SPECIFICATIONS TABLE OF CONTENTS
<br />SECTION 26 24 16 -PANELBOARDS
<br />PART 1 -GENERAL
<br />1.1 SECTION INCLUDES
<br />A. LIGHTING AND APPLIANCE BRANCH CIRCUIT PANELBOARDS
<br />1.2 RELATED SECTIONS AND WORK
<br />A. REFER TO THE ELECTRICAL DISTRIBUTION DIAGRAM AND ELECTRICAL SCHEDULES FOR SIZE,
<br />RATING, AND CONFIGURATION.
<br />1.3 REFERENCES
<br />A. NEMA AB 1 -MOLDED CASE CIRCUIT BREAKERS
<br />B. NEMA PB 1 -PANELBOARDS
<br />C. NEMA PB 1.1 -INSTRUCTIONS FOR SAFE INSTALLATION, OPERATION AND MAINTENANCE OF
<br />PANELBOARDS RATED 600 VOLTS OR LESS
<br />1.4 SUBMITTALS
<br />A. SUBMIT SHOP DRAWINGS FOR EQUIPMENT AND COMPONENT DEVICES UNDER PROVISIONS OF
<br />SECTION 26 05 00.
<br />B. INCLUDE OUTLINE AND SUPPORT POINT DIMENSIONS, VOLTAGE, MAIN BUS AMPACITY,
<br />INTEGRATED SHORT CIRCUIT AMPERE RATING, CIRCUIT BREAKER ARRANGEMENT AND SIZES.
<br />C. SUBMIT MANUFACTURER'S INSTRUCTIONS UNDER PROVISIONS OF SECTION 26 05 00.
<br />1.5 SPARE PARTS
<br />A. KEYS: FURNISH FOUR (4) EACH TO THE OWNER.
<br />PART 2 -PRODUCTS
<br />2.1 RATINGS
<br />A. DEFINITIONS:
<br />1. FULLY RATED EQUIPMENT SHALL BE DEFINED AS EQUIPMENT WHERE ALL DEVICES IN THAT
<br />EQUIPMENT SHALL CARRY A MINIMUM OF THE AIC RATING THAT IS SPECIFIED.
<br />B. THE PANELBOARDS FOR THIS PROJECT SHALL BE FULLY RATED.
<br />2.2 BRANCH CIRCUIT PANELBOARDS
<br />A. GENERAL
<br />1. MANUFACTURERS:
<br />a. SQUARE D NQ, NF
<br />b. ABB RELIAGEAR SERIES
<br />c. SIEMENS P1
<br />d. EATON PRL1, PRL2
<br />B. LIGHTING AND APPLIANCE BRANCH CIRCUIT PANELBOARDS: NEMA PB 1; CIRCUIT BREAKER
<br />TYPE.
<br />C. ENCLOSURE: NEMA PB 1; TYPE 1.
<br />D. PROVIDE CABINET FRONT WITH DOOR-IN-DOOR CONSTRUCTION, CONCEALED HINGE, AND
<br />FLUSH LOCK ALL KEYED ALIKE. DOOR HARDWARE SHALL PROVIDE SWING CLEAR OPERATION
<br />(180-DEGREE SWING). FINISH IN MANUFACTURER'S STANDARD GRAY ENAMEL.
<br />E. PROVIDE PANELBOARDS WITH ALUMINUM BUS, RATINGS AS SCHEDULED ON THE DRAWINGS.
<br />PROVIDE COPPER GROUND BUS IN ALL PANELBOARDS.
<br />F. ALL UNLABELED CIRCUITS SHOWN ON THE PANELBOARD SCHEDULE SHALL BE FULLY
<br />PREPARED SPACES FOR FUTURE BREAKERS.
<br />G. MINIMUM INTEGRATED SHORT CIRCUIT RATING: AS SHOWN ON THE DRAWINGS.
