Laserfiche WebLink
12. PANELS SHALL BE OF THE DEAD FRONT SAFETY TYPE. PANELS SHALL BE MINIMUM 20" <br />WIDE AND 5-3/4" DEEP UNLESS OTHERWISE NOTED ON PLAN. <br />13. COORDINATE WITH APPLICABLE TRADE TO INSURE RECESSED MOUNTED <br />PANELBOARDS WILL SEAT FLUSH IN THE WALLS PROVIDED. PANEL TRIMS SHALL HAVE <br />CONCEALED DOORS AND FASTENERS WITH FLUSH TYPE COMBINATION LOCK AND CATCH, <br />TWO MILLED TYPE KEYS SUPPLIED WITH EACH PANEL. ALL LOCKS SHALL BE KEYED ALIKE <br />AND EACH DOOR SHALL HAVE A PLASTIC COVERED DIRECTORY FRAME WITH A TYPED <br />IDENTIFICATION CARD OF ALL CIRCUIT AND PANEL NUMBERS FOR BRANCH CIRCUIT <br />PANELBOARDS. <br />11. ALL CIRCUIT BREAKERS SHALL BE BOLT-ON TYPE AND SHALL BE SUITABLE FOR 75 <br />DEGREE AMPACITY CONDUCTORS. <br />9. PROVIDE BREAKER INTERLOCK WITH ADJACENT BREAKER(S) FOR ANY MULTI-WIRE BRANCH <br />CIRCUIT. BREAKER INTERLOCK GROUPING SHALL BE BY BRANCH CIRCUIT GROUP (i.e. MULTIPLE <br />CIRCUITS SHARING A COMMON NEUTRAL (NEC, OR CEC WHERE ADOPTED, 210.4(B),) COMMON <br />YOKE (NEC, OR CEC WHERE ADOPTED, 210.7,) OR FURNITURE SYSTEM NEC OR CEC WHERE <br />ADOPTED, 605.6 AND 605.5 ). WHERE AN EXISTING PANEL IS BEING ALTERED OR MODIFIED IN ANY <br />WAY, CONTRACTOR SHALL INCLUDE ALL COSTS IN BASE BID TO ADD BREAKER INTERLOCKS TO <br />EXISTING MULTI-WIRE BRANCH CIRCUITS BASED ON CONTRACTOR'S INVESTIGATION OF EXISTING <br />CONDITIONS. <br />8. ALL CIRCUIT BREAKERS USED AS SWITCHES SHALL BE UL LISTED AND LABELED <br />"SWD" FOR SWITCHING DUTY. <br />7. ALL BUSSING SHALL BE TIN PLATED ALUMINUM. <br />6. WHERE PANEL IS INDICATED AS RECESSED OR FLUSH MOUNTED, PROVIDE SPARE <br />CONDUITS STUBBED UP INTO THE ACCESSIBLE CEILING SPACE. PROVIDE ONE (1) 3/4" CONDUIT <br />ONLY FOR EACH THREE (3) SPARES OR SPACES, MINIMUM OF TWO (2). EACH CONDUIT SHALL <br />BE TAGGED, CAPPED AND MARKED FOR FUTURE USE. <br />5. WHERE PANEL CIRCUIT BREAKER RATING IS SHOWN AS SERIES RATED, PROVIDE <br />CIRCUIT BREAKERS IN PANELBOARD WHICH ARE SERIES RATED WITH THE UPSTREAM <br />SYSTEM FOR THE AVAILABLE FAULT CURRENT. THE PANELBOARD SHALL BE MARKED <br />WITH THE SERIES CONNECTED RATINGS, AS WELL AS ALL MARKING AS REQUIRED BY <br />THE NEC, OR CEC WHERE ADOPTED, 240-86(B). <br />4. WHERE PANEL IS INDICATED TO INCLUDE AN I/G BUS, PROVIDE PANELBOARDS <br />WITH AN ISOLATED GROUND BUS, DRILLED AND TAPPED