SPECIFICATIONS TABLE OF CONTENTS
<br />SECTION 26 05 05 -ELECTRICAL DEMOLITION FOR REMODELING
<br />PART 1 -GENERAL
<br />1.1 SECTION INCLUDES
<br />A. ELECTRICAL DEMOLITION
<br />PART 2 -PRODUCTS
<br />2.1 MATERIALS AND EQUIPMENT
<br />A. MATERIALS AND EQUIPMENT FOR PATCHING AND EXTENDING WORK SHALL BE AS SPECIFIED IN
<br />INDIVIDUAL SECTIONS.
<br />PART 3 -EXECUTION
<br />3.1 EXAMINATION
<br />A. THE DRAWINGS ARE INTENDED TO INDICATE THE SCOPE OF WORK REQUIRED AND DO NOT
<br />INDICATE EVERY BOX, CONDUIT, OR WIRE THAT MUST BE REMOVED. THE CONTRACTOR SHALL
<br />VISIT THE SITE PRIOR TO SUBMITTING A BID AND VERIFY EXISTING CONDITIONS.
<br />B. WHERE WALLS, CEILINGS, STRUCTURES, ETC., ARE INDICATED AS BEING REMOVED ON
<br />GENERAL OR ELECTRICAL DRAWINGS, THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE
<br />REMOVAL OF ALL ELECTRICAL EQUIPMENT, DEVICES, FIXTURES, RACEWAYS, WIRING,
<br />SYSTEMS, ETC., FROM THE REMOVED AREA.
<br />C. WHERE CEILINGS, WALLS, STRUCTURES, ETC., ARE TEMPORARILY REMOVED AND REPLACED
<br />BY OTHERS, THIS CONTRACTOR SHALL BE RESPONSIBLE FOR THE REMOVAL, STORAGE, AND
<br />REPLACEMENT OF EQUIPMENT, DEVICES, FIXTURES, RACEWAYS, WIRING, SYSTEMS, ETC.
<br />D. WHERE MECHANICAL OR TECHNOLOGY EQUIPMENT IS INDICATED AS BEING REMOVED ON
<br />ELECTRICAL, MECHANICAL, OR TECHNOLOGY DRAWINGS, THE CONTRACTOR SHALL BE
<br />RESPONSIBLE FOR DISCONNECTING THE EQUIPMENT AND REMOVING ALL STARTERS, VFD,
<br />CONTROLLERS, ELECTRICAL EQUIPMENT, RACEWAYS, WIRING, ETC. ASSOCIATED WITH THE
<br />DEVICE.
<br />E. VERIFY THAT ABANDONED WIRING AND EQUIPMENT SERVE ONLY ABANDONED EQUIPMENT OR
<br />FACILITIES. EXTEND CONDUIT AND WIRE TO FACILITIES AND EQUIPMENT THAT WILL REMAIN IN
<br />OPERATION FOLLOWING DEMOLITION. EXTENSION OF CONDUIT AND WIRE TO EQUIPMENT
<br />SHALL BE COMPATIBLE WITH THE SURROUNDING AREA. EXTENDED CONDUIT AND
<br />CONDUCTORS TO MATCH EXISTING SIZE AND MATERIAL.
<br />F. COORDINATE SCOPE OF WORK WITH ALL OTHER CONTRACTORS AND THE OWNER AT THE
<br />PROJECT SITE. SCHEDULE REMOVAL OF EQUIPMENT AND ELECTRICAL SERVICE TO AVOID
<br />CONFLICTS.
<br />G. BID SUBMITTAL SHALL MEAN THE CONTRACTOR HAS VISITED THE PROJECT SITE AND HAS
<br />VERIFIED EXISTING CONDITIONS AND SCOPE OF WORK.
<br />3.2 PREPARATION
<br />A. THE CONTRACTOR SHALL OBTAIN APPROVAL FROM THE OWNER BEFORE TURNING OFF POWER
<br />TO CIRCUITS, FEEDERS, PANELS, ETC. COORDINATE ALL OUTAGES WITH OWNER.
<br />B. PROVIDE TEMPORARY WIRING AND CONNECTIONS TO MAINTAIN EXISTING SYSTEMS IN SERVICE
<br />DURING CONSTRUCTION. WHEN WORK MUST BE PERFORMED ON ENERGIZED EQUIPMENT OR
<br />CIRCUITS, USE PERSONNEL EXPERIENCED IN SUCH OPERATIONS. ASSUME ALL EQUIPMENT
<br />AND SYSTEMS MUST REMAIN OPERATIONAL UNLESS SPECIFICALLY NOTED OTHERWISE ON
<br />DRAWINGS.
<br />C. DISCONNECT ELECTRICAL SYSTEMS IN WALLS, FLOORS, STRUCTURES, AND CEILINGS
<br />SCHEDULED FOR REMOVAL.
<br />D. EXISTING ELECTRICAL SERVICE: MAINTAIN EXISTING SYSTEM IN SERVICE UNTIL NEW SYSTEM IS
<br />COMPLETE AND READY FOR SERVICE. DISABLE SYSTEM ONLY TO MAKE SWITCHOVERS AND
<br />CONNECTIONS. OBTAIN PERMISSION FROM OWNER AT LEAST 72 HOURS BEFORE PARTIALLY OR
<br />COMPLETELY DISABLING SYSTEM. MINIMIZE OUTAGE DURATION.
<br />3.3 DEMOLITION AND EXTENSION OF EXISTING ELECTRICAL WORK
<br />A. DEMOLISH AND EXTEND EXISTING ELECTRICAL WORK UNDER PROVISIONS OF DIVISION 1 OF
<br />SPECIFICATIONS AND THIS SECTION.
<br />B. REMOVE, RELOCATE, AND EXTEND EXISTING INSTALLATIONS TO ACCOMMODATE NEW
<br />CONSTRUCTION.
<br />C. REMOVE ABANDONED WIRING AND RACEWAY TO SOURCE OF SUPPLY.
<br />D. REMOVE EXPOSED ABANDONED RACEWAY, INCLUDING ABANDONED RACEWAY ABOVE
<br />ACCESSIBLE CEILING FINISHES. CUT RACEWAY FLUSH WITH WALLS AND FLOORS, AND PATCH
<br />SURFACES. REMOVE ALL ASSOCIATED CLAMPS, HANGERS, SUPPORTS, ETC. ASSOCIATED WITH
<br />RACEWAY REMOVAL.
<br />E. DISCONNECT AND REMOVE OUTLETS AND DEVICES THAT ARE TO BE DEMOLISHED. REMOVE
<br />OUTLET OR DEVICES' ASSOCIATED BACK BOX, SUPPORTS, AND CONDUIT AND CONDUCTORS
<br />BACK TO SOURCE. PATCH OPENING CREATED FROM REMOVAL OF DEVICE TO MATCH
<br />SURROUNDING FINISHES.
