SPECIFICATIONS TABLE OF CONTENTS <br />SECTION 26 24 16 -PANELBOARDS <br />PART 1 -GENERAL <br />1.1 SECTION INCLUDES <br />A. LIGHTING AND APPLIANCE BRANCH CIRCUIT PANELBOARDS <br />1.2 RELATED SECTIONS AND WORK <br />A. REFER TO THE ELECTRICAL DISTRIBUTION DIAGRAM AND ELECTRICAL SCHEDULES FOR SIZE, <br />RATING, AND CONFIGURATION. <br />1.3 REFERENCES <br />A. NEMA AB 1 -MOLDED CASE CIRCUIT BREAKERS <br />B. NEMA PB 1 -PANELBOARDS <br />C. NEMA PB 1.1 -INSTRUCTIONS FOR SAFE INSTALLATION, OPERATION AND MAINTENANCE OF <br />PANELBOARDS RATED 600 VOLTS OR LESS <br />1.4 SUBMITTALS <br />A. SUBMIT SHOP DRAWINGS FOR EQUIPMENT AND COMPONENT DEVICES UNDER PROVISIONS OF <br />SECTION 26 05 00. <br />B. INCLUDE OUTLINE AND SUPPORT POINT DIMENSIONS, VOLTAGE, MAIN BUS AMPACITY, <br />INTEGRATED SHORT CIRCUIT AMPERE RATING, CIRCUIT BREAKER ARRANGEMENT AND SIZES. <br />C. SUBMIT MANUFACTURER'S INSTRUCTIONS UNDER PROVISIONS OF SECTION 26 05 00. <br />1.5 SPARE PARTS <br />A. KEYS: FURNISH FOUR (4) EACH TO THE OWNER. <br />PART 2 -PRODUCTS <br />2.1 RATINGS <br />A. DEFINITIONS: <br />1. FULLY RATED EQUIPMENT SHALL BE DEFINED AS EQUIPMENT WHERE ALL DEVICES IN THAT <br />EQUIPMENT SHALL CARRY A MINIMUM OF THE AIC RATING THAT IS SPECIFIED. <br />B. THE PANELBOARDS FOR THIS PROJECT SHALL BE FULLY RATED. <br />2.2 BRANCH CIRCUIT PANELBOARDS <br />A. GENERAL <br />1. MANUFACTURERS: <br />a. SQUARE D NQ, NF <br />b. ABB RELIAGEAR SERIES <br />c. SIEMENS P1 <br />d. EATON PRL1, PRL2 <br />B. LIGHTING AND APPLIANCE BRANCH CIRCUIT PANELBOARDS: NEMA PB 1; CIRCUIT BREAKER <br />TYPE. <br />C. ENCLOSURE: NEMA PB 1; TYPE 1. <br />D. PROVIDE CABINET FRONT WITH DOOR-IN-DOOR CONSTRUCTION, CONCEALED HINGE, AND <br />FLUSH LOCK ALL KEYED ALIKE. DOOR HARDWARE SHALL PROVIDE SWING CLEAR OPERATION <br />(180-DEGREE SWING). FINISH IN MANUFACTURER'S STANDARD GRAY ENAMEL. <br />E. PROVIDE PANELBOARDS WITH ALUMINUM BUS, RATINGS AS SCHEDULED ON THE DRAWINGS. <br />PROVIDE COPPER GROUND BUS IN ALL PANELBOARDS. <br />F. ALL UNLABELED CIRCUITS SHOWN ON THE PANELBOARD SCHEDULE SHALL BE FULLY <br />PREPARED SPACES FOR FUTURE BREAKERS. <br />G. MINIMUM INTEGRATED SHORT CIRCUIT RATING: AS SHOWN ON THE DRAWINGS. <br />H. MOLDED CASE CIRCUIT BREAKERS: BOLT-ON TYPE THERMAL MAGNETIC TRIP CIRCUIT <br />BREAKERS, WITH COMMON TRIP HANDLE FOR ALL POLES. PROVIDE CIRCUIT BREAKERS UL <br />LISTED AS TYPE SWD FOR LIGHTING CIRCUITS. PROVIDE UL CLASS A GROUND FAULT <br />INTERRUPTER CIRCUIT BREAKERS WHERE SCHEDULED ON THE DRAWINGS. DO NOT USE <br />TANDEM CIRCUIT BREAKERS. <br />PART 3 -EXECUTION <br />3.1 INSTALLATION <br />A. INSTALL PANELBOARDS PLUMB AS INDICATED ON THE DRAWINGS IN CONFORMANCE WITH <br />NEMA PB 1.1. <br />B. HEIGHT: 6 FEET TO HANDLE OF HIGHEST DEVICE. <br />C. PROVIDE FILLER PLATES FOR UNUSED SPACES IN PANELBOARDS. <br />D. PROVIDE CUSTOM TYPED CIRCUIT DIRECTORY FOR EACH BRANCH CIRCUIT PANELBOARD. <br />LABEL SHALL INCLUDE EQUIPMENT NAME OR FINAL APPROVED ROOM NAME, ROOM NUMBER, <br />AND LOAD TYPE FOR EACH CIRCUIT (EXAMPLES: SUMP SP-1 OR ROOM 101 RECEPT). REVISE <br />DIRECTORY TO REFLECT CIRCUIT CHANGES REQUIRED TO BALANCE PHASE LOADS. PRINTED <br />COPIES OF THE BID DOCUMENT PANEL SCHEDULES ARE NOT ACCEPTABLE AS CIRCUIT <br />DIRECTORIES. <br />E. STUB FIVE (5) EMPTY ONE-INCH CONDUITS TO ACCESSIBLE LOCATION ABOVE CEILING OUT OF <br />EACH RECESSED PANELBOARD. <br />3.2 FIELD QUALITY CONTROL <br />A. MEASURE STEADY STATE LOAD CURRENTS AT EACH PANELBOARD FEEDER. SHOULD THE <br />DIFFERENCE AT ANY PANELBOARD BETWEEN PHASES EXCEED 20 PERCENT, REARRANGE <br />CIRCUITS IN THE PANELBOARD TO BALANCE THE PHASE LOADS WITHIN 20 PERCENT. TAKE <br />CARE TO MAINTAIN PROPER PHASING FOR MULTI-WIRE BRANCH CIRCUITS. <br />B. VISUAL AND MECHANICAL INSPECTION: INSPECT FOR PHYSICAL DAMAGE, PROPER ALIGNMENT, <br />ANCHORAGE, AND GROUNDING. CHECK PROPER INSTALLATION AND TIGHTNESS OF <br />CONNECTIONS FOR CIRCUIT BREAKERS. <br />END OF SECTION <br />• SECTION 26 24 16 -PANELBOARDS <br />• SECTION 26 51 19 -LED LIGHTING <br />1.6 WARRANTY <br />A. THE WARRANTY PERIOD BEGINS AT THE DATE OF SUBSTANTIAL COMPLETION. <br />B. LED LIGHT ENGINES AND DRIVERS: <br />1. LED DRIVERS AND DIMMING DRIVERS: FIVE (5) YEARS <br />2. LIGHT EMITTING DIODE (LED) LIGHT ENGINES: FIVE (5) YEARS <br />C.EMERGENCY DRIVERS: <br />1. EMERGENCY LED DRIVER: FIVE (5) YEARS <br />PART 2 -PRODUCTS <br />2.1 INTERIOR LUMINAIRES AND ACCESSORIES -GENERAL <br />A. LENSED TROFFERS: PROVIDE HINGED FRAMES WITH LATCHES AND 0.125-INCH THICK VIRGIN <br />ACRYLIC LENSES. PRISMATIC LENSES SHALL HAVE DEPTH OF NO LESS THAN 0.080", KSH12 OR <br />EQUAL. OTHER LENSES AS SCHEDULED. <br />B. RECESSED LUMINAIRES: CONFIRM CEILING AND WALL TYPE AND FURNISH TRIM AND <br />ACCESSORIES NECESSARY TO PERMIT PROPER INSTALLATION IN EACH SYSTEM. WHERE FIRE- <br />RATED CEILING OR WALL ASSEMBLIES ARE SPECIFIED, FURNISH AND INSTALL LISTED <br />ENCLOSURES AROUND LUMINAIRES THAT MAINTAIN THE SYSTEM RATING. <br />2.2 LIGHT EMITTING DIODE (LED) LUMINAIRE SYSTEMS <br />A. REFER TO THE LUMINAIRE SCHEDULE FOR COLOR TEMPERATURE AND MINIMUM COLOR <br />RENDERING INDEX CRI REQUIREMENTS. PROVIDE LIGHT SOURCE COLOR CONSISTENCY BY <br />UTILIZING A BINNING TOLERANCE WITHIN A MAXIMUM 3-STEP MCADAM ELLIPSE UNLESS NOTED <br />OTHERWISE. <br />B. RATED LIFE SHALL BE MINIMUM OF 50,000 HOURS AT L70. <br />C. LED CHIPS SHALL BE WIRED SO THAT FAILURE OF ONE CHIP DOES NOT PROHIBIT OPERATION <br />OF THE REMAINDER OF THE CHIP ARRAY. <br />D. LUMINAIRE DELIVERED LUMENS IS DEFINED AS THE ABSOLUTE LUMENS PER THE <br />MANUFACTURERS LM-79-08 TEST REPORT. <br />E. LED LUMINAIRES SHALL BE DESIGNED FOR EASE OF COMPONENT REPLACEMENT INCLUDING <br />MODULAR REPLACEABLE BOARDS OR ZHAGA SOCKETS. LUMINAIRES THAT ARE FACTORY <br />SEALED AND DO NOT HAVE FIELD REPLACEABLE PARTS