12. PANELS SHALL BE OF THE DEAD FRONT SAFETY TYPE. PANELS SHALL BE MINIMUM 20"
<br />WIDE AND 5-3/4" DEEP UNLESS OTHERWISE NOTED ON PLAN.
<br />13. COORDINATE WITH APPLICABLE TRADE TO INSURE RECESSED MOUNTED
<br />PANELBOARDS WILL SEAT FLUSH IN THE WALLS PROVIDED. PANEL TRIMS SHALL HAVE
<br />CONCEALED DOORS AND FASTENERS WITH FLUSH TYPE COMBINATION LOCK AND CATCH,
<br />TWO MILLED TYPE KEYS SUPPLIED WITH EACH PANEL. ALL LOCKS SHALL BE KEYED ALIKE
<br />AND EACH DOOR SHALL HAVE A PLASTIC COVERED DIRECTORY FRAME WITH A TYPED
<br />IDENTIFICATION CARD OF ALL CIRCUIT AND PANEL NUMBERS FOR BRANCH CIRCUIT
<br />PANELBOARDS.
<br />11. ALL CIRCUIT BREAKERS SHALL BE BOLT-ON TYPE AND SHALL BE SUITABLE FOR 75
<br />DEGREE AMPACITY CONDUCTORS.
<br />9. PROVIDE BREAKER INTERLOCK WITH ADJACENT BREAKER(S) FOR ANY MULTI-WIRE BRANCH
<br />CIRCUIT. BREAKER INTERLOCK GROUPING SHALL BE BY BRANCH CIRCUIT GROUP (i.e. MULTIPLE
<br />CIRCUITS SHARING A COMMON NEUTRAL (NEC, OR CEC WHERE ADOPTED, 210.4(B),) COMMON
<br />YOKE (NEC, OR CEC WHERE ADOPTED, 210.7,) OR FURNITURE SYSTEM NEC OR CEC WHERE
<br />ADOPTED, 605.6 AND 605.5 ). WHERE AN EXISTING PANEL IS BEING ALTERED OR MODIFIED IN ANY
<br />WAY, CONTRACTOR SHALL INCLUDE ALL COSTS IN BASE BID TO ADD BREAKER INTERLOCKS TO
<br />EXISTING MULTI-WIRE BRANCH CIRCUITS BASED ON CONTRACTOR'S INVESTIGATION OF EXISTING
<br />CONDITIONS.
<br />8. ALL CIRCUIT BREAKERS USED AS SWITCHES SHALL BE UL LISTED AND LABELED
<br />"SWD" FOR SWITCHING DUTY.
<br />7. ALL BUSSING SHALL BE TIN PLATED ALUMINUM.
<br />6. WHERE PANEL IS INDICATED AS RECESSED OR FLUSH MOUNTED, PROVIDE SPARE
<br />CONDUITS STUBBED UP INTO THE ACCESSIBLE CEILING SPACE. PROVIDE ONE (1) 3/4" CONDUIT
<br />ONLY FOR EACH THREE (3) SPARES OR SPACES, MINIMUM OF TWO (2). EACH CONDUIT SHALL
<br />BE TAGGED, CAPPED AND MARKED FOR FUTURE USE.
<br />5. WHERE PANEL CIRCUIT BREAKER RATING IS SHOWN AS SERIES RATED, PROVIDE
<br />CIRCUIT BREAKERS IN PANELBOARD WHICH ARE SERIES RATED WITH THE UPSTREAM
<br />SYSTEM FOR THE AVAILABLE FAULT CURRENT. THE PANELBOARD SHALL BE MARKED
<br />WITH THE SERIES CONNECTED RATINGS, AS WELL AS ALL MARKING AS REQUIRED BY
<br />THE NEC, OR CEC WHERE ADOPTED, 240-86(B).
<br />4. WHERE PANEL IS INDICATED TO INCLUDE AN I/G BUS, PROVIDE PANELBOARDS
<br />WITH AN ISOLATED GROUND BUS, DRILLED AND TAPPED FOR NUMBER OF ISOLATED
<br />GROUND CONDUCTORS SHOWN, AS WELL AS FOR ALL SPARES AND SPACES SHOWN
<br />ON THE PANELBOARD.