<br />F. DISCONNECT AND REMOVE ABANDONED PANELBOARDS AND DISTRIBUTION EQUIPMENT.
<br />G. DISCONNECT AND REMOVE ELECTRICAL DEVICES AND EQUIPMENT SERVING UTILIZATION
<br />EQUIPMENT THAT HAS BEEN REMOVED.
<br />H. DISCONNECT AND REMOVE ABANDONED LUMINAIRES. REMOVE BRACKETS, STEMS, HANGERS,
<br />AND OTHER ACCESSORIES. BALLASTS IN LIGHT FIXTURES INSTALLED PRIOR TO 1980 SHALL BE
<br />INCINERATED IN EPA APPROVED INCINERATOR OR DISPOSED OF IN EPA CERTIFIED
<br />CONTAINERS AND DEPOSITED IN AN EPA LANDFILL CERTIFIED FOR PCB DISPOSAL OR
<br />RECYCLED BY PERMITTED BALLAST RECYCLER. PUNCTURED OR LEAKING BALLASTS MUST BE
<br />DISPOSED OF ACCORDING TO FEDERAL REGULATIONS UNDER THE TOXIC SUBSTANCE
<br />CONTROL ACT. PROVIDE OWNER AND ARCHITECT/ENGINEER WITH A CERTIFICATE OF
<br />DESTRUCTION TO VERIFY PROPER DISPOSAL.
<br />I. REPAIR ADJACENT CONSTRUCTION AND FINISHES DAMAGED DURING DEMOLITION AND
<br />EXTENSION WORK. PATCH OPENINGS TO MATCH EXISTING SURROUNDING FINISHES.
<br />J. MAINTAIN ACCESS TO EXISTING ELECTRICAL INSTALLATIONS THAT REMAIN ACTIVE. MODIFY
<br />INSTALLATION OR PROVIDE JUNCTION BOXES AND ACCESS PANEL AS APPROPRIATE.
<br />K. EXTEND EXISTING INSTALLATIONS USING MATERIALS AND METHODS COMPATIBLE WITH
<br />EXISTING ELECTRICAL INSTALLATIONS, OR AS SPECIFIED. EXTENDED CONDUIT AND
<br />CONDUCTORS TO MATCH EXISTING SIZE AND MATERIAL.
<br />L. HID AND FLUORESCENT LAMPS, DETERMINED BY THE TOXICITY CHARACTERISTIC LEACHATE
<br />PROCEDURE (TCLP), TO BE HAZARDOUS WASTE SHALL BE DISPOSED OF IN AN EPA-PERMITTED
<br />HAZARDOUS WASTE DISPOSAL FACILITY OR BY A PERMITTED LAMP RECYCLER.
<br />M. REGULATORY REQUIREMENTS: COMPLY WITH GOVERNING EPA NOTIFICATION REGULATIONS
<br />BEFORE BEGINNING DEMOLITION. COMPLY WITH HAULING AND DISPOSAL REGULATIONS OF
<br />AUTHORITIES HAVING JURISDICTION.
<br />N. THIS CONTRACTOR IS RESPONSIBLE FOR ALL COSTS INCURRED IN REPAIR, RELOCATIONS, OR
<br />REPLACEMENT OF ANY CABLES, CONDUITS, OR OTHER SERVICES IF DAMAGED WITHOUT
<br />PROPER INVESTIGATION.
<br />3.4 CLEANING AND REPAIR
<br />A. CLEAN AND REPAIR EXISTING MATERIALS AND EQUIPMENT THAT REMAIN OR ARE TO BE
<br />REUSED.
<br />B. PANELBOARDS: CLEAN EXPOSED SURFACES AND CHECK TIGHTNESS OF ELECTRICAL
<br />CONNECTIONS. REPLACE DAMAGED CIRCUIT BREAKERS AND PROVIDE CLOSURE PLATES FOR
<br />VACANT POSITIONS. PROVIDE TYPED CIRCUIT DIRECTORY SHOWING REVISED CIRCUITING
<br />ARRANGEMENT.
<br />C. ELECTRICAL ITEMS (E.G., LIGHTING FIXTURES, RECEPTACLES, SWITCHES, CONDUIT, WIRE, ETC.)
<br />REMOVED AND NOT RELOCATED REMAIN THE PROPERTY OF THE OWNER. CONTRACTOR SHALL
<br />PLACE ITEMS RETAINED BY THE OWNER IN A LOCATION COORDINATED WITH THE OWNER. THE
<br />CONTRACTOR SHALL BE RESPONSIBLE FOR THE DISPOSAL OF MATERIAL THE OWNER DOES
<br />NOT WANT.
<br />3.5 INSTALLATION
<br />A. INSTALL RELOCATED MATERIALS AND EQUIPMENT UNDER THE PROVISIONS OF DIVISION 1 OF
<br />SPECIFICATIONS.
<br />END OF SECTION
<br />• SECTION 26 05 05 -ELECTRICAL DEMOLITION FOR REMODELING
<br />• SECTION 26 05 13 -WIRE AND CABLE
<br />• SECTION 26 05 26 -GROUNDING AND BONDING
<br />• SECTION 26 05 27 -SUPPORTING DEVICES
<br />• SECTION 26 05 33 -CONDUIT AND BOXES
<br />SECTION 26 05 13 -WIRE AND CABLE
<br />PART 1 -GENERAL
<br />1.1 SECTION INCLUDES
<br />A. BUILDING WIRE
<br />B. CABLING FOR REMOTE CONTROL, SIGNAL, AND POWER LIMITED CIRCUITS
<br />1.2 RELATED WORK
<br />A. SECTION 26 05 53 -ELECTRICAL IDENTIFICATION: REFER TO ELECTRICAL IDENTIFICATION FOR
<br />COLOR AND IDENTIFICATION LABELING REQUIREMENTS.
<br />1.3 REFERENCES
<br />A. NEMA WC 70 -POWER CABLES RATED 2,000V OR LESS FOR THE DISTRIBUTION OF ELECTRICAL
<br />ENERGY
<br />B. CEC CALIFORNIA ELECTRICAL CODE
<br />C. UL 44 -THERMOSET-INSULATED WIRES AND CABLES
<br />D. UL 83 -THERMOPLASTIC-INSULATED WIRES AND CABLES
<br />E. UL 1581 -STANDARD FOR ELECTRICAL WIRES, CABLES, AND FLEXIBLE CORDS
<br />1.4 SUBMITTALS
<br />A. SUBMIT SHOP DRAWINGS AND PRODUCT DATA UNDER THE PROVISIONS OF SECTION 26 05 00.
<br />PART 2 -PRODUCTS
<br />2.1 BUILDING WIRE
<br />A. FEEDERS AND BRANCH CIRCUITS 8 AWG AND LARGER: COPPER, STRANDED CONDUCTOR, 600-
<br />VOLT INSULATION, THHN/THWN OR XHHW-2.
