHONE AND DATA
<br />\ ` ABOVE COUNTER, TYP
<br />WALL, TYP
<br />FLOOR, TYP
<br />A
<br />MULTI -SERVICE POWER POLE WITH TELEPHONE, DATA AND POWER
<br />z
<br />OUTLETS A = TYPE, REFER TO PLANS, SCHEDULES AND
<br />SPECIFICATIONS
<br />MULTI -SERVICE FLOOR BOX WITH TELEPHONE, DATA AND POWER
<br />�A
<br />OUTLETS A = TYPE, REFER TO PLANS, SCHEDULES AND
<br />SPECIFICATIONS
<br />OA
<br />POKE THROUGH, A = TYPE, REFER TO PLANS, SCHEDULES AND
<br />SPECIFICATIONS
<br />�T
<br />THERMOSTAT
<br />fl O
<br />JUNCTION/OUTLET BOX
<br />SP
<br />SPEAKER
<br />AP
<br />WIRELESS ACCESS POINT
<br />SYMBOL DEMONSTRATED WITH DUPLEX RECEPTACLE, WHEN USED IN COMBINATION
<br />WITH OTHER DEVICES MEANING IS SIMILAR FOR THOSE DEVICE TYPES.
<br />REFER TO LIGHTING CONTROL DEVICE SCHEDULE FOR MORE INFORMATION.
<br />ELECTRICAL ONE -LINE & RISER DIAGRAM
<br />SWITCH (RATING AS INDICATED)
<br />1 3P
<br />C� PA DRAWOUT CIRCUIT BREAKER (RATINGS AS INDICA
<br />v
<br />##A FUSED SWITCH (RATING, POLES AND FUSE TYPE AS IN ICATED)
<br />ID#AB
<br />3P
<br />-AP COMBINATION FUSED SWITCH/STARTER AND STARTER SIZE
<br />'E.A" PE
<br />EMA#
<br />ICIRCUIT BREAKER (RATINGS AS INDICATED) MaStE
<br />PA 3P
<br />CI I
<br />I11111AI •
<br />31113 COMBINATION CIRCUIT BREAKER/STARTER AND STAR RWte.
<br />IS
<br />❑ m PANELBOARD, SINGLE OR MULTI -SECTION (REFER TO
<br />ISOLATED POWER PANELBOARD W/ INTEGRAL TRANSFORMER
<br />r
<br />(REFER TO SCHEDULES)
<br />Tx#
<br />TRANSFORMER (TYPE AND RATINGS AS INDICATED)
<br />TX#
<br />SHIELDED TRANSFORMER (TYPE AND RATINGS AS INDICATED)
<br />ATS#
<br />AUTOMATIC TRANSFER SWITCH (RATINGS AS INDICATED)
<br />I� ##A
<br />ATS#
<br />(W/BYPASS)
<br />AUTOMATIC TRANSFER SWITCH WITH BYPASS (RATINGS AS
<br />INDICATED)
<br />##A
<br />## KW GENERATOR
<br />10, 4W
<br />1111Y1111V,
<br />M/G GENERATOR (RATINGS AS INDICATED)
<br />##A. 3P
<br />_ - NON -SEPARATELY DERIVED SOURCE
<br />OR
<br />SEPARATELY DERIVED SOURCE
<br />MDPSWITCHBOARD ELEC ROOM
<br />##DAMPS 4BOY/27TV304W SWITCHGEAR, SWITCHBOARD AND/OR DISTRIBUTION
<br />PANELBOARD (TYPE, RATING, DEVICES AND
<br />ACCESSORIES AS INDICATED)
<br />DIGITAL
<br />VM AM COMBINATION DIGITAL VOLT METER/AMMETER
<br />### CIRCUIT IDENTIFICATION (REFER TO CIRCUIT SCHEDULE)
<br />GFR GROUND FAULT RELAY
<br />PFR PHASE FAILURE RELAY
<br />HE KIRK -KEY INTERLOCK (# INDICATES KEY PAIR)
<br />ST SHUNT TRIP