FOR NUMBER OF ISOLATED <br />GROUND CONDUCTORS SHOWN, AS WELL AS FOR ALL SPARES AND SPACES SHOWN <br />ON THE PANELBOARD. <br />3. WHERE PANEL IS INDICATED TO INCLUDE 200% NEUTRAL, PROVIDE PANELBOARDS <br />UL LISTED AS HAVING NEUTRAL BUSSES RATED TO CARRY 200 PERCENT OF THE <br />CURRENT CARRYING CAPACITY OF THE PHASE BUSSING. OTHERWISE, NEUTRAL <br />BUSSING TO BE FULL SIZE AND RECTANGULAR. <br />2. WHERE PANEL IS INDICATED TO INCLUDE DOUBLE LUGS, PROVIDE A DOUBLE LUG <br />KIT AT THE SAME END OF THE PANELBOARD AS THE PANELBOARD MAIN LUGS. <br />1. WHERE PANEL IS INDICATED TO INCLUDE FEED THRU LUGS, PROVIDE FEED THROUGH <br />LUGS AT THE OPPOSITE END OF THE PANELBOARD FROM THE PANELBOARD MAIN LUGS. <br />GENERAL PANEL SCHEDULE NOTES: <br />PANEL SCHEDULE INDEX <br />"F" <br />- <br />PA <br />LA <br />14. UPON PROJECT COMPLETION, CONTRACTOR SHALL INSTALL TYPED AS-BUILT PANEL <br />DIRECTORIES IN EACH PANEL WITHIN THE MFGR-PROVIDED DIRECTORY HOLDER. THE <br />DIRECTORY SHALL CLEARLY IDENTIFY EACH CIRCUIT TO ITS CLEAR, EVIDENT, AND SPECIFIC <br />PURPOSE OR USE. EACH CIRCUIT IDENTITY SHALL INCLUDE SUFFICIENT DETAIL TO ALLOW <br />EACH CIRCUIT TO BE DISTINGUISHED FROM ALL OTHERS PER NEC, OR CEC WHERE ADOPTED, <br />ART 408.1 AND 408.4 . HANDWRITTEN DIRECTORIES ARE UNACCEPTABLE. COPIES OF AS-BUILT <br />PANEL SCHEDULES SHALL BE PLACED IN PANEL DIRECTORIES. E.C. TO INCLUDE ALL COSTS <br />REQUIRED FOR LARGER-THAN-STANDARD CUSTOM PANEL DIRECTORY HOLDERS TO <br />ACCOMMODATE COPIES OF AS-BUILT PANEL SCHEDULES. <br />15. PANELBOARDS SHALL BE MANUFACTURED BY G.E., CUTLER-HAMMER, SIEMENS, OR <br />SQUARE "D". FUSED PANEL BOARDS SHALL BE BY COOPER BUSSMANN. <br />SPECIFIC PANEL SCHEDULE NOTES: <br />"E" <br />"D" <br />"C" <br />"B" <br />"A" <br />16. PROVIDE SHOP DRAWING SUBMITTAL PER THE ELECTRICAL SPECIFICATION <br />SUBMITTAL REQUIREMENTS FOR EACH PANEL DEPICTING CONFORMANCE WITH <br />THE ABOVE NOTES AND SCHEDULES. <br />"G" <br />"H"PROVIDE AFCI TYPE DEVICE COMPLYING WITH NEC, OR CEC WHERE ADOPTED, <br />210.12(A),(B),(C). <br />- <br />- <br />- <br />- <br />PROVIDE LOCK-ON DEVICE. <br />PROVIDE LOCK-OFF DEVICE. <br />PROVIDE SHUNT TRIP DEVICE. <br />PROVIDE GFCI TYPE DEVICE. <br />PROVIDE A RED CIRCUIT BREAKER. <br />PROVIDE A NEW BREAKER TO MATCH THE EXISTING IN PANEL. <br />EXISTING BREAKER WITH NEW LOAD. <br />AS-BUILT PANEL DIRECTORY NOTE: <br />BRANCH CIRCUIT LOCATIONS NOTED WITH "(E)" INDICATE EXISTING CIRCUIT(S). THE <br />IDENTITIES OF THESE CIRCUITS ARE BASED ON EXISTING PANEL DIRECTORIES AND/OR <br />LIMITED AS-BUILT INFORMATION. CONTRACTOR SHALL FIELD VERIFY EACH BRANCH <br />CIRCUIT AND PROVIDE COMPLETE, TYPED AS-BUILT PANEL DIRECTORIES AS REQUIRED <br />THAT DISTINGUISH EACH CIRCUIT PER NEC, OR CEC WHERE ADOPTED, ART 408.1 AND <br />408.4. COMPLETED DIRECTORIES SHALL BE SUBMITTED TO THE ELECTRICAL INSPECTOR <br />PRIOR TO FINAL ELECTRICAL INSPECTION. INCLUDE ALL COSTS IN BID. <br />EXISTING CIRCUIT BREAKER NOTE: <br />PROVIDE BREAKER INTERLOCK WITH ADJACENT BREAKER(S) FOR ANY MULTI-WIRE BRANCH CIRCUIT. <br />BREAKER INTERLOCK GROUPING SHALL BE BY BRANCH CIRCUIT GROUP (i.e. MULTIPLE CIRCUITS <br />SHARING A COMMON NEUTRAL (NEC, OR CEC WHERE ADOPTED, 210.4(B),) COMMON YOKE (NEC, OR <br />CEC WHERE ADOPTED, 210.7,) OR FURNITURE SYSTEM NEC OR CEC WHERE ADOPTED, 605.5 AND <br />605.7). WHERE AN EXISTING PANEL IS BEING ALTERED OR MODIFIED IN ANY WAY, CONTRACTOR SHALL <br />INCLUDE ALL COSTS IN BASE BID TO ADD BREAKER INTERLOCKS TO EXISTING MULTI-WIRE BRANCH <br />CIRCUITS BASED ON CONTRACTOR'S INVESTIGATION OF EXISTING CONDITIONS. <br />10. PROVIDE BREAKER LOCK OFF DEVICE ON ANY CIRCUIT BREAKER FEEDING A <br />TRANSFORMER AS REQUIRED, PER NEC, OR CEC WHERE ADOPTED, 450.14. WHERE AN EXISTING <br />PANEL IS BEING ALTERED OR MODIFIED IN ANY WAY, CONTRACTOR SHALL INCLUDE ALL COSTS <br />IN BASE BID TO ADD BREAKER LOCK-OFF DEVICES TO EXISTING TRANSFORMER CIRCUIT <br />BREAKERS BASED ON CONTRACTOR'S INVESTIGATION OF EXISTING CONDITIONS. <br />11870 Pierce Street, Suite 160 <br />Riverside, California 92505 <br />951.299.4160 www.tk1sc.com <br />C O L L A B O R A T I V E <br />THIS DOCUMENT CONTAINS INFORMATION PROPRIETARY TO SVA ARCHITECTS <br />INC. AND IS FURNISHED IN CONFIDENCE FOR THE LIMITED PURPOSE OF <br />EVALUATION, BIDDING OR REVIEW. THIS DOCUMENT OR ITS CONTENTS MAY <br />NOT BE USED FOR ANY OTHER PURPOSE AND MAY NOT BE REPRODUCED OR <br />DISCLOSED TO OTHERS WITHOUT THE PRIOR WRITTEN CONSENT OF SVA <br />ARCHITECTS INC. ALL RIGHTS RESERVED, © COPYRIGHT 2018. <br />SCALE: <br />REVISIONS: <br />OW <br />N <br />E <br />R <br />: <br />PR <br />O <br />J <br />E <br />C <br />T <br /> <br />N <br />A <br />M <br />E <br />: <br />CL <br />I <br />E <br />N <br />T <br /> <br />A <br />D <br />D <br />R <br />E <br />S <br />S <br />: <br />DATE ISSUED: <br />PROJECT NO: <br />Project Leader -BILL VOLLER <br />tk1sc Job #:B2202330.000 <br />12" = 1'-0" <br />Issue Date <br />E40.3 <br />PANEL <br />SCHEDULES <br />2022-40123 <br />CI <br />T <br />Y <br /> <br />O <br />F <br /> <br />S <br />A <br />N <br />T <br />A <br /> <br />A <br />N <br />A <br />NE <br />W <br />H <br />O <br />P <br />E <br /> <br />L <br />I <br />B <br />R <br />A <br />R <br />Y <br />MO <br />D <br />E <br />R <br />N <br />I <br />Z <br />A <br />T <br />I <br />O <br />N <br />12 <br />2 <br /> <br />N <br />. <br /> <br />N <br />E <br />W <br />H <br />O <br />P <br />E <br /> <br />S <br />T <br />. <br />, <br /> <br />S <br />A <br />N <br />T <br />A <br /> <br />A <br />N <br />A <br /> <br />C <br />A <br /> <br />9 <br />2 <br />7 <br />0 <br />3 <br />W = WATER HEATER <br />R = RECEPTACLE <br />P = POWER <br />M = MOTOR HIGH PHASE: 29 A 3431 VA <br />L = LIGHTING TOTAL DEMAND LOAD: 29.6 A 10657 VA <br />K = KITCHEN Lighting 640 VA 100.00% 640 VA TOTAL CONNECTED LOAD: 24.0 A 8654 VA <br />H = HVAC EQUIP L 8014 VA 125.00% 10017 VA AMPS KVA <br />LOAD TYPE KEY LOAD CLASSIFICATION CONNECTED LOAD AVG. DEMAND... ESTIMATED DEMAND PANEL TOTALS <br />COMMENTS:24.9 A 29.3 A 19.3 A <br />PHASE TOTALS:2903.00 VA 3431.20 VA 2319.40 VA <br />SPACE -- 1 -- 41 -- -- 42 -- 1 -- SPACE <br />SPACE -- 1 -- 39 -- -- 40 -- 1 -- SPACE <br />SPACE -- 1 -- 37 -- -- 38 -- 1 -- SPACE <br />SPACE -- 1 -- 35 -- -- 36 -- 1 -- SPACE <br />SPACE -- 1 -- 33 -- -- 34 -- 1 -- SPACE <br />SPACE -- 1 -- 31 -- -- 32 -- 1 -- SPACE <br />SPACE -- 1 -- 29 -- -- 30 -- 1 -- SPACE <br />SPACE -- 1 -- 27 -- -- 28 -- 1 -- SPACE <br />SPACE -- 1 -- 25 -- -- 26 -- 1 -- SPACE <br />SPACE -- 1 -- 23 -- -- 24 -- 1 -- SPACE <br />SPACE -- 1 -- 21 -- -- 22 -- 1 -- SPACE <br />SPACE -- 1 -- 19 -- -- 20 -- 1 -- SPACE <br />SPARE 20 A 1 -- 17 0 0 18 -- 1 20 A SPARE <br />SPARE 20 A 1 -- 15 0 0 16 -- 1 20 A SPARE <br />LTG. SIGNAGE 20 A 1 L 13 500 0 14 -- 1 20 A SPARE <br />LTG. Room 107, 101, 102, 103 20 A 1 L 11 532 359 12 L 1 20 A LTG. Room 101, 133 <br />LTG. Room 122, 137, 121, 119, 118, 136 20 A 1 L 9 461 1024 10 L;... 1 20 A LTG. Room 124, 131, 132, 126 <br />LTG. MULTIPURPOSE ROOM 110 20 A 1 L 7 653 960 8 L;... 