<br />H. MOLDED CASE CIRCUIT BREAKERS: BOLT-ON TYPE THERMAL MAGNETIC TRIP CIRCUIT
<br />BREAKERS, WITH COMMON TRIP HANDLE FOR ALL POLES. PROVIDE CIRCUIT BREAKERS UL
<br />LISTED AS TYPE SWD FOR LIGHTING CIRCUITS. PROVIDE UL CLASS A GROUND FAULT
<br />INTERRUPTER CIRCUIT BREAKERS WHERE SCHEDULED ON THE DRAWINGS. DO NOT USE
<br />TANDEM CIRCUIT BREAKERS.
<br />PART 3 -EXECUTION
<br />3.1 INSTALLATION
<br />A. INSTALL PANELBOARDS PLUMB AS INDICATED ON THE DRAWINGS IN CONFORMANCE WITH
<br />NEMA PB 1.1.
<br />B. HEIGHT: 6 FEET TO HANDLE OF HIGHEST DEVICE.
<br />C. PROVIDE FILLER PLATES FOR UNUSED SPACES IN PANELBOARDS.
<br />D. PROVIDE CUSTOM TYPED CIRCUIT DIRECTORY FOR EACH BRANCH CIRCUIT PANELBOARD.
<br />LABEL SHALL INCLUDE EQUIPMENT NAME OR FINAL APPROVED ROOM NAME, ROOM NUMBER,
<br />AND LOAD TYPE FOR EACH CIRCUIT (EXAMPLES: SUMP SP-1 OR ROOM 101 RECEPT). REVISE
<br />DIRECTORY TO REFLECT CIRCUIT CHANGES REQUIRED TO BALANCE PHASE LOADS. PRINTED
<br />COPIES OF THE BID DOCUMENT PANEL SCHEDULES ARE NOT ACCEPTABLE AS CIRCUIT
<br />DIRECTORIES.
<br />E. STUB FIVE (5) EMPTY ONE-INCH CONDUITS TO ACCESSIBLE LOCATION ABOVE CEILING OUT OF
<br />EACH RECESSED PANELBOARD.
<br />3.2 FIELD QUALITY CONTROL
<br />A. MEASURE STEADY STATE LOAD CURRENTS AT EACH PANELBOARD FEEDER. SHOULD THE
<br />DIFFERENCE AT ANY PANELBOARD BETWEEN PHASES EXCEED 20 PERCENT, REARRANGE
<br />CIRCUITS IN THE PANELBOARD TO BALANCE THE PHASE LOADS WITHIN 20 PERCENT. TAKE
<br />CARE TO MAINTAIN PROPER PHASING FOR MULTI-WIRE BRANCH CIRCUITS.
<br />B. VISUAL AND MECHANICAL INSPECTION: INSPECT FOR PHYSICAL DAMAGE, PROPER ALIGNMENT,
<br />ANCHORAGE, AND GROUNDING. CHECK PROPER INSTALLATION AND TIGHTNESS OF
<br />CONNECTIONS FOR CIRCUIT BREAKERS.
<br />END OF SECTION
<br />• SECTION 26 24 16 -PANELBOARDS
<br />• SECTION 26 51 19 -LED LIGHTING
<br />1.6 WARRANTY
<br />A. THE WARRANTY PERIOD BEGINS AT THE DATE OF SUBSTANTIAL COMPLETION.
<br />B. LED LIGHT ENGINES AND DRIVERS:
<br />1. LED DRIVERS AND DIMMING DRIVERS: FIVE (5) YEARS
<br />2. LIGHT EMITTING DIODE (LED) LIGHT ENGINES: FIVE (5) YEARS
<br />C.EMERGENCY DRIVERS:
<br />1. EMERGENCY LED DRIVER: FIVE (5) YEARS
<br />PART 2 -PRODUCTS
<br />2.1 INTERIOR LUMINAIRES AND ACCESSORIES -GENERAL
<br />A. LENSED TROFFERS: PROVIDE HINGED FRAMES WITH LATCHES AND 0.125-INCH THICK VIRGIN
<br />ACRYLIC LENSES. PRISMATIC LENSES SHALL HAVE DEPTH OF NO LESS THAN 0.080", KSH12 OR
<br />EQUAL. OTHER LENSES AS SCHEDULED.