<br />3. WHERE PANEL IS INDICATED TO INCLUDE 200% NEUTRAL, PROVIDE PANELBOARDS
<br />UL LISTED AS HAVING NEUTRAL BUSSES RATED TO CARRY 200 PERCENT OF THE
<br />CURRENT CARRYING CAPACITY OF THE PHASE BUSSING. OTHERWISE, NEUTRAL
<br />BUSSING TO BE FULL SIZE AND RECTANGULAR.
<br />2. WHERE PANEL IS INDICATED TO INCLUDE DOUBLE LUGS, PROVIDE A DOUBLE LUG
<br />KIT AT THE SAME END OF THE PANELBOARD AS THE PANELBOARD MAIN LUGS.
<br />1. WHERE PANEL IS INDICATED TO INCLUDE FEED THRU LUGS, PROVIDE FEED THROUGH
<br />LUGS AT THE OPPOSITE END OF THE PANELBOARD FROM THE PANELBOARD MAIN LUGS.
<br />GENERAL PANEL SCHEDULE NOTES:
<br />PANEL SCHEDULE INDEX
<br />"F"
<br />-
<br />PA
<br />LA
<br />14. UPON PROJECT COMPLETION, CONTRACTOR SHALL INSTALL TYPED AS-BUILT PANEL
<br />DIRECTORIES IN EACH PANEL WITHIN THE MFGR-PROVIDED DIRECTORY HOLDER. THE
<br />DIRECTORY SHALL CLEARLY IDENTIFY EACH CIRCUIT TO ITS CLEAR, EVIDENT, AND SPECIFIC
<br />PURPOSE OR USE. EACH CIRCUIT IDENTITY SHALL INCLUDE SUFFICIENT DETAIL TO ALLOW
<br />EACH CIRCUIT TO BE DISTINGUISHED FROM ALL OTHERS PER NEC, OR CEC WHERE ADOPTED,
<br />ART 408.1 AND 408.4 . HANDWRITTEN DIRECTORIES ARE UNACCEPTABLE. COPIES OF AS-BUILT
<br />PANEL SCHEDULES SHALL BE PLACED IN PANEL DIRECTORIES. E.C. TO INCLUDE ALL COSTS
<br />REQUIRED FOR LARGER-THAN-STANDARD CUSTOM PANEL DIRECTORY HOLDERS TO
<br />ACCOMMODATE COPIES OF AS-BUILT PANEL SCHEDULES.
<br />15. PANELBOARDS SHALL BE MANUFACTURED BY G.E., CUTLER-HAMMER, SIEMENS, OR
<br />SQUARE "D". FUSED PANEL BOARDS SHALL BE BY COOPER BUSSMANN.
<br />SPECIFIC PANEL SCHEDULE NOTES:
<br />"E"
<br />"D"
<br />"C"
<br />"B"
<br />"A"
<br />16. PROVIDE SHOP DRAWING SUBMITTAL PER THE ELECTRICAL SPECIFICATION
<br />SUBMITTAL REQUIREMENTS FOR EACH PANEL DEPICTING CONFORMANCE WITH
<br />THE ABOVE NOTES AND SCHEDULES.
<br />"G"
<br />"H"PROVIDE AFCI TYPE DEVICE COMPLYING WITH NEC, OR CEC WHERE ADOPTED,
<br />210.12(A),(B),(C).
<br />-
<br />-
<br />-
<br />-
<br />PROVIDE LOCK-ON DEVICE.
<br />PROVIDE LOCK-OFF DEVICE.
<br />PROVIDE SHUNT TRIP DEVICE.
<br />PROVIDE GFCI TYPE DEVICE.
<br />PROVIDE A RED CIRCUIT BREAKER.
<br />PROVIDE A NEW BREAKER TO MATCH THE EXISTING IN PANEL.
<br />EXISTING BREAKER WITH NEW LOAD.