<br />B. FEEDERS AND BRANCH CIRCUITS 10 AWG AND SMALLER: COPPER, SOLID OR STRANDED
<br />CONDUCTOR, 600-VOLT INSULATION, THHN/THWN, UNLESS OTHERWISE NOTED ON THE
<br />DRAWINGS.
<br />C. CONTROL CIRCUITS: COPPER, STRANDED CONDUCTOR 600-VOLT INSULATION, THHN/THWN.
<br />D. EACH 120 AND 277-VOLT BRANCH CIRCUIT SHALL HAVE A DEDICATED NEUTRAL CONDUCTOR.
<br />NEUTRAL CONDUCTORS SHALL BE CONSIDERED CURRENT-CARRYING CONDUCTORS FOR WIRE
<br />DERATING.
<br />2.2 CABLING FOR REMOTE CONTROL, SIGNAL, AND POWER LIMITED CIRCUITS
<br />A. WIRE FOR THE FOLLOWING SPECIALIZED SYSTEMS SHALL BE AS DESIGNATED ON THE
<br />DRAWINGS, OR ELSEWHERE IN THESE SPECIFICATIONS. IF NOT DESIGNATED ON THE
<br />DRAWINGS OR SPECIFICATIONS, THE SYSTEM MANUFACTURER'S RECOMMENDATIONS SHALL
<br />BE FOLLOWED.
<br />1. FIRE ALARM
<br />2. LOW VOLTAGE SWITCHING AND LIGHTING CONTROL
<br />2.3 HEALTHCARE RATED AC CABLE
<br />A. HEALTHCARE GRADE ARMORED CABLE WITH REDUNDANT COPPER GROUND CONDUCTOR
<br />WITH GREEN IDENTIFYING STRIP ON THE EXTERIOR OF THE ARMOR.
<br />B. ARMORED CABLE SHALL BE CONSTRUCTED IN ACCORDANCE WITH UL, INC STANDARD FOR
<br />TYPE AC CABLES, UL 4, AND INCLUDE A FLEXIBLE METALLIC INTERLOCKED ARMOR, LISTED AS A
<br />REDUNDANT GROUND PATH.
<br />C. MINIMUM CONDUCTOR SIZE FOR BRANCH CIRCUIT WIRING SHALL BE 12 AWG. EACH 120 AND 277
<br />VOLT CIRCUIT SHALL HAVE A DEDICATED NEUTRAL CONDUCTOR.
<br />D. CABLE SHALL BE SUPPORTED BY AN APPROVED MEANS EVERY 4.5 FEET AND WITHIN 12 INCHES
<br />OR OUTLLET BOXES, JUNCTION BOXES, OR FITTINGS.
<br />PART 3 -EXECUTION
<br />3.1 WIRE AND CABLE INSTALLATION SCHEDULE
<br />A. ABOVE ACCESSIBLE CEILINGS:
<br />1. BUILDING WIRE SHALL BE INSTALLED IN RACEWAY.
<br />2. METAL CLAD CABLE, TYPE MC, 1/2" SIZE WITH MINIMUM #12 CONDUCTORS AND GROUND,
<br />SHALL BE ALLOWED FOR FLEXIBLE WHIPS TO INDIVIDUAL LUMINAIRES ON NON-ESSENTIAL
<br />CIRCUITS. THE FLEXIBLE WHIPS SHALL BE BETWEEN 18" TO 72" IN LENGTH PER ELECTRICAL
<br />CODE.
<br />B.ALL OTHER LOCATIONS: BUILDING WIRE IN RACEWAY.
<br />C.ABOVE GRADE: ALL CONDUCTORS INSTALLED ABOVE GRADE SHALL BE TYPE "THHN".
<br />3.2 GENERAL WIRING METHODS
<br />A. USE NO WIRE SMALLER THAN 12 AWG FOR POWER AND LIGHTING CIRCUITS, AND NO SMALLER
<br />THAN 14 AWG FOR CONTROL WIRING.
<br />B. USE NO WIRE SMALLER THAN 18 AWG FOR LOW VOLTAGE CONTROL WIRING BELOW 100 VOLTS.
<br />C. USE 10 AWG CONDUCTOR FOR 20 AMPERE, 120-VOLT BRANCH CIRCUIT HOME RUNS LONGER
<br />THAN 75 FEET, AND FOR 20 AMPERE, 277-VOLT BRANCH CIRCUIT HOME RUNS LONGER THAN 200
<br />FEET.
<br />D. THE AMPACITY OF MULTIPLE CONDUCTORS IN ONE CONDUIT SHALL BE DERATED PER THE
<br />ELECTRICAL CODE. IN NO CASE SHALL MORE THAN 4 CONDUCTORS BE INSTALLED IN ONE
<br />CONDUIT TO SUCH LOADS AS MOTORS LARGER THAN 1/4 HP, PANELBOARDS, MOTOR CONTROL
<br />CENTERS, ETC.
<br />E. WHERE INSTALLING PARALLEL FEEDERS, PLACE AN EQUAL NUMBER OF CONDUCTORS FOR
<br />EACH PHASE OF A CIRCUIT IN SAME RACEWAY OR CABLE.
<br />F. SPLICE ONLY IN JUNCTION OR OUTLET BOXES.
<br />G. NEATLY TRAIN AND LACE WIRING INSIDE BOXES, EQUIPMENT, AND PANELBOARDS.
<br />H. MAKE CONDUCTOR LENGTHS FOR PARALLEL CIRCUITS EQUAL.
<br />I. ALL CONDUCTORS SHALL BE CONTINUOUS IN CONDUIT FROM LAST OUTLET TO THEIR
<br />TERMINATION.
<br />J. TERMINATE ALL SPARE CONDUCTORS ON TERMINAL BLOCKS, AND LABEL THE SPARE
<br />CONDUCTORS.
<br />K. CABLES OR WIRES SHALL NOT BE LAID OUT ON THE GROUND BEFORE PULLING.
<br />L. CABLES OR WIRES SHALL NOT BE DRAGGED OVER EARTH OR PAVING.
<br />M. CARE SHALL BE TAKEN SO AS NOT TO SUBJECT THE CABLE OR WIRE TO HIGH MECHANICAL
<br />STRESSES THAT WOULD CAUSE DAMAGE TO THE WIRE AND CABLE.
<br />N. AT LEAST SIX (6)-INCH LOOPS OR ENDS SHALL BE LEFT AT EACH OUTLET FOR INSTALLATION
<br />CONNECTION OF LUMINAIRES OR OTHER DEVICES.
<br />O. ALL WIRES IN OUTLET BOXES NOT CONNECTED TO FIXTURES OR OTHER DEVICES SHALL BE
<br />ROLLED UP, SPLICED IF CONTINUITY OF CIRCUIT IS REQUIRED, AND INSULATED.
