ELECTRICAL -SPECIFICATIONS (AS APPLICABLE)
<br />CITY OF SANTA ANA
<br />Plannin �ar1Q.GYYI�iOG.YQP.ncY
<br />PART I - GENERAL
<br />1. CONDITIONS
<br />1.1. FURNISH & INSTALL A COMPLETELY WIRED & OPERATIONAL ELECTRICAL SYSTEM
<br />AS SHOWN & SPECIFIED ON THE DRAWINGS HEREIN, INCLUDING BUT NOT LIMITED
<br />TO, THESE ITEMS:
<br />1.1.1. LIGHTING FIXTURES AS INDICATED & SPECIFIED ON THE PLANS.
<br />1.1.2. ELECTRICAL PANELS, SERVICING, CONDUITS, WIRING, ETC. FOR ALL OUTLETS
<br />& EQUIPMENT.
<br />1.1.3. TELEPHONE OUTLETS & CONDUITS AS INDICATED.
<br />2. RELATED WORK BY OTHERS
<br />2.1. THE ELECTRICAL CONTRACTOR SHALL PROVIDE CONDUIT, TRENCH, & BACKFILL
<br />FOR A ELECTRICAL SERVICE ENTRANCE FROM THE MAIN SERVICE TO THE UTILITY
<br />POINT OF ELECTRICAL SERVICE. THE ELECTRICAL CONTRACTOR SHALL
<br />COORDINATE THE INSTALLATION OF ENTRANCE w/ THE SERVING UTILITY
<br />COMPANY.
<br />2.2. THE ELECTRICAL CONTRACTOR SHALL PROVIDE CONDUIT, TRENCH, & BACKFILL
<br />FOR PRIMARY PHONE & CATV SERVICE FROM THE TELEPHONE TERMINAL BOARD
<br />OR CABINET TO THE PHONE COMPANY & CATV COMPANY POINT OF SERVICE.
<br />3. CODES, REGULATIONS AND STANDARDS
<br />3.1. THE INSTALLATION SHALL COMPLY w/ APPLICABLE LOCAL & STATE CODES,
<br />ORDINANCES, & THE REGULATIONS OF THE CURRENTLY ACCEPTED EDITION OF
<br />THE N.E.C. IT SHALL ALSO COMPLY w/ THE POWER, TELEPHONE, & CATV COMPANY
<br />FURNISHINGS REQUIREMENTS FOR THE INSTALLATION.
<br />3.2. THE FOLLOWING INDUSTRY STANDARDS, SPECIFICATIONS, & CODES ARE MIN.
<br />REQUIREMENTS:
<br />3.2.1. THE NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION STANDARDS.
<br />3.2.2. THE NATIONAL ELECTRICAL CODE, INCLUDING LOCAL AMENDMENTS.
<br />3.2.3. U.L.'s INCORPORATED STANDARDS.
<br />3.2.4. AMERICAN NATIONAL STANDARDS INSTITUTE.
<br />4. INSPECTION OF SITE
<br />4.1. PRIOR TO SUBMITTING A BID FOR ELECTRICAL WORK, THE CONTRACTOR SHALL
<br />VISIT THE PROPOSED SITE OF CONSTRUCTION & SHALL THOROUGHLY ACQUAINT
<br />HIMSELF (HERSELF) w/ EXISTING UTILITIES, & WORKING CONDITIONS TO BE
<br />ENCOUNTERED, ETC. ALLOWANCE WILL NOT BE MADE FOR NONCOMPLIANCE w/
<br />THIS CONDITION AFTER BIDDING.
<br />4.2. ELECTRICAL INSTALLATION SHALL MEET THE EXISTING CONDITIONS.
<br />1. MATERIALS
<br />1.1. ALL MATERIALS SHALL BE NEW & OF THE QUALITY SPECIFIED ON THE PLANS OR
<br />SPECIFICATIONS & MUST CARRY THE U.L.'s APPROVAL COVERING THE PURPOSE
<br />FOR WHICH THEY ARE USED & MEET ALL REQUIREMENTS OF CURRENT
<br />APPLICABLE CODES & REGULATIONS.
<br />2. CONDUIT
<br />2.1. ALL WIRING SHALL BE INSTALLED IN LISTED METALLIC CONDUIT EXCEPT AS
<br />PERMITTED BELOW:
<br />2.1.1. GALVANIZED RIGID STEEL CONDUIT, w/ A 20 MIL PVC COATING WILL BE USED
<br />WHEN IN CONTACT w/ EARTH.
<br />2.1.2. INTERMEDIATE METAL CONDUIT MAY BE USED IN INDOOR LOCATIONS NOT IN
<br />CONTACT w/ THE EARTH.
<br />2.1.3. ELECTRICAL METALLIC TUBING MAY BE USED IN INDOOR LOCATIONS NOT IN
<br />CONTACT w/ EARTH, NOT IN CONCRETE SLABS OR WALLS & NOT SUBJECT TO
<br />DAMAGE.
<br />2.1.4. PVC MAY BE USED IN OR BELOW CONCRETE & DIRECTLY BURIED IN EARTH.
<br />2.1.5. FLEXIBLE STEEL CONDUIT SHALL BE USED FOR INDOOR FINAL CONNECTIONS
<br />TO EQUIPMENT IN LENGTHS NOT TO EXCEED 72".
<br />2.1.6. LIQUID -TIGHT FLEXIBLE STEEL CONDUIT SHALL BE FOR OUTDOOR FINAL
<br />CONNECTIONS TO EQUIPMENT NOT TO EXCEED 36".