<br />AM AMMETER (RANGE AS SPECIFIED OR REQUIRED)
<br />VM VOLTMETER (RANGE AS SPECIFIED OR REQUIRED)
<br />UTILITY
<br />METER M UTILITY METER (AS REQUIRED BY UTILITY)
<br />AS AMMETER SWITCH
<br />VS VOLTMETER SWITCH
<br />WH D WATT-HOUR METER, "D" DENOTES DEMAND REGISTER, "15'
<br />15 DENOTES MINUTES OF DEMAND INTERVAL
<br />CURRENT TRANSFORMER RATING AS SPECIFIED OR REQUIRED
<br />POTENTIAL TRANSFORMER RATING AS SPECIFIED OR REQUIRED
<br />SPD SURGE -PROTECTIVE DEVICE
<br />•--I GROUND CONNECTION
<br />GROUND CONNECTION WITH TEST WELL
<br />Q—� GROUND ROD
<br />LIGHTNING ARRESTER
<br />H CAPACITOR
<br />- CONTACT (OPEN OR CLOSED)
<br />HEATER
<br />HP MOTOR
<br />BLOCK LOAD KW OR KVA
<br />X F# X FP# FAULT POINT REFERENCED IN SHORT CIRCUIT CURRENT AND
<br />VOLTAGE DROP SPREADSHEET
<br />Arch i t e c t u ra I
<br />Corporation
<br />9431 HAVEN AVENUE, SUITE 212
<br />RANCHO CUCAMONGA, CA 91730
<br />P. 909.259.9971 1 F. 909.944.8409
<br />www.AmorArch.com
<br />BRISTOL CENTER
<br />PROPERTIES LLC
<br />714 S PLYMOUTH BLVD
<br />LOS ANGELES, CA 90005
<br />AMIR HOURIANI
<br />aihouriani@gmail.com
<br />CONSULTANT
<br />MECHANICAL I ELECTRICAL I PLUMBING
<br />909-997-0905
<br />CARLOS RIVAS
<br />carlos@rivasdesignconsultants.com
<br />Z
<br />F-
<br />U O
<br />wF—
<br />� Q
<br />OU
<br />Q�O
<br />0- .J
<br />I—
<br />z
<br />5W
<br />G
<br />O
<br />J
<br />W
<br />W
<br />0
<br />W
<br />I—
<br />� O
<br />W ti
<br />N
<br />J O
<br />OU
<br />IY Q
<br />co Z
<br />Z Q
<br />O Z
<br />Cfl
<br />U)
<br />STAMP
<br />z
<br />O
<br />Q
<br />LLJ
<br />Of
<br />Q
<br />z
<br />Q
<br />0
<br />2-7
<br />LL1
<br />Lu
<br />J
<br />U)
<br />J
<br />O
<br />cm
<br />G
<br />U)
<br />J
<br />w 0
<br />J _
<br />H
<br />~
<br />w Lu
<br />J
<br />Lu Lu
<br />�I i I
<br />•
<br />-24421
<br />8/31/2025
<br />Nc* RENEWAL
<br />DATE �Q
<br />qT o CA0F��
<br />DATE SIGNED: 08/13/2024
<br />SHEETS BEARING THIS SEAL AND WET SIGNATURE
<br />ARE AUTHENTICATED. RESPONSIBILITY FOR ALL
<br />OLDER PLANS, SPECIFICATIONS OR INSTRUMENTS
<br />ARE DISCLAIMED.
<br />REVISIONS
<br />DATE
<br />2024.08.15
<br />PROJECT NUMBER
<br />A2641
<br />SHEET NUMBER
<br />COPYRIGHT 2024 - DESIGNS, DRAWINGS AND SPECIFICATIONS ARE INSTRUMENTS OF SERVICE AND ARE THE PROPERTY OF THE DESIGN PROFESSIONAL. REPRODUCTION PROHIBITED WITHOUT THE EXPRESSED WRITTEN CONSENT OF THE DESIGN PROFESSIONAL.
<br />E0.2