SHALL PROVIDE A 10-YEAR WARRANTY. <br />F. LED LIGHT ENGINE SHALL HAVE A MAXIMUM LLD OF 0.85 AT 50,000 HOURS AT 25°C AMBIENT. <br />G. LED DRIVER: <br />1. SOLID STATE DRIVER WITH INTEGRAL HEAT SINK. DRIVER SHALL HAVE OVER-HEAT, SHORT- <br />CIRCUIT AND OVERLOAD PROTECTION, POWER FACTOR 0.90 OR ABOVE AND MAXIMUM <br />TOTAL HARMONIC DISTORTION OF 10%. DRIVER SHALL HAVE A VOLTAGE FLUCTUATION <br />TOLERANCE OF +/-10%. <br />2. DRIVERS SHALL HAVE DIMMING CAPABILITIES AS OUTLINED IN THE LUMINAIRE SCHEDULE <br />FOR EACH LUMINAIRE TYPE. DIMMING SHALL CONTROL LIGHT OUTPUT IN A CONTINUOUS <br />CURVE FROM 100% TO 10% UNLESS NOTED OTHERWISE. <br />3. DRIVER SHALL HAVE A MINIMUM OF 50,000 HOURS RATED LIFE. <br />4. DRIVER SHALL BE TESTED TO ANSI C82-16 FOR INPUT CURRENT INRUSH, TOTAL HARMONIC <br />DISTORTION (THD), AND POWER FACTOR. DRIVER START TIME SHALL BE LESS THAN 0.5 <br />SECONDS TO 98% OF INITIAL LIGHT OUTPUT. FLICKER SHOULD BE LESS THAN 30% <br />THROUGHOUT THE OPERATING RANGE. <br />5. DRIVER SHALL BE FIELD REPLACEABLE WITHOUT REMOVAL OF THE LUMINAIRE. <br />6. CLASS A SOUND RATING; INAUDIBLE IN A 27 DBA AMBIENT. <br />7. DEMONSTRATE NO VISIBLE CHANGE IN LIGHT OUTPUT WITH A VARIATION OF PLUS OR <br />MINUS 10 PERCENT CHANGE IN LINE-VOLTAGE INPUT. <br />PART 3 -EXECUTION <br />3.1 INSTALLATION <br />A. SECURELY FASTEN LUMINAIRES TO THE LISTED AND LABELED CEILING FRAMING MEMBER BY <br />MECHANICAL MEANS SUCH AS BOLTS, SCREWS, RIVETS OR LISTED CLIPS IDENTIFIED FOR USE <br />WITH THE TYPE OF CEILING FRAMING MEMBERS. LUMINAIRES AND WIRING INSTALLED IN FIRE- <br />RATED CEILING ASSEMBLIES SHALL BE INDEPENDENTLY SUPPORTED FOR ALL APPLICATIONS. <br />1. INSTALL RECESSED FLANGED LUMINAIRES TO PERMIT REMOVAL FROM BELOW. USE <br />MANUFACTURER-SUPPLIED PLASTER FRAMES AND SWING GATE SUPPORTS. <br />B.DO NOT FASTEN LUMINAIRE SUPPORTS TO PIPING, DUCTWORK, MECHANICAL EQUIPMENT, OR <br /> CONDUIT, UNLESS OTHERWISE NOTED. SUPPORT WIRES SHALL BE TIGHTLY WRAPPED <br /> (MINIMUM OF THREE TURNS WITHIN 3 INCHES OF THE CONNECTION) AND SHARPLY BEND TO <br /> PREVENT VERTICAL MOVEMENT. <br />C.SUPPORT WIRE USED TO INDEPENDENTLY SUPPORT LUMINAIRES, RACEWAYS, AND WIRING <br /> SYSTEMS SHALL BE DISTINGUISHABLE FROM CEILING SUPPORT SYSTEMS BY COLOR (FIELD <br /> PAINT), TAGGING OR EQUIVALENT MEANS. <br />3.2 RELAMPING <br />A. REPLACE FAILED LED LIGHT ENGINE MODULES OR ARRAYS AT COMPLETION OF WORK. <br />3.3 ADJUSTING AND CLEANING <br />A. ALIGN LUMINAIRES AND CLEAN LENSES AND DIFFUSERS AT COMPLETION OF WORK. CLEAN <br />PAINT SPLATTERS, DIRT, AND DEBRIS FROM INSTALLED LUMINAIRES. <br />B. TOUCH UP LUMINAIRE FINISH AT COMPLETION OF WORK. <br />3.4 LUMINAIRE SCHEDULE <br />A. AS SHOWN ON THE DRAWINGS. <br />END OF SECTION <br />SECTION 26 51 19 -LED LIGHTING <br />PART 1 -GENERAL <br />1.1 SECTION INCLUDES <br />A. INTERIOR LUMINAIRES AND ACCESSORIES <br />B. LIGHT-EMITTING DIODE (LED) LUMINAIRE