<br />AS-BUILT PANEL DIRECTORY NOTE:
<br />BRANCH CIRCUIT LOCATIONS NOTED WITH "(E)" INDICATE EXISTING CIRCUIT(S). THE
<br />IDENTITIES OF THESE CIRCUITS ARE BASED ON EXISTING PANEL DIRECTORIES AND/OR
<br />LIMITED AS-BUILT INFORMATION. CONTRACTOR SHALL FIELD VERIFY EACH BRANCH
<br />CIRCUIT AND PROVIDE COMPLETE, TYPED AS-BUILT PANEL DIRECTORIES AS REQUIRED
<br />THAT DISTINGUISH EACH CIRCUIT PER NEC, OR CEC WHERE ADOPTED, ART 408.1 AND
<br />408.4. COMPLETED DIRECTORIES SHALL BE SUBMITTED TO THE ELECTRICAL INSPECTOR
<br />PRIOR TO FINAL ELECTRICAL INSPECTION. INCLUDE ALL COSTS IN BID.
<br />EXISTING CIRCUIT BREAKER NOTE:
<br />PROVIDE BREAKER INTERLOCK WITH ADJACENT BREAKER(S) FOR ANY MULTI-WIRE BRANCH CIRCUIT.
<br />BREAKER INTERLOCK GROUPING SHALL BE BY BRANCH CIRCUIT GROUP (i.e. MULTIPLE CIRCUITS
<br />SHARING A COMMON NEUTRAL (NEC, OR CEC WHERE ADOPTED, 210.4(B),) COMMON YOKE (NEC, OR
<br />CEC WHERE ADOPTED, 210.7,) OR FURNITURE SYSTEM NEC OR CEC WHERE ADOPTED, 605.5 AND
<br />605.7). WHERE AN EXISTING PANEL IS BEING ALTERED OR MODIFIED IN ANY WAY, CONTRACTOR SHALL
<br />INCLUDE ALL COSTS IN BASE BID TO ADD BREAKER INTERLOCKS TO EXISTING MULTI-WIRE BRANCH
<br />CIRCUITS BASED ON CONTRACTOR'S INVESTIGATION OF EXISTING CONDITIONS.
<br />10. PROVIDE BREAKER LOCK OFF DEVICE ON ANY CIRCUIT BREAKER FEEDING A
<br />TRANSFORMER AS REQUIRED, PER NEC, OR CEC WHERE ADOPTED, 450.14. WHERE AN EXISTING
<br />PANEL IS BEING ALTERED OR MODIFIED IN ANY WAY, CONTRACTOR SHALL INCLUDE ALL COSTS
<br />IN BASE BID TO ADD BREAKER LOCK-OFF DEVICES TO EXISTING TRANSFORMER CIRCUIT
<br />BREAKERS BASED ON CONTRACTOR'S INVESTIGATION OF EXISTING CONDITIONS.
<br />11870 Pierce Street, Suite 160
<br />Riverside, California 92505
<br />951.299.4160 www.tk1sc.com
<br />C O L L A B O R A T I V E
<br />THIS DOCUMENT CONTAINS INFORMATION PROPRIETARY TO SVA ARCHITECTS
<br />INC. AND IS FURNISHED IN CONFIDENCE FOR THE LIMITED PURPOSE OF
<br />EVALUATION, BIDDING OR REVIEW. THIS DOCUMENT OR ITS CONTENTS MAY
<br />NOT BE USED FOR ANY OTHER PURPOSE AND MAY NOT BE REPRODUCED OR
<br />DISCLOSED TO OTHERS WITHOUT THE PRIOR WRITTEN CONSENT OF SVA
<br />ARCHITECTS INC. ALL RIGHTS RESERVED, © COPYRIGHT 2018.