<br />3.3 WIRING INSTALLATION IN RACEWAYS
<br />A. PULL ALL CONDUCTORS INTO A RACEWAY AT THE SAME TIME. USE UL LISTED WIRE PULLING
<br />LUBRICANT FOR PULLING 4 AWG AND LARGER WIRES.
<br />B. PULLING SHALL BE CONTINUOUS WITHOUT UNNECESSARY STOPS AND STARTS WITH WIRE OR
<br />CABLE ONLY PARTIALLY THROUGH RACEWAY.
<br />C. WHERE REELS OF CABLE OR WIRE ARE USED, THEY SHALL BE SET UP ON JACKS CLOSE TO THE
<br />POINT WHERE THE WIRE OR CABLE ENTERS THE CONDUIT OR DUCT SO THAT THE CABLE OR
<br />WIRE MAY BE UNREELED AND RUN INTO THE CONDUIT OR DUCT WITH A MINIMUM OF CHANGE
<br />IN THE DIRECTION OF THE BEND.
<br />D. CONDUCTORS SHALL NOT BE PULLED THROUGH CONDUITS UNTIL PLASTERING OR MASONRY
<br />WORK IS COMPLETED AND CONDUITS ARE FREE FROM MOISTURE. CARE SHALL BE TAKEN SO
<br />THAT LONG PULLS OF WIRE OR PULLS AROUND SEVERAL BENDS ARE NOT MADE WHERE THE
<br />WIRE MAY BE PERMANENTLY STRETCHED AND THE INSULATION DAMAGED.
<br />E. ONLY NYLON ROPE SHALL BE PERMITTED TO PULL CABLES INTO CONDUIT AND DUCTS.
<br />F. COMPLETELY AND THOROUGHLY SWAB RACEWAY SYSTEM BEFORE INSTALLING CONDUCTORS.
<br />G. CONDUCTOR SUPPORTS IN VERTICAL RACEWAYS:
<br />1. SUPPORT CONDUCTORS IN VERTICAL RACEWAYS IN ACCORDANCE WITH THE ELECTRICAL
<br />CODE SPACING OF CONDUCTORS SUPPORTS.
<br />2. SUPPORTS SHALL BE OF INSULATED WEDGE TYPE (OZ GEDNEY TYPE S, OR EQUAL) AND
<br />INSTALLED IN A TAPERED INSULATED BUSHING FITTING OR A METAL WOVEN MESH WITH A
<br />SUPPORT RING THAT FITS INSIDE CONDUIT FITTING INSTALLED IN AN ACCESSIBLE
<br />JUNCTION BOX (HUBBELL KELLEMS SUPPORT GRIP OR EQUAL).
<br />3.4 WIRING CONNECTIONS AND TERMINATIONS
<br />A. SPLICE AND TAP ONLY IN ACCESSIBLE JUNCTION BOXES.
<br />B. USE SOLDERLESS, TIN-PLATED COPPER, COMPRESSION TERMINALS (LUGS) APPLIED WITH
<br />CIRCUMFERENTIAL CRIMP FOR CONDUCTOR TERMINATIONS, 8 AWG AND LARGER.
<br />C. USE SOLDERLESS, TIN-PLATED, COMPRESSION TERMINALS (LUGS) APPLIED WITH INDENTER
<br />CRIMP FOR COPPER CONDUCTOR TERMINATIONS, 10 AWG AND SMALLER.
<br />D. USE SOLDERLESS PRESSURE CONNECTORS WITH INSULATING COVERS FOR COPPER WIRE
<br />SPLICES AND TAPS, 8 AWG AND SMALLER. FOR 10 AWG AND SMALLER, USE INSULATED SPRING
<br />WIRE CONNECTORS WITH PLASTIC CAPS.
<br />E. USE COMPRESSION CONNECTORS APPLIED WITH CIRCUMFERENTIAL CRIMP FOR CONDUCTOR
<br />SPLICES AND TAPS, 6 AWG AND LARGER. TAPE UNINSULATED CONDUCTORS AND
<br />CONNECTORS WITH ELECTRICAL TAPE TO 150 PERCENT OF THE INSULATION VALUE OF
<br />CONDUCTOR.
<br />F. THOROUGHLY CLEAN WIRES BEFORE INSTALLING LUGS AND CONNECTORS.
<br />G. MAKE SPLICES, TAPS AND TERMINATIONS TO CARRY FULL AMPACITY OF CONDUCTORS
<br />WITHOUT PERCEPTIBLE TEMPERATURE RISE.
<br />H. PHASE SEQUENCE: ALL APPARATUS SHALL BE CONNECTED TO OPERATE IN THE PHASE
<br />SEQUENCE A-B-C REPRESENTING THE TIME SEQUENCE IN WHICH THE PHASE CONDUCTORS SO
<br />IDENTIFIED REACH POSITIVE MAXIMUM VOLTAGE.
<br />I. AS A GENERAL RULE, APPLICABLE TO SWITCHES, CIRCUIT BREAKERS, STARTERS,
<br />PANELBOARDS, SWITCHGEAR AND THE LIKE, THE CONNECTIONS TO PHASE CONDUCTORS ARE
<br />INTENDED THUS:
<br />1. FACING THE FRONT AND OPERATING SIDE OF THE EQUIPMENT, THE PHASE IDENTIFICATION
<br />SHALL BE:
<br />a. LEFT TO RIGHT -A-B-C
<br />b. TOP TO BOTTOM -A-B-C
<br />J.CONNECTION REVISIONS AS REQUIRED TO ACHIEVE CORRECT ROTATION OF MOTORS SHALL
<br /> BE MADE AT THE LOAD TERMINALS OF THE STARTERS OR DISCONNECT SWITCHES.
<br />3.5 FIELD QUALITY CONTROL
<br />A. FIELD INSPECTION AND TESTING WILL BE PERFORMED UNDER PROVISIONS OF DIVISION 1.
<br />B. INSPECT WIRE AND CABLE FOR PHYSICAL DAMAGE AND PROPER CONNECTION.
<br />C. TORQUE TEST CONDUCTOR CONNECTIONS AND TERMINATIONS TO MANUFACTURER'S
<br />RECOMMENDED VALUES.
<br />D. PERFORM CONTINUITY TEST ON ALL POWER AND EQUIPMENT BRANCH CIRCUIT CONDUCTORS.
<br />VERIFY PROPER PHASING CONNECTIONS.
<br />END OF SECTION
<br />SECTION 26 05 26 -GROUNDING AND BONDING
<br />PART 1 -GENERAL
<br />1.1 SECTION INCLUDES
<br />A. EQUIPMENT GROUNDING SYSTEM
<br />1.2 REFERENCES
<br />A. CEC CALIFORNIA ELECTRICAL CODE
<br />B. NFPA 99 -STANDARD FOR HEALTHCARE FACILITIES
<br />1.3 SUMMARY
<br />A. THIS SECTION INCLUDES GROUNDING OF ELECTRICAL SYSTEMS AND EQUIPMENT. GROUNDING
<br />REQUIREMENTS SPECIFIED IN THIS SECTION MAY BE SUPPLEMENTED BY SPECIAL
<br />REQUIREMENTS OF SYSTEMS DESCRIBED IN OTHER SECTIONS.