1 20 A LTG. OPEN 132 <br />LTG. Room 105, 107, 116, 115, 117, 111, 113, 112,... 20 A 1 L 5 309 1120 6 L;... 1 20 A LTG. OPEN 134 <br />LTG. INNOVATION CENTER 104 20 A 1 L 3 1218 728 4 L 1 20 A LTG. OPEN 131 <br />LTG. EXTERIOR 20 A 1 L 1 160 630 2 L 1 20 A LTG. OPEN 133 <br />N <br />O <br />T <br />E <br />DESCRIPTION <br />B <br />K <br />R <br />P <br />O <br />L <br />E <br />T <br />Y <br />P <br />E <br />C <br />I <br />R <br />C <br />A (VA) B (VA) C (VA) <br />C <br />I <br />R <br />C <br />T <br />Y <br />P <br />E <br />P <br />O <br />L <br />E <br />B <br />K <br />R DESCRIPTION <br />N <br />O <br />T <br />E <br />M.L.O.:No AIC:10000 BUS:225 A <br />FEED THRU:No I/G BUS:No WIRE:4 MCB:200A <br />NEMA 3R:No 200% NEUTRAL:No PHASE:3 LOCATION:ELEC. RM 111 <br />MOUNTING:SURFACE DOUBLE-LUGS:No VOLTS:120/208 Wye SUPPLY FROM: <br />PANEL: LA <br />W = WATER HEATER <br />R = RECEPTACLE <br />P = POWER <br />M = MOTOR HIGH PHASE: 156 A 18524 VA <br />L = LIGHTING M 27224 VA 104.13% 28349 VA TOTAL DEMAND LOAD: 132.0 A 47564 VA <br />K = KITCHEN R 22070 VA 72.66% 16035 VA TOTAL CONNECTED LOAD: 145.7 A 52474 VA <br />H = HVAC EQUIP P 3180 VA 100.00% 3180 VA AMPS KVA <br />LOAD TYPE KEY LOAD CLASSIFICATION CONNECTED LOAD AVG. DEMAND... ESTIMATED DEMAND PANEL TOTALS <br />COMMENTS:135.6 A 149.1 A 156.2 A <br />PHASE TOTALS:16270.00 VA 17680.00 VA 18524.00 VA <br />SPACE -- 1 -- 83 -- -- 84 -- 1 -- SPACE <br />SPACE -- 1 -- 81 -- -- 82 -- 1 -- SPACE <br />SPACE -- 1 -- 79 -- -- 80 -- 1 -- SPACE <br />SPACE -- 1 -- 77 -- -- 78 -- 1 -- SPACE <br />SPACE -- 1 -- 75 -- -- 76 -- 1 -- SPACE <br />SPACE -- 1 -- 73 -- -- 74 -- 1 -- SPACE <br />SPACE -- 1 -- 71 -- -- 72 -- 1 -- SPACE <br />SPACE -- 1 -- 69 -- -- 70 -- 1 -- SPACE <br />SPACE -- 1 -- 67 -- -- 68 -- 1 -- SPACE <br />SPARE 20 A 1 -- 65 0 0 66 -- 1 20 A SPARE <br />SPARE 20 A 1 -- 63 0 0 64 -- 1 20 A SPARE <br />SPARE 20 A 1 -- 61 0 0 62 -- 1 20 A SPARE <br />R MULTIPURPOSE ROOM 110 PROJECTOR &... 