Laserfiche WebLink
ELECTRICAL -SPECIFICATIONS (AS APPLICABLE) <br />CITY OF SANTA ANA <br />Plannin �ar1Q.GYYI�iOG.YQP.ncY <br />PART I - GENERAL <br />1. CONDITIONS <br />1.1. FURNISH & INSTALL A COMPLETELY WIRED & OPERATIONAL ELECTRICAL SYSTEM <br />AS SHOWN & SPECIFIED ON THE DRAWINGS HEREIN, INCLUDING BUT NOT LIMITED <br />TO, THESE ITEMS: <br />1.1.1. LIGHTING FIXTURES AS INDICATED & SPECIFIED ON THE PLANS. <br />1.1.2. ELECTRICAL PANELS, SERVICING, CONDUITS, WIRING, ETC. FOR ALL OUTLETS <br />& EQUIPMENT. <br />1.1.3. TELEPHONE OUTLETS & CONDUITS AS INDICATED. <br />2. RELATED WORK BY OTHERS <br />2.1. THE ELECTRICAL CONTRACTOR SHALL PROVIDE CONDUIT, TRENCH, & BACKFILL <br />FOR A ELECTRICAL SERVICE ENTRANCE FROM THE MAIN SERVICE TO THE UTILITY <br />POINT OF ELECTRICAL SERVICE. THE ELECTRICAL CONTRACTOR SHALL <br />COORDINATE THE INSTALLATION OF ENTRANCE w/ THE SERVING UTILITY <br />COMPANY. <br />2.2. THE ELECTRICAL CONTRACTOR SHALL PROVIDE CONDUIT, TRENCH, & BACKFILL <br />FOR PRIMARY PHONE & CATV SERVICE FROM THE TELEPHONE TERMINAL BOARD <br />OR CABINET TO THE PHONE COMPANY & CATV COMPANY POINT OF SERVICE. <br />3. CODES, REGULATIONS AND STANDARDS <br />3.1. THE INSTALLATION SHALL COMPLY w/ APPLICABLE LOCAL & STATE CODES, <br />ORDINANCES, & THE REGULATIONS OF THE CURRENTLY ACCEPTED EDITION OF <br />THE N.E.C. IT SHALL ALSO COMPLY w/ THE POWER, TELEPHONE, & CATV COMPANY <br />FURNISHINGS REQUIREMENTS FOR THE INSTALLATION. <br />3.2. THE FOLLOWING INDUSTRY STANDARDS, SPECIFICATIONS, & CODES ARE MIN. <br />REQUIREMENTS: <br />3.2.1. THE NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION STANDARDS. <br />3.2.2. THE NATIONAL ELECTRICAL CODE, INCLUDING LOCAL AMENDMENTS. <br />3.2.3. U.L.'s INCORPORATED STANDARDS. <br />3.2.4. AMERICAN NATIONAL STANDARDS INSTITUTE. <br />4. INSPECTION OF SITE <br />4.1. PRIOR TO SUBMITTING A BID FOR ELECTRICAL WORK, THE CONTRACTOR SHALL <br />VISIT THE PROPOSED SITE OF CONSTRUCTION & SHALL THOROUGHLY ACQUAINT <br />HIMSELF (HERSELF) w/ EXISTING UTILITIES, & WORKING CONDITIONS TO BE <br />ENCOUNTERED, ETC. ALLOWANCE WILL NOT BE MADE FOR NONCOMPLIANCE w/ <br />THIS CONDITION AFTER BIDDING. <br />4.2. ELECTRICAL INSTALLATION SHALL MEET THE EXISTING CONDITIONS. <br />1. MATERIALS <br />1.1. ALL MATERIALS SHALL BE NEW & OF THE QUALITY SPECIFIED ON THE PLANS OR <br />SPECIFICATIONS & MUST CARRY THE U.L.'s APPROVAL COVERING THE PURPOSE <br />FOR WHICH THEY ARE USED & MEET ALL REQUIREMENTS OF CURRENT <br />APPLICABLE CODES & REGULATIONS. <br />2. CONDUIT <br />2.1. ALL WIRING SHALL BE INSTALLED IN LISTED METALLIC CONDUIT EXCEPT AS <br />PERMITTED BELOW: <br />2.1.1. GALVANIZED RIGID STEEL CONDUIT, w/ A 20 MIL PVC COATING WILL BE USED <br />WHEN IN CONTACT w/ EARTH. <br />2.1.2. INTERMEDIATE METAL CONDUIT MAY BE USED IN INDOOR LOCATIONS NOT IN <br />CONTACT w/ THE EARTH. <br />2.1.3. ELECTRICAL METALLIC TUBING MAY BE USED IN INDOOR LOCATIONS NOT IN <br />CONTACT w/ EARTH, NOT IN CONCRETE SLABS OR WALLS & NOT SUBJECT TO <br />DAMAGE. <br />2.1.4. PVC MAY BE USED IN OR BELOW CONCRETE & DIRECTLY BURIED IN EARTH. <br />2.1.5. FLEXIBLE STEEL CONDUIT SHALL BE USED FOR INDOOR FINAL CONNECTIONS <br />TO EQUIPMENT IN LENGTHS NOT TO EXCEED 72". <br />2.1.6. LIQUID -TIGHT FLEXIBLE STEEL CONDUIT SHALL BE FOR OUTDOOR FINAL <br />CONNECTIONS TO EQUIPMENT NOT TO EXCEED 36". <br />2.2. WHERE CONDUITS ENTER OUTLET BOXES, FIXTURES