<br />2.2. WHERE CONDUITS ENTER OUTLET BOXES, FIXTURES OR CABINETS, FIRMLY
<br />FASTEN w/ STEEL SET SCREW, COMPRESSION CONNECTORS, OR DOUBLE
<br />LOCKNUTS FOR GALVANIZED RIGID CONDUIT. ALL CONNECTIONS SHALL HAVE
<br />BUSHINGS OR INSULATED THROAT CONNECTORS. FIRMLY FASTEN CONDUIT TO
<br />THE BUILDING CONSTRUCTION. RUN EXPOSED CONDUIT PARALLEL TO THE
<br />BUILDING LINES, SUPPORTED BY APPROPRIATE HANGERS (UNISTRUT, T & B,
<br />APPLETON, OR EQUAL).
<br />2.3. COVER METALLIC CONDUIT CONTACTING THE EARTH w/ POLYETHYLENE TAPED
<br />SPIRAL WRAPPED, 1/2 LAPPED TO PROVIDE 20 MIL. THICKNESS. TAPE SHALL BE
<br />SCOTCH NO. 50 TAPE. CONDUITS & DUCTS NOT UNDER BUILDINGS & FEEDER
<br />DUCTS SHALL COMPLY w/ N.E.C. 300-5. MAKE JOINTS w/ COMPOUND WATERTIGHT.
<br />2.4. FITTINGS & CONDUIT BODIES SHALL BE STEEL. NO DIECAST FITTINGS.
<br />2.5. CONDUIT SIZES SHALL BE AS REQUIRED BY CODE & AS INDICATED OR SPECIFIED.
<br />2.6. ALL EMPTY CONDUIT SYSTEMS SHALL HAVE A NYLON PULL STRING TO
<br />FACILITATE INSTALLATION OF FUTURE WIRE.
<br />2.7. SCHEDULE 40 PVC CONDUIT SHALL BE PERMITTED UNDERGROUND w/ PROPER
<br />FITTINGS, ALL U.L. APPROVED & CEMENTED JOINTS. PENETRATIONS THROUGH
<br />FLOOR SLABS & BENDS GREATER THAN 22 DEGREES SHALL BE WRAPPED RIGID
<br />5. STORAGE AND HANDLING OF MATERIAL GALVANIZED STEEL ELBOWS.
<br />5.1. DELIVER MATERIALS & EQUIPMENT TO THE PROJECT IN THE MANUFACTURER' 2.8. CONDUITS & OUTLETS SHALL BE CONCEALED w/ THE BUILDING STRUCTURE,
<br />ORIGINAL, UNOPENED, LABELED CONTAINERS. PROTECT AGAINST MOISTURE, EXCEPT THAT CERTAIN MOTOR & LIGHTING FEEDER CONDUITS MAY BE RUN
<br />TAMPERING, OR DAMAGE FROM IMPROPER HANDLING & STORAGE. CONTRACTOR EXPOSED IN CERTAIN AREAS AS INDICATED ON THE DRAWINGS. CONDUITS
<br />SHALL BE RESPONSIBLE FOR ANY DAMAGE TO WORK OR MATERIALS UNTIL FINAL SHOWN TO BE INSTALLED IN CABINETS, COUNTERS, & CASEWORK SHALL BE RUN
<br />ACCEPTANCE BY THE OWNER, & SHALL MAKE GOOD w/o COST TO THE OWNER, ANY AS DIRECTED BY THE ARCHITECT.
<br />DAMAGE OR LOSS THAT MAY OCCUR DURING THIS PERIOD.
<br />PART II - PRODUCTS & EXECUTION
<br />5.PANELBOARDS
<br />5.1. CIRCUIT BREAKER TYPE AS INDICATED ON DRAWINGS. U.N.O., ALL PANELS SHALL
<br />HAVE PANELBOARD TYPE CONSTRUCTION w/ BOLT -ON CIRCUITS. BREAKERS FOR
<br />3PHASE PANELS. MANUFACTURER's SHALL BE GENERAL ELECTRIC, SQUARE D,
<br />SIEMENS, CUTLER -HAMMER OR EQUAL w/ VOLTAGE, SIZES, & RATINGS AS
<br />INDICATED ON DRAWINGS.
<br />5.2. THE CIRCUIT BREAKERS SHALL BE OPERABLE IN ANY POSITION & BE REMOVABLE
<br />FROM THE FRONT OF THE PANELBOARD w/o DISTURBING ADJACENT UNITS.
<br />BRANCH BREAKERS SHALL BE OF SUCH DESIGN THAT COMBINATION OF
<br />SINGLE-P, DOUBLE-P, & TRIPLE-P BREAKERS CAN BE ASSEMBLED ON THE SAME
<br />PANEL. EACH BRANCH CIRCUIT SHALL BE CLEARLY NUMBERED. BRANCH & MAIN
<br />TERMINALS SHALL BE OF THE SOLDERLESS TYPE. HANDLE TIES TO FORM
<br />MULTI -POLE BREAKERS NOT ACCEPTABLE.
<br />5.3. WIRE TERMINATION FOR PANELBOARDS & CIRCUIT BREAKERS SHALL BE LISTED
<br />AS SUITABLE FOR 75 DEGREES CELSIUS.
<br />5.4. PROVIDE A TYPEWRITTEN CIRCUIT INDEX BEHIND CLEAR PLASTIC ON THE INSIDE
<br />OF THE DOOR. INFORMATION SHALL INCLUDE ROOM & TYPE LOAD SERVED. ALL
<br />CIRCUIT BREAKERS SHALL BE IDENTIFIED, INCLUDING SPARES. INDEX CARD
<br />FRAME SHALL BE METAL, SECURED TO DOOR.
