My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
505 E Central Ave #B - DEF 1 - Plan
PBA
>
Building
>
ProjectDox
>
C
>
Central Ave
>
505 E Central Ave Unit# B
>
505 E Central Ave #B - DEF 1 - Plan
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
2/24/2026 5:01:47 AM
Creation date
2/24/2026 5:00:42 AM
Metadata
Fields
Template:
Plan
Permit Number
20181754
30146722
40138703
101117766
101124090
Full Address
505 E Central Ave Unit# B
Street Number
505
Street Direction
E
Street Name
Central
Street Suffix
Ave
Unit Number
B
Document Relationships
101117766 - Permit
(Permit - Plan)
Path:
\Building\Permits\C\Central Ave\505 E Central Ave Unit# B
101124090 - Permit
(Permit - Plan)
Path:
\Building\Permits\C\Central Ave\505 E Central Ave Unit# B
20181754 - Permit
(Permit - Plan)
Path:
\Building\Permits\C\Central Ave\505 E Central Ave Unit# B
30146722 - Permit
(Permit - Plan)
Path:
\Building\Permits\C\Central Ave\505 E Central Ave Unit# B
40138703 - Permit
(Permit - Plan)
Path:
\Building\Permits\C\Central Ave\505 E Central Ave Unit# B
Jump to thumbnail
< previous set
next set >
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
994
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
Show annotations
View images
View plain text
CITY OF SANTA ANA <br />SPECIFICATIONS <br />PROJECT NO.: XX-XXXX <br />PROJECT TITLE <br /> <br />208 <br />Switches shall be 20A-AC. Specification grade equal to AH-1991-1. Provide <br />stainless steel cover in switchboard. Mount switch separate from panel front. <br />Hand-off auto switches shall be SPDT and be heavy duty oil light with contacts open <br />in center position and one pair closed in left position and other pair closed in rigid <br />position. Switches shall be equal to Square D Class 9001-Type T and K. Provide <br />legend plate and nameplate. <br />G. PANEL BOARDS <br />Branch circuit panelboards shall be of the dead front safety type equipped with <br />thermal magnetic bolt-on Type 40 degrees C circuit breakers. Bus shall be copper. <br />Circuit breakers shall be rated for interrupting capacity as noted on the drawings or as <br />required and shall be the number of poles and current capacity as indicated on the <br />panel schedule. Branch circuit panelboards shall be Square "“"”or approved equal <br />with separate isolated ground bus, Type NQO or NEHB. All breakers shall be <br />lockable in “OFF” position. Trims shall have doors equipped with flush type <br />combination lock and catch, two milled type keys supplied with each panel. All locks <br />shall be alike and each door shall have a plastic covered directory frame with a typed <br />identification card of all circuit and panel numbers for branch circuit panelboards and <br />engraved lamicoid nameplates for power distribution panelboards. <br />Provide nameplates for all panelboards, 1/8” thick, micarta or phenolic plate of <br />approved size, with beveled edges and engraved white letters on black background <br />and laced together. Wireways shall be 4” sides and 5-3/4” top and bottom. <br />All circuit breakers shall conform to Federal Specifications W-C-375, Class 2b or 2c <br />for 120/240 volt and shall be provided with a device for locking circuit breaker in <br />“OFF” position. <br />H. CONTACTORS AND RELAYS <br />Contactors shall be designed for 600 volts AC mechanically or electrically held as <br />noted and be rated for tungsten, mercury arc or other reactive lighting loads and shall <br />be equal to Square D-Type M. Clas 8903 in NEMA 1 housing. <br />Electrically held coil voltage as noted. <br />Relays shall be 120-v AC coil, 10 amp contacts housed in NEMA 1 housing. Relays <br />shall be of the latching where noted. Relays shall be equal to Square D Class. <br />I. LIGHT FIXTURES <br />Light fixtures shall be as noted on plans. <br />505 E Central Ave <br />#B11/6/2024
The URL can be used to link to this page
Your browser does not support the video tag.