ANNOTATIONS
<br />A-1&3&5
<br />A-1,3
<br />TELEPHONE OUTLET BOX, CEILING MOUNTED
<br />COMBINATION TELEPHONE AND DATA OUTLET BOX FLUSH MOUNTED IN CEILING
<br />PB
<br />a,bC
<br />B
<br />A
<br />UTILITY COMPANY METER. PROVIDE "CT's" AND "PT's" AS REQUIRED, REFER TO SINGLE LINE
<br />DIAGRAM.
<br />NON-FUSED DISCONNECT SWITCH, HP RATED AND WEATHERPROOF AS REQUIRED. PROVIDE
<br />FINAL CONNECTION TO UNIT EQUIPMENT. SEE MOTORIZED EQUIPMENT SCHEDULE FOR
<br />DISCONNECT SIZES.
<br />FUSED DISCONNECT SWITCH, HP RATED, OR COMBINATION MOTOR STARTER/DISCONNECT
<br />SWITCH WITH FUSES PER EQUIPMENT MANUFACTURER AND WEATHERPROOF AS REQUIRED.
<br />PROVIDE FINAL CONNECTION TO UNIT EQUIPMENT. SEE MOTORIZED EQUIPMENT SCHEDULE
<br />FOR DISCONNECT AND STARTER SIZES.
<br />DUPLEX RECEPTACLE, WALL MOUNTED +18" AFF OR AS NOTED.
<br />DOUBLE DUPLEX RECEPTACLE, WALL MOUNTED +18" AFF OR AS NOTED.
<br />DUPLEX, GFCI RECEPTACLE, WALL MOUNTED +18" AFF OR AS NOTED. WP INDICATES
<br />WEATHERPROOF.
<br />DOUBLE DUPLEX, GFCI RECEPTACLE, WALL MOUNTED. WP INDICATES WEATHERPROOF.
<br />DUPLEX RECEPTACLE, ONE HALF SWITCHED, WALL MOUNTED +18" AFF OR AS NOTED.
<br />DUPLEX, ISOLATED GROUND RECEPTACLE, WALL MOUNTED +18" AFF OR AS NOTED.
<br />SIMPLEX RECEPTACLE, WALL MOUNTED +18" AFF OR AS NOTED.
<br />JUNCTION BOX, WALL MOUNTED AT +18" A.F.F. OR AS NOTED. 4S/DP MINIMUM OR AS
<br />REQUIRED BY N.E.C..
<br />JUNCTION BOX, MOUNTED IN ACCESSIBLE CEILING FOR APPLICATION DENOTED ON PLAN.
<br />4S/DP MINIMUM OR AS REQUIRED BY N.E.C..
<br />JUNCTION BOX, WALL MOUNTED AT 6" ABOVE COUNTER OR SPLASH. 4S/DP MINIMUM OR AS
<br />REQUIRED BY N.E.C..
<br />THERMOSTAT OUTLET BOX, PROVIDE 1/2"C.O. TO RESPECTIVE MECHANICAL UNIT.
<br />EXHAUST FAN, OR MOTOR LOAD. REFER TO MECHANICAL, PLUMBING OR KITCHEN DRAWINGS
<br />FOR SPECIFIC LOAD REQUIREMENTS OR AS NOTED.
<br />TRANSFORMER, REFER TO SINGLE LINE DIAGRAM.
<br />DENOTES TWO SINGLE PHASE CIRCUITS WITH SEPARATE NEUTRAL WIRE. 3/4"
<br />CONDUIT- 4#12 + 1/#12 GRD
<br />REFER TO DERATING TABLE.
<br />CONCEALED CONDUIT OR BRANCH CIRCUIT UNLESS OTHERWISE NOTED. 3/4"
<br />CONDUIT MINIMUM, 2 #12 +1#12 GRD CONDUCTORS MINIMUM.
<br />CONDUIT OR BRANCH CIRCUIT CONCEALED BELOW GRADE, 3/4" CONDUIT MINIMUM
<br />WITH (2) 12 AWG CONDUCTORS MINIMUM AND A CODE SIZED EQUIPMENT GROUND.
<br />CIRCUIT BREAKER: "A" REPRESENTS CIRCUIT BREAKER AMPERE RATING, "B" REPRESENTS
<br />NUMBER OF POLES AND "C" REPRESENTS MISCELLANEOUS BREAKER FEATURES.
<br />FUSIBLE SWITCH: "A" REPRESENTS SWITCH / FRAME AMPERE RATING, "B"
<br />REPRESENTS THE FUSE AMPERE RATING, "C" INDICATES NUMBER OF POLES AND "D"
<br />REPRESENTS MISCELLANEOUS FUSE / SWITCH FEATURES.
<br />SINGLE POLE SWITCHES, WALL MOUNTED. SUBSCRIPTS AT SYMBOL INDICATE THE
<br />FOLLOWING:
<br />NOTE: ALL WALL SWITCHES CONTROLLING EMERGENCY CIRCUITS SHALL BE
<br />ENGRAVED WITH "EMERGENCY".
<br />EMERGENCY POWER OFF STATION, WALL MOUNTED PER EPO SYSTEM DETAIL.