20 A 1 R; P 59 860 540 60 R 1 20 A R OPEN 131 <br />R Room 132, 131 COMPUTERS 20 A 1 R 57 720 500 58 P 1 20 A P IRRIGATION CONTROLLER <br />R CORRIDOR 102 COMPUTER 20 A 1 R 55 360 10 56 R 1 20 A R CORRIDOR 103 DRINK FTN/BTL FILL <br />COPIER 20 A 1 R 53 1000 500 54 P 1 20 A P LOBBY 101 BOOK DETECTION SYSTEM <br />R MULTIPURPOSE ROOM 110 20 A 1 R 51 1080 180 52 R 1 20 A AWE STATION OPEN 131 <br />R MULTIPURPOSE ROOM 110 20 A 1 R 49 1080 720 50 R 1 20 A R OPEN 131 <br />-- -- -- -- -- 47 2250 920 48 -- -- -- -- -- <br />EWH-1 20 A 2 M 45 2250 920 46 M 2 15 A HRU-2 <br />MECHO SHADES 104 20 A 1 P 43 500 920 44 -- -- -- -- -- <br />MECHO SHADES 104 20 A 1 P 41 500 920 42 M 2 15 A HRU-1 <br />CP-1 20 A 1 R 39 180 1130 40 M 1 20 A EF-4 <br />-- -- -- -- -- 37 1380 1130 38 M 1 20 A EF-3 <br />FC-4 20 A 2 M 35 1380 920 36 -- -- -- -- -- <br />-- -- -- -- -- 33 920 920 34 M 2 15 A FC-8 <br />FC-3 20 A 2 M 31 920 920 32 -- -- -- -- -- <br />-- -- -- -- -- 29 920 920 30 M 2 15 A FC-7 <br />FC-2 15 A 2 M 27 920 920 28 -- -- -- -- -- <br />-- -- -- -- -- 25 920 920 26 M 2 15 A FC-6 <br />FC-1 15 A 2 M 23 920 920 24 -- -- -- -- -- <br />REC. EXTERIOR 20 A 1 R 21 540 920 22 M 2 15 A FC-5 <br />REC. STAFF/OFFICE 121 20 A 1 R 19 540 1130 20 M 1 20 A EF-1 <br />REC. MULTIPURPOSE ROOM 110 20 A 1 R 17 1080 14 18 M 1 20 A EF-2 <br />REC. STAFF WORKROOM/ LOUNGE 122 20 A 1 R 15 1080 360 16 R 1 20 A TV MONITORS <br />REC. LIBRARIAN 137 20 A 1 R 13 900 500 14 P 1 20 A FACP AE <br />REC. Room 101, 103, 102 20 A 1 R; P 11 1440 360 12 R 1 20 A R LOBBY 101 <br />REC. Room 113, 116, 115, 117, 123 20 A 1 R 9 1080 720 10 R 1 20 A REC. OPEN 133 <br />REC. Room 105, 107 20 A 1 R 7 900 900 8 R 1 20 A REC. Room 133, 131 <br />REC. INNOVATION CENTER 104 20 A 1 R 5 1260 900 6 R 1 20 A REC. OPEN 131 <br />REC. INNOVATION CENTER 104 20 A 1 R 3 1260 1080 4 R 1 20 A REC. Room 130, 126 <br />REC. INNOVATION CENTER 104 20 A 1 R 1 1260 360 2 R 1 20 A REC. PATIO 135, EXTERIOR <br />N <br />O <br />T <br />E <br />DESCRIPTION <br />B <br />K <br />R <br />P <br />O <br />L <br />E <br />T <br />Y <br />P <br />E <br />C <br />I <br />R <br />C <br />A (VA) B (VA) C (VA) <br />C <br />I <br />R <br />C <br />T <br />Y <br />P <br />E <br />P <br />O <br />L <br />E <br />B <br />K <br />R DESCRIPTION <br />N <br />O <br />T <br />E <br />M.L.O.:No AIC:10000 BUS:225 A <br />FEED THRU:No I/G BUS:No WIRE:4 MCB:150A <br />NEMA 3R:No 200% NEUTRAL:No PHASE:3 LOCATION:ELEC. RM 111 <br />MOUNTING:SURFACE DOUBLE-LUGS:No VOLTS:120/208 Wye SUPPLY FROM: <br />PANEL: PA <br />(E) MS (E) MS <br />2 <br />2 <br />DESCRIPTION DATE <br />100%CD 08/16/23 <br />1 ASI#1 4/9/25 <br />2 ASI#2 6/11/25