<br />5.5. WHERE PANELBOARDS ARE INSTALLED FLUSH w/ THE WALLS, EXTEND EMPTY
<br />CONDUITS FROM THE PANELBOARD TO AN ACCESSIBLE SPACE ABOVE OR
<br />BELOW. PROVIDE 3/4" (MIN. SIZE) CONDUIT FOR EVERY (3) THREE SINGLE SPARE
<br />CIRCUIT BREAKERS OR SPACE EQUIVALENT MULTI -POLE ARRANGEMENT, OR
<br />FRACTION THEREOF, BUT NOT LESS THAN (2) TWO CONDUITS FOR EACH PANEL.
<br />5.6. PANELBOARDS TO BE PROVIDED w/ COPPER BUSSING ONLY.
<br />5.7. LOAD CENTERS SHALL NOT BE ALLOWED U.N.O.
<br />5.8. ALL NEW PANELBOARDS SHALL COMPLY w/ N.E.0 ARTICLE 110.16. EQUIPMENT
<br />MANUFACTURER's SHALL PROVIDE WARNING LABELS FOR ALL PANELBOARDS,
<br />GENERATORS, AUTOMATIC TRANSFER SWITCHES, ETC. TO WARN QUALIFIED
<br />PERSONS OF POTENTIAL ELECTRIC ARC FLASH HAZARDS. THE MARKING SHALL
<br />BE LOCATED SO AS TO BE CLEARLY VISIBLE BEFORE EXAMINATION,
<br />ADJUSTMENT, SERVICE, OR MAINTENANCE OF THE EQUIPMENT.
<br />6. WIRE
<br />6.1. CONDUCTOR SIZES SHOWN ON THE DRAWINGS ARE BASED ON COPPER WIRE.
<br />U.N.O., ALL WIRE SHALL BE TYPE XHHW FOR FEEDERS OR BRANCH CIRCUITS
<br />LARGER THAN 4 AMERICAN WIRE GAUGE, TYPE THHN/THWN INSULATION FOR
<br />FEEDERS & BRANCH CIRCUITS 4 AMERICAN WIRE GAUGE & SMALLER. ALL
<br />BRANCH CIRCUIT WIRING SHALL BE COPPER. SERVICE & PANEL FEEDERS #1/0 &
<br />LARGER MAY BE ALUMINUM, PROVIDED THE CONDUCTOR SIZES ARE INCREASED
<br />FOR EQUAL OR GREATER AMPACITY & EQUAL OR LESS EQUIVALENT VOLTAGE
<br />DROP. INCREASE CONDUIT SIZE AS REQUIRED. THE WIRES SHALL BE MARKED w/
<br />COLOR TO SIMPLIFY CIRCUIT IDENTIFICATION. U.N.O., BY LOCAL ORDINANCES
<br />GROUND WIRES SHALL BE GREEN, NEUTRAL WIRES SHALL BE 120V-WHITE,
<br />277V-GRAY, & LIVE WIRES 208Y/120V & 120/240 SHALL BE BLACK (PHASE A), RED
<br />(PHASE B), & BLUE (PHASE Q. FOR 480Y/277V CIRCUITS, THE COLOR CODE SHALL
<br />BE BROWN (PHASE A), ORANGE (PHASE B), & YELLOW (PHASE C). THE WIRE SHALL
<br />BE 12 AMERICAN WIRE GAUGE U.N.O. CIRCUIT SHALL BE LABELED IN EACH J-BOX.
<br />6.2. WHERE ALUMINUM WIRE IS USED, ALUMINUM CONDUCTOR MATERIAL SHALL
<br />COMPLY w/ N.E.C. 310-14 & ALL CONNECTIONS & TERMINATIONS SHALL BE
<br />MACHINE COMPRESSION TYPE EQUAL TO BURNDY "HI PLUG" OR "MACADAPT", NO
<br />2.9. ALL CONDUIT SYSTEMS SHALL HAVE A CODE SIZED COPPER GROUND EXCEPTIONS.
<br />5.2. ARRANGE FOR TIMELY DELIVERY OF MATERIALS & EQUIPMENT TO THE JOB SITE IN CONDUCTOR INCREASE CONDUIT SIZE AS REQUIRED.
<br />ORDER TO MINIMIZE THE LENGTH OF TIME BETWEEN DELIVERY & INSTALLATION.
<br />2.10.
<br />CONDUIT PENETRATION THROUGH ROOF SHALL HAVE ROOF FLASHING w/ CAULK
<br />5.3. COVER & PROTECT ANY MATERIAL THAT MAY BE AFFECTED BY WEATHER WHILE IN
<br />TYPE COUNTER FLASHING SLEEVE. INSTALLATION SHALL BE WATERTIGHT.
<br />TRANSIT OR STORED AT THE PROJECT SITE. ANY MATERIAL FOUND DEFECTIVE OR
<br />NOT INSTALLED IN ACCORDANCE w/ THE CONSTRUCTION DOCUMENTS MAY BE
<br />2.11.
<br />CONDUITS SHALL BE ROUTED SURFACE ON THE STRUCTURE, PARALLEL &
<br />REJECTED BY THE ENGINEER.
<br />PERPENDICULAR TO THE STRUCTURE.
<br />6. CLEANUP
<br />3. OUTLET,
<br />PULL, & JUNCTION BOXES
<br />6.1. KEEP THE PREMISES FREE FROM ACCUMULATION OF WASTE MATERIALS, OR
<br />3.1.
<br />EACH SWITCH, LIGHT, RECEPTACLE OR OTHER OUTLET SHALL BE PROVIDED w/A
<br />RUBBISH CAUSED BY EMPLOYEES OR WORK UNDER THIS DIVISION OF THE
<br />CODE GAUGE, GALVANIZED STEEL OUTLET BOX. JUNCTION & PULL BOXES SHALL
<br />SPECIFICATIONS. AT THE COMPLETION OF THE WORK REMOVE ALL SURPLUS
<br />BE CODE GAUGE, GALVANIZED STEEL. OUTLET BOXES SHALL BE OF THE ONE
<br />MATERIALS, TOOLS, ETC., & LEAVE THE PREMISES BROOM -CLEAN.
