SPECIFICATIONS TABLE OF CONTENTS <br />SECTION 26 05 05 -ELECTRICAL DEMOLITION FOR REMODELING <br />PART 1 -GENERAL <br />1.1 SECTION INCLUDES <br />A. ELECTRICAL DEMOLITION <br />PART 2 -PRODUCTS <br />2.1 MATERIALS AND EQUIPMENT <br />A. MATERIALS AND EQUIPMENT FOR PATCHING AND EXTENDING WORK SHALL BE AS SPECIFIED IN <br />INDIVIDUAL SECTIONS. <br />PART 3 -EXECUTION <br />3.1 EXAMINATION <br />A. THE DRAWINGS ARE INTENDED TO INDICATE THE SCOPE OF WORK REQUIRED AND DO NOT <br />INDICATE EVERY BOX, CONDUIT, OR WIRE THAT MUST BE REMOVED. THE CONTRACTOR SHALL <br />VISIT THE SITE PRIOR TO SUBMITTING A BID AND VERIFY EXISTING CONDITIONS. <br />B. WHERE WALLS, CEILINGS, STRUCTURES, ETC., ARE INDICATED AS BEING REMOVED ON <br />GENERAL OR ELECTRICAL DRAWINGS, THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE <br />REMOVAL OF ALL ELECTRICAL EQUIPMENT, DEVICES, FIXTURES, RACEWAYS, WIRING, <br />SYSTEMS, ETC., FROM THE REMOVED AREA. <br />C. WHERE CEILINGS, WALLS, STRUCTURES, ETC., ARE TEMPORARILY REMOVED AND REPLACED <br />BY OTHERS, THIS CONTRACTOR SHALL BE RESPONSIBLE FOR THE REMOVAL, STORAGE, AND <br />REPLACEMENT OF EQUIPMENT, DEVICES, FIXTURES, RACEWAYS, WIRING, SYSTEMS, ETC. <br />D. WHERE MECHANICAL OR TECHNOLOGY EQUIPMENT IS INDICATED AS BEING REMOVED ON <br />ELECTRICAL, MECHANICAL, OR TECHNOLOGY DRAWINGS, THE CONTRACTOR SHALL BE <br />RESPONSIBLE FOR DISCONNECTING THE EQUIPMENT AND REMOVING ALL STARTERS, VFD, <br />CONTROLLERS, ELECTRICAL EQUIPMENT, RACEWAYS, WIRING, ETC. ASSOCIATED WITH THE <br />DEVICE. <br />E. VERIFY THAT ABANDONED WIRING AND EQUIPMENT SERVE ONLY ABANDONED EQUIPMENT OR <br />FACILITIES. EXTEND CONDUIT AND WIRE TO FACILITIES AND EQUIPMENT THAT WILL REMAIN IN <br />OPERATION FOLLOWING DEMOLITION. EXTENSION OF CONDUIT AND WIRE TO EQUIPMENT <br />SHALL BE COMPATIBLE WITH THE SURROUNDING AREA. EXTENDED CONDUIT AND <br />CONDUCTORS TO MATCH EXISTING SIZE AND MATERIAL. <br />F. COORDINATE SCOPE OF WORK WITH ALL OTHER CONTRACTORS AND THE OWNER AT THE <br />PROJECT SITE. SCHEDULE REMOVAL OF EQUIPMENT AND ELECTRICAL SERVICE TO AVOID <br />CONFLICTS. <br />G. BID SUBMITTAL SHALL MEAN THE CONTRACTOR HAS VISITED THE PROJECT SITE AND HAS <br />VERIFIED EXISTING CONDITIONS AND SCOPE OF WORK. <br />3.2 PREPARATION <br />A. THE CONTRACTOR SHALL OBTAIN APPROVAL FROM THE OWNER BEFORE TURNING OFF POWER <br />TO CIRCUITS, FEEDERS, PANELS, ETC. COORDINATE ALL OUTAGES WITH OWNER. <br />B. PROVIDE TEMPORARY WIRING AND CONNECTIONS TO MAINTAIN EXISTING SYSTEMS IN SERVICE <br />DURING CONSTRUCTION. WHEN WORK MUST BE PERFORMED ON ENERGIZED EQUIPMENT OR <br />CIRCUITS, USE PERSONNEL EXPERIENCED IN SUCH OPERATIONS. ASSUME ALL EQUIPMENT <br />AND SYSTEMS MUST REMAIN OPERATIONAL UNLESS SPECIFICALLY NOTED OTHERWISE ON <br />DRAWINGS. <br />C. DISCONNECT ELECTRICAL SYSTEMS IN WALLS, FLOORS, STRUCTURES, AND CEILINGS <br />SCHEDULED FOR REMOVAL. <br />D. EXISTING ELECTRICAL SERVICE: MAINTAIN EXISTING SYSTEM IN SERVICE UNTIL NEW SYSTEM IS <br />COMPLETE AND READY FOR SERVICE. DISABLE SYSTEM ONLY TO MAKE SWITCHOVERS AND <br />CONNECTIONS. OBTAIN PERMISSION FROM OWNER AT LEAST 72 HOURS BEFORE PARTIALLY OR <br />COMPLETELY DISABLING SYSTEM. MINIMIZE OUTAGE DURATION. <br />3.3 DEMOLITION AND EXTENSION OF EXISTING ELECTRICAL WORK <br />A. DEMOLISH AND EXTEND EXISTING ELECTRICAL WORK UNDER PROVISIONS OF DIVISION 1 OF <br />SPECIFICATIONS AND THIS SECTION. <br />B. REMOVE, RELOCATE, AND EXTEND EXISTING INSTALLATIONS TO ACCOMMODATE NEW <br />CONSTRUCTION. <br />C. REMOVE ABANDONED WIRING AND RACEWAY TO SOURCE OF SUPPLY. <br />D. REMOVE EXPOSED ABANDONED RACEWAY, INCLUDING ABANDONED RACEWAY ABOVE <br />ACCESSIBLE CEILING FINISHES. CUT RACEWAY FLUSH WITH WALLS AND FLOORS, AND PATCH <br />SURFACES. REMOVE ALL ASSOCIATED CLAMPS, HANGERS, SUPPORTS, ETC. ASSOCIATED WITH <br />RACEWAY REMOVAL. <br />E. DISCONNECT AND REMOVE OUTLETS AND DEVICES THAT ARE TO BE DEMOLISHED. REMOVE <br />OUTLET OR DEVICES' ASSOCIATED BACK BOX, SUPPORTS, AND CONDUIT AND CONDUCTORS <br />BACK TO SOURCE. PATCH OPENING CREATED FROM REMOVAL OF DEVICE TO MATCH <br />SURROUNDING FINISHES. <br />F. DISCONNECT AND REMOVE ABANDONED PANELBOARDS AND DISTRIBUTION EQUIPMENT. <br />G. DISCONNECT AND REMOVE ELECTRICAL DEVICES AND EQUIPMENT SERVING UTILIZATION <br />EQUIPMENT THAT HAS BEEN REMOVED. <br />H. DISCONNECT AND REMOVE ABANDONED LUMINAIRES. REMOVE BRACKETS, STEMS, HANGERS, <br />AND OTHER ACCESSORIES. BALLASTS IN LIGHT FIXTURES INSTALLED PRIOR TO 1980 SHALL BE <br />INCINERATED IN EPA APPROVED INCINERATOR OR DISPOSED OF IN EPA CERTIFIED <br />CONTAINERS AND DEPOSITED IN AN EPA LANDFILL CERTIFIED FOR PCB DISPOSAL OR <br />RECYCLED BY PERMITTED BALLAST RECYCLER. PUNCTURED OR LEAKING BALLASTS MUST BE <br />DISPOSED OF ACCORDING TO FEDERAL REGULATIONS UNDER THE TOXIC SUBSTANCE <br />CONTROL ACT. PROVIDE OWNER AND ARCHITECT/ENGINEER WITH A CERTIFICATE OF <br />DESTRUCTION TO VERIFY PROPER DISPOSAL. <br />I. REPAIR ADJACENT CONSTRUCTION AND FINISHES DAMAGED DURING DEMOLITION AND <br />EXTENSION WORK. PATCH OPENINGS TO MATCH EXISTING SURROUNDING FINISHES. <br />J. MAINTAIN ACCESS TO EXISTING ELECTRICAL INSTALLATIONS THAT REMAIN ACTIVE. MODIFY <br />INSTALLATION OR PROVIDE JUNCTION BOXES AND ACCESS PANEL AS APPROPRIATE. <br />K. EXTEND EXISTING INSTALLATIONS USING MATERIALS AND METHODS COMPATIBLE WITH <br />EXISTING ELECTRICAL INSTALLATIONS, OR AS SPECIFIED. EXTENDED CONDUIT AND <br />CONDUCTORS TO MATCH EXISTING SIZE AND MATERIAL. <br />L. HID AND FLUORESCENT LAMPS, DETERMINED BY THE TOXICITY CHARACTERISTIC LEACHATE <br />PROCEDURE (TCLP), TO BE HAZARDOUS WASTE SHALL BE DISPOSED OF IN AN EPA-PERMITTED <br />HAZARDOUS WASTE DISPOSAL FACILITY OR BY A PERMITTED LAMP RECYCLER. <br />M. REGULATORY REQUIREMENTS: COMPLY WITH GOVERNING EPA NOTIFICATION REGULATIONS <br />BEFORE BEGINNING DEMOLITION. COMPLY WITH HAULING AND DISPOSAL REGULATIONS OF <br />AUTHORITIES HAVING JURISDICTION. <br />N. THIS CONTRACTOR IS RESPONSIBLE FOR ALL COSTS INCURRED IN REPAIR, RELOCATIONS, OR <br />REPLACEMENT OF ANY CABLES, CONDUITS, OR OTHER SERVICES IF DAMAGED WITHOUT <br />PROPER INVESTIGATION. <br />3.4 CLEANING AND REPAIR <br />A. CLEAN AND REPAIR EXISTING MATERIALS AND EQUIPMENT THAT REMAIN OR ARE TO BE <br />REUSED. <br />B. PANELBOARDS: CLEAN EXPOSED SURFACES AND CHECK TIGHTNESS OF ELECTRICAL <br />CONNECTIONS. REPLACE DAMAGED CIRCUIT BREAKERS AND PROVIDE CLOSURE PLATES FOR <br />VACANT POSITIONS. PROVIDE TYPED CIRCUIT DIRECTORY SHOWING REVISED CIRCUITING <br />ARRANGEMENT. <br />C. ELECTRICAL ITEMS (E.G., LIGHTING FIXTURES, RECEPTACLES, SWITCHES, CONDUIT, WIRE, ETC.) <br />REMOVED AND NOT RELOCATED REMAIN THE PROPERTY OF THE OWNER. CONTRACTOR SHALL <br />PLACE ITEMS RETAINED BY THE OWNER IN A LOCATION COORDINATED WITH THE OWNER. THE <br />CONTRACTOR SHALL BE RESPONSIBLE FOR THE DISPOSAL OF MATERIAL THE OWNER DOES <br />NOT WANT. <br />3.5 INSTALLATION <br />A. INSTALL RELOCATED MATERIALS AND EQUIPMENT UNDER THE PROVISIONS OF DIVISION 1 OF <br />SPECIFICATIONS. <br />END OF SECTION <br />• SECTION 26 05 05 -ELECTRICAL DEMOLITION FOR REMODELING <br />• SECTION 26 05 13 -WIRE AND CABLE <br />• SECTION 26 05 26 -GROUNDING AND BONDING <br />• SECTION 26 05 27 -SUPPORTING DEVICES <br />• SECTION 26 05 33 -CONDUIT AND BOXES <br />SECTION 26 05 13 -WIRE AND CABLE <br />PART 1 -GENERAL <br />1.1 SECTION INCLUDES <br />A. BUILDING WIRE <br />B. CABLING FOR REMOTE CONTROL, SIGNAL, AND POWER LIMITED CIRCUITS <br />1.2 RELATED WORK <br />A. SECTION 26 05 53 -ELECTRICAL IDENTIFICATION: REFER TO ELECTRICAL IDENTIFICATION FOR <br />COLOR AND IDENTIFICATION LABELING REQUIREMENTS. <br />1.3 REFERENCES <br />A. NEMA WC 70 -POWER CABLES RATED 2,000V OR LESS FOR THE DISTRIBUTION OF ELECTRICAL <br />ENERGY <br />B. CEC CALIFORNIA ELECTRICAL CODE <br />C. UL 44 -THERMOSET-INSULATED WIRES AND CABLES <br />D. UL 83 -THERMOPLASTIC-INSULATED WIRES AND CABLES <br />E. UL 1581 -STANDARD FOR ELECTRICAL WIRES, CABLES, AND FLEXIBLE CORDS <br />1.4 SUBMITTALS <br />A. SUBMIT SHOP DRAWINGS AND PRODUCT DATA UNDER THE PROVISIONS OF SECTION 26 05 00. <br />PART 2 -PRODUCTS <br />2.1 BUILDING WIRE <br />A. FEEDERS AND BRANCH CIRCUITS 8 AWG AND LARGER: COPPER, STRANDED CONDUCTOR, 600- <br />VOLT INSULATION, THHN/THWN OR XHHW-2. <br />B. FEEDERS AND BRANCH CIRCUITS 10 AWG AND SMALLER: COPPER, SOLID OR STRANDED <br />CONDUCTOR, 600-VOLT INSULATION, THHN/THWN, UNLESS OTHERWISE NOTED ON THE <br />DRAWINGS. <br />C. CONTROL CIRCUITS: COPPER, STRANDED CONDUCTOR 600-VOLT INSULATION, THHN/THWN. <br />D. EACH 120 AND 277-VOLT BRANCH CIRCUIT SHALL HAVE A DEDICATED NEUTRAL CONDUCTOR. <br />NEUTRAL CONDUCTORS SHALL BE CONSIDERED CURRENT-CARRYING CONDUCTORS FOR WIRE <br />DERATING. <br />2.2 CABLING FOR REMOTE CONTROL, SIGNAL, AND POWER LIMITED CIRCUITS <br />A. WIRE FOR THE FOLLOWING SPECIALIZED SYSTEMS SHALL BE AS DESIGNATED ON THE <br />DRAWINGS, OR ELSEWHERE IN THESE SPECIFICATIONS. IF NOT DESIGNATED ON THE <br />DRAWINGS OR SPECIFICATIONS, THE SYSTEM MANUFACTURER'S RECOMMENDATIONS SHALL <br />BE FOLLOWED. <br />1. FIRE ALARM <br />2. LOW VOLTAGE SWITCHING AND LIGHTING CONTROL <br />2.3 HEALTHCARE RATED AC CABLE <br />A. HEALTHCARE GRADE ARMORED CABLE WITH REDUNDANT COPPER GROUND CONDUCTOR <br />WITH GREEN IDENTIFYING STRIP ON THE EXTERIOR OF THE ARMOR. <br />B. ARMORED CABLE SHALL BE CONSTRUCTED IN ACCORDANCE WITH UL, INC STANDARD FOR <br />TYPE AC CABLES, UL 4, AND INCLUDE A FLEXIBLE METALLIC INTERLOCKED ARMOR, LISTED AS A <br />REDUNDANT GROUND PATH. <br />C. MINIMUM CONDUCTOR SIZE FOR BRANCH CIRCUIT WIRING SHALL BE 12 AWG. EACH 120 AND 277 <br />VOLT CIRCUIT SHALL HAVE A DEDICATED NEUTRAL CONDUCTOR. <br />D. CABLE SHALL BE SUPPORTED BY AN APPROVED MEANS EVERY 4.5 FEET AND WITHIN 12 INCHES <br />OR OUTLLET BOXES, JUNCTION BOXES, OR FITTINGS. <br />PART 3 -EXECUTION <br />3.1 WIRE AND CABLE INSTALLATION SCHEDULE <br />A. ABOVE ACCESSIBLE CEILINGS: <br />1. BUILDING WIRE SHALL BE INSTALLED IN RACEWAY. <br />2. METAL CLAD CABLE, TYPE MC, 1/2" SIZE WITH MINIMUM #12 CONDUCTORS AND GROUND, <br />SHALL BE ALLOWED FOR FLEXIBLE WHIPS TO INDIVIDUAL LUMINAIRES ON NON-ESSENTIAL <br />CIRCUITS. THE FLEXIBLE WHIPS SHALL BE BETWEEN 18" TO 72" IN LENGTH PER ELECTRICAL <br />CODE. <br />B.ALL OTHER LOCATIONS: BUILDING WIRE IN RACEWAY. <br />C.ABOVE GRADE: ALL CONDUCTORS INSTALLED ABOVE GRADE SHALL BE TYPE "THHN". <br />3.2 GENERAL WIRING METHODS <br />A. USE NO WIRE SMALLER THAN 12 AWG FOR POWER AND LIGHTING CIRCUITS, AND NO SMALLER <br />THAN 14 AWG FOR CONTROL WIRING. <br />B. USE NO WIRE SMALLER THAN 18 AWG FOR LOW VOLTAGE CONTROL WIRING BELOW 100 VOLTS. <br />C. USE 10 AWG CONDUCTOR FOR 20 AMPERE, 120-VOLT BRANCH CIRCUIT HOME RUNS LONGER <br />THAN 75 FEET, AND FOR 20 AMPERE, 277-VOLT BRANCH CIRCUIT HOME RUNS LONGER THAN 200 <br />FEET. <br />D. THE AMPACITY OF MULTIPLE CONDUCTORS IN ONE CONDUIT SHALL BE DERATED PER THE <br />ELECTRICAL CODE. IN NO CASE SHALL MORE THAN 4 CONDUCTORS BE INSTALLED IN ONE <br />CONDUIT TO SUCH LOADS AS MOTORS LARGER THAN 1/4 HP, PANELBOARDS, MOTOR CONTROL <br />CENTERS, ETC. <br />E. WHERE INSTALLING PARALLEL FEEDERS, PLACE AN EQUAL NUMBER OF CONDUCTORS FOR <br />EACH PHASE OF A CIRCUIT IN SAME RACEWAY OR CABLE. <br />F. SPLICE ONLY IN JUNCTION OR OUTLET BOXES. <br />G. NEATLY TRAIN AND LACE WIRING INSIDE BOXES, EQUIPMENT, AND PANELBOARDS. <br />H. MAKE CONDUCTOR LENGTHS FOR PARALLEL CIRCUITS EQUAL. <br />I. ALL CONDUCTORS SHALL BE CONTINUOUS IN CONDUIT FROM LAST OUTLET TO THEIR <br />TERMINATION. <br />J. TERMINATE ALL SPARE CONDUCTORS ON TERMINAL BLOCKS, AND LABEL THE SPARE <br />CONDUCTORS. <br />K. CABLES OR WIRES SHALL NOT BE LAID OUT ON THE GROUND BEFORE PULLING. <br />L. CABLES OR WIRES SHALL NOT BE DRAGGED OVER EARTH OR PAVING. <br />M. CARE SHALL BE TAKEN SO AS NOT TO SUBJECT THE CABLE OR WIRE TO HIGH MECHANICAL <br />STRESSES THAT WOULD CAUSE DAMAGE TO THE WIRE AND CABLE. <br />N. AT LEAST SIX (6)-INCH LOOPS OR ENDS SHALL BE LEFT AT EACH OUTLET FOR INSTALLATION <br />CONNECTION OF LUMINAIRES OR OTHER DEVICES. <br />O. ALL WIRES IN OUTLET BOXES NOT CONNECTED TO FIXTURES OR OTHER DEVICES SHALL BE <br />ROLLED UP, SPLICED IF CONTINUITY OF CIRCUIT IS REQUIRED, AND INSULATED. <br />3.3 WIRING INSTALLATION IN RACEWAYS <br />A. PULL ALL CONDUCTORS INTO A RACEWAY AT THE SAME TIME. USE UL LISTED WIRE PULLING <br />LUBRICANT FOR PULLING 4 AWG AND LARGER WIRES. <br />B. PULLING SHALL BE CONTINUOUS WITHOUT UNNECESSARY STOPS AND STARTS WITH WIRE OR <br />CABLE ONLY PARTIALLY THROUGH RACEWAY. <br />C. WHERE REELS OF CABLE OR WIRE ARE USED, THEY SHALL BE SET UP ON JACKS CLOSE TO THE <br />POINT WHERE THE WIRE OR CABLE ENTERS THE CONDUIT OR DUCT SO THAT THE CABLE OR <br />WIRE MAY BE UNREELED AND RUN INTO THE CONDUIT OR DUCT WITH A MINIMUM OF CHANGE <br />IN THE DIRECTION OF THE BEND. <br />D. CONDUCTORS SHALL NOT BE PULLED THROUGH CONDUITS UNTIL PLASTERING OR MASONRY <br />WORK IS COMPLETED AND CONDUITS ARE FREE FROM MOISTURE. CARE SHALL BE TAKEN SO <br />THAT LONG PULLS OF WIRE OR PULLS AROUND SEVERAL BENDS ARE NOT MADE WHERE THE <br />WIRE MAY BE PERMANENTLY STRETCHED AND THE INSULATION DAMAGED. <br />E. ONLY NYLON ROPE SHALL BE PERMITTED TO PULL CABLES INTO CONDUIT AND DUCTS. <br />F. COMPLETELY AND THOROUGHLY SWAB RACEWAY SYSTEM BEFORE INSTALLING CONDUCTORS. <br />G. CONDUCTOR SUPPORTS IN VERTICAL RACEWAYS: <br />1. SUPPORT CONDUCTORS IN VERTICAL RACEWAYS IN ACCORDANCE WITH THE ELECTRICAL <br />CODE SPACING OF CONDUCTORS SUPPORTS. <br />2. SUPPORTS SHALL BE OF INSULATED WEDGE TYPE (OZ GEDNEY TYPE S, OR EQUAL) AND <br />INSTALLED IN A TAPERED INSULATED BUSHING FITTING OR A METAL WOVEN MESH WITH A <br />SUPPORT RING THAT FITS INSIDE CONDUIT FITTING INSTALLED IN AN ACCESSIBLE <br />JUNCTION BOX (HUBBELL KELLEMS SUPPORT GRIP OR EQUAL). <br />3.4 WIRING CONNECTIONS AND TERMINATIONS <br />A. SPLICE AND TAP ONLY IN ACCESSIBLE JUNCTION BOXES. <br />B. USE SOLDERLESS, TIN-PLATED COPPER, COMPRESSION TERMINALS (LUGS) APPLIED WITH <br />CIRCUMFERENTIAL CRIMP FOR CONDUCTOR TERMINATIONS, 8 AWG AND LARGER. <br />C. USE SOLDERLESS, TIN-PLATED, COMPRESSION TERMINALS (LUGS) APPLIED WITH INDENTER <br />CRIMP FOR COPPER CONDUCTOR TERMINATIONS, 10 AWG AND SMALLER. <br />D. USE SOLDERLESS PRESSURE CONNECTORS WITH INSULATING COVERS FOR COPPER WIRE <br />SPLICES AND TAPS, 8 AWG AND SMALLER. FOR 10 AWG AND SMALLER, USE INSULATED SPRING <br />WIRE CONNECTORS WITH PLASTIC CAPS. <br />E. USE COMPRESSION CONNECTORS APPLIED WITH CIRCUMFERENTIAL CRIMP FOR CONDUCTOR <br />SPLICES AND TAPS, 6 AWG AND LARGER. TAPE UNINSULATED CONDUCTORS AND <br />CONNECTORS WITH ELECTRICAL TAPE TO 150 PERCENT OF THE INSULATION VALUE OF <br />CONDUCTOR. <br />F. THOROUGHLY CLEAN WIRES BEFORE INSTALLING LUGS AND CONNECTORS. <br />G. MAKE SPLICES, TAPS AND TERMINATIONS TO CARRY FULL AMPACITY OF CONDUCTORS <br />WITHOUT PERCEPTIBLE TEMPERATURE RISE. <br />H. PHASE SEQUENCE: ALL APPARATUS SHALL BE CONNECTED TO OPERATE IN THE PHASE <br />SEQUENCE A-B-C REPRESENTING THE TIME SEQUENCE IN WHICH THE PHASE CONDUCTORS SO <br />IDENTIFIED REACH POSITIVE MAXIMUM VOLTAGE. <br />I. AS A GENERAL RULE, APPLICABLE TO SWITCHES, CIRCUIT BREAKERS, STARTERS, <br />PANELBOARDS, SWITCHGEAR AND THE LIKE, THE CONNECTIONS TO PHASE CONDUCTORS ARE <br />INTENDED THUS: <br />1. FACING THE FRONT AND OPERATING SIDE OF THE EQUIPMENT, THE PHASE IDENTIFICATION <br />SHALL BE: <br />a. LEFT TO RIGHT -A-B-C <br />b. TOP TO BOTTOM -A-B-C <br />J.CONNECTION REVISIONS AS REQUIRED TO ACHIEVE CORRECT ROTATION OF MOTORS SHALL <br /> BE MADE AT THE LOAD TERMINALS OF THE STARTERS OR DISCONNECT SWITCHES. <br />3.5 FIELD QUALITY CONTROL <br />A. FIELD INSPECTION AND TESTING WILL BE PERFORMED UNDER PROVISIONS OF DIVISION 1. <br />B. INSPECT WIRE AND CABLE FOR PHYSICAL DAMAGE AND PROPER CONNECTION. <br />C. TORQUE TEST CONDUCTOR CONNECTIONS AND TERMINATIONS TO MANUFACTURER'S <br />RECOMMENDED VALUES. <br />D. PERFORM CONTINUITY TEST ON ALL POWER AND EQUIPMENT BRANCH CIRCUIT CONDUCTORS. <br />VERIFY PROPER PHASING CONNECTIONS. <br />END OF SECTION <br />SECTION 26 05 26 -GROUNDING AND BONDING <br />PART 1 -GENERAL <br />1.1 SECTION INCLUDES <br />A. EQUIPMENT GROUNDING SYSTEM <br />1.2 REFERENCES <br />A. CEC CALIFORNIA ELECTRICAL CODE <br />B. NFPA 99 -STANDARD FOR HEALTHCARE FACILITIES <br />1.3 SUMMARY <br />A. THIS SECTION INCLUDES GROUNDING OF ELECTRICAL SYSTEMS AND EQUIPMENT. GROUNDING <br />REQUIREMENTS SPECIFIED IN THIS SECTION MAY BE SUPPLEMENTED