<br />B. RECESSED LUMINAIRES: CONFIRM CEILING AND WALL TYPE AND FURNISH TRIM AND
<br />ACCESSORIES NECESSARY TO PERMIT PROPER INSTALLATION IN EACH SYSTEM. WHERE FIRE-
<br />RATED CEILING OR WALL ASSEMBLIES ARE SPECIFIED, FURNISH AND INSTALL LISTED
<br />ENCLOSURES AROUND LUMINAIRES THAT MAINTAIN THE SYSTEM RATING.
<br />2.2 LIGHT EMITTING DIODE (LED) LUMINAIRE SYSTEMS
<br />A. REFER TO THE LUMINAIRE SCHEDULE FOR COLOR TEMPERATURE AND MINIMUM COLOR
<br />RENDERING INDEX CRI REQUIREMENTS. PROVIDE LIGHT SOURCE COLOR CONSISTENCY BY
<br />UTILIZING A BINNING TOLERANCE WITHIN A MAXIMUM 3-STEP MCADAM ELLIPSE UNLESS NOTED
<br />OTHERWISE.
<br />B. RATED LIFE SHALL BE MINIMUM OF 50,000 HOURS AT L70.
<br />C. LED CHIPS SHALL BE WIRED SO THAT FAILURE OF ONE CHIP DOES NOT PROHIBIT OPERATION
<br />OF THE REMAINDER OF THE CHIP ARRAY.
<br />D. LUMINAIRE DELIVERED LUMENS IS DEFINED AS THE ABSOLUTE LUMENS PER THE
<br />MANUFACTURERS LM-79-08 TEST REPORT.
<br />E. LED LUMINAIRES SHALL BE DESIGNED FOR EASE OF COMPONENT REPLACEMENT INCLUDING
<br />MODULAR REPLACEABLE BOARDS OR ZHAGA SOCKETS. LUMINAIRES THAT ARE FACTORY
<br />SEALED AND DO NOT HAVE FIELD REPLACEABLE PARTS SHALL PROVIDE A 10-YEAR WARRANTY.
<br />F. LED LIGHT ENGINE SHALL HAVE A MAXIMUM LLD OF 0.85 AT 50,000 HOURS AT 25°C AMBIENT.
<br />G. LED DRIVER:
<br />1. SOLID STATE DRIVER WITH INTEGRAL HEAT SINK. DRIVER SHALL HAVE OVER-HEAT, SHORT-
<br />CIRCUIT AND OVERLOAD PROTECTION, POWER FACTOR 0.90 OR ABOVE AND MAXIMUM
<br />TOTAL HARMONIC DISTORTION OF 10%. DRIVER SHALL HAVE A VOLTAGE FLUCTUATION
<br />TOLERANCE OF +/-10%.
<br />2. DRIVERS SHALL HAVE DIMMING CAPABILITIES AS OUTLINED IN THE LUMINAIRE SCHEDULE
<br />FOR EACH LUMINAIRE TYPE. DIMMING SHALL CONTROL LIGHT OUTPUT IN A CONTINUOUS
<br />CURVE FROM 100% TO 10% UNLESS NOTED OTHERWISE.
<br />3. DRIVER SHALL HAVE A MINIMUM OF 50,000 HOURS RATED LIFE.
<br />4. DRIVER SHALL BE TESTED TO ANSI C82-16 FOR INPUT CURRENT INRUSH, TOTAL HARMONIC
<br />DISTORTION (THD), AND POWER FACTOR. DRIVER START TIME SHALL BE LESS THAN 0.5
<br />SECONDS TO 98% OF INITIAL LIGHT OUTPUT. FLICKER SHOULD BE LESS THAN 30%
<br />THROUGHOUT THE OPERATING RANGE.
<br />5. DRIVER SHALL BE FIELD REPLACEABLE WITHOUT REMOVAL OF THE LUMINAIRE.
<br />6. CLASS A SOUND RATING; INAUDIBLE IN A 27 DBA AMBIENT.
<br />7. DEMONSTRATE NO VISIBLE CHANGE IN LIGHT OUTPUT WITH A VARIATION OF PLUS OR
<br />MINUS 10 PERCENT CHANGE IN LINE-VOLTAGE INPUT.