OR CABINETS, FIRMLY <br />FASTEN w/ STEEL SET SCREW, COMPRESSION CONNECTORS, OR DOUBLE <br />LOCKNUTS FOR GALVANIZED RIGID CONDUIT. ALL CONNECTIONS SHALL HAVE <br />BUSHINGS OR INSULATED THROAT CONNECTORS. FIRMLY FASTEN CONDUIT TO <br />THE BUILDING CONSTRUCTION. RUN EXPOSED CONDUIT PARALLEL TO THE <br />BUILDING LINES, SUPPORTED BY APPROPRIATE HANGERS (UNISTRUT, T & B, <br />APPLETON, OR EQUAL). <br />2.3. COVER METALLIC CONDUIT CONTACTING THE EARTH w/ POLYETHYLENE TAPED <br />SPIRAL WRAPPED, 1/2 LAPPED TO PROVIDE 20 MIL. THICKNESS. TAPE SHALL BE <br />SCOTCH NO. 50 TAPE. CONDUITS & DUCTS NOT UNDER BUILDINGS & FEEDER <br />DUCTS SHALL COMPLY w/ N.E.C. 300-5. MAKE JOINTS w/ COMPOUND WATERTIGHT. <br />2.4. FITTINGS & CONDUIT BODIES SHALL BE STEEL. NO DIECAST FITTINGS. <br />2.5. CONDUIT SIZES SHALL BE AS REQUIRED BY CODE & AS INDICATED OR SPECIFIED. <br />2.6. ALL EMPTY CONDUIT SYSTEMS SHALL HAVE A NYLON PULL STRING TO <br />FACILITATE INSTALLATION OF FUTURE WIRE. <br />2.7. SCHEDULE 40 PVC CONDUIT SHALL BE PERMITTED UNDERGROUND w/ PROPER <br />FITTINGS, ALL U.L. APPROVED & CEMENTED JOINTS. PENETRATIONS THROUGH <br />FLOOR SLABS & BENDS GREATER THAN 22 DEGREES SHALL BE WRAPPED RIGID <br />5. STORAGE AND HANDLING OF MATERIAL GALVANIZED STEEL ELBOWS. <br />5.1. DELIVER MATERIALS & EQUIPMENT TO THE PROJECT IN THE MANUFACTURER' 2.8. CONDUITS & OUTLETS SHALL BE CONCEALED w/ THE BUILDING STRUCTURE, <br />ORIGINAL, UNOPENED, LABELED CONTAINERS. PROTECT AGAINST MOISTURE, EXCEPT THAT CERTAIN MOTOR & LIGHTING FEEDER CONDUITS MAY BE RUN <br />TAMPERING, OR DAMAGE FROM IMPROPER HANDLING & STORAGE. CONTRACTOR EXPOSED IN CERTAIN AREAS AS INDICATED ON THE DRAWINGS. CONDUITS <br />SHALL BE RESPONSIBLE FOR ANY DAMAGE TO WORK OR MATERIALS UNTIL FINAL SHOWN TO BE INSTALLED IN CABINETS, COUNTERS, & CASEWORK SHALL BE RUN <br />ACCEPTANCE BY THE OWNER, & SHALL MAKE GOOD w/o COST TO THE OWNER, ANY AS DIRECTED BY THE ARCHITECT. <br />DAMAGE OR LOSS THAT MAY OCCUR DURING THIS PERIOD. <br />PART II - PRODUCTS & EXECUTION <br />5.PANELBOARDS <br />5.1. CIRCUIT BREAKER TYPE AS INDICATED ON DRAWINGS. U.N.O., ALL PANELS SHALL <br />HAVE PANELBOARD TYPE CONSTRUCTION w/ BOLT -ON CIRCUITS. BREAKERS FOR <br />3PHASE PANELS. MANUFACTURER's SHALL BE GENERAL ELECTRIC, SQUARE D, <br />SIEMENS, CUTLER -HAMMER OR EQUAL w/ VOLTAGE, SIZES, & RATINGS AS <br />INDICATED ON DRAWINGS. <br />5.2. THE CIRCUIT BREAKERS SHALL BE OPERABLE IN ANY POSITION & BE REMOVABLE <br />FROM THE FRONT OF THE PANELBOARD w/o DISTURBING ADJACENT UNITS. <br />BRANCH BREAKERS SHALL BE OF SUCH DESIGN THAT COMBINATION OF <br />SINGLE-P, DOUBLE-P, & TRIPLE-P BREAKERS CAN BE ASSEMBLED ON THE SAME <br />PANEL. EACH BRANCH CIRCUIT SHALL BE CLEARLY NUMBERED. BRANCH & MAIN <br />TERMINALS SHALL BE OF THE SOLDERLESS TYPE. HANDLE TIES TO FORM <br />MULTI -POLE BREAKERS NOT ACCEPTABLE. <br />5.3. WIRE TERMINATION FOR PANELBOARDS & CIRCUIT BREAKERS SHALL BE LISTED <br />AS SUITABLE FOR 75 DEGREES CELSIUS. <br />5.4. PROVIDE A TYPEWRITTEN CIRCUIT INDEX BEHIND CLEAR PLASTIC ON THE INSIDE <br />OF THE DOOR. INFORMATION SHALL INCLUDE ROOM & TYPE LOAD SERVED. ALL <br />CIRCUIT BREAKERS SHALL BE IDENTIFIED, INCLUDING SPARES. INDEX CARD <br />FRAME SHALL BE METAL, SECURED TO DOOR. <br />5.5. WHERE PANELBOARDS ARE INSTALLED FLUSH w/ THE WALLS, EXTEND EMPTY <br />CONDUITS FROM THE PANELBOARD TO AN ACCESSIBLE SPACE ABOVE OR <br />BELOW. PROVIDE 3/4" (MIN. SIZE) CONDUIT FOR EVERY (3) THREE SINGLE SPARE <br />CIRCUIT BREAKERS OR SPACE EQUIVALENT MULTI -POLE ARRANGEMENT, OR <br />FRACTION THEREOF, BUT NOT LESS THAN (2) TWO CONDUITS FOR EACH PANEL. <br />5.6. PANELBOARDS TO BE PROVIDED w/ COPPER BUSSING ONLY. <br />5.7. LOAD CENTERS SHALL NOT BE ALLOWED U.N.O. <br />5.8. ALL NEW PANELBOARDS SHALL COMPLY w/ N.E.0 ARTICLE 110.16. EQUIPMENT <br />MANUFACTURER's SHALL PROVIDE WARNING LABELS FOR ALL PANELBOARDS, <br />GENERATORS, AUTOMATIC TRANSFER SWITCHES, ETC. TO WARN QUALIFIED <br />PERSONS OF POTENTIAL ELECTRIC ARC FLASH HAZARDS. THE MARKING SHALL <br />BE LOCATED SO AS TO BE CLEARLY VISIBLE BEFORE EXAMINATION, <br />ADJUSTMENT, SERVICE, OR MAINTENANCE OF THE EQUIPMENT. <br />6. WIRE <br />6.1. CONDUCTOR SIZES SHOWN ON THE DRAWINGS ARE BASED ON COPPER WIRE. <br />U.N.O., ALL WIRE SHALL BE TYPE XHHW FOR FEEDERS OR BRANCH CIRCUITS <br />LARGER THAN 4 AMERICAN WIRE GAUGE, TYPE THHN/THWN INSULATION FOR <br />FEEDERS & BRANCH CIRCUITS 4 AMERICAN WIRE GAUGE & SMALLER. ALL <br />BRANCH CIRCUIT WIRING SHALL BE COPPER. SERVICE & PANEL FEEDERS #1/0 & <br />LARGER MAY BE ALUMINUM, PROVIDED THE CONDUCTOR SIZES ARE INCREASED <br />FOR EQUAL OR GREATER AMPACITY & EQUAL OR LESS EQUIVALENT VOLTAGE <br />DROP. INCREASE CONDUIT SIZE AS REQUIRED. THE WIRES SHALL BE MARKED w/ <br />COLOR TO SIMPLIFY CIRCUIT IDENTIFICATION. U.N.O., BY LOCAL ORDINANCES <br />GROUND WIRES SHALL BE GREEN, NEUTRAL WIRES SHALL BE 120V-WHITE, <br />277V-GRAY, & LIVE WIRES 208Y/120V & 120/240 SHALL BE BLACK (PHASE A), RED <br />(PHASE B), & BLUE (PHASE Q. FOR 480Y/277V CIRCUITS, THE COLOR CODE SHALL <br />BE BROWN (PHASE A), ORANGE (PHASE B), & YELLOW (PHASE C). THE WIRE SHALL <br />BE 12 AMERICAN WIRE GAUGE U.N.O. CIRCUIT SHALL BE LABELED IN EACH J-BOX. <br />6.2. WHERE ALUMINUM WIRE IS USED, ALUMINUM CONDUCTOR MATERIAL SHALL <br />COMPLY w/ N.E.C. 310-14 & ALL CONNECTIONS & TERMINATIONS SHALL BE <br />MACHINE COMPRESSION TYPE EQUAL TO BURNDY "HI PLUG" OR "MACADAPT", NO <br />2.9. ALL CONDUIT SYSTEMS SHALL HAVE A CODE SIZED COPPER GROUND EXCEPTIONS. <br />5.2. ARRANGE FOR TIMELY DELIVERY OF MATERIALS & EQUIPMENT TO THE JOB SITE IN CONDUCTOR INCREASE CONDUIT SIZE AS REQUIRED. <br />ORDER TO MINIMIZE THE LENGTH OF TIME BETWEEN DELIVERY & INSTALLATION. <br />2.10. <br />CONDUIT PENETRATION THROUGH ROOF SHALL HAVE ROOF FLASHING w/ CAULK <br />5.3. COVER & PROTECT ANY MATERIAL THAT MAY BE AFFECTED BY WEATHER WHILE IN <br />TYPE COUNTER FLASHING SLEEVE. INSTALLATION SHALL BE WATERTIGHT. <br />TRANSIT OR STORED AT THE PROJECT SITE. ANY MATERIAL FOUND DEFECTIVE OR <br />NOT INSTALLED IN ACCORDANCE w/ THE CONSTRUCTION DOCUMENTS MAY BE <br />2.11. <br />CONDUITS SHALL BE ROUTED SURFACE ON THE STRUCTURE, PARALLEL & <br />REJECTED BY THE ENGINEER. <br />PERPENDICULAR TO THE STRUCTURE. <br />6. CLEANUP <br />3. OUTLET, <br />PULL, & JUNCTION BOXES <br />6.1. KEEP THE PREMISES FREE FROM ACCUMULATION OF WASTE MATERIALS, OR <br />3.1. <br />EACH SWITCH, LIGHT, RECEPTACLE OR OTHER OUTLET SHALL BE PROVIDED w/A <br />RUBBISH CAUSED BY EMPLOYEES OR WORK UNDER THIS DIVISION OF THE <br />CODE GAUGE, GALVANIZED STEEL OUTLET BOX. JUNCTION & PULL BOXES SHALL <br />SPECIFICATIONS. AT THE COMPLETION OF THE WORK REMOVE ALL SURPLUS <br />BE CODE GAUGE, GALVANIZED STEEL. OUTLET BOXES SHALL BE OF THE ONE <br />MATERIALS, TOOLS, ETC., & LEAVE THE