<br />PART 2 -PRODUCTS
<br />2.1 GROUNDING CONDUCTORS
<br />A. FOR INSULATED CONDUCTORS, COMPLY WITH DIVISION 26 SECTION 26 05 13 "WIRE AND CABLE".
<br />B. MATERIAL: COPPER.
<br />C. EQUIPMENT GROUNDING CONDUCTORS: INSULATED. REFER TO SECTION 26 05 53 FOR
<br />INSULATION COLOR.
<br />2.2 CONNECTOR PRODUCTS
<br />A. COMPLY WITH UL 467; LISTED FOR USE FOR SPECIFIC TYPES, SIZES, AND COMBINATIONS OF
<br />CONDUCTORS AND CONNECTED ITEMS.
<br />B. CONNECTORS: HYDRAULIC COMPRESSION TYPE, IN KIT FORM, AND SELECTED PER
<br />MANUFACTURER'S WRITTEN INSTRUCTIONS.
<br />C. BOLTED CONNECTORS: BOLTED-PRESSURE-TYPE CONNECTORS.
<br />PART 3 -EXECUTION
<br />3.1 CONNECTIONS
<br />A. GENERAL: MAKE CONNECTIONS SO GALVANIC ACTION OR ELECTROLYSIS POSSIBILITY IS
<br />MINIMIZED. SELECT CONNECTORS, CONNECTION HARDWARE, CONDUCTORS, AND
<br />CONNECTION METHODS SO METALS IN DIRECT CONTACT WILL BE GALVANICALLY COMPATIBLE.
<br />1. USE ELECTROPLATED OR HOT-TIN-COATED MATERIALS TO ENSURE HIGH CONDUCTIVITY
<br />AND TO MAKE CONTACT POINTS CLOSER TO ORDER OF GALVANIC SERIES.
<br />2. MAKE CONNECTIONS WITH CLEAN, BARE METAL AT POINTS OF CONTACT.
<br />3. MAKE ALUMINUM-TO-STEEL CONNECTIONS WITH STAINLESS-STEEL SEPARATORS AND
<br />MECHANICAL CLAMPS.
<br />4. MAKE ALUMINUM-TO-GALVANIZED STEEL CONNECTIONS WITH TIN-PLATED COPPER
<br />JUMPERS AND MECHANICAL CLAMPS.
<br />5. COAT AND SEAL CONNECTIONS HAVING DISSIMILAR METALS WITH INERT MATERIAL TO
<br />PREVENT FUTURE PENETRATION OF MOISTURE TO CONTACT SURFACES.
<br />B.COMPRESSION-TYPE CONNECTIONS: USE HYDRAULIC COMPRESSION TOOLS TO PROVIDE
<br /> CORRECT CIRCUMFERENTIAL PRESSURE FOR COMPRESSION CONNECTORS. USE TOOLS AND
<br /> DIES RECOMMENDED BY CONNECTOR MANUFACTURER. PROVIDE EMBOSSING DIE CODE OR
<br /> OTHER STANDARD METHOD TO MAKE A VISIBLE INDICATION THAT A CONNECTOR HAS BEEN
<br /> ADEQUATELY COMPRESSED ON GROUNDING CONDUCTOR.
<br />C.EQUIPMENT GROUNDING CONDUCTOR TERMINATIONS: FOR NO. 8 AWG AND LARGER, USE
<br /> PRESSURE-TYPE GROUNDING LUGS. NO. 10 AWG AND SMALLER GROUNDING CONDUCTORS
<br /> MAY BE TERMINATED WITH WINGED PRESSURE-TYPE CONNECTORS.
<br />D.NONCONTACT METAL RACEWAY TERMINATIONS: IF METALLIC RACEWAYS TERMINATE AT METAL
<br /> HOUSINGS WITHOUT MECHANICAL AND ELECTRICAL CONNECTION TO HOUSING, TERMINATE
<br /> EACH CONDUIT WITH A GROUNDING BUSHING. CONNECT GROUNDING BUSHINGS WITH A BARE
<br /> GROUNDING CONDUCTOR TO GROUNDING BUS OR TERMINAL IN HOUSING. BOND
<br /> ELECTRICALLY NON-CONTINUOUS CONDUITS AT ENTRANCES AND EXITS WITH GROUNDING
<br /> BUSHINGS AND BARE GROUNDING CONDUCTORS, UNLESS OTHERWISE INDICATED.
<br />E.CONNECTIONS AT BACK BOXES, JUNCTION BOXES, PULL BOXES, AND EQUIPMENT
<br /> TERMINATIONS: THE EQUIPMENT GROUNDING CONDUCTOR(S) ASSOCIATED WITH ALL
<br /> CIRCUITS IN THE BOX SHALL BE CONNECTED TOGETHER AND TO THE BOX USING A SUITABLE
<br /> GROUNDING SCREW. THE REMOVAL OF THE RESPECTIVE RECEPTACLE, LUMINAIRE, OR OTHER
<br /> DEVICE SERVED BY THE BOX SHALL NOT INTERRUPT THE GROUNDING CONTINUITY.
<br />F.TIGHTEN SCREWS AND BOLTS FOR GROUNDING AND BONDING CONNECTORS AND TERMINALS
<br /> ACCORDING TO MANUFACTURER'S PUBLISHED TORQUE-TIGHTENING VALUES. IF
<br /> MANUFACTURER'S TORQUE VALUES ARE NOT INDICATED, USE THOSE SPECIFIED IN UL 486A.
<br />G.MOISTURE PROTECTION: IF INSULATED GROUNDING CONDUCTORS ARE CONNECTED TO
<br /> GROUND RODS OR GROUNDING BUSES, INSULATE ENTIRE AREA OF CONNECTION AND SEAL
<br /> AGAINST MOISTURE PENETRATION OF INSULATION AND CABLE.
<br />3.2 INSTALLATION
<br />A. GROUNDING CONDUCTORS: ROUTE ALONG SHORTEST AND STRAIGHTEST PATHS POSSIBLE,
<br />UNLESS OTHERWISE INDICATED. AVOID OBSTRUCTING ACCESS OR PLACING CONDUCTORS
<br />WHERE THEY MAY BE SUBJECTED TO STRAIN, IMPACT, OR DAMAGE. EACH GROUNDING
<br />CONDUCTOR THAT PASSES THROUGH A BELOW GRADE WALL MUST BE PROVIDED WITH A
<br />WATERSTOP.