<br />PART 3 -EXECUTION
<br />3.1 INSTALLATION
<br />A. SECURELY FASTEN LUMINAIRES TO THE LISTED AND LABELED CEILING FRAMING MEMBER BY
<br />MECHANICAL MEANS SUCH AS BOLTS, SCREWS, RIVETS OR LISTED CLIPS IDENTIFIED FOR USE
<br />WITH THE TYPE OF CEILING FRAMING MEMBERS. LUMINAIRES AND WIRING INSTALLED IN FIRE-
<br />RATED CEILING ASSEMBLIES SHALL BE INDEPENDENTLY SUPPORTED FOR ALL APPLICATIONS.
<br />1. INSTALL RECESSED FLANGED LUMINAIRES TO PERMIT REMOVAL FROM BELOW. USE
<br />MANUFACTURER-SUPPLIED PLASTER FRAMES AND SWING GATE SUPPORTS.
<br />B.DO NOT FASTEN LUMINAIRE SUPPORTS TO PIPING, DUCTWORK, MECHANICAL EQUIPMENT, OR
<br /> CONDUIT, UNLESS OTHERWISE NOTED. SUPPORT WIRES SHALL BE TIGHTLY WRAPPED
<br /> (MINIMUM OF THREE TURNS WITHIN 3 INCHES OF THE CONNECTION) AND SHARPLY BEND TO
<br /> PREVENT VERTICAL MOVEMENT.
<br />C.SUPPORT WIRE USED TO INDEPENDENTLY SUPPORT LUMINAIRES, RACEWAYS, AND WIRING
<br /> SYSTEMS SHALL BE DISTINGUISHABLE FROM CEILING SUPPORT SYSTEMS BY COLOR (FIELD
<br /> PAINT), TAGGING OR EQUIVALENT MEANS.
<br />3.2 RELAMPING
<br />A. REPLACE FAILED LED LIGHT ENGINE MODULES OR ARRAYS AT COMPLETION OF WORK.
<br />3.3 ADJUSTING AND CLEANING
<br />A. ALIGN LUMINAIRES AND CLEAN LENSES AND DIFFUSERS AT COMPLETION OF WORK. CLEAN
<br />PAINT SPLATTERS, DIRT, AND DEBRIS FROM INSTALLED LUMINAIRES.
<br />B. TOUCH UP LUMINAIRE FINISH AT COMPLETION OF WORK.
<br />3.4 LUMINAIRE SCHEDULE
<br />A. AS SHOWN ON THE DRAWINGS.
<br />END OF SECTION
<br />SECTION 26 51 19 -LED LIGHTING
<br />PART 1 -GENERAL
<br />1.1 SECTION INCLUDES
<br />A. INTERIOR LUMINAIRES AND ACCESSORIES
<br />B. LIGHT-EMITTING DIODE (LED) LUMINAIRE SYSTEMS
<br />1.2 RELATED SECTIONS
<br />A. THE LIGHTING SYSTEM DESIGN INCLUDES A COMBINATION OF LUMINAIRE SOURCES, LIGHTING
<br />CONTROL COMPONENTS, PROGRAMMING SEQUENCES, AND SUPPLEMENTARY COMPONENTS
<br />FOR BUILDING AND ENERGY CODE COMPLIANCE. THE DESIGN USES PERFORMANCE-BASED
<br />SPECIFICATIONS FOR PORTIONS OF THE LIGHTING SYSTEM TO ACCOUNT FOR THE LIMITATION
<br />OF COMPARABLE PRODUCT SOLUTIONS AVAILABLE BY COMPETITIVE MANUFACTURERS. THE
<br />CONTRACTOR SHALL REFERENCE RELATED SPECIFICATION SECTIONS, PLANS, SCHEDULES,
<br />AND DETAILS PRIOR TO SUBMITTING PRICING, SUBMITTALS, AND INSTALLATION. THE
<br />CONTRACTOR SHALL COORDINATE SYSTEM COMPONENT COMPATIBILITY AMONG VARIOUS
<br />MANUFACTURERS AND SUPPLIERS FOR A TURNKEY LIGHTING SYSTEM.