PREMISES BROOM -CLEAN. <br />PIECE, KNOCKOUT TYPE, IN GENERAL 4" SQUARE WITH PLASTER RING. PLASTER <br />RINGS SHALL BE SET TO PROVIDE NOT MORE THAN 1/8" FROM WALL SURFACE TO <br />7. EXCAVATION <br />RING. IN NO CASE SHALL PLASTER RING PROJECT BEYOND SURFACE OF WALL. <br />SINGLE GANG RINGS SIMILAR TO STEEL CITY 52050 SHALL BE USED FOR 4" BOXES <br />7.1. PERFORM ALL EXCAVATION & BACK FILLING REQUIRED FOR WORK PERFORMED <br />IN UNFINISHED BRICK NUMBER 180 BOXES MAY BE USED FOR UNFINISHED <br />UNDER THIS DIVISION OF THE SPECIFICATIONS. USE EXCAVATED MATERIALS FOR <br />MASONRY FLUSH WALL OUTLETS. CENTER ALL OUTLET BOXES IN BLOCK <br />BACKFILL UNLESS OFF SITE MATERIALS ARE DEEMED NECESSARY. <br />COURSE. <br />8. DRAWINGS <br />3.2. <br />BOXES INSTALLED IN POURED CEMENT FLOORS SHALL BE FLUSH TYPE CAST <br />IRON OR STEEL w/ WATERTIGHT CASKETED COVERS. WHERE BOXES ARE <br />8.1. THE DRAWINGS INDICATE THE GENERAL ARRANGEMENT & LOCATIONS OF THE <br />INSTALLED IN FLOORS w/ TILE OR CARPET FLOOR COVERING, COVERS SHALL BE <br />ELECTRICAL WORK. DATA PRESENTED ON THESE DRAWINGS ARE AS ACCURATE <br />OF THE RECESSED TYPE TO ACCOMMODATE THE FLOOR COVERING. <br />AS PLANNING CAN DETERMINE, BUT FIELD VERIFICATION OF ALL DIMENSIONS, <br />LOCATIONS, LEVELS, ETC., TO SUIT FIELD CONDITIONS IS REQUIRED. REVIEW ALL <br />3.3. <br />BOXES INSTALLED FOR THE ALARM, COMPUTER, & SECURITY SYSTEM SHALL BE <br />ARCHITECTURAL, STRUCTURAL, & MECHANICAL DRAWINGS & ADJUST ALL WORK <br />PROVIDED w/ APPROPRIATE COVER PLATES. <br />TO MEET THE REQUIREMENTS OF CONDITIONS SHOWN. THE ARCHITECTURAL <br />DRAWINGS SHALL TAKE PRECEDENCE OVER ALL OTHER DRAWINGS. <br />3.4. <br />BOXES FOR TELEPHONE, COMPUTER, T.V., FIRE ALARM, SECURITY, & SIMILAR <br />DISCREPANCIES BETWEEN DIFFERENT PLANS, OR BETWEEN DRAWINGS & <br />SYSTEMS SHALL BE MIN. 4" SQUARE AND 2-1/8" DEEP. <br />SPECIFICATIONS, OR REGULATIONS & CODES GOVERNING THE INSTALLATION <br />SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER IN WRITING BEFORE <br />4. SWITCHBOARDS <br />THE DATE OF BID OPENING. IF DISCREPANCIES ARE NOT REPORTED, THE <br />CONTRACTOR SHALL BID THE GREATER QUANTITY OR BETTER QUALITY, & <br />4.1. <br />SWITCHBOARDS SHALL BE PROVIDED w/ FULLY RATED COPPER OR ALUMINUM <br />cn <br />APPROPRIATE ADJUSTMENTS WILL BE MADE AFTER CONTRACT AWARD. <br />BUS. HORIZONTAL TAPERED BUSSING SHALL NOT BE ALLOWED. <br />2 <br />CONTRACTOR SHALL BE RESPONSIBLE TO FIELD MEASURE & CONFIRM MOUNTING <br />HEIGHTS & LOCATION OF ELECTRICAL EQUIPMENT w/ RESPECT TO COUNTERS, <br />4.2. <br />ACCEPTABLE MANUFACTURERS - CUTLER HAMMER, SEIMENS, SQUARE D OR <br />RADIATION, ETC. DO NOT SCALE DISTANCES OFF THE ELECTRICAL DRAWINGS, USE <br />APPROVED EQUAL. <br />c, <br />ACTUAL BUILDING DIMENSIONS. <br />�I <br />4.3. <br />FACTORY ASSEMBLED DEAD FRONT, METAL ENCLOSED, & SELF-SUPPORTING <br />ca <br />9. EXCAVATION, CUTTING & FITTING <br />SWITCHBOARD ASSEMBLY CONFORMING TO N.E.M.A. PB 2, U.L. 891, & COMPLETE <br />FROM INCOMING LINE TERMINALS TO LOAD SIDE TERMINATIONS. <br />c <br />9.1. PERFORM THE EXCAVATION, CUTTING, FITTING, REPAIRING, & FINISHING OF THE <br />cn <br />WORK NECESSARY FOR THE INSTALLATION OF THE EQUIPMENT OF THIS SECTION. <br />4.4. <br />LINE & LOAD TERMINATIONS: ACCESSIBLE FROM ONLY THE FRONT OF THE <br />N <br />N <br />HOWEVER, NO CUTTING OF THE WORK OF OTHER TRADES OR OF ANY <br />SWITCHBOARD. SUITABLE