BY SPECIAL <br />REQUIREMENTS OF SYSTEMS DESCRIBED IN OTHER SECTIONS. <br />PART 2 -PRODUCTS <br />2.1 GROUNDING CONDUCTORS <br />A. FOR INSULATED CONDUCTORS, COMPLY WITH DIVISION 26 SECTION 26 05 13 "WIRE AND CABLE". <br />B. MATERIAL: COPPER. <br />C. EQUIPMENT GROUNDING CONDUCTORS: INSULATED. REFER TO SECTION 26 05 53 FOR <br />INSULATION COLOR. <br />2.2 CONNECTOR PRODUCTS <br />A. COMPLY WITH UL 467; LISTED FOR USE FOR SPECIFIC TYPES, SIZES, AND COMBINATIONS OF <br />CONDUCTORS AND CONNECTED ITEMS. <br />B. CONNECTORS: HYDRAULIC COMPRESSION TYPE, IN KIT FORM, AND SELECTED PER <br />MANUFACTURER'S WRITTEN INSTRUCTIONS. <br />C. BOLTED CONNECTORS: BOLTED-PRESSURE-TYPE CONNECTORS. <br />PART 3 -EXECUTION <br />3.1 CONNECTIONS <br />A. GENERAL: MAKE CONNECTIONS SO GALVANIC ACTION OR ELECTROLYSIS POSSIBILITY IS <br />MINIMIZED. SELECT CONNECTORS, CONNECTION HARDWARE, CONDUCTORS, AND <br />CONNECTION METHODS SO METALS IN DIRECT CONTACT WILL BE GALVANICALLY COMPATIBLE. <br />1. USE ELECTROPLATED OR HOT-TIN-COATED MATERIALS TO ENSURE HIGH CONDUCTIVITY <br />AND TO MAKE CONTACT POINTS CLOSER TO ORDER OF GALVANIC SERIES. <br />2. MAKE CONNECTIONS WITH CLEAN, BARE METAL AT POINTS OF CONTACT. <br />3. MAKE ALUMINUM-TO-STEEL CONNECTIONS WITH STAINLESS-STEEL SEPARATORS AND <br />MECHANICAL CLAMPS. <br />4. MAKE ALUMINUM-TO-GALVANIZED STEEL CONNECTIONS WITH TIN-PLATED COPPER <br />JUMPERS AND MECHANICAL CLAMPS. <br />5. COAT AND SEAL CONNECTIONS HAVING DISSIMILAR METALS WITH INERT MATERIAL TO <br />PREVENT FUTURE PENETRATION OF MOISTURE TO CONTACT SURFACES. <br />B.COMPRESSION-TYPE CONNECTIONS: USE HYDRAULIC COMPRESSION TOOLS TO PROVIDE <br /> CORRECT CIRCUMFERENTIAL PRESSURE FOR COMPRESSION CONNECTORS. USE TOOLS AND <br /> DIES RECOMMENDED BY CONNECTOR MANUFACTURER. PROVIDE EMBOSSING DIE CODE OR <br /> OTHER STANDARD METHOD TO MAKE A VISIBLE INDICATION THAT A CONNECTOR HAS BEEN <br /> ADEQUATELY COMPRESSED ON GROUNDING CONDUCTOR. <br />C.EQUIPMENT GROUNDING CONDUCTOR TERMINATIONS: FOR NO. 8 AWG AND LARGER, USE <br /> PRESSURE-TYPE GROUNDING LUGS. NO. 10 AWG AND SMALLER GROUNDING CONDUCTORS <br /> MAY BE TERMINATED WITH WINGED PRESSURE-TYPE CONNECTORS. <br />D.NONCONTACT METAL RACEWAY TERMINATIONS: IF METALLIC RACEWAYS TERMINATE AT METAL <br /> HOUSINGS WITHOUT MECHANICAL AND ELECTRICAL CONNECTION TO HOUSING, TERMINATE <br /> EACH CONDUIT WITH A GROUNDING BUSHING. CONNECT GROUNDING BUSHINGS WITH A BARE <br /> GROUNDING CONDUCTOR TO GROUNDING BUS OR TERMINAL IN HOUSING. BOND <br /> ELECTRICALLY NON-CONTINUOUS CONDUITS AT ENTRANCES AND EXITS WITH GROUNDING <br /> BUSHINGS AND BARE GROUNDING CONDUCTORS, UNLESS OTHERWISE INDICATED. <br />E.CONNECTIONS AT BACK BOXES, JUNCTION BOXES, PULL BOXES, AND EQUIPMENT <br /> TERMINATIONS: THE EQUIPMENT GROUNDING CONDUCTOR(S) ASSOCIATED WITH ALL <br /> CIRCUITS IN THE BOX SHALL BE CONNECTED TOGETHER AND TO THE BOX USING A SUITABLE <br /> GROUNDING SCREW. THE REMOVAL OF THE RESPECTIVE RECEPTACLE, LUMINAIRE, OR OTHER <br /> DEVICE SERVED BY THE BOX SHALL NOT INTERRUPT THE GROUNDING CONTINUITY. <br />F.TIGHTEN SCREWS AND BOLTS FOR GROUNDING AND BONDING CONNECTORS AND TERMINALS <br /> ACCORDING TO MANUFACTURER'S PUBLISHED TORQUE-TIGHTENING VALUES. IF <br /> MANUFACTURER'S TORQUE VALUES ARE NOT INDICATED, USE THOSE SPECIFIED IN UL 486A. <br />G.MOISTURE PROTECTION: IF INSULATED GROUNDING CONDUCTORS ARE CONNECTED TO <br /> GROUND RODS OR GROUNDING BUSES, INSULATE ENTIRE AREA OF CONNECTION AND SEAL <br /> AGAINST MOISTURE PENETRATION OF INSULATION AND CABLE. <br />3.2 INSTALLATION <br />A. GROUNDING CONDUCTORS: ROUTE ALONG SHORTEST AND STRAIGHTEST PATHS POSSIBLE, <br />UNLESS OTHERWISE INDICATED. AVOID OBSTRUCTING ACCESS OR PLACING CONDUCTORS <br />WHERE THEY MAY BE SUBJECTED TO STRAIN, IMPACT, OR DAMAGE. EACH GROUNDING <br />CONDUCTOR THAT PASSES THROUGH A BELOW GRADE WALL MUST BE PROVIDED WITH A <br />WATERSTOP. <br />B. IN RACEWAYS, USE INSULATED EQUIPMENT GROUNDING CONDUCTORS. <br />3.3 EQUIPMENT GROUNDING SYSTEM <br />A. COMPLY WITH ELECTRICAL CODE, FOR TYPES, SIZES, AND QUANTITIES OF EQUIPMENT <br />GROUNDING