<br />PIECE, KNOCKOUT TYPE, IN GENERAL 4" SQUARE WITH PLASTER RING. PLASTER
<br />RINGS SHALL BE SET TO PROVIDE NOT MORE THAN 1/8" FROM WALL SURFACE TO
<br />7. EXCAVATION
<br />RING. IN NO CASE SHALL PLASTER RING PROJECT BEYOND SURFACE OF WALL.
<br />SINGLE GANG RINGS SIMILAR TO STEEL CITY 52050 SHALL BE USED FOR 4" BOXES
<br />7.1. PERFORM ALL EXCAVATION & BACK FILLING REQUIRED FOR WORK PERFORMED
<br />IN UNFINISHED BRICK NUMBER 180 BOXES MAY BE USED FOR UNFINISHED
<br />UNDER THIS DIVISION OF THE SPECIFICATIONS. USE EXCAVATED MATERIALS FOR
<br />MASONRY FLUSH WALL OUTLETS. CENTER ALL OUTLET BOXES IN BLOCK
<br />BACKFILL UNLESS OFF SITE MATERIALS ARE DEEMED NECESSARY.
<br />COURSE.
<br />8. DRAWINGS
<br />3.2.
<br />BOXES INSTALLED IN POURED CEMENT FLOORS SHALL BE FLUSH TYPE CAST
<br />IRON OR STEEL w/ WATERTIGHT CASKETED COVERS. WHERE BOXES ARE
<br />8.1. THE DRAWINGS INDICATE THE GENERAL ARRANGEMENT & LOCATIONS OF THE
<br />INSTALLED IN FLOORS w/ TILE OR CARPET FLOOR COVERING, COVERS SHALL BE
<br />ELECTRICAL WORK. DATA PRESENTED ON THESE DRAWINGS ARE AS ACCURATE
<br />OF THE RECESSED TYPE TO ACCOMMODATE THE FLOOR COVERING.
<br />AS PLANNING CAN DETERMINE, BUT FIELD VERIFICATION OF ALL DIMENSIONS,
<br />LOCATIONS, LEVELS, ETC., TO SUIT FIELD CONDITIONS IS REQUIRED. REVIEW ALL
<br />3.3.
<br />BOXES INSTALLED FOR THE ALARM, COMPUTER, & SECURITY SYSTEM SHALL BE
<br />ARCHITECTURAL, STRUCTURAL, & MECHANICAL DRAWINGS & ADJUST ALL WORK
<br />PROVIDED w/ APPROPRIATE COVER PLATES.
<br />TO MEET THE REQUIREMENTS OF CONDITIONS SHOWN. THE ARCHITECTURAL
<br />DRAWINGS SHALL TAKE PRECEDENCE OVER ALL OTHER DRAWINGS.
<br />3.4.
<br />BOXES FOR TELEPHONE, COMPUTER, T.V., FIRE ALARM, SECURITY, & SIMILAR
<br />DISCREPANCIES BETWEEN DIFFERENT PLANS, OR BETWEEN DRAWINGS &
<br />SYSTEMS SHALL BE MIN. 4" SQUARE AND 2-1/8" DEEP.
<br />SPECIFICATIONS, OR REGULATIONS & CODES GOVERNING THE INSTALLATION
<br />SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER IN WRITING BEFORE
<br />4. SWITCHBOARDS
<br />THE DATE OF BID OPENING. IF DISCREPANCIES ARE NOT REPORTED, THE
<br />CONTRACTOR SHALL BID THE GREATER QUANTITY OR BETTER QUALITY, &
<br />4.1.
<br />SWITCHBOARDS SHALL BE PROVIDED w/ FULLY RATED COPPER OR ALUMINUM
<br />cn
<br />APPROPRIATE ADJUSTMENTS WILL BE MADE AFTER CONTRACT AWARD.
<br />BUS. HORIZONTAL TAPERED BUSSING SHALL NOT BE ALLOWED.
<br />2
<br />CONTRACTOR SHALL BE RESPONSIBLE TO FIELD MEASURE & CONFIRM MOUNTING
<br />HEIGHTS & LOCATION OF ELECTRICAL EQUIPMENT w/ RESPECT TO COUNTERS,
<br />4.2.
<br />ACCEPTABLE MANUFACTURERS - CUTLER HAMMER, SEIMENS, SQUARE D OR
<br />RADIATION, ETC. DO NOT SCALE DISTANCES OFF THE ELECTRICAL DRAWINGS, USE
<br />APPROVED EQUAL.
<br />c,
<br />ACTUAL BUILDING DIMENSIONS.
<br />�I
<br />4.3.
<br />FACTORY ASSEMBLED DEAD FRONT, METAL ENCLOSED, & SELF-SUPPORTING
<br />ca
<br />9. EXCAVATION, CUTTING & FITTING
<br />SWITCHBOARD ASSEMBLY CONFORMING TO N.E.M.A. PB 2, U.L. 891, & COMPLETE
<br />FROM INCOMING LINE TERMINALS TO LOAD SIDE TERMINATIONS.
<br />c
<br />9.1. PERFORM THE EXCAVATION, CUTTING, FITTING, REPAIRING, & FINISHING OF THE
<br />cn
<br />WORK NECESSARY FOR THE INSTALLATION OF THE EQUIPMENT OF THIS SECTION.
<br />4.4.
<br />LINE & LOAD TERMINATIONS: ACCESSIBLE FROM ONLY THE FRONT OF THE
<br />N
<br />N
<br />HOWEVER, NO CUTTING OF THE WORK OF OTHER TRADES OR OF ANY
<br />SWITCHBOARD. SUITABLE FOR THE CONDUCTOR MATERIALS & NUMBER OF
<br />D
<br />STRUCTURAL MEMBERS SHALL BE DONE w/o THE CONSENT OF THE ARCHITECT.