FOR THE CONDUCTOR MATERIALS & NUMBER OF <br />D <br />STRUCTURAL MEMBERS SHALL BE DONE w/o THE CONSENT OF THE ARCHITECT. <br />CONDUCTORS USED. <br />10. COOPERATION w. OTHER CONTRACTORS <br />4.5. <br />BUS CONNECTIONS: BOLTED. ACCESSIBLE FROM FRONT FOR MAINTENANCE. <br />PROVIDE BELLEVILLE WASHERS FOR CONNECTION & PROPERLY TORQUE. <br />10.1. COOPERATE w/ THE OTHER TRADES SO THAT THE INSTALLATION OF THE <br />L <br />ELECTRICAL OUTLETS & EQUIPMENT WILL BE PROPERLY COORDINATED TO AVOID <br />4.6. <br />PROVIDE FULLY -RATED NEUTRAL BUS & FULLY RATED GROUND BUS MATCHING <br />CONFLICT w/ THE PIPING, DUCTWORK, STEEL, BEAMS, OR OTHER OBSTRUCTIONS. <br />MATERIAL USED FOR MAIN BUS. <br />CAREFULLY CHECK LOCATIONS OF OUTLET BOXES & DETERMINE THAT THEY HAVE <br />o NOT BEEN DISTURBED DURING THE INSTALLATION OF OTHER TRADE MATERIALS. 4.7. FUTURE PROVISIONS: FULLY EQUIP SPACES FOR FUTURE DEVICES w/ BUSSING & <br />,It BUS CONNECTIONS. SUITABLY INSULATED & BRACED FOR SHORT CIRCUIT <br />Nt <br />0 10.2. COORDINATE THE LOCATION OF THE TRENCHES & CONDUITS FOR ELECTRICAL & CURRENTS. CONTINUOUS CURRENT RATING AS INDICATED ON DRAWINGS. <br />TELEPHONE UTILITY SERVICES w/ THE GENERAL CONTRACTOR. <br />co <br />6.3. NO WIRE SHALL BE INSTALLED IN THE CONDUIT SYSTEM UNTIL THE CONDUIT <br />SYSTEM IS COMPLETE. USE MINERALAC NO. 100 OR EQUIVALENT AS A <br />LUBRICANT TO FACILITATE THE INSTALLATION OF THE CONDUCTORS IN THE <br />CONDUIT SYSTEM. <br />6.4. SPLICES IN EXTERIOR PULL BOXES & MANHOLES SHALL BE WEATHERPROOF <br />USING "SCOTCHCAST" SPLICE KIT OR APPROVED EQUAL. SEAL ENDS OF <br />CONDUITS & DUCTS w/ "DUCTSEAL" OR APPROVED EQUAL. <br />6.5. PROVIDE SOLID CONDUCTOR FOR 12 AMERICAN WIRE GAUGE & SMALLER. <br />7. WIRING DEVICES <br />7.1. WALL SWITCHES SHALL BE SPECIFICATION GRADE AC SILENT TYPE SWITCHES, <br />20A, 120/277 VOLT. <br />7.2. RECEPTACLES SHALL BE SPECIFICATION GRADE, DUPLEX TYPE, NEMA 5-20R, 20 <br />AMPERE, 120 VOLT GROUNDED TYPE. SPECIAL APPLICATION RECEPTACLES <br />SHALL BE INDICATED ON PLANS. MOUNT w/ THE GROUND DOWN. <br />7.3. DEVICE PLATES SHALL BE EQUAL TO SIERRA SMOOTH -LINE PLASTIC WALL <br />PLATES. COLOR SHALL BE WHITE, U.N.O. <br />7.4. RECEPTACLES IN OUTDOOR & WET LOCATIONS SHALL BE INSTALLED w/ A HINGED <br />OUTLET COVER/ENCLOSURE CLEARLY MARKED & U.L. LISTED SUITABLE FOR WET <br />LOCATIONS WHILE IN USE, EQUAL TO TAYMAC SPECIFICATION GRADE. <br />8. LIGHTING FIXTURE <br />8.1. PROVIDE ALL LIGHTING FIXTURES, WIRED & CONNECTED. THE DRAWINGS <br />INDICATE THE FIXTURES FOR EACH LOCATION. PROVIDE LAMPS FOR ALL <br />FIXTURES. THE LAMPS SHALL BE BY THE SAME MANUFACTURER. VERIFY CEILING <br />CONSTRUCTION BEFORE ORDERING RECESSED UNITS. PROVIDE PLASTER <br />FRAMES & HANGERS AS REQUIRED. CEILING CONSTRUCTION, ARCHITECTURAL <br />ACCESSORIES, VOLTAGE, & BALLASTS TO MEET THE EXISTING CONDITION. <br />9. SERVICE ENTRANCE SECTION <br />9.1. SERVICE ENTRANCE EQUIPMENT SHALL BE AS INDICATED ON THE DRAWINGS <br />EQUIPMENT SHALL CARRY THE U.L. LABEL & CONFORM TO THE POWER COMPANY <br />REGULATIONS. <br />9.2. SERVICE ENTRANCE EQUIPMENT SHALL BE PROVIDED w/ A FULLY RATED COPPER <br />OR ALUMINUM BUS. HORIZONTALLY TAPERED BUSSING SHALL NOT BE ALLOWED. <br />10. SYSTEM GROUNDING <br />10.1. GROUNDING SHALL COMPLY w/ REQUIREMENTS OF ARTICLE 250. ALL EXPOSED <br />NONCURRENT CARRYING METALLIC PARTS OF ELECTRICAL EQUIPMENT, <br />METALLIC