<br />SCALE:
<br />REVISIONS:
<br />OW
<br />N
<br />E
<br />R
<br />:
<br />PR
<br />O
<br />J
<br />E
<br />C
<br />T
<br />
<br />N
<br />A
<br />M
<br />E
<br />:
<br />CL
<br />I
<br />E
<br />N
<br />T
<br />
<br />A
<br />D
<br />D
<br />R
<br />E
<br />S
<br />S
<br />:
<br />DATE ISSUED:
<br />PROJECT NO:
<br />Project Leader -BILL VOLLER
<br />tk1sc Job #:B2202330.000
<br />12" = 1'-0"
<br />Issue Date
<br />E40.3
<br />PANEL
<br />SCHEDULES
<br />2022-40123
<br />CI
<br />T
<br />Y
<br />
<br />O
<br />F
<br />
<br />S
<br />A
<br />N
<br />T
<br />A
<br />
<br />A
<br />N
<br />A
<br />NE
<br />W
<br />H
<br />O
<br />P
<br />E
<br />
<br />L
<br />I
<br />B
<br />R
<br />A
<br />R
<br />Y
<br />MO
<br />D
<br />E
<br />R
<br />N
<br />I
<br />Z
<br />A
<br />T
<br />I
<br />O
<br />N
<br />12
<br />2
<br />
<br />N
<br />.
<br />
<br />N
<br />E
<br />W
<br />H
<br />O
<br />P
<br />E
<br />
<br />S
<br />T
<br />.
<br />,
<br />
<br />S
<br />A
<br />N
<br />T
<br />A
<br />
<br />A
<br />N
<br />A
<br />
<br />C
<br />A
<br />
<br />9
<br />2
<br />7
<br />0
<br />3
<br />W = WATER HEATER
<br />R = RECEPTACLE
<br />P = POWER
<br />M = MOTOR HIGH PHASE: 29 A 3431 VA
<br />L = LIGHTING TOTAL DEMAND LOAD: 29.6 A 10657 VA
<br />K = KITCHEN Lighting 640 VA 100.00% 640 VA TOTAL CONNECTED LOAD: 24.0 A 8654 VA
<br />H = HVAC EQUIP L 8014 VA 125.00% 10017 VA AMPS KVA
<br />LOAD TYPE KEY LOAD CLASSIFICATION CONNECTED LOAD AVG. DEMAND... ESTIMATED DEMAND PANEL TOTALS
<br />COMMENTS:24.9 A 29.3 A 19.3 A
<br />PHASE TOTALS:2903.00 VA 3431.20 VA 2319.40 VA
<br />SPACE -- 1 -- 41 -- -- 42 -- 1 -- SPACE
<br />SPACE -- 1 -- 39 -- -- 40 -- 1 -- SPACE
<br />SPACE -- 1 -- 37 -- -- 38 -- 1 -- SPACE
<br />SPACE -- 1 -- 35 -- -- 36 -- 1 -- SPACE
<br />SPACE -- 1 -- 33 -- -- 34 -- 1 -- SPACE
<br />SPACE -- 1 -- 31 -- -- 32 -- 1 -- SPACE
<br />SPACE -- 1 -- 29 -- -- 30 -- 1 -- SPACE
<br />SPACE -- 1 -- 27 -- -- 28 -- 1 -- SPACE
<br />SPACE -- 1 -- 25 -- -- 26 -- 1 -- SPACE
<br />SPACE -- 1 -- 23 -- -- 24 -- 1 -- SPACE
<br />SPACE -- 1 -- 21 -- -- 22 -- 1 -- SPACE
<br />SPACE -- 1 -- 19 -- -- 20 -- 1 -- SPACE
<br />SPARE 20 A 1 -- 17 0 0 18 -- 1 20 A SPARE
<br />SPARE 20 A 1 -- 15 0 0 16 -- 1 20 A SPARE
<br />LTG. SIGNAGE 20 A 1 L 13 500 0 14 -- 1 20 A SPARE
<br />LTG. Room 107, 101, 102, 103 20 A 1 L 11 532 359 12 L 1 20 A LTG. Room 101, 133
