GENERAL NOTES: <br />A.ALL EQUIPMENT SHOWN IN THE SINGLE LINE DIAGRAM ARE NEW U.O.N. <br />B.ALL EQUIPMENT AND DEVICES OUTDOOR SHALL BE NEMA 3R RATED AND WEATHER <br />PROOF. <br />C.ALL OVERCURRENT DEVICES IN AN INDIVIDUAL PIECE OF EQUIPMENT SHALL HAVE <br />AN AIC RATING EQUAL TO THE OVERALL RATING OF THE EQUIPMENT-SERIES <br />RATING OF DEVICES WITHIN A PIECE OF EQUIPMENT IS NOT ALLOWED. <br />D.ALL TERMINATIONS AND ENCLOSURES SHALL BE RATED FOR USE WITH 75 DEGREE <br />CELSIUS CONDUCTORS. <br />E.ALLOWABLE DIMENSIONS IN MAIN ELECTRICAL ROOM ARE A CRITICAL <br />COORDINATION ITEM. CONTRACTOR SHALL PROVIDE 1/4"= 1'-0" SCALE DRAWINGS <br />WITH SWITCHGEAR SUBMITTALS SHOWING THAT ALL PROPOSED EQUIPMENT WILL <br />FIT IN THE SPACE PROVIDED. SUBMITTALS WITHOUT THIS DRAWING SHALL BE <br />REJECTED AS INCOMPLETE. <br />F.WHERE REQUIRED BY THE LOCAL AUTHORITY HAVING JURISDICTION OR WHERE A <br />NEW GROUND FAULT PROTECTIVE DEVICE IS BEING INSTALLED, A GROUND FAULT <br />SYSTEM TEST SHALL BE CONDUCTED BY AN INDEPENDENT TESTING AGENCY PER <br />NEC (OR CEC-WHERE ADOPTED) 230.95(C) . THE GROUND FAULT SYSTEM TEST <br />SHALL BE PERFORMED IN THE PRESENCE OF THE LOCAL AUTHORITY HAVING <br />JURISDICTION. VERIFICATION OF DEVICE SETTINGS PER THE POWER SYSTEMS <br />STUDY SPECIFICATION SHALL BE PERFORMED BY THE SAME INDEPENDENT <br />TESTING AGENCY. THE GROUND FAULT TEST RESULTS SHALL BE DELIVERED TO <br />THE ENGINEER OF RECORD. <br />G.EACH FEEDER AND BRANCH CIRCUITS SHALL BE COPPER AND IN RIGID CONDUIT <br />U.O.N. <br />H.EACH 120V BRANCH CIRCUIT SHALL BE PROVIDED WITH A NEUTRAL WIRE. DO NOT <br />SHARE NEUTRAL WIRE. <br />I.MAIN SWITCHBOARD, DISTRIBUTION BOARD AND PANEL BOARDS SHALL BE <br />PROVIDED WITH AT LEAST 20% SPARE OR SPACE CIRCUIT AND CAPACITY FOR <br />FUTURE USE OF THE PROJECT. <br />J.EACH CIRCUIT BREAKERS SHALL HAVE AIC RATINGS THAT, AT MINIMUM, MATCH OR <br />ARE GREATER THAN THE AIC RATING FOR THE NEAREST & HIGHEST-RATED <br />UPSTREAM/LINE SIDE OVERCURRENT PROTECTIVE DEVICE (PREFERRED OR <br />ALTERNATE SOURCE). SERIES RATING WITH UPSTREAM DEVICES IS NOT ALLOWED. <br />CIRCUIT BREAKERS UTILIZED FOR MSS UNITS SHALL BE FROM THE SAME <br />MANUFACTURER AS THE BALANCE OF THE PROJECT'S ELECTRICAL DISTRIBUTION <br />EQUIPMENT. <br />K.ALL ELECTRICAL EQUIPMENT AND MATERIALS SHALL BE LISTED, LABELED AND <br />APPROVED BY A DULY AUTHORIZED ELECTRICAL