<br />CONDUCTORS USED.
<br />10. COOPERATION w. OTHER CONTRACTORS
<br />4.5.
<br />BUS CONNECTIONS: BOLTED. ACCESSIBLE FROM FRONT FOR MAINTENANCE.
<br />PROVIDE BELLEVILLE WASHERS FOR CONNECTION & PROPERLY TORQUE.
<br />10.1. COOPERATE w/ THE OTHER TRADES SO THAT THE INSTALLATION OF THE
<br />L
<br />ELECTRICAL OUTLETS & EQUIPMENT WILL BE PROPERLY COORDINATED TO AVOID
<br />4.6.
<br />PROVIDE FULLY -RATED NEUTRAL BUS & FULLY RATED GROUND BUS MATCHING
<br />CONFLICT w/ THE PIPING, DUCTWORK, STEEL, BEAMS, OR OTHER OBSTRUCTIONS.
<br />MATERIAL USED FOR MAIN BUS.
<br />CAREFULLY CHECK LOCATIONS OF OUTLET BOXES & DETERMINE THAT THEY HAVE
<br />o NOT BEEN DISTURBED DURING THE INSTALLATION OF OTHER TRADE MATERIALS. 4.7. FUTURE PROVISIONS: FULLY EQUIP SPACES FOR FUTURE DEVICES w/ BUSSING &
<br />,It BUS CONNECTIONS. SUITABLY INSULATED & BRACED FOR SHORT CIRCUIT
<br />Nt
<br />0 10.2. COORDINATE THE LOCATION OF THE TRENCHES & CONDUITS FOR ELECTRICAL & CURRENTS. CONTINUOUS CURRENT RATING AS INDICATED ON DRAWINGS.
<br />TELEPHONE UTILITY SERVICES w/ THE GENERAL CONTRACTOR.
<br />co
<br />6.3. NO WIRE SHALL BE INSTALLED IN THE CONDUIT SYSTEM UNTIL THE CONDUIT
<br />SYSTEM IS COMPLETE. USE MINERALAC NO. 100 OR EQUIVALENT AS A
<br />LUBRICANT TO FACILITATE THE INSTALLATION OF THE CONDUCTORS IN THE
<br />CONDUIT SYSTEM.
<br />6.4. SPLICES IN EXTERIOR PULL BOXES & MANHOLES SHALL BE WEATHERPROOF
<br />USING "SCOTCHCAST" SPLICE KIT OR APPROVED EQUAL. SEAL ENDS OF
<br />CONDUITS & DUCTS w/ "DUCTSEAL" OR APPROVED EQUAL.
<br />6.5. PROVIDE SOLID CONDUCTOR FOR 12 AMERICAN WIRE GAUGE & SMALLER.
<br />7. WIRING DEVICES
<br />7.1. WALL SWITCHES SHALL BE SPECIFICATION GRADE AC SILENT TYPE SWITCHES,
<br />20A, 120/277 VOLT.
<br />7.2. RECEPTACLES SHALL BE SPECIFICATION GRADE, DUPLEX TYPE, NEMA 5-20R, 20
<br />AMPERE, 120 VOLT GROUNDED TYPE. SPECIAL APPLICATION RECEPTACLES
<br />SHALL BE INDICATED ON PLANS. MOUNT w/ THE GROUND DOWN.
<br />7.3. DEVICE PLATES SHALL BE EQUAL TO SIERRA SMOOTH -LINE PLASTIC WALL
<br />PLATES. COLOR SHALL BE WHITE, U.N.O.
<br />7.4. RECEPTACLES IN OUTDOOR & WET LOCATIONS SHALL BE INSTALLED w/ A HINGED
<br />OUTLET COVER/ENCLOSURE CLEARLY MARKED & U.L. LISTED SUITABLE FOR WET
<br />LOCATIONS WHILE IN USE, EQUAL TO TAYMAC SPECIFICATION GRADE.
<br />8. LIGHTING FIXTURE
<br />8.1. PROVIDE ALL LIGHTING FIXTURES, WIRED & CONNECTED. THE DRAWINGS
<br />INDICATE THE FIXTURES FOR EACH LOCATION. PROVIDE LAMPS FOR ALL
<br />FIXTURES. THE LAMPS SHALL BE BY THE SAME MANUFACTURER. VERIFY CEILING
<br />CONSTRUCTION BEFORE ORDERING RECESSED UNITS. PROVIDE PLASTER
<br />FRAMES & HANGERS AS REQUIRED. CEILING CONSTRUCTION, ARCHITECTURAL
<br />ACCESSORIES, VOLTAGE, & BALLASTS TO MEET THE EXISTING CONDITION.
<br />9. SERVICE ENTRANCE SECTION
<br />9.1. SERVICE ENTRANCE EQUIPMENT SHALL BE AS INDICATED ON THE DRAWINGS
<br />EQUIPMENT SHALL CARRY THE U.L. LABEL & CONFORM TO THE POWER COMPANY
<br />REGULATIONS.
<br />9.2. SERVICE ENTRANCE EQUIPMENT SHALL BE PROVIDED w/ A FULLY RATED COPPER
<br />OR ALUMINUM BUS. HORIZONTALLY TAPERED BUSSING SHALL NOT BE ALLOWED.
<br />10. SYSTEM GROUNDING
<br />10.1. GROUNDING SHALL COMPLY w/ REQUIREMENTS OF ARTICLE 250. ALL EXPOSED
<br />NONCURRENT CARRYING METALLIC PARTS OF ELECTRICAL EQUIPMENT,
<br />METALLIC RACEWAY SYSTEMS, METALLIC CABLE ARMOR, GROUNDING
<br />CONDUCTORS OF NONMETALLIC SHEATHED CABLES, GROUNDING CONDUCTORS
<br />IN NONMETALLIC RACEWAYS, & GROUNDED CONDUCTORS OF THE WIRING
<br />SYSTEMS SHALL BE GROUNDED.