<br />B. IN RACEWAYS, USE INSULATED EQUIPMENT GROUNDING CONDUCTORS.
<br />3.3 EQUIPMENT GROUNDING SYSTEM
<br />A. COMPLY WITH ELECTRICAL CODE, FOR TYPES, SIZES, AND QUANTITIES OF EQUIPMENT
<br />GROUNDING CONDUCTORS, UNLESS SPECIFIC TYPES, LARGER SIZES, OR MORE CONDUCTORS
<br />THAN REQUIRED BY ELECTRICAL CODE ARE INDICATED.
<br />B. INSTALL EQUIPMENT GROUNDING CONDUCTORS IN ALL FEEDERS AND CIRCUITS. TERMINATE
<br />EACH END ON A GROUNDING LUG OR BUS.
<br />END OF SECTION
<br />SECTION 26 05 27 -SUPPORTING DEVICES
<br />PART 1 -GENERAL
<br />1.1 SECTION INCLUDES
<br />A. CONDUIT AND EQUIPMENT SUPPORTS
<br />B. FASTENING HARDWARE
<br />1.2 QUALITY ASSURANCE
<br />A. SUPPORT SYSTEMS SHALL BE ADEQUATE FOR WEIGHT OF EQUIPMENT AND CONDUIT,
<br />INCLUDING WIRING, WHICH THEY CARRY.
<br />PART 2 -PRODUCTS
<br />2.1 MANUFACTURERS
<br />A. COOPER B-LINE
<br />B. ERICO, INC.
<br />C. HILTI
<br />2.2 MATERIAL
<br />A. SUPPORT CHANNEL: HOT-DIP GALVANIZED FOR INTERIOR/DRY LOCATIONS. ALL FIELD CUT
<br />ENDS SHALL BE TOUCHED UP WITH MATCHING FINISH TO INHIBIT RUSTING.
<br />B. HARDWARE: CORROSION RESISTANT.
<br />PART 3 -EXECUTION
<br />3.1 INSTALLATION
<br />A. FASTEN HANGER RODS, CONDUIT CLAMPS, AND OUTLET AND JUNCTION BOXES TO BUILDING
<br />STRUCTURE USING EXPANSION ANCHORS IN CONCRETE AND BEAM CLAMPS ON STRUCTURAL
<br />STEEL.
<br />B. TRAPEZE SUPPORT INSTALLATION: CUT HANGER RODS BACK AT TRAPEZE SUPPORTS SO THEY
<br />DO NOT EXTEND MORE THAN 3/4" BELOW BOTTOM FACE OF LOWEST FASTENER AND BLUNT
<br />ANY SHARP EDGES.
<br />C. USE TOGGLE BOLTS OR HOLLOW WALL FASTENERS IN HOLLOW MASONRY, PLASTER, OR
<br />GYPSUM BOARD PARTITIONS AND WALLS; EXPANSION ANCHORS OR PRESET INSERTS IN SOLID
<br />MASONRY WALLS; SELF-DRILLING ANCHORS OR EXPANSION ANCHOR ON CONCRETE
<br />SURFACES; SHEET METAL SCREWS IN SHEET METAL STUDS; AND WOOD SCREWS IN WOOD
<br />CONSTRUCTION.
<br />D. DO NOT FASTEN SUPPORTS TO CEILING SYSTEMS, PIPING, DUCTWORK, MECHANICAL
<br />EQUIPMENT, OR CONDUIT, UNLESS OTHERWISE NOTED.
<br />E. DO NOT USE POWDER-ACTUATED ANCHORS WITHOUT SPECIFIC PERMISSION.
<br />F. DO NOT DRILL STRUCTURAL STEEL MEMBERS.
<br />G. BRIDGE STUDS TOP AND BOTTOM WITH CHANNELS TO SUPPORT FLUSH-MOUNTED CABINETS
<br />AND PANELBOARDS IN STUD WALLS.
<br />3.2 FINISH
<br />A. PRIME COAT EXPOSED STEEL HANGERS AND SUPPORTS. HANGERS AND SUPPORTS IN CRAWL
<br />SPACES, PIPE SHAFTS, AND ABOVE SUSPENDED CEILING SPACES ARE NOT CONSIDERED
<br />EXPOSED.
<br />B. TRIM ALL ENDS OF EXPOSED FIELD FABRICATED STEEL HANGERS, SLOTTED CHANNEL AND
<br />THREADED ROD TO WITHIN 1" OF SUPPORT OR FASTENER TO ELIMINATE POTENTIAL INJURY TO
<br />PERSONNEL UNLESS SHOWN OTHERWISE ON THE DRAWINGS. SMOOTH ENDS AND INSTALL
<br />ELASTOMERIC INSULATION WITH TWO COATS OF LATEX PAINT IF EXPOSED STEEL IS WITHIN
<br />6'-6" OF FINISH FLOOR AND PRESENTS POTENTIAL INJURY TO PERSONNEL.
<br />END OF SECTION
<br />SECTION 26 05 33 -CONDUIT AND BOXES
<br />PART 1 -GENERAL
<br />1.1 SECTION INCLUDES
<br />A. RIGID METALLIC CONDUIT AND FITTINGS (RMC)
<br />B. ELECTRICAL METALLIC TUBING AND FITTINGS (EMT)
<br />C. FLEXIBLE METALLIC CONDUIT AND FITTINGS (FMC)
<br />D. LIQUIDTIGHT FLEXIBLE METALLIC CONDUIT AND FITTINGS (LFMC)
<br />E. WALL AND CEILING OUTLET BOXES
<br />F. ELECTRICAL CONNECTION
<br />G. PULL AND JUNCTION BOXES
<br />H. HANDHOLES
<br />1.2 RELATED WORK
<br />A. SECTION 26 05 53 -ELECTRICAL IDENTIFICATION: REFER TO ELECTRICAL IDENTIFICATION FOR
<br />COLOR AND IDENTIFICATION LABELING REQUIREMENTS.
<br />1.3 REFERENCES
<br />A. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI):
<br />1. ANSI C80.1 -RIGID STEEL CONDUIT, ZINC-COATED
<br />2. ANSI C80.3 -ELECTRICAL METALLIC TUBING, ZINC-COATED AND FITTINGS
<br />3. ANSI C80.4 -FITTINGS FOR RIGID METAL CONDUIT AND ELECTRICAL METALLIC TUBING
<br />4. ANSI/NEMA OS 1 -SHEET-STEEL OUTLET BOXES, DEVICE BOXES, COVERS AND BOX
<br />SUPPORTS
<br />B.FEDERAL SPECIFICATIONS (FS):
<br />1. A-A-50553A -FITTINGS FOR CONDUIT, METAL, RIGID, (THICK-WALL AND THIN-WALL (EMT)
<br />TYPE
<br />2. A-A-55810 -SPECIFICATION FOR FLEXIBLE METAL CONDUIT
<br />C.NECA "STANDARDS OF INSTALLATION"
<br />D.NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA):
<br />1. ANSI/NEMA FB 1 -FITTINGS, CAST METAL BOXES, AND CONDUIT BODIES FOR CONDUIT,
<br />ELECTRICAL METALLIC TUBING AND CABLE
<br />E.CEC CALIFORNIA ELECTRICAL CODE
<br />F.UNDERWRITERS LABORATORIES (UL): APPLICABLE LISTINGS
<br />1. UL 1 -FLEXIBLE METAL CONDUIT
<br />2. UL 6 -RIGID METAL CONDUIT
<br />3. UL 360 -LIQUID TIGHT FLEXIBLE STEEL CONDUIT
<br />4. UL514-B -CONDUIT TUBING AND CABLE FITTINGS
<br />5. UL797 -ELECTRICAL METAL TUBING
<br />G.DEFINITIONS:
<br />1. FITTINGS: CONDUIT CONNECTION OR COUPLING.