<br />LTG. Room 122, 137, 121, 119, 118, 136 20 A 1 L 9 461 1024 10 L;... 1 20 A LTG. Room 124, 131, 132, 126
<br />LTG. MULTIPURPOSE ROOM 110 20 A 1 L 7 653 960 8 L;... 1 20 A LTG. OPEN 132
<br />LTG. Room 105, 107, 116, 115, 117, 111, 113, 112,... 20 A 1 L 5 309 1120 6 L;... 1 20 A LTG. OPEN 134
<br />LTG. INNOVATION CENTER 104 20 A 1 L 3 1218 728 4 L 1 20 A LTG. OPEN 131
<br />LTG. EXTERIOR 20 A 1 L 1 160 630 2 L 1 20 A LTG. OPEN 133
<br />N
<br />O
<br />T
<br />E
<br />DESCRIPTION
<br />B
<br />K
<br />R
<br />P
<br />O
<br />L
<br />E
<br />T
<br />Y
<br />P
<br />E
<br />C
<br />I
<br />R
<br />C
<br />A (VA) B (VA) C (VA)
<br />C
<br />I
<br />R
<br />C
<br />T
<br />Y
<br />P
<br />E
<br />P
<br />O
<br />L
<br />E
<br />B
<br />K
<br />R DESCRIPTION
<br />N
<br />O
<br />T
<br />E
<br />M.L.O.:No AIC:10000 BUS:225 A
<br />FEED THRU:No I/G BUS:No WIRE:4 MCB:200A
<br />NEMA 3R:No 200% NEUTRAL:No PHASE:3 LOCATION:ELEC. RM 111
<br />MOUNTING:SURFACE DOUBLE-LUGS:No VOLTS:120/208 Wye SUPPLY FROM:
<br />PANEL: LA
<br />W = WATER HEATER
<br />R = RECEPTACLE
<br />P = POWER
<br />M = MOTOR HIGH PHASE: 156 A 18524 VA
<br />L = LIGHTING M 27224 VA 104.13% 28349 VA TOTAL DEMAND LOAD: 132.0 A 47564 VA
<br />K = KITCHEN R 22070 VA 72.66% 16035 VA TOTAL CONNECTED LOAD: 145.7 A 52474 VA
<br />H = HVAC EQUIP P 3180 VA 100.00% 3180 VA AMPS KVA
<br />LOAD TYPE KEY LOAD CLASSIFICATION CONNECTED LOAD AVG. DEMAND... ESTIMATED DEMAND PANEL TOTALS
<br />COMMENTS:135.6 A 149.1 A 156.2 A
<br />PHASE TOTALS:16270.00 VA 17680.00 VA 18524.00 VA
<br />SPACE -- 1 -- 83 -- -- 84 -- 1 -- SPACE
<br />SPACE -- 1 -- 81 -- -- 82 -- 1 -- SPACE
<br />SPACE -- 1 -- 79 -- -- 80 -- 1 -- SPACE
<br />SPACE -- 1 -- 77 -- -- 78 -- 1 -- SPACE
<br />SPACE -- 1 -- 75 -- -- 76 -- 1 -- SPACE
<br />SPACE -- 1 -- 73 -- -- 74 -- 1 -- SPACE
<br />SPACE -- 1 -- 71 -- -- 72 -- 1 -- SPACE
<br />SPACE -- 1 -- 69 -- -- 70 -- 1 -- SPACE
<br />SPACE -- 1 -- 67 -- -- 68 -- 1 -- SPACE
<br />SPARE 20 A 1 -- 65 0 0 66 -- 1 20 A SPARE
<br />SPARE 20 A 1 -- 63 0 0 64 -- 1 20 A SPARE
<br />SPARE 20 A 1 -- 61 0 0 62 -- 1 20 A SPARE
<br />R MULTIPURPOSE ROOM 110 PROJECTOR &... 20 A 1 R; P 59 860 540 60 R 1 20 A R OPEN 131
<br />R Room 132, 131 COMPUTERS 20 A 1 R 57 720 500 58 P 1 20 A P IRRIGATION CONTROLLER
<br />R CORRIDOR 102 COMPUTER 20 A 1 R 55 360 10 56 R 1 20 A R CORRIDOR 103 DRINK FTN/BTL FILL
<br />COPIER 20 A 1 R 53 1000 500 54 P 1 20 A P LOBBY 101 BOOK DETECTION SYSTEM