<br />10.2. GROUNDING CONDUCTOR (NEUTRAL) OF THE WIRING SYSTEM SHALL BE
<br />CONNECTED TO THE SYSTEM GROUNDING CONDUCTOR AT A SINGLE PLACE IN
<br />EACH SYSTEM BY REMOVABLE BONDING JUMPERS; SIZED ACCORDING TO THE
<br />APPLICABLE PROVISIONS OF THE N.E.C. THE GROUNDED CONDUCTOR (NEUTRAL)
<br />TO THE GROUNDING CONDUCTOR CONNECTION SHALL BE LOCATED IN THE
<br />ENCLOSURE FOR THE SYSTEM's OVERCURRENT PROTECTION OR WHERE
<br />OTHERWISE INDICATED ON THE PLANS OR SPECIFICATIONS.
<br />10.3. A GROUND BUS SEPARATE FROM THE NEUTRAL BUS SHALL BE PROVIDED IN ALL
<br />SWITCHBOARDS & PANELBOARDS. GROUND BUS SHALL BE TORQUED (CHECKED)
<br />PRIOR TO ENERGIZING EQUIPMENT PER MANUFACTURER's RECOMMENDATIONS.
<br />10.4. GROUND BUSES & NEUTRAL BUSES IN ALL DISTRIBUTION PANELS,
<br />SWITCHBOARDS, PANELBOARDS, & THOSE PROVIDED IN ANY EQUIPMENT SHALL
<br />BE ISOLATED EXCEPT WHERE REQUIRED TO BE CONNECTED AS SPECIFIED
<br />ABOVE FOR THE SERVICE ENTRANCE & IN TRANSFORMER TERMINAL
<br />COMPARTMENTS.
<br />10.5. WHEN INDICATED ON THE DRAWINGS, EQUIPMENT GROUNDING CONDUCTORS
<br />SHALL BE EXTENDED FROM THE GROUND BUS IN THE DISTRIBUTION EQUIPMENT
<br />TO THE RECEPTACLE, FIXTURE OR DEVICE LUGS WHERE THEY ARE PROVIDED.
<br />WHERE LUGS ARE NOT PROVIDED, EQUIPMENT GROUNDING CONDUCTORS SHALL
<br />BE CONNECTED TO EQUIPMENT ENCLOSURES. THE CONNECTIONS SHALL BE
<br />ARRANGED SUCH THAT REMOVAL OF THE RECEPTACLE, EQUIPMENT GROUND
<br />CONDUCTORS, OR GROUND JUMPERS FROM GROUND BUSING SHALL NOT
<br />AFFECT THE GROUND SYSTEM.
<br />10.6. RACEWAYS MAY NOT BE USED AS A GROUNDING CONDUCTOR FOR POWER &
<br />LIGHTING CIRCUITS. ALL CONDUITS SHALL HAVE SEPARATE CODE SIZED GREEN
<br />GROUND WIRE INSTALLED IN THE CONDUIT TO INSURE A CONTINUOUS
<br />GROUNDING PATH.
<br />10.7. IN INACCESSIBLE LOCATIONS, MAKE CONNECTIONS BY EXOTHERMIC WELD
<br />PROCESS.
<br />10.8. IN ACCESSIBLE LOCATIONS, CONNECTIONS SHALL BE MADE w/ BOLTED
<br />THROUGH, APPROVED SOLDERLESS BRONZE GROUNDING DEVICES.
<br />10.9. BOND TOGETHER METAL SIDING NOT ATTACHED TO GROUNDED STRUCTURE.
<br />11. TELEPHONE SYSTEM
<br />11.1. TELEPHONE WALL OUTLETS SHALL CONSIST OF STANDARD BOXES MOUNTED 18"
<br />ABOVE THE FLOOR U.N.O. CONNECT OUTLETS TO TELEPHONE TERMINAL w/
<br />SEPARATE 3/4" CONDUIT U.N.O. ON DRAWINGS. PROVIDE A TERMINAL MOUNTING
<br />BOARD FOR THE INCOMING SERVICE CABLE.
<br />12. LIGHTING CONTROL
<br />12.1. FURNISH & INSTALL TIME SWITCHES, PHOTOCELLS, CONTACTORS & FULL
<br />LIGHTING CONTROL SYSTEMS AS REQUIRED FOR LIGHTING CONTROLS
<br />INDICATED ON THE DRAWINGS.
<br />12.2. TIME SWITCHES SHALL BE EQUAL TO PARAGON, GENERAL ELECTRIC, TORK, OR
<br />INTERMATIC & SHALL HAVE SIZE & NUMBER OF POLES AS REQUIRED.
<br />12.3. PHOTOCELLS SHALL BE EQUAL TO TORK OR INTERMATIC w/ VOLTAGE AS
<br />INDICATED.
<br />13. LIGHTING INVERTER SYSTEM
<br />13.1. LIGHTING INVERTERS SHALL HAVE A CENTRAL BATTERY AS EMERGENCY POWER
<br />SOURCE FOR EGRESS LIGHTING w/ SIZE & VOLTAGE AS INDICATED ON THE
<br />DRAWINGS.
<br />13.2. ACCEPTABLE MANUFACTURES - DUAL-LITE, HUBBELL LIGHTING, LITHONIA
<br />LIGHTING EMERGENCY LIGHTING SYSTEMS, MCPHILBEN EMERGENCY LIGHTING
<br />OR APPROVED EQ.