<br />2. BODY: ENLARGED FITTINGS WITH OPENING ALLOWING ACCESS TO THE CONDUCTORS FOR
<br />PULLING PURPOSES ONLY.
<br />3. MECHANICAL SPACES: ENCLOSED AREAS, USUALLY KEPT SEPARATED FROM THE GENERAL
<br />PUBLIC, WHERE THE PRIMARY USE IS TO HOUSE SERVICE EQUIPMENT AND TO ROUTE
<br />SERVICES. THESE SPACES GENERALLY HAVE EXPOSED STRUCTURES, BARE CONCRETE
<br />AND NON-ARCHITECTURALLY EMPHASIZED FINISHES.
<br />4. FINISHED SPACES: ENCLOSED AREAS WHERE THE PRIMARY USE IS TO HOUSE PERSONNEL
<br />AND THE GENERAL PUBLIC. THESE SPACES GENERALLY HAVE ARCHITECTURALLY
<br />EMPHASIZED FINISHES, CEILINGS AND/OR FLOORS.
<br />5. CONCEALED: NOT VISIBLE BY THE GENERAL PUBLIC. OFTEN INDICATES A LOCATION EITHER
<br />ABOVE THE CEILING, IN THE WALLS, IN OR BENEATH THE FLOOR SLAB, IN COLUMN
<br />COVERINGS, OR IN THE CEILING CONSTRUCTION.
<br />6. ABOVE GRADE: NOT DIRECTLY IN CONTACT WITH THE EARTH. FOR EXAMPLE, AN INTERIOR
<br />WALL LOCATED AT AN ELEVATION BELOW THE FINISHED GRADE SHALL BE CONSIDERED
<br />ABOVE GRADE BUT A WALL RETAINING EARTH SHALL BE CONSIDERED BELOW GRADE.
<br />1.4 SUBMITTALS
<br />A. INCLUDE FITTINGS AND CONDUITS. INCLUDE ALL IN-FLOOR AND UNDERFLOOR CONDUIT IN
<br />COORDINATION FILES. REFER TO SECTION 26 05 00 FOR COORDINATION DRAWING
<br />REQUIREMENTS.
<br />PART 2 -PRODUCTS
<br />2.1 RIGID METALLIC CONDUIT (RMC) AND FITTINGS
<br />A. MANUFACTURERS:
<br />1. ALLIED
<br />2. LTV
<br />3. STEELDUCT
<br />4. CALBOND CALPIPE
<br />5. WHEATLAND TUBE CO
<br />6. O-Z GEDNEY
<br />7. OR APPROVED EQUAL.
<br />B.MANUFACTURERS OF RMC CONDUIT FITTINGS:
<br />1. APPLETON ELECTRIC
<br />2. O-Z/GEDNEY CO.
<br />3. ELECTROLINE
<br />4. RACO
<br />5. BRIDGEPORT
<br />6. MIDWEST
<br />7. REGAL
<br />8. THOMAS & BETTS
<br />9. ORBIT INDUSTRIES
<br />10. OR APPROVED EQUAL.
<br />C.MINIMUM SIZE GALVANIZED STEEL: 3/4 INCH, UNLESS OTHERWISE NOTED.
<br />D.FITTINGS AND CONDUIT BODIES:
<br />1. END BELL FITTINGS: MALLEABLE IRON, HOT DIP GALVANIZED, THREADED FLARE TYPE WITH
<br />PROVISIONS FOR MOUNTING TO FORM.
<br />2. EXPANSION JOINTS: MALLEABLE IRON AND HOT DIP GALVANIZED PROVIDING A MINIMUM OF
<br />4 INCHES OF MOVEMENT. FITTING SHALL BE WATERTIGHT W ITH AN INSULATING BUSHING
<br />AND A BONDING JUMPER.
<br />3. CONDUIT END BUSHINGS: MALLEABLE IRON TYPE WITH MOLDED-ON HIGH IMPACT
<br />PHENOLIC THERMOSETTING INSULATION. WHERE REQUIRED ELSEWHERE IN THE
<br />CONTRACT DOCUMENTS, BUSHING SHALL BE COMPLETE WITH GROUND CONDUCTOR
<br />SADDLE AND CLAMP. HIGH IMPACT PHENOLIC THREADED TYPE BUSHINGS ARE NOT
<br />ACCEPTABLE.
<br />4. ALL OTHER FITTINGS AND CONDUIT BODIES SHALL BE OF MALLEABLE IRON CONSTRUCTION
<br />AND HOT DIP GALVANIZED.
<br />2.2 ELECTRICAL METALLIC TUBING (EMT) AND FITTINGS
<br />A. MINIMUM SIZE ELECTRICAL METALLIC TUBING: 3/4 INCH, UNLESS OTHERWISE NOTED.
<br />B. MANUFACTURERS OF EMT CONDUIT:
<br />1. ALLIED
<br />2. CALBOND CALPIPE
<br />3. LTV
<br />4. STEELDUCT
<br />5. WHEATLAND TUBE CO
<br />6. OR APPROVED EQUAL.
<br />C.FITTINGS AND CONDUIT BODIES:
<br />1. 2" DIAMETER OR SMALLER: STEEL SET SCREW TYPE OF STEEL DESIGNED FOR THEIR
<br />SPECIFIC APPLICATION.
<br />2. LARGER THAN 2": COMPRESSION TYPE OF STEEL DESIGNED FOR THEIR SPECIFIC
<br />APPLICATION.
<br />3. MANUFACTURERS OF EMT CONDUIT FITTINGS:
<br />a. APPLETON ELECTRIC
<br />b. O-Z/GEDNEY CO.
<br />c. ELECTROLINE
<br />d. RACO
<br />e. BRIDGEPORT
<br />f. MIDWEST
<br />g. REGAL
<br />h. THOMAS & BETTS
<br />i. ORBIT INDUSTRIES
<br />j. OR APPROVED EQUAL.