<br />R MULTIPURPOSE ROOM 110 20 A 1 R 51 1080 180 52 R 1 20 A AWE STATION OPEN 131
<br />R MULTIPURPOSE ROOM 110 20 A 1 R 49 1080 720 50 R 1 20 A R OPEN 131
<br />-- -- -- -- -- 47 2250 920 48 -- -- -- -- --
<br />EWH-1 20 A 2 M 45 2250 920 46 M 2 15 A HRU-2
<br />MECHO SHADES 104 20 A 1 P 43 500 920 44 -- -- -- -- --
<br />MECHO SHADES 104 20 A 1 P 41 500 920 42 M 2 15 A HRU-1
<br />CP-1 20 A 1 R 39 180 1130 40 M 1 20 A EF-4
<br />-- -- -- -- -- 37 1380 1130 38 M 1 20 A EF-3
<br />FC-4 20 A 2 M 35 1380 920 36 -- -- -- -- --
<br />-- -- -- -- -- 33 920 920 34 M 2 15 A FC-8
<br />FC-3 20 A 2 M 31 920 920 32 -- -- -- -- --
<br />-- -- -- -- -- 29 920 920 30 M 2 15 A FC-7
<br />FC-2 15 A 2 M 27 920 920 28 -- -- -- -- --
<br />-- -- -- -- -- 25 920 920 26 M 2 15 A FC-6
<br />FC-1 15 A 2 M 23 920 920 24 -- -- -- -- --
<br />REC. EXTERIOR 20 A 1 R 21 540 920 22 M 2 15 A FC-5
<br />REC. STAFF/OFFICE 121 20 A 1 R 19 540 1130 20 M 1 20 A EF-1
<br />REC. MULTIPURPOSE ROOM 110 20 A 1 R 17 1080 14 18 M 1 20 A EF-2
<br />REC. STAFF WORKROOM/ LOUNGE 122 20 A 1 R 15 1080 360 16 R 1 20 A TV MONITORS
<br />REC. LIBRARIAN 137 20 A 1 R 13 900 500 14 P 1 20 A FACP AE
<br />REC. Room 101, 103, 102 20 A 1 R; P 11 1440 360 12 R 1 20 A R LOBBY 101
<br />REC. Room 113, 116, 115, 117, 123 20 A 1 R 9 1080 720 10 R 1 20 A REC. OPEN 133
<br />REC. Room 105, 107 20 A 1 R 7 900 900 8 R 1 20 A REC. Room 133, 131
<br />REC. INNOVATION CENTER 104 20 A 1 R 5 1260 900 6 R 1 20 A REC. OPEN 131
<br />REC. INNOVATION CENTER 104 20 A 1 R 3 1260 1080 4 R 1 20 A REC. Room 130, 126
<br />REC. INNOVATION CENTER 104 20 A 1 R 1 1260 360 2 R 1 20 A REC. PATIO 135, EXTERIOR
<br />N
<br />O
<br />T
<br />E
<br />DESCRIPTION
<br />B
<br />K
<br />R
<br />P
<br />O
<br />L
<br />E
<br />T
<br />Y
<br />P
<br />E
<br />C
<br />I
<br />R
<br />C
<br />A (VA) B (VA) C (VA)
<br />C
<br />I
<br />R
<br />C
<br />T
<br />Y
<br />P
<br />E
<br />P
<br />O
<br />L
<br />E
<br />B
<br />K
<br />R DESCRIPTION
<br />N
<br />O
<br />T
<br />E
<br />M.L.O.:No AIC:10000 BUS:225 A
<br />FEED THRU:No I/G BUS:No WIRE:4 MCB:150A
<br />NEMA 3R:No 200% NEUTRAL:No PHASE:3 LOCATION:ELEC. RM 111
<br />MOUNTING:SURFACE DOUBLE-LUGS:No VOLTS:120/208 Wye SUPPLY FROM:
<br />PANEL: PA
<br />(E) MS (E) MS
<br />2
<br />2
<br />DESCRIPTION DATE
<br />100%CD 08/16/23
<br />1 ASI#1 4/9/25
<br />2 ASI#2 6/11/25
|