CONDUCTORS, UNLESS SPECIFIC TYPES, LARGER SIZES, OR MORE CONDUCTORS <br />THAN REQUIRED BY ELECTRICAL CODE ARE INDICATED. <br />B. INSTALL EQUIPMENT GROUNDING CONDUCTORS IN ALL FEEDERS AND CIRCUITS. TERMINATE <br />EACH END ON A GROUNDING LUG OR BUS. <br />END OF SECTION <br />SECTION 26 05 27 -SUPPORTING DEVICES <br />PART 1 -GENERAL <br />1.1 SECTION INCLUDES <br />A. CONDUIT AND EQUIPMENT SUPPORTS <br />B. FASTENING HARDWARE <br />1.2 QUALITY ASSURANCE <br />A. SUPPORT SYSTEMS SHALL BE ADEQUATE FOR WEIGHT OF EQUIPMENT AND CONDUIT, <br />INCLUDING WIRING, WHICH THEY CARRY. <br />PART 2 -PRODUCTS <br />2.1 MANUFACTURERS <br />A. COOPER B-LINE <br />B. ERICO, INC. <br />C. HILTI <br />2.2 MATERIAL <br />A. SUPPORT CHANNEL: HOT-DIP GALVANIZED FOR INTERIOR/DRY LOCATIONS. ALL FIELD CUT <br />ENDS SHALL BE TOUCHED UP WITH MATCHING FINISH TO INHIBIT RUSTING. <br />B. HARDWARE: CORROSION RESISTANT. <br />PART 3 -EXECUTION <br />3.1 INSTALLATION <br />A. FASTEN HANGER RODS, CONDUIT CLAMPS, AND OUTLET AND JUNCTION BOXES TO BUILDING <br />STRUCTURE USING EXPANSION ANCHORS IN CONCRETE AND BEAM CLAMPS ON STRUCTURAL <br />STEEL. <br />B. TRAPEZE SUPPORT INSTALLATION: CUT HANGER RODS BACK AT TRAPEZE SUPPORTS SO THEY <br />DO NOT EXTEND MORE THAN 3/4" BELOW BOTTOM FACE OF LOWEST FASTENER AND BLUNT <br />ANY SHARP EDGES. <br />C. USE TOGGLE BOLTS OR HOLLOW WALL FASTENERS IN HOLLOW MASONRY, PLASTER, OR <br />GYPSUM BOARD PARTITIONS AND WALLS; EXPANSION ANCHORS OR PRESET INSERTS IN SOLID <br />MASONRY WALLS; SELF-DRILLING ANCHORS OR EXPANSION ANCHOR ON CONCRETE <br />SURFACES; SHEET METAL SCREWS IN SHEET METAL STUDS; AND WOOD SCREWS IN WOOD <br />CONSTRUCTION. <br />D. DO NOT FASTEN SUPPORTS TO CEILING SYSTEMS, PIPING, DUCTWORK, MECHANICAL <br />EQUIPMENT, OR CONDUIT, UNLESS OTHERWISE NOTED. <br />E. DO NOT USE POWDER-ACTUATED ANCHORS WITHOUT SPECIFIC PERMISSION. <br />F. DO NOT DRILL STRUCTURAL STEEL MEMBERS. <br />G. BRIDGE STUDS TOP AND BOTTOM WITH CHANNELS TO SUPPORT FLUSH-MOUNTED CABINETS <br />AND PANELBOARDS IN STUD WALLS. <br />3.2 FINISH <br />A. PRIME COAT EXPOSED STEEL HANGERS AND SUPPORTS. HANGERS AND SUPPORTS IN CRAWL <br />SPACES, PIPE SHAFTS, AND ABOVE SUSPENDED CEILING SPACES ARE NOT CONSIDERED <br />EXPOSED. <br />B. TRIM ALL ENDS OF EXPOSED FIELD FABRICATED STEEL HANGERS, SLOTTED CHANNEL AND <br />THREADED ROD TO WITHIN 1" OF SUPPORT OR FASTENER TO ELIMINATE POTENTIAL INJURY TO <br />PERSONNEL UNLESS SHOWN OTHERWISE ON THE DRAWINGS. SMOOTH ENDS AND INSTALL <br />ELASTOMERIC INSULATION WITH TWO COATS OF LATEX PAINT IF EXPOSED STEEL IS WITHIN <br />6'-6" OF FINISH FLOOR AND PRESENTS POTENTIAL INJURY TO PERSONNEL. <br />END OF SECTION <br />SECTION 26 05 33 -CONDUIT AND BOXES <br />PART 1 -GENERAL <br />1.1 SECTION INCLUDES <br />A. RIGID METALLIC CONDUIT AND FITTINGS (RMC) <br />B. ELECTRICAL METALLIC TUBING AND FITTINGS (EMT) <br />C. FLEXIBLE METALLIC CONDUIT AND FITTINGS (FMC) <br />D. LIQUIDTIGHT FLEXIBLE METALLIC CONDUIT AND FITTINGS (LFMC) <br />E. WALL AND CEILING OUTLET BOXES <br />F. ELECTRICAL CONNECTION <br />G. PULL AND JUNCTION BOXES <br />H. HANDHOLES <br />1.2 RELATED WORK <br />A. SECTION 26 05 53 -ELECTRICAL IDENTIFICATION: REFER TO ELECTRICAL IDENTIFICATION FOR <br />COLOR AND IDENTIFICATION LABELING REQUIREMENTS. <br />1.3 REFERENCES <br />A. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI): <br />1. ANSI C80.1 -RIGID STEEL CONDUIT, ZINC-COATED <br />2. ANSI C80.3 -ELECTRICAL METALLIC TUBING, ZINC-COATED AND FITTINGS <br />3. ANSI C80.4 -FITTINGS FOR RIGID METAL CONDUIT AND ELECTRICAL METALLIC TUBING <br />4. ANSI/NEMA OS 1 -SHEET-STEEL OUTLET BOXES, DEVICE BOXES, COVERS AND BOX <br />SUPPORTS <br />B.FEDERAL SPECIFICATIONS (FS): <br />1. A-A-50553A -FITTINGS FOR CONDUIT, METAL, RIGID, (THICK-WALL AND THIN-WALL (EMT) <br />TYPE <br />2. A-A-55810 -SPECIFICATION FOR FLEXIBLE METAL CONDUIT <br />C.NECA "STANDARDS OF INSTALLATION" <br />D.NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA): <br />1. ANSI/NEMA FB 1 -FITTINGS, CAST METAL BOXES, AND CONDUIT BODIES FOR CONDUIT, <br />ELECTRICAL METALLIC TUBING AND CABLE <br />E.CEC CALIFORNIA ELECTRICAL CODE <br />F.UNDERWRITERS LABORATORIES (UL): APPLICABLE LISTINGS <br />1. UL 1 -FLEXIBLE METAL CONDUIT <br />2. UL 6 -RIGID METAL CONDUIT <br />3. UL 360 -LIQUID TIGHT FLEXIBLE STEEL CONDUIT <br />4. UL514-B -CONDUIT TUBING AND CABLE FITTINGS <br />5. UL797 -ELECTRICAL METAL TUBING <br />G.DEFINITIONS: <br />1. FITTINGS: CONDUIT CONNECTION OR COUPLING. <br />2. BODY: ENLARGED FITTINGS WITH OPENING ALLOWING ACCESS TO THE CONDUCTORS FOR <br />PULLING PURPOSES ONLY. <br />3. MECHANICAL SPACES: ENCLOSED AREAS, USUALLY KEPT SEPARATED FROM THE GENERAL <br />PUBLIC, WHERE THE PRIMARY USE IS TO HOUSE SERVICE EQUIPMENT AND TO ROUTE <br />SERVICES. THESE SPACES GENERALLY HAVE EXPOSED STRUCTURES, BARE CONCRETE <br />AND NON-ARCHITECTURALLY EMPHASIZED FINISHES. <br />4. FINISHED SPACES: ENCLOSED AREAS WHERE THE PRIMARY USE IS TO HOUSE PERSONNEL <br />AND THE GENERAL PUBLIC. THESE SPACES GENERALLY HAVE ARCHITECTURALLY <br />EMPHASIZED FINISHES, CEILINGS AND/OR FLOORS. <br />5. CONCEALED: NOT VISIBLE BY THE GENERAL PUBLIC. OFTEN INDICATES A LOCATION EITHER <br />ABOVE THE CEILING, IN THE WALLS, IN OR BENEATH THE FLOOR SLAB, IN COLUMN <br />COVERINGS, OR IN THE CEILING CONSTRUCTION. <br />6. ABOVE GRADE: NOT DIRECTLY IN CONTACT WITH THE EARTH. FOR EXAMPLE, AN INTERIOR <br />WALL LOCATED AT AN ELEVATION BELOW THE FINISHED GRADE SHALL BE CONSIDERED <br />ABOVE GRADE BUT A WALL RETAINING EARTH SHALL BE CONSIDERED BELOW GRADE. <br />1.4 SUBMITTALS <br />A. INCLUDE FITTINGS AND CONDUITS. INCLUDE ALL IN-FLOOR AND UNDERFLOOR CONDUIT IN <br />COORDINATION FILES. REFER TO SECTION 26 05 00 FOR COORDINATION DRAWING <br />REQUIREMENTS. <br />PART 2 -PRODUCTS <br />2.1 RIGID METALLIC CONDUIT (RMC) AND FITTINGS <br />A. MANUFACTURERS: <br />1. ALLIED <br />2. LTV <br />3. STEELDUCT <br />4. CALBOND CALPIPE <br />5. WHEATLAND TUBE CO <br />6. O-Z GEDNEY <br />7. OR APPROVED EQUAL. <br />B.MANUFACTURERS OF RMC CONDUIT FITTINGS: <br />1. APPLETON ELECTRIC <br />2. O-Z/GEDNEY CO. <br />3. ELECTROLINE <br />4. RACO <br />5. BRIDGEPORT <br />6. MIDWEST <br />7. REGAL <br />8. THOMAS & BETTS <br />9. ORBIT INDUSTRIES <br />10. OR APPROVED EQUAL. <br />C.MINIMUM SIZE GALVANIZED STEEL: 3/4 INCH, UNLESS OTHERWISE NOTED. <br />D.FITTINGS AND CONDUIT BODIES: <br />1. END BELL FITTINGS: MALLEABLE IRON, HOT DIP GALVANIZED, THREADED FLARE TYPE WITH <br />PROVISIONS FOR MOUNTING TO FORM. <br />2. EXPANSION JOINTS: MALLEABLE IRON AND HOT DIP GALVANIZED PROVIDING A MINIMUM OF <br />4 INCHES OF MOVEMENT. FITTING SHALL BE WATERTIGHT W ITH AN INSULATING BUSHING <br />AND A BONDING JUMPER. <br />3. CONDUIT END BUSHINGS: MALLEABLE IRON TYPE WITH MOLDED-ON HIGH IMPACT <br />PHENOLIC THERMOSETTING INSULATION. WHERE REQUIRED ELSEWHERE IN THE <br />CONTRACT DOCUMENTS, BUSHING SHALL BE COMPLETE WITH GROUND CONDUCTOR <br />SADDLE AND CLAMP. HIGH IMPACT PHENOLIC THREADED TYPE BUSHINGS ARE NOT <br />ACCEPTABLE. <br />4. ALL OTHER FITTINGS AND CONDUIT BODIES SHALL BE OF MALLEABLE IRON CONSTRUCTION <br />AND HOT DIP GALVANIZED. <br />2.2 ELECTRICAL METALLIC TUBING (EMT) AND FITTINGS <br />A. MINIMUM SIZE ELECTRICAL METALLIC TUBING: 3/4 INCH, UNLESS OTHERWISE NOTED. <br />B. MANUFACTURERS OF EMT CONDUIT: <br />1. ALLIED <br />2. CALBOND CALPIPE <br />3. LTV <br />4. STEELDUCT <br />5. WHEATLAND TUBE CO <br />6. OR APPROVED EQUAL. <br />C.FITTINGS AND CONDUIT BODIES: <br />1. 2" DIAMETER OR SMALLER: STEEL SET SCREW TYPE OF STEEL DESIGNED FOR THEIR <br />SPECIFIC APPLICATION. <br />2. LARGER THAN 2": COMPRESSION TYPE OF STEEL DESIGNED FOR THEIR SPECIFIC <br />APPLICATION. <br />3. MANUFACTURERS OF EMT CONDUIT FITTINGS: <br />a. APPLETON ELECTRIC <br />b. O-Z/GEDNEY CO. <br />c. ELECTROLINE <br />d. RACO <br />e. BRIDGEPORT <br />f. MIDWEST <br />g. REGAL <br />h. THOMAS & BETTS <br />i. ORBIT INDUSTRIES <br />j. OR APPROVED EQUAL. <br />2.3 FLEXIBLE METALLIC CONDUIT (FMC) AND FITTINGS <br />A. MINIMUM SIZE GALVANIZED STEEL: 3/4 INCH, UNLESS OTHERWISE NOTED. LIGHTING BRANCH <br />CIRCUIT WIRING TO AN INDIVIDUAL LUMINAIRE MAY BE A MANUFACTURED, UL LISTED 1/2"" <br />FLEXIBLE METAL