RACEWAY SYSTEMS, METALLIC CABLE ARMOR, GROUNDING <br />CONDUCTORS OF NONMETALLIC SHEATHED CABLES, GROUNDING CONDUCTORS <br />IN NONMETALLIC RACEWAYS, & GROUNDED CONDUCTORS OF THE WIRING <br />SYSTEMS SHALL BE GROUNDED. <br />10.2. GROUNDING CONDUCTOR (NEUTRAL) OF THE WIRING SYSTEM SHALL BE <br />CONNECTED TO THE SYSTEM GROUNDING CONDUCTOR AT A SINGLE PLACE IN <br />EACH SYSTEM BY REMOVABLE BONDING JUMPERS; SIZED ACCORDING TO THE <br />APPLICABLE PROVISIONS OF THE N.E.C. THE GROUNDED CONDUCTOR (NEUTRAL) <br />TO THE GROUNDING CONDUCTOR CONNECTION SHALL BE LOCATED IN THE <br />ENCLOSURE FOR THE SYSTEM's OVERCURRENT PROTECTION OR WHERE <br />OTHERWISE INDICATED ON THE PLANS OR SPECIFICATIONS. <br />10.3. A GROUND BUS SEPARATE FROM THE NEUTRAL BUS SHALL BE PROVIDED IN ALL <br />SWITCHBOARDS & PANELBOARDS. GROUND BUS SHALL BE TORQUED (CHECKED) <br />PRIOR TO ENERGIZING EQUIPMENT PER MANUFACTURER's RECOMMENDATIONS. <br />10.4. GROUND BUSES & NEUTRAL BUSES IN ALL DISTRIBUTION PANELS, <br />SWITCHBOARDS, PANELBOARDS, & THOSE PROVIDED IN ANY EQUIPMENT SHALL <br />BE ISOLATED EXCEPT WHERE REQUIRED TO BE CONNECTED AS SPECIFIED <br />ABOVE FOR THE SERVICE ENTRANCE & IN TRANSFORMER TERMINAL <br />COMPARTMENTS. <br />10.5. WHEN INDICATED ON THE DRAWINGS, EQUIPMENT GROUNDING CONDUCTORS <br />SHALL BE EXTENDED FROM THE GROUND BUS IN THE DISTRIBUTION EQUIPMENT <br />TO THE RECEPTACLE, FIXTURE OR DEVICE LUGS WHERE THEY ARE PROVIDED. <br />WHERE LUGS ARE NOT PROVIDED, EQUIPMENT GROUNDING CONDUCTORS SHALL <br />BE CONNECTED TO EQUIPMENT ENCLOSURES. THE CONNECTIONS SHALL BE <br />ARRANGED SUCH THAT REMOVAL OF THE RECEPTACLE, EQUIPMENT GROUND <br />CONDUCTORS, OR GROUND JUMPERS FROM GROUND BUSING SHALL NOT <br />AFFECT THE GROUND SYSTEM. <br />10.6. RACEWAYS MAY NOT BE USED AS A GROUNDING CONDUCTOR FOR POWER & <br />LIGHTING CIRCUITS. ALL CONDUITS SHALL HAVE SEPARATE CODE SIZED GREEN <br />GROUND WIRE INSTALLED IN THE CONDUIT TO INSURE A CONTINUOUS <br />GROUNDING PATH. <br />10.7. IN INACCESSIBLE LOCATIONS, MAKE CONNECTIONS BY EXOTHERMIC WELD <br />PROCESS. <br />10.8. IN ACCESSIBLE LOCATIONS, CONNECTIONS SHALL BE MADE w/ BOLTED <br />THROUGH, APPROVED SOLDERLESS BRONZE GROUNDING DEVICES. <br />10.9. BOND TOGETHER METAL SIDING NOT ATTACHED TO GROUNDED STRUCTURE. <br />11. TELEPHONE SYSTEM <br />11.1. TELEPHONE WALL OUTLETS SHALL CONSIST OF STANDARD BOXES MOUNTED 18" <br />ABOVE THE FLOOR U.N.O. CONNECT OUTLETS TO TELEPHONE TERMINAL w/ <br />SEPARATE 3/4" CONDUIT U.N.O. ON DRAWINGS. PROVIDE A TERMINAL MOUNTING <br />BOARD FOR THE INCOMING SERVICE CABLE. <br />12. LIGHTING CONTROL <br />12.1. FURNISH & INSTALL TIME SWITCHES, PHOTOCELLS, CONTACTORS & FULL <br />LIGHTING CONTROL SYSTEMS AS REQUIRED FOR LIGHTING CONTROLS <br />INDICATED ON THE DRAWINGS. <br />12.2. TIME SWITCHES SHALL BE EQUAL TO PARAGON, GENERAL ELECTRIC, TORK, OR <br />INTERMATIC & SHALL HAVE SIZE & NUMBER OF POLES AS REQUIRED. <br />12.3. PHOTOCELLS SHALL BE EQUAL TO TORK OR INTERMATIC w/ VOLTAGE AS <br />INDICATED. <br />13. LIGHTING INVERTER SYSTEM <br />13.1. LIGHTING INVERTERS SHALL HAVE A CENTRAL BATTERY AS EMERGENCY POWER <br />SOURCE FOR EGRESS LIGHTING w/ SIZE & VOLTAGE AS INDICATED ON THE <br />DRAWINGS. <br />13.2. ACCEPTABLE MANUFACTURES - DUAL-LITE, HUBBELL LIGHTING, LITHONIA <br />LIGHTING EMERGENCY LIGHTING SYSTEMS, MCPHILBEN EMERGENCY LIGHTING <br />OR APPROVED EQ. <br />13.3. UNIT