<br />2.3 FLEXIBLE METALLIC CONDUIT (FMC) AND FITTINGS
<br />A. MINIMUM SIZE GALVANIZED STEEL: 3/4 INCH, UNLESS OTHERWISE NOTED. LIGHTING BRANCH
<br />CIRCUIT WIRING TO AN INDIVIDUAL LUMINAIRE MAY BE A MANUFACTURED, UL LISTED 1/2""
<br />FLEXIBLE METAL CONDUIT AND FITTINGS WITH #12 AWG THHN CONDUCTORS AND AN
<br />INSULATED GROUND WIRE. MAXIMUM LENGTH OF 1/2" FMC SHALL BE SIX (6) FEET.
<br />B. MANUFACTURERS:
<br />1. AMERICAN FLEX
<br />2. ALFLEX
<br />3. ELECTRI-FLEX CO
<br />4. OR APPROVED EQUAL.
<br />C.CONSTRUCTION: FLEXIBLE STEEL, APPROVED FOR CONDUIT GROUND, ZINC COATED,
<br /> THREADLESS TYPE FORMED FROM A CONTINUOUS LENGTH OF SPIRALLY WOUND,
<br /> INTERLOCKED ZINC COATED STRIP STEEL. PROVIDE A SEPARATE EQUIPMENT GROUNDING
<br /> CONDUCTOR WHEN USED FOR EQUIPMENT WHERE FLEXIBILITY IS REQUIRED.
<br />D.FITTINGS AND CONDUIT BODIES:
<br />1. THREADLESS HINGED CLAMP TYPE, GALVANIZED ZINC COATED CADMIUM PLATED
<br />MALLEABLE CAST IRON.
<br />2. FITTINGS AND CONDUIT BODIES SHALL INCLUDE PLASTIC OR CAST METAL INSERTS
<br />SUPPLIED BY THE MANUFACTURER TO PROTECT CONDUCTORS FROM SHARP EDGES.
<br />TO BE CONTINUE ON E0-04
<br />TE OLIRFFOAC
<br />LANRP
<br />E 23191
<br />STA
<br />ER
<br />REGIST
<br />ED
<br />INA
<br />N
<br />REENIGE
<br />FO OISSE
<br />E AICLCERTL
<br />Exp. 06/30/26
<br />MIRASOPHOCLISGEORGY
<br />IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,
<br />TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
<br />AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND SHALL
<br />NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE
<br />EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP.
<br />©2022 IMEG CORP.
<br />REF. SCALE IN INCHES
<br />0 1 2 3
<br />The FUTURE. Built Smarter www.imegcorp.com
<br />R
<br />SHEET TITLE
<br />PROJECT
<br />FACILITY
<br />FAC NO: BLDG NO: FLOOR LEV: SECTION:
<br />KP PROJ. NO.
<br />PERMIT NO.
<br />555 W. 5th St Suite 2950 | Los Angeles, CA 90013 USA
<br />Phone 310.820.4600 | Fax 310.207.4215
<br />www.huitt-zollars.com
<br />ARCHITECT
<br />CONSULTANT
<br />ARCHITECT SEAL CONSULTANT SEAL
<br />KAISER FOUNDATION
<br />HOSPITALS NATIONAL
<br />FACILITIES SERVICES 1800
<br />HARRISON STREET OAKLAND,
<br />CALIFORNIA 94612
<br />ISSUE / REVISION LOG
<br />NO. ISSUED DATE
<br />0
<br />5'
<br />
<br />5
<br />0
<br />'
<br />GR
<br />A
<br />P
<br />H
<br />I
<br />C
<br />
<br />S
<br />C
<br />A
<br />L
<br />E
<br />S
<br />:
<br />
<br />1
<br />/
<br />1
<br />6
<br />"
<br />
<br />=
<br />
<br />1
<br />'
<br />-
<br />0
<br />"
<br />0
<br />25
<br />'
<br />1/
<br />8
<br />"
<br />
<br />=
<br />
<br />1
<br />'
<br />-
<br />0
<br />"
<br />5'
<br />0
<br />12
<br />'
<br />1/
<br />4
<br />"
<br />
<br />=
<br />
<br />1
<br />'
<br />-
<br />0
<br />"
<br />1'
<br />0
<br />6'
<br />1/
<br />2
<br />"
<br />
<br />=
<br />
<br />1
<br />'
<br />-
<br />0
<br />"
<br />1'
<br />0
<br />2'
<br />1-
<br />1
<br />/
<br />2
<br />"
<br />
<br />=
<br />
<br />1
<br />'
<br />-
<br />0
<br />"
<br />0
<br />1'
<br />3"
<br />
<br />=
<br />
<br />1
<br />'
<br />-
<br />0
<br />"
<br />IF
<br />
<br />T
<br />H
<br />I
<br />S
<br />
<br />S
<br />H
<br />E
<br />E
<br />T
<br />
<br />I
<br />S
<br />
<br />N
<br />O
<br />T
<br />
<br />30
<br />"
<br />x
<br />4
<br />2
<br />"
<br />,
<br />
<br />I
<br />T
<br />
<br />I
<br />S
<br />
<br />A
<br />
<br />R
<br />E
<br />D
<br />U
<br />C
<br />E
<br />D
<br />
<br />PR
<br />I
<br />N
<br />T
<br />
<br />-
<br />
<br />S
<br />C
<br />A
<br />L
<br />E
<br />
<br />AC
<br />C
<br />O
<br />R
<br />D
<br />I
<br />N
<br />G
<br />L
<br />Y
<br />AGENCY APPLICATION NUMBER
<br />AGENCY APPROVAL STAMP
<br />THIS DOCUMENT IS THE PROPERTY OF THE OWNER AND IS
<br />NOT TO BE USED WITHOUT OWNER'S WRITTEN PERMISSION.
<br />HZ PROJ. NO.
<br />222 S. HARBOR BOULEVARD, SUITE 800 I ANAHEIM, CA 92805
<br />PH: 714.490.5555 I FAX: 714.490.5560
<br />IMEG PROJ. NO.: 22008618.00
<br />PROJECT #22008618.00
<br />SOCC 2022 R HBM 1st Fl KPOJ
<br />REMODEL
<br />E0-03
<br />ELECTRICAL SPECIFICATION
<br />CA394-1
<br />CAP0227721R314412.35
<br />HARBOR/MacARTHUR MEDICAL OFF
<br />3401 S. HARBOR BLVD.
<br />SANTA ANA, CALIFORNIA 92704
<br />CITY SUBMITTAL 11/03/2025
<br />1 CITY BACKCHECK #1 01/06/2026
<br />101125520, 20187249, 40140902
<br />555 W. Fifth Street Suite 2950 | Los Angeles, CA 90013 USA
<br />ARCHITECT
<br />www.huitt-zollars.com
<br />Phone 310.820.4600 | Fax 310.207.4215
|