CONDUIT AND FITTINGS WITH #12 AWG THHN CONDUCTORS AND AN <br />INSULATED GROUND WIRE. MAXIMUM LENGTH OF 1/2" FMC SHALL BE SIX (6) FEET. <br />B. MANUFACTURERS: <br />1. AMERICAN FLEX <br />2. ALFLEX <br />3. ELECTRI-FLEX CO <br />4. OR APPROVED EQUAL. <br />C.CONSTRUCTION: FLEXIBLE STEEL, APPROVED FOR CONDUIT GROUND, ZINC COATED, <br /> THREADLESS TYPE FORMED FROM A CONTINUOUS LENGTH OF SPIRALLY WOUND, <br /> INTERLOCKED ZINC COATED STRIP STEEL. PROVIDE A SEPARATE EQUIPMENT GROUNDING <br /> CONDUCTOR WHEN USED FOR EQUIPMENT WHERE FLEXIBILITY IS REQUIRED. <br />D.FITTINGS AND CONDUIT BODIES: <br />1. THREADLESS HINGED CLAMP TYPE, GALVANIZED ZINC COATED CADMIUM PLATED <br />MALLEABLE CAST IRON. <br />2. FITTINGS AND CONDUIT BODIES SHALL INCLUDE PLASTIC OR CAST METAL INSERTS <br />SUPPLIED BY THE MANUFACTURER TO PROTECT CONDUCTORS FROM SHARP EDGES. <br />TO BE CONTINUE ON E0-04 <br />TE OLIRFFOAC <br />LANRP <br />E 23191 <br />STA <br />ER <br />REGIST <br />ED <br />INA <br />N <br />REENIGE <br />FO OISSE <br />E AICLCERTL <br />Exp. 06/30/26 <br />MIRASOPHOCLISGEORGY <br />IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, <br />TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING <br />AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND SHALL <br />NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE <br />EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. <br />©2022 IMEG CORP. <br />REF. SCALE IN INCHES <br />0 1 2 3 <br />The FUTURE. Built Smarter www.imegcorp.com <br />R <br />SHEET TITLE <br />PROJECT <br />FACILITY <br />FAC NO: BLDG NO: FLOOR LEV: SECTION: <br />KP PROJ. NO. <br />PERMIT NO. <br />555 W. 5th St Suite 2950 | Los Angeles, CA 90013 USA <br />Phone 310.820.4600 | Fax 310.207.4215 <br />www.huitt-zollars.com <br />ARCHITECT <br />CONSULTANT <br />ARCHITECT SEAL CONSULTANT SEAL <br />KAISER FOUNDATION <br />HOSPITALS NATIONAL <br />FACILITIES SERVICES 1800 <br />HARRISON STREET OAKLAND, <br />CALIFORNIA 94612 <br />ISSUE / REVISION LOG <br />NO. ISSUED DATE <br />0 <br />5' <br /> <br />5 <br />0 <br />' <br />GR <br />A <br />P <br />H <br />I <br />C <br /> <br />S <br />C <br />A <br />L <br />E <br />S <br />: <br /> <br />1 <br />/ <br />1 <br />6 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />0 <br />25 <br />' <br />1/ <br />8 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />5' <br />0 <br />12 <br />' <br />1/ <br />4 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />1' <br />0 <br />6' <br />1/ <br />2 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />1' <br />0 <br />2' <br />1- <br />1 <br />/ <br />2 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />0 <br />1' <br />3" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />IF <br /> <br />T <br />H <br />I <br />S <br /> <br />S <br />H <br />E <br />E <br />T <br /> <br />I <br />S <br /> <br />N <br />O <br />T <br /> <br />30 <br />" <br />x <br />4 <br />2 <br />" <br />, <br /> <br />I <br />T <br /> <br />I <br />S <br /> <br />A <br /> <br />R <br />E <br />D <br />U <br />C <br />E <br />D <br /> <br />PR <br />I <br />N <br />T <br /> <br />- <br /> <br />S <br />C <br />A <br />L <br />E <br /> <br />AC <br />C <br />O <br />R <br />D <br />I <br />N <br />G <br />L <br />Y <br />AGENCY APPLICATION NUMBER <br />AGENCY APPROVAL STAMP <br />THIS DOCUMENT IS THE PROPERTY OF THE OWNER AND IS <br />NOT TO BE USED WITHOUT OWNER'S WRITTEN PERMISSION. <br />HZ PROJ. NO. <br />222 S. HARBOR BOULEVARD, SUITE 800 I ANAHEIM, CA 92805 <br />PH: 714.490.5555 I FAX: 714.490.5560 <br />IMEG PROJ. NO.: 22008618.00 <br />PROJECT #22008618.00 <br />SOCC 2022 R HBM 1st Fl KPOJ <br />REMODEL <br />E0-03 <br />ELECTRICAL SPECIFICATION <br />CA394-1 <br />CAP0227721R314412.35 <br />HARBOR/MacARTHUR MEDICAL OFF <br />3401 S. HARBOR BLVD. <br />SANTA ANA, CALIFORNIA 92704 <br />CITY SUBMITTAL 11/03/2025 <br />1 CITY BACKCHECK #1 01/06/2026 <br />101125520, 20187249, 40140902 <br />555 W. Fifth Street Suite 2950 | Los Angeles, CA 90013 USA <br />ARCHITECT <br />www.huitt-zollars.com <br />Phone 310.820.4600 | Fax 310.207.4215