SYSTEMS <br />1.2 RELATED SECTIONS <br />A. THE LIGHTING SYSTEM DESIGN INCLUDES A COMBINATION OF LUMINAIRE SOURCES, LIGHTING <br />CONTROL COMPONENTS, PROGRAMMING SEQUENCES, AND SUPPLEMENTARY COMPONENTS <br />FOR BUILDING AND ENERGY CODE COMPLIANCE. THE DESIGN USES PERFORMANCE-BASED <br />SPECIFICATIONS FOR PORTIONS OF THE LIGHTING SYSTEM TO ACCOUNT FOR THE LIMITATION <br />OF COMPARABLE PRODUCT SOLUTIONS AVAILABLE BY COMPETITIVE MANUFACTURERS. THE <br />CONTRACTOR SHALL REFERENCE RELATED SPECIFICATION SECTIONS, PLANS, SCHEDULES, <br />AND DETAILS PRIOR TO SUBMITTING PRICING, SUBMITTALS, AND INSTALLATION. THE <br />CONTRACTOR SHALL COORDINATE SYSTEM COMPONENT COMPATIBILITY AMONG VARIOUS <br />MANUFACTURERS AND SUPPLIERS FOR A TURNKEY LIGHTING SYSTEM. <br />1. 26 09 33 LIGHTING CONTROL SYSTEMS <br />2. ELECTRICAL DRAWINGS: PLANS, LUMINAIRE SCHEDULES, LIGHTING CONTROL SEQUENCE <br />OF OPERATIONS, DIAGRAMS, AND DETAILS. <br />1.3 REFERENCES <br />A. ANSI C78.377 -SPECIFICATIONS FOR THE CHROMATICITY OF SOLID STATE LIGHTING PRODUCTS <br />B. ANSI C82.16 -LIGHT-EMITTING DIODE DRIVERS -METHOD OF MEASUREMENT <br />C. NEMA SSL1 -ELECTRONIC DRIVERS FOR LED DEVICES, ARRAYS OR SYSTEM <br />D. UL 8750 -LIGHT EMITTING DIODE (LED) EQUIPMENT FOR USE IN LIGHTING PRODUCTS <br />E. LM-80 -MEASURING LUMINOUS FLUX AND COLOR MAINTENANCE OF LED <br />F. UL 924 -STANDARD FOR EMERGENCY LIGHTING AND POWER EQUIPMENT <br />1.4 SUBMITTALS <br />A. SUBMIT PRODUCT DATA UNDER PROVISIONS OF SECTION 26 05 00. <br />B. BASIC REQUIREMENTS OF SUBMITTAL: <br />1. SUBMIT PRODUCT DATA SHEETS FOR LUMINAIRES, LED LIGHT ENGINES, DRIVERS AND <br />POLES. INCLUDE COMPLETE PRODUCT MODEL NUMBER WITH ALL OPTIONS AS SPECIFIED. <br />SUBMITTAL SHALL BE ARRANGED WITH LUMINAIRES LISTED IN ASCENDING ORDER, AND <br />WITH EACH LUMINAIRE'S, LED LIGHT ENGINE, DRIVER, OR POLE INFORMATION FOLLOWING <br />LUMINAIRE'S PRODUCT DATA. FAILURE TO ORGANIZE SUBMITTAL IN THIS MANNER WILL <br />RESULT IN THE SUBMITTAL BEING REJECTED. <br />2. SUBMIT MANUFACTURER ORIGIN OF LED CHIPSET AND DRIVER. <br />C.LED LIGHTING -CONTROL COMPATIBILITY SUBMITTAL: <br />1. SUBMIT LIGHTING CONTROL CAPABILITY DATA FOR EACH LED LUMINAIRE. THE SUBMITTAL <br />SHALL CLEARLY IDENTIFY DEVICE DATA PROPOSED BY THE CONTRACTOR AND APPROVED <br />BY THE LUMINAIRE MANUFACTURER FOR DIMMING, SWITCHING, ADDRESSABLE, WIRELESS, <br />AND SIMILAR CONTROL CHARACTERISTICS. <br />1.5 DELIVERY, STORAGE, AND HANDLING <br />A. DELIVER PRODUCTS TO SITE. STORE AND PROTECT UNDER PROVISIONS OF SECTION 26 05 00. <br />B. PROTECT LUMINAIRE FINISHES, LENSES, AND TRIMS FROM DAMAGE DURING STORAGE AND <br />INSTALLATION. DO NOT REMOVE PROTECTIVE FILMS UNTIL CONSTRUCTION CLEANUP WITHIN <br />EACH AREA IS COMPLETE. <br />TE OLIRFFOAC <br />LANRP <br />E 23191 <br />STA <br />ER <br />REGIST <br />ED <br />INA <br />N <br />REENIGE <br />FO OISSE <br />E AICLCERTL <br />Exp. 