TESTING AGENCY. <br />L.NO PIPING, DUCTS OR EQUIPMENT FOREIGN TO ELECTRICAL EQUIPMENT SHALL BE <br />PERMITTED TO BE LOCATED WITHIN DEDICATED SPACE ABOVE THE ELECTRICAL <br />EQUIPMENT AS REQUIRED. <br />M.PROVIDE AND MAINTAIN REQUIRED WORK SPACE, ADEQUATE ILLUMINATION, <br />ACCESS TO WORK SPACE AND HEAD ROOM ABOVE ELECTRICAL EQUIPMENT AND <br />DEDICATED SPACE AS OF ELECTRICAL EQUIPMENT. <br />N.PROVIDE PERMANENT ENGRAVED LABEL TO EACH NEW BOARD, DISCONNECT & <br />PANEL BOARDS. <br />O.ALL CONDUIT STUBS SHALL BE FIELD COORDINATED WITH EQUIPMENT <br />INSTALLATION MANUALS PRIOR TO ANY ROUGH-INS. <br />P.CONTRACTOR TO CHECK EQUIPMENT LANDING LUGS AND PROVIDE REQUIRED LUG <br />SIZE TO ACCOMMODATE SPECIFIED WIRE SIZE PER FEEDER SCHEDULE. <br />CONTRACTOR TO FIELD COORDINATE. <br />Q.ALL ELECTRICAL WORK RELATED UTILITY SHALL BE PER UTILITY COMPANY <br />STANDARDS AND SPECIFICATIONS. CONTRACTOR TO FIELD COORDINATE WITH <br />UTILITY COMPANY FOR A SET OF APPROVED ELECTRICAL UTILITY DESIGN <br />DRAWINGS AND SPECIFICATIONS. CONTRACTOR TO FIELD COORDINATE FOR ALL <br />REQUIRED INSPECTIONS BY SERVING UTILITY COMPANY. <br />R.PROVIDE PULL BOX SIZED PER CODE AS REQUIRED. <br />S.VERIFY ALL DISTANCES IN THE FIELD. CONTRACTOR TO FIELD MEASURE THE EXACT <br />LOCATION AND DISTANCES OF EACH FEEDERS FROM THE MAIN SWITCHBOARD TO <br />EACH NEW PANEL LOCATION. <br />G.EACH SERVICE EQUIPMENT (SWITCHBOARD, PANELBOARDS, ETC.) SHALL BE <br />LABELED WITH AN NEC, OR CEC WHERE ADOPTED, 110.16 COMPLIANT ARC FLASH <br />HAZARD WARNING (BRADY LABEL #94913 GENERIC ARC FLASH LABEL). <br />1 <br />KEY NOTES: <br />PROVIDE NEW PANEL 200A,120/208V, 3Ø, 4 WIRE. <br />VERIFY EXACT LOCATION IN THE FIELD. <br />REFER TO SHEET E5.02 DETAIL 10 & 11 FOR COMPLETE <br />GROUNDING SYSTEM REQUIREMENT. <br />PROVIDE 2-4" CONDUIT PER POWER COMPANY STANDARD AND <br />REQUIREMENT.VERIFY AND COORDINATE WITH POWER COMPANY FINAL <br />CONSTRUCTION DRAWING <br />PROVIDE SHUNT TRIP TYPE CIRCUIT BREAKER AND INTEGRATE WITH FIRE <br />SUPRESSION SYSTEM. <br />1 SCALE: NTS <br />SINGLE LINE DIAGRAM <br />TO POWER COMPANY <br />POINT OF CONNECTION <br />NEW MSB 600A, 120/208V, 3Ø, 4W <br />200A <br />3P <br />N <br />G <br />600A <br />3P <br />MAIN <br />PANEL <br />"L" <br />SPARE SPARE SPARE <br />600A BUS, 120/208V, 3Ø, 4W <br />M <br />1 <br />PANEL <br />"P" <br />PANEL <br />"K" <br />200A <br />3P <br />200A <br />3P <br />2 <br />3 <br />Scale <br />Date <br />Drawn By <br />Checked By <br />Project Number <br />14 <br />3 <br />0 <br /> <br />E <br /> <br />E <br />D <br />I <br />N <br />G <br />E <br />R <br /> <br />A <br />V <br />E <br />, <br /> <br />S <br />A <br />N <br />T <br />A <br /> <br />A <br />N <br />A <br />, <br /> <br />C <br />A <br /> <br />9 <br />2 <br />7 <br />0 <br />5 <br />NOVUM <br />A R C H I T E C T U R E, Inc <br />www.novumarchitecture.com <br />OFFICES: SOUTH BAY / ORANGE COUNTY <br />116 S CATALINA AVE. STE. 122, <br />REDONDO BEACH, CA 90277 <br />TEL: 310-383-1827 / 310-709-4476 <br />N <br />AS SHOWN <br />TO <br />M <br />' <br />S <br /> <br />J <br />R <br />CAD <br />Author <br />9-1-2023 <br />tom's2023 <br />Mr <br />. <br /> <br />S <br />p <br />i <br />r <br />o <br />s <br /> <br />P <br />o <br />l <br />i <br />t <br />i <br />s <br />No.Description Date <br />1 PC Comments 08/08/2024 <br />2 HlthDep.Corr.2 09/03/2024 <br />SINGLE LINE <br />DIAGRAM <br />E-103 <br />200A <br />3P <br />SCE SERVICE REQUEST#3574717 <br />200A <br />3P <br />200A <br />3P <br />11 <br />204 204 204 <br />3 <br />2 <br />FEEDER SCHEDULE - CU <br />FOUR WIRE FEEDERS <br />FEEDER TAG CONDUIT CONDUCTORS <br />QTY SIZE QTY SIZE GND <br />024 1 EA 3/4"4 EA 12 12 <br />034 1 EA 3/4"4 EA 10 10 <br />044 1 EA 1"4 EA 8 10 <br />054 1 EA 1 1/4"4 EA 6 10 <br />064 1 EA 1 1/4"4 EA 4 10 <br />074 1 EA 1 1/4"4 EA 4 8 <br />084 1 EA 1 1/2"4 EA 2 8 <br />094 1 EA 1 1/2"4 EA 2 8 <br />104 1 EA 2"4 EA 1 8 <br />114 1 EA 2"4 EA 1 6 <br />123 1 EA 2"4 EA 1/0 6 <br />154 1 EA 2"4 EA 1/0 6 <br />174 1 EA 2"4 EA 2/0 6 <br />204 1 EA 2 1/2"4 EA 3/0 6 <br />224 1 EA 2 1/2"4 EA 4/0 4 <br />254 1 EA 3"4 EA 250 4 <br />304 1 EA 3"4 EA 350 4 <br />354 1 EA 3 1/2"4 EA 500 3 <br />404 1 EA 4"4 EA 600 3 <br />454 2 EA 2 1/2"4 EA 4/0 2 <br />504 2 EA 3"4 EA 250 2 <br />604 2 EA 3"4 EA 350 1 <br />704 2 EA 3 1/2"4 EA 500 1/0 <br />804 2 EA 3 1/2"4 EA 500 1/0 <br />1004 3 EA 3 1/2"4 EA 400 2/0 <br />1204 3 EA 4"4 EA 600 3/0 <br />1604 4 EA 4"4 EA 600 4/0 <br />2004 5 EA 4"4 EA 600 250 <br />2504 6 EA 4"4 EA 600 350 <br />3004 8 EA 4"4 EA 500 400 <br />4004 10 EA 4"4 EA 600 500 <br />3 SCALE: NTS <br />SHORT CIRCUIT AND VOLTAGE DROP ANALYSIS <br />3 SCALE: NTS <br />FEEDER SCHEDULE <br />4 <br />44 <br />1430 E Edinger Ave <br />3/27/2025