<br />13.3. UNIT SHALL AUTOMATICALLY SENSE LOSS OF NORMAL AC SUPPLY & USE A
<br />SOLID-STATE SWITCH TO TRANSFER LOADS. TRANSFER IN 0.004 SECOND OR
<br />LESS FROM NORMAL SUPPLY TO BATTERY -INVERTER SUPPLY. INVERTER SHALL
<br />BE COMPATIBLE w/ INCANDESCENT, MAGNETIC & ELECTRONIC FLUORESCENT
<br />BALLASTS, HIGH POWER FACTOR COMPACT FLUORESCENT, & HIGH INTENSITY
<br />DISCHARGE LAMP TYPES.
<br />13.4. UNIT SHALL SUPPLY POWER TO OUTPUT CIRCUITS FROM A SINGLE, EXTERNAL,
<br />NORMAL SUPPLY SOURCE. UNIT AUTOMATICALLY TRANSFERS LOAD FROM
<br />NORMAL SOURCE TO INTERNAL BATTERY/INVERTER SOURCE. RETRANSFER TO
<br />NORMAL IS AUTOMATIC WHEN NORMAL POWER IS RESTORED.
<br />13.5. UNIT SHALL COMPLY w/ NATIONAL FIRE PROTECTION AGENCY 70 & 101. & BE U.L.
<br />924 LISTED.
<br />13.6. UNIT SHALL SUSTAIN A FULL -CAPACITY OUTPUT FOR A MIN. OF 90 MINUTES.
<br />PROVIDE BATTERIES THAT ARE MAINTENANCE FREE, SEALED LEAD CALCIUM
<br />BATTERY w/ AN EXPECTED LIFE OF NO LESS THAN 10 YEARS.
<br />13.7. UNIT SHALL CONTAIN GROUP DISPLAYS, INDICATIONS, & BASIC SYSTEM
<br />CONTROLS ON COMMON CONTROL PANEL ON FRONT OF CENTRAL BATTERY
<br />INVERTER ENCLOSURE.
<br />13.8. ENCLOSURE SHALL BE STEEL, w/ HINGED LOCKABLE DOORS, SUITABLE FOR
<br />FLOOR MOUNTING. MANUFACTURER's STANDARD CORROSION -RESISTANT FINISH.
<br />14. UNINTERRUPTIBLE POWER SUPPLY (UPS)
<br />14.1. UPS SHALL BE A CONTINUOUS DUTY, (3) THREE PHASE, ONLINE, SOLID STATE
<br />UNINTERRUPTIBLE POWER SUPPLY SYSTEM w/ SIZE & VOLT. AS INDICATED ON
<br />THE DRAWINGS.
<br />14.2. ACCEPTABLE MANUFACTURERS: TOSHIBA INTERNATIONAL CORPORATION, MGE
<br />UPS SYSTEMS & MITSUBISHI.
<br />14.3. UPS SHALL AUTOMATICALLY SENSE LOSS OF NORMAL AC POWER SUPPLY &
<br />CONVERT IT TO DC POWER. THE DC POWER IS THEN USED TO CHARGE THE
<br />BATTERY BANK WHILE PROVIDING CLEAN, DC POWER TO THE INVERTER
<br />CIRCUITRY. THE INVERTER WILL CONVERT DC POWER TO REGULATED AC POWER
<br />TO FEED THE LOAD.
<br />14.4. UPON FAILURE OF COMMERCIAL AC POWER, THE UPS SHALL DERIVE POWER
<br />FROM THE BATTERY BANK & CONTINUE FEEDING THE LOAD w/ CLEAN,
<br />REGULATED AC POWER. THERE SHALL BE NO INTERRUPTION TO THE CRITICAL
<br />LOAD UPON FAILURE OR RESTORATION OF COMMERCIAL AC POWER.
<br />14.5. UPON RESTORATION OF THE COMMERCIAL AC SOURCE, THE
<br />RECTIFIER/CHOPPER POWERS THE INVERTER WHILE SIMULTANEOUSLY
<br />RECHARGING THE BATTERY BANK.
<br />14.6. UNIT SHALL COMPLY w/ NATIONAL FIRE PROTECTION AGENCY 7), AMERICAN
<br />NATIONAL STANDARDS INSTITUTE C62.41 (IEEE 587), INTERNATIONAL
<br />ORGANIZATION FOR STANDARDIZATION 9001, 14001 & BE U.L. 1778 LISTED.
<br />14.7. THE UPS SHALL SUSTAIN A FULL -CAPACITY OUTPUT FOR A MIN. OF 4lblJjF P
<br />PROVIDE BATTERIES THAT ARE MAINTENANCE FREE, ABSOR ED S
<br />(AGM) w/ AN EXPECTED LIFE OF NO LESS THAN 10 YEARS.
<br />14.8. UNIT SHALL CONTAIN GROUP DISPLAYS, INDICATIONS & BASIC EYSTEM
<br />CONTROLS ON COMMON CONTROL PANEL ON FRONT OF UPS ENCLOSURE.
<br />14.9. ENCLOSURE SHALL BE STEEL, w/ HINGED LOCKABLE DOORS, S IT
<br />� FLOOR MOUNTING. MANUFACTURER's STANDARD CORROSIO -RL9�`H�1 SH1
<br />14.10. UPS TO BE PROVIDED w/ AN EMERGENCY POWER OFF SWITCH TDA&M THE
<br />UPS & BATTERY CIRCUIT BREAKERS. UPS SHALL CONTAIN Ac ERIAL DATA LINK TO
<br />ENABLE UPS TO INTERFACE TO A COMPUTER THAT WILL PRO IDE STATUS &
<br />DIAGNOSTIC INFORMATION.