SHALL AUTOMATICALLY SENSE LOSS OF NORMAL AC SUPPLY & USE A <br />SOLID-STATE SWITCH TO TRANSFER LOADS. TRANSFER IN 0.004 SECOND OR <br />LESS FROM NORMAL SUPPLY TO BATTERY -INVERTER SUPPLY. INVERTER SHALL <br />BE COMPATIBLE w/ INCANDESCENT, MAGNETIC & ELECTRONIC FLUORESCENT <br />BALLASTS, HIGH POWER FACTOR COMPACT FLUORESCENT, & HIGH INTENSITY <br />DISCHARGE LAMP TYPES. <br />13.4. UNIT SHALL SUPPLY POWER TO OUTPUT CIRCUITS FROM A SINGLE, EXTERNAL, <br />NORMAL SUPPLY SOURCE. UNIT AUTOMATICALLY TRANSFERS LOAD FROM <br />NORMAL SOURCE TO INTERNAL BATTERY/INVERTER SOURCE. RETRANSFER TO <br />NORMAL IS AUTOMATIC WHEN NORMAL POWER IS RESTORED. <br />13.5. UNIT SHALL COMPLY w/ NATIONAL FIRE PROTECTION AGENCY 70 & 101. & BE U.L. <br />924 LISTED. <br />13.6. UNIT SHALL SUSTAIN A FULL -CAPACITY OUTPUT FOR A MIN. OF 90 MINUTES. <br />PROVIDE BATTERIES THAT ARE MAINTENANCE FREE, SEALED LEAD CALCIUM <br />BATTERY w/ AN EXPECTED LIFE OF NO LESS THAN 10 YEARS. <br />13.7. UNIT SHALL CONTAIN GROUP DISPLAYS, INDICATIONS, & BASIC SYSTEM <br />CONTROLS ON COMMON CONTROL PANEL ON FRONT OF CENTRAL BATTERY <br />INVERTER ENCLOSURE. <br />13.8. ENCLOSURE SHALL BE STEEL, w/ HINGED LOCKABLE DOORS, SUITABLE FOR <br />FLOOR MOUNTING. MANUFACTURER's STANDARD CORROSION -RESISTANT FINISH. <br />14. UNINTERRUPTIBLE POWER SUPPLY (UPS) <br />14.1. UPS SHALL BE A CONTINUOUS DUTY, (3) THREE PHASE, ONLINE, SOLID STATE <br />UNINTERRUPTIBLE POWER SUPPLY SYSTEM w/ SIZE & VOLT. AS INDICATED ON <br />THE DRAWINGS. <br />14.2. ACCEPTABLE MANUFACTURERS: TOSHIBA INTERNATIONAL CORPORATION, MGE <br />UPS SYSTEMS & MITSUBISHI. <br />14.3. UPS SHALL AUTOMATICALLY SENSE LOSS OF NORMAL AC POWER SUPPLY & <br />CONVERT IT TO DC POWER. THE DC POWER IS THEN USED TO CHARGE THE <br />BATTERY BANK WHILE PROVIDING CLEAN, DC POWER TO THE INVERTER <br />CIRCUITRY. THE INVERTER WILL CONVERT DC POWER TO REGULATED AC POWER <br />TO FEED THE LOAD. <br />14.4. UPON FAILURE OF COMMERCIAL AC POWER, THE UPS SHALL DERIVE POWER <br />FROM THE BATTERY BANK & CONTINUE FEEDING THE LOAD w/ CLEAN, <br />REGULATED AC POWER. THERE SHALL BE NO INTERRUPTION TO THE CRITICAL <br />LOAD UPON FAILURE OR RESTORATION OF COMMERCIAL AC POWER. <br />14.5. UPON RESTORATION OF THE COMMERCIAL AC SOURCE, THE <br />RECTIFIER/CHOPPER POWERS THE INVERTER WHILE SIMULTANEOUSLY <br />RECHARGING THE BATTERY BANK. <br />14.6. UNIT SHALL COMPLY w/ NATIONAL FIRE PROTECTION AGENCY 7), AMERICAN <br />NATIONAL STANDARDS INSTITUTE C62.41 (IEEE 587), INTERNATIONAL <br />ORGANIZATION FOR STANDARDIZATION 9001, 14001 & BE U.L. 1778 LISTED. <br />14.7. THE UPS SHALL SUSTAIN A FULL -CAPACITY OUTPUT FOR A MIN. OF 4lblJjF P <br />PROVIDE BATTERIES THAT ARE MAINTENANCE FREE, ABSOR ED S <br />(AGM) w/ AN EXPECTED LIFE OF NO LESS THAN 10 YEARS. <br />14.8. UNIT SHALL CONTAIN GROUP DISPLAYS, INDICATIONS & BASIC EYSTEM <br />CONTROLS ON COMMON CONTROL PANEL ON FRONT OF UPS ENCLOSURE. <br />14.9. ENCLOSURE SHALL BE STEEL, w/ HINGED LOCKABLE DOORS, S IT <br />� FLOOR MOUNTING. MANUFACTURER's STANDARD CORROSIO -RL9�`H�1 SH1 <br />14.10. UPS TO BE PROVIDED w/ AN EMERGENCY POWER OFF SWITCH TDA&M THE <br />UPS & BATTERY CIRCUIT BREAKERS. UPS SHALL CONTAIN Ac ERIAL DATA LINK TO <br />ENABLE UPS TO INTERFACE TO A COMPUTER THAT WILL PRO IDE STATUS & <br />DIAGNOSTIC INFORMATION. <br />14.11. UPS SHALL USE INSULATED -GATE BIPOLAR TRANSISTOR TECHNOLOGY FOR THE <br />POWER INPUT SECTION. UPS SHALL NOT REQUIRE AN OVERSIZED GENERATOR <br />TO MAINTAIN CONTINUOUS POWER TO EQUIPMENT. <br />15. GUARANTEE <br />15.1. IT IS GUARANTEED THAT ALL MATERIAL FURNISHED & ALL WORKMANSHIP <br />PERFORMED FOR A PERIOD OF (1) ONE YEAR FROM DATE OF FINAL ACCEPTANCE <br />OF WORK. ANY DEFECTS DEVELOPING WITHIN THIS PERIOD, TRACEABLE TO <br />MATERIAL FURNISHED AS A PART OF THIS SECTION OR WORKMANSHIP <br />PERFORMED HEREUNDER, SHALL BE MADE GOOD AT NO EXPENSE TO THE <br />OWNER. <br />16. SHOP DRAWINGS & APPROVALS <br />16.1. THE ITEMS SPECIFIED HEREIN & ON DRAWINGS ARE USED AS A STANDARD OF <br />QUALITY. ANY MATERIALS OF EQUAL QUALITY & AESTHETIC VALUE WILL BE GIVEN <br />CONSIDERATION AS A SUBSTITUTE FOR THE MATERIALS SPECIFIED. NO <br />APPROVAL WILL BE GIVEN TO A SPECIFIC CATALOG NUMBER, MODEL, OR TYPE <br />OF EQUIPMENT, PRIOR TO BIDDING. AFTER BIDDING, THE DECISION OF THE <br />ARCHITECT &/or ENGINEER DETERMINING EQUAL MATERIALS WILL BE FINAL. <br />16.2. THE CONTRACTOR SHALL SUBMIT (7) SEVEN IDENTICAL BOUND SETS OF SHOP <br />DRAWINGS ON THE FOLLOWING ITEMS: <br />16.2.1. LIGHTING FIXTURE CUTS & PERFORMANCE DATA. <br />16.2.2. OUTLINE DRAWINGS & DATA SHEETS OF EACH PANELBOARD & <br />SWITCHBOARD. <br />16.2.3. OUTLINE DRAWINGS OF ALL SWITCHGEAR. <br />16.3. SUBMIT ITEMS AT ONE TIME IN A NEAT & ORDERLY MANNER WITHIN 15 DAYS OF <br />AWARD OF CONTRACT. PARTIAL SUBMITTALS WILL NOT BE ACCEPTABLE. <br />17. RECORD & AS -BUILT DRAWINGS <br />17.1. THE ELECTRICAL CONTRACTOR SHALL MAINTAIN A SET OF DRAWINGS AT THE <br />JOB SITE FOR THE EXCLUSIVE PURPOSE OF MAINTAINING A RECORD OF ALL <br />WORK INSTALLED & TO SHOW ANY DEVIATIONS FROM THE WORK INDICATED ON <br />THE DRAWINGS. <br />17.2. AT THE COMPLETION OF THE PROJECT, ONE SET OF REPRODUCIBLE DRAWINGS, <br />SHOWING ALL AS -BUILT CONDITIONS, SHALL BE DELIVERED TO THE OWNER FOR <br />ACCEPTANCE PRIOR TO FINAL PAYMENT. <br />E <br />Arch i t e c t u ra I <br />Corporation <br />9431 HAVEN AVENUE, SUITE 212 <br />RANCHO CUCAMONGA, CA 91730 <br />P. 909.259.9971 1 F. 909.944.8409 <br />www.AmorArch.com <br />BRISTOL CENTER <br />PROPERTIES LLC <br />714 S PLYMOUTH BLVD <br />LOS ANGELES, CA 90005 <br />AMIR HOURIANI <br />aihouriani@gmail.com <br />NKellilk [.Y11Imr_\LNN <br />MECHANICAL I ELECTRICAL I PLUMBING <br />909-997-0905 <br />CARLOS RIVAS <br />carlos@rivasdesignconsultants.com <br />Z <br />Lu <br />O <br />\W <br />W <br />W <br />m <br />STAMI <br />Lu <br />J <br />w <br />Lu <br />U) <br />m <br />3 <br />C - 24421 <br />8/31 /2025 <br />U) <br />Z <br />O <br />Q <br />0 <br />LL <br />W <br />CIL <br />U) <br />J <br />Q <br />U_ <br />Lu <br />J <br />Lu <br />* RENEWAL <br />cSj DATE <br />�TFOF CWFo� <br />DATE SIGNED: 08/13/2024 <br />SHEETS BEARING THIS SEAL AND WET SIGNATURE <br />ARE AUTHENTICATED. RESPONSIBILITY FOR ALL <br />OLDER PLANS, SPECIFICATIONS OR INSTRUMENTS <br />ARE DISCLAIMED. <br />REVISIONS <br />0 <br />0 <br />0 <br />0 <br />DATE <br />2024.08.15 <br />PROJECT NUMBER <br />A2641 <br />SHEET NUMBER <br />003 <br />co <br />10.3. COORDINATE HVAC EQUIPMENT CONNECTION REQUIREMENTS w/ HVAC <br />o CONTRACTOR. <br />nCCOPYRIGHT 2024 - DESIGNS, DRAWINGS AND SPECIFICATIONS ARE INSTRUMENTS OF SERVICE AND ARE THE PROPERTY OF THE DESIGN PROFESSIONAL. REPRODUCTION PROHIBITED WITHOUT THE EXPRESSED WRITTEN CONSENT OF THE DESIGN PROFESSIONAL <br />