06/30/26 <br />MIRASOPHOCLISGEORGY <br />IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, <br />TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING <br />AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND SHALL <br />NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE <br />EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. <br />©2022 IMEG CORP. <br />REF. SCALE IN INCHES <br />0 1 2 3 <br />The FUTURE. Built Smarter www.imegcorp.com <br />R <br />SHEET TITLE <br />PROJECT <br />FACILITY <br />FAC NO: BLDG NO: FLOOR LEV: SECTION: <br />KP PROJ. NO. <br />PERMIT NO. <br />555 W. 5th St Suite 2950 | Los Angeles, CA 90013 USA <br />Phone 310.820.4600 | Fax 310.207.4215 <br />www.huitt-zollars.com <br />ARCHITECT <br />CONSULTANT <br />ARCHITECT SEAL CONSULTANT SEAL <br />KAISER FOUNDATION <br />HOSPITALS NATIONAL <br />FACILITIES SERVICES 1800 <br />HARRISON STREET OAKLAND, <br />CALIFORNIA 94612 <br />ISSUE / REVISION LOG <br />NO. ISSUED DATE <br />0 <br />5' <br /> <br />5 <br />0 <br />' <br />GR <br />A <br />P <br />H <br />I <br />C <br /> <br />S <br />C <br />A <br />L <br />E <br />S <br />: <br /> <br />1 <br />/ <br />1 <br />6 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />0 <br />25 <br />' <br />1/ <br />8 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />5' <br />0 <br />12 <br />' <br />1/ <br />4 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />1' <br />0 <br />6' <br />1/ <br />2 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />1' <br />0 <br />2' <br />1- <br />1 <br />/ <br />2 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />0 <br />1' <br />3" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />IF <br /> <br />T <br />H <br />I <br />S <br /> <br />S <br />H <br />E <br />E <br />T <br /> <br />I <br />S <br /> <br />N <br />O <br />T <br /> <br />30 <br />" <br />x <br />4 <br />2 <br />" <br />, <br /> <br />I <br />T <br /> <br />I <br />S <br /> <br />A <br /> <br />R <br />E <br />D <br />U <br />C <br />E <br />D <br /> <br />PR <br />I <br />N <br />T <br /> <br />- <br /> <br />S <br />C <br />A <br />L <br />E <br /> <br />AC <br />C <br />O <br />R <br />D <br />I <br />N <br />G <br />L <br />Y <br />AGENCY APPLICATION NUMBER <br />AGENCY APPROVAL STAMP <br />THIS DOCUMENT IS THE PROPERTY OF THE OWNER AND IS <br />NOT TO BE USED WITHOUT OWNER'S WRITTEN PERMISSION. <br />HZ PROJ. NO. <br />222 S. HARBOR BOULEVARD, SUITE 800 I ANAHEIM, CA 92805 <br />PH: 714.490.5555 I FAX: 714.490.5560 <br />IMEG PROJ. NO.: 22008618.00 <br />PROJECT #22008618.00 <br />SOCC 2022 R HBM 1st Fl KPOJ <br />REMODEL <br />E0-06 <br />ELECTRICAL SPECIFICATION <br />CA394-1 <br />CAP0227721R314412.35 <br />HARBOR/MacARTHUR MEDICAL OFF <br />3401 S. HARBOR BLVD. <br />SANTA ANA, CALIFORNIA 92704 <br />CITY SUBMITTAL 11/03/2025 <br />1 CITY BACKCHECK #1 01/06/2026 <br />101125520, 20187249, 40140902