<br />14.11. UPS SHALL USE INSULATED -GATE BIPOLAR TRANSISTOR TECHNOLOGY FOR THE
<br />POWER INPUT SECTION. UPS SHALL NOT REQUIRE AN OVERSIZED GENERATOR
<br />TO MAINTAIN CONTINUOUS POWER TO EQUIPMENT.
<br />15. GUARANTEE
<br />15.1. IT IS GUARANTEED THAT ALL MATERIAL FURNISHED & ALL WORKMANSHIP
<br />PERFORMED FOR A PERIOD OF (1) ONE YEAR FROM DATE OF FINAL ACCEPTANCE
<br />OF WORK. ANY DEFECTS DEVELOPING WITHIN THIS PERIOD, TRACEABLE TO
<br />MATERIAL FURNISHED AS A PART OF THIS SECTION OR WORKMANSHIP
<br />PERFORMED HEREUNDER, SHALL BE MADE GOOD AT NO EXPENSE TO THE
<br />OWNER.
<br />16. SHOP DRAWINGS & APPROVALS
<br />16.1. THE ITEMS SPECIFIED HEREIN & ON DRAWINGS ARE USED AS A STANDARD OF
<br />QUALITY. ANY MATERIALS OF EQUAL QUALITY & AESTHETIC VALUE WILL BE GIVEN
<br />CONSIDERATION AS A SUBSTITUTE FOR THE MATERIALS SPECIFIED. NO
<br />APPROVAL WILL BE GIVEN TO A SPECIFIC CATALOG NUMBER, MODEL, OR TYPE
<br />OF EQUIPMENT, PRIOR TO BIDDING. AFTER BIDDING, THE DECISION OF THE
<br />ARCHITECT &/or ENGINEER DETERMINING EQUAL MATERIALS WILL BE FINAL.
<br />16.2. THE CONTRACTOR SHALL SUBMIT (7) SEVEN IDENTICAL BOUND SETS OF SHOP
<br />DRAWINGS ON THE FOLLOWING ITEMS:
<br />16.2.1. LIGHTING FIXTURE CUTS & PERFORMANCE DATA.
<br />16.2.2. OUTLINE DRAWINGS & DATA SHEETS OF EACH PANELBOARD &
<br />SWITCHBOARD.
<br />16.2.3. OUTLINE DRAWINGS OF ALL SWITCHGEAR.
<br />16.3. SUBMIT ITEMS AT ONE TIME IN A NEAT & ORDERLY MANNER WITHIN 15 DAYS OF
<br />AWARD OF CONTRACT. PARTIAL SUBMITTALS WILL NOT BE ACCEPTABLE.
<br />17. RECORD & AS -BUILT DRAWINGS
<br />17.1. THE ELECTRICAL CONTRACTOR SHALL MAINTAIN A SET OF DRAWINGS AT THE
<br />JOB SITE FOR THE EXCLUSIVE PURPOSE OF MAINTAINING A RECORD OF ALL
<br />WORK INSTALLED & TO SHOW ANY DEVIATIONS FROM THE WORK INDICATED ON
<br />THE DRAWINGS.
<br />17.2. AT THE COMPLETION OF THE PROJECT, ONE SET OF REPRODUCIBLE DRAWINGS,
<br />SHOWING ALL AS -BUILT CONDITIONS, SHALL BE DELIVERED TO THE OWNER FOR
<br />ACCEPTANCE PRIOR TO FINAL PAYMENT.
<br />E
<br />Arch i t e c t u ra I
<br />Corporation
<br />9431 HAVEN AVENUE, SUITE 212
<br />RANCHO CUCAMONGA, CA 91730
<br />P. 909.259.9971 1 F. 909.944.8409
<br />www.AmorArch.com
<br />BRISTOL CENTER
<br />PROPERTIES LLC
<br />714 S PLYMOUTH BLVD
<br />LOS ANGELES, CA 90005
<br />AMIR HOURIANI
<br />aihouriani@gmail.com
<br />NKellilk [.Y11Imr_\LNN
<br />MECHANICAL I ELECTRICAL I PLUMBING
<br />909-997-0905
<br />CARLOS RIVAS
<br />carlos@rivasdesignconsultants.com
<br />Z
<br />Lu
<br />O
<br />\W
<br />W
<br />W
<br />m
<br />STAMI
<br />Lu
<br />J
<br />w
<br />Lu
<br />U)
<br />m
<br />3
<br />C - 24421
<br />8/31 /2025
<br />U)
<br />Z
<br />O
<br />Q
<br />0
<br />LL
<br />W
<br />CIL
<br />U)
<br />J
<br />Q
<br />U_
<br />Lu
<br />J
<br />Lu
<br />* RENEWAL
<br />cSj DATE
<br />�TFOF CWFo�
<br />DATE SIGNED: 08/13/2024
<br />SHEETS BEARING THIS SEAL AND WET SIGNATURE
<br />ARE AUTHENTICATED. RESPONSIBILITY FOR ALL
<br />OLDER PLANS, SPECIFICATIONS OR INSTRUMENTS
<br />ARE DISCLAIMED.
<br />REVISIONS
<br />0
<br />0
<br />0
<br />0
<br />DATE
<br />2024.08.15
<br />PROJECT NUMBER
<br />A2641
<br />SHEET NUMBER
<br />003
<br />co
<br />10.3. COORDINATE HVAC EQUIPMENT CONNECTION REQUIREMENTS w/ HVAC
<br />o CONTRACTOR.
<br />nCCOPYRIGHT 2024 - DESIGNS, DRAWINGS AND SPECIFICATIONS ARE INSTRUMENTS OF SERVICE AND ARE THE PROPERTY OF THE DESIGN PROFESSIONAL. REPRODUCTION PROHIBITED WITHOUT THE EXPRESSED WRITTEN CONSENT OF THE DESIGN PROFESSIONAL