<br />1. 26 09 33 LIGHTING CONTROL SYSTEMS
<br />2. ELECTRICAL DRAWINGS: PLANS, LUMINAIRE SCHEDULES, LIGHTING CONTROL SEQUENCE
<br />OF OPERATIONS, DIAGRAMS, AND DETAILS.
<br />1.3 REFERENCES
<br />A. ANSI C78.377 -SPECIFICATIONS FOR THE CHROMATICITY OF SOLID STATE LIGHTING PRODUCTS
<br />B. ANSI C82.16 -LIGHT-EMITTING DIODE DRIVERS -METHOD OF MEASUREMENT
<br />C. NEMA SSL1 -ELECTRONIC DRIVERS FOR LED DEVICES, ARRAYS OR SYSTEM
<br />D. UL 8750 -LIGHT EMITTING DIODE (LED) EQUIPMENT FOR USE IN LIGHTING PRODUCTS
<br />E. LM-80 -MEASURING LUMINOUS FLUX AND COLOR MAINTENANCE OF LED
<br />F. UL 924 -STANDARD FOR EMERGENCY LIGHTING AND POWER EQUIPMENT
<br />1.4 SUBMITTALS
<br />A. SUBMIT PRODUCT DATA UNDER PROVISIONS OF SECTION 26 05 00.
<br />B. BASIC REQUIREMENTS OF SUBMITTAL:
<br />1. SUBMIT PRODUCT DATA SHEETS FOR LUMINAIRES, LED LIGHT ENGINES, DRIVERS AND
<br />POLES. INCLUDE COMPLETE PRODUCT MODEL NUMBER WITH ALL OPTIONS AS SPECIFIED.
<br />SUBMITTAL SHALL BE ARRANGED WITH LUMINAIRES LISTED IN ASCENDING ORDER, AND
<br />WITH EACH LUMINAIRE'S, LED LIGHT ENGINE, DRIVER, OR POLE INFORMATION FOLLOWING
<br />LUMINAIRE'S PRODUCT DATA. FAILURE TO ORGANIZE SUBMITTAL IN THIS MANNER WILL
<br />RESULT IN THE SUBMITTAL BEING REJECTED.
<br />2. SUBMIT MANUFACTURER ORIGIN OF LED CHIPSET AND DRIVER.
<br />C.LED LIGHTING -CONTROL COMPATIBILITY SUBMITTAL:
<br />1. SUBMIT LIGHTING CONTROL CAPABILITY DATA FOR EACH LED LUMINAIRE. THE SUBMITTAL
<br />SHALL CLEARLY IDENTIFY DEVICE DATA PROPOSED BY THE CONTRACTOR AND APPROVED
<br />BY THE LUMINAIRE MANUFACTURER FOR DIMMING, SWITCHING, ADDRESSABLE, WIRELESS,
<br />AND SIMILAR CONTROL CHARACTERISTICS.
<br />1.5 DELIVERY, STORAGE, AND HANDLING
<br />A. DELIVER PRODUCTS TO SITE. STORE AND PROTECT UNDER PROVISIONS OF SECTION 26 05 00.
<br />B. PROTECT LUMINAIRE FINISHES, LENSES, AND TRIMS FROM DAMAGE DURING STORAGE AND
<br />INSTALLATION. DO NOT REMOVE PROTECTIVE FILMS UNTIL CONSTRUCTION CLEANUP WITHIN
<br />EACH AREA IS COMPLETE.
<br />TE OLIRFFOAC
<br />LANRP
<br />E 23191
<br />STA
<br />ER
<br />REGIST
<br />ED
<br />INA
<br />N
<br />REENIGE
<br />FO OISSE
<br />E AICLCERTL
<br />Exp. 06/30/26
<br />MIRASOPHOCLISGEORGY
<br />IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,
<br />TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
<br />AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND SHALL
<br />NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE
<br />EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP.
<br />©2022 IMEG CORP.
<br />REF. SCALE IN INCHES
<br />0 1 2 3
<br />The FUTURE. Built Smarter www.imegcorp.com
<br />R
<br />SHEET TITLE
<br />PROJECT
<br />FACILITY
<br />FAC NO: BLDG NO: FLOOR LEV: SECTION:
<br />KP PROJ. NO.
<br />PERMIT NO.
<br />555 W. 5th St Suite 2950 | Los Angeles, CA 90013 USA
<br />Phone 310.820.4600 | Fax 310.207.4215
<br />www.huitt-zollars.com
<br />ARCHITECT
<br />CONSULTANT
<br />ARCHITECT SEAL CONSULTANT SEAL
<br />KAISER FOUNDATION
<br />HOSPITALS NATIONAL
<br />FACILITIES SERVICES 1800
<br />HARRISON STREET OAKLAND,
<br />CALIFORNIA 94612
<br />ISSUE / REVISION LOG
<br />NO. ISSUED DATE
<br />0
<br />5'
<br />
<br />5
<br />0
<br />'
<br />GR
<br />A
<br />P
<br />H
<br />I
<br />C
<br />
<br />S
<br />C
<br />A
<br />L
<br />E
<br />S
<br />:
<br />
<br />1
<br />/
<br />1
<br />6
<br />"
<br />
<br />=
<br />
<br />1
<br />'
<br />-
<br />0
<br />"
<br />0
<br />25
<br />'
<br />1/
<br />8
<br />"
<br />
<br />=
<br />
<br />1
<br />'
<br />-
<br />0
<br />"
<br />5'
<br />0
<br />12
<br />'
<br />1/
<br />4
<br />"
<br />
<br />=
<br />
<br />1
<br />'
<br />-
<br />0
<br />"
<br />1'
<br />0
<br />6'
<br />1/
<br />2
<br />"
<br />
<br />=
<br />
<br />1
<br />'
<br />-
<br />0
<br />"
<br />1'
<br />0
<br />2'
<br />1-
<br />1
<br />/
<br />2
<br />"
<br />
<br />=
<br />
<br />1
<br />'
<br />-
<br />0
<br />"
<br />0
<br />1'
<br />3"
<br />
<br />=
<br />
<br />1
<br />'
<br />-
<br />0
<br />"
<br />IF
<br />
<br />T
<br />H
<br />I
<br />S
<br />
<br />S
<br />H
<br />E
<br />E
<br />T
<br />
<br />I
<br />S
<br />
<br />N
<br />O
<br />T
<br />
<br />30
<br />"
<br />x
<br />4
<br />2
<br />"
<br />,
<br />
<br />I
<br />T
<br />
<br />I
<br />S
<br />
<br />A
<br />
<br />R
<br />E
<br />D
<br />U
<br />C
<br />E
<br />D
<br />
<br />PR
<br />I
<br />N
<br />T
<br />
<br />-
<br />
<br />S
<br />C
<br />A
<br />L
<br />E
<br />
<br />AC
<br />C
<br />O
<br />R
<br />D
<br />I
<br />N
<br />G
<br />L
<br />Y
<br />AGENCY APPLICATION NUMBER
<br />AGENCY APPROVAL STAMP
<br />THIS DOCUMENT IS THE PROPERTY OF THE OWNER AND IS
<br />NOT TO BE USED WITHOUT OWNER'S WRITTEN PERMISSION.
<br />HZ PROJ. NO.
<br />222 S. HARBOR BOULEVARD, SUITE 800 I ANAHEIM, CA 92805
<br />PH: 714.490.5555 I FAX: 714.490.5560
<br />IMEG PROJ. NO.: 22008618.00
<br />PROJECT #22008618.00
<br />SOCC 2022 R HBM 1st Fl KPOJ
<br />REMODEL
<br />E0-06
<br />ELECTRICAL SPECIFICATION
<br />CA394-1
<br />CAP0227721R314412.35
<br />HARBOR/MacARTHUR MEDICAL OFF
<br />3401 S. HARBOR BLVD.
<br />SANTA ANA, CALIFORNIA 92704
<br />CITY SUBMITTAL 11/03/2025
<br />1 CITY BACKCHECK #1 01/06/2026
<br />101125520, 20187249, 40140902
|