<br />PULLBOX, SIZED PER N.E.C. OR AS NOTED.
<br />GROUND CONNECTION, SIZE AS INDICATED AND REQUIRED.
<br />CONDUIT STUB OUT, CAP, MARK AND RECORD ON AS-BUILT DRAWINGS
<br />CONDUIT CONTINUATION.
<br />CONDUIT STUB DOWN
<br />CONDUIT STUB UP
<br />TV OUTLET, WALL MOUNTED. STUB A 3/4"C.O. UP 6" ABOVE THE ACCESSIBLE CEILING AND
<br />PROVIDE BUSHING.
<br />MECHANICAL EQUIPMENT CALLOUT, "AC" INDICATES UNIT TYPE AND "2" INDICATES UNIT
<br />NUMBER. REFER TO MECHANICAL DRAWINGS FOR EXACT LOCATION AND ELECTRICAL
<br />REQUIREMENTS.
<br />DETAIL CALLOUT, "3" INDICATES DETAIL NUMBER "E-1" INDICATES SHEET NUMBER.
<br />PLAN NOTE REFERENCE, REFER TO NOTES ON SHEET, OR AS DIRECTED.
<br />REVISION REFERENCE.
<br />WYE CONFIGURATION DELTA CONFIGURATION GROUND
<br />TELEPHONE OUTLET BOX, WALL MOUNTED. STUB A 1" C.O. UP 6" ABOVE THE ACCESSIBLE
<br />CEILING AND PROVIDE A BUSHING. 4S/DP MINIMUM WITH SINGLE GANG RING.
<br />DATA OUTLET BOX, WALL MOUNTED. STUB A 1" C.O. UP 6" ABOVE THE ACCESSIBLE
<br />CEILING AND PROVIDE A BUSHING. 4S/DP MINIMUM WITH SINGLE GANG RING.
<br />COMBINATION TELEPHONE AND DATA OUTLET BOX, WALL MOUNTED. STUB A 1" C.O.
<br />UP 6" ABOVE THE ACCESSIBLE CEILING AND PROVIDE A BUSHING. 4S/DP MINIMUM
<br />WITH SINGLE GANG RING.
<br />FLUSH MOUNTED, LOCKABLE TERMINAL CABINET WITH TERMINAL STRIPS AS REQUIRED.
<br />SURFACE MOUNTED, LOCKABLE TERMINAL CABINET WITH TERMINAL STRIPS AS REQUIRED.
<br />TELEPHONE TERMINAL BACKBOARD SIZED AS NOTED, REFER TO SYSTEM GROUND DETAIL.
<br />J
<br />J
<br />J
<br />T
<br />T
<br />TV
<br />2
<br />4
<br />3
<br />E-1
<br />AC
<br />2
<br />A
<br />S
<br />M
<br />F
<br />ELECTRICAL SYMBOL LISTS
<br />A-1
<br />DENOTES 120V OR 277V CIRCUIT WITH NEUTRAL WIRE. 3/4" CONDUIT- 2/#12 + 1/#12
<br />GRD MIN.
<br />DENOTES THREE PHASE CIRCUIT NO NEUTRAL WIRE. 3/4" CONDUIT- 3#12 + 1/#12 GRD
<br />A-1&3
<br />DENOTES SINGLE PHASE CIRCUIT NO NEUTRAL WIRE. 3/4" CONDUIT- 2#12 + 1/#12 GRD
<br />DATA OUTLET BOX, CEILING MOUNTED
<br />TELEPHONE OUTLET BOX, FLUSH MOUNTED IN FLOOR
<br />COMBINATION TELEPHONE AND DATA OUTLET BOX FLUSH MOUNTED IN FLOOR
<br />DATA OUTLET BOX, FLUSH MOUNTED IN FLOOR
<br />SYMBOL INDICATES MOUNTED FLUSH ON FLOOR
<br />SYMBOL INDICATES CEILING MOUNTED
<br />IG
<br />ASTRONOMICAL TIME CLOCK.TC
<br />EXIT SIGN. ARROW AND SHADE DENOTES DIRECTION. REFER TO EMERGENCY SYSTEM
<br />FOR CIRCUITING.
<br />POLE LIGHT. REFER TO STRUCTURAL PLANS FOR POLE BASE REQUIREMENT AND
<br />SPECIFICATION.
<br />EMERGENCY BUG EYE. PROVIDE MINIMUM 90 MIN BACK-UP BATTERY
<br />SURFACE DOWNLIGHT. HATCH INDICATES ON EMERGENCY. PROVIDE 90 MIN BATTERY
<br />PACK OR EMERGENCY CIRCUIT CONNECTION. REFER TO EMERGENCY SYSTEM FOR
<br />EXACT REQUIREMENT.
<br />NORMAL POWER SURFACE MOUNTED STRIP LIGHT
<br />RECESSED DOWNLIGHT. HATCH INDICATES ON EMERGENCY. PROVIDE 90 MIN
<br />BATTERY PACK OR EMERGENCY CIRCUIT CONNECTION. REFER TO EMERGENCY
<br />SYSTEM FOR EXACT REQUIREMENT.
<br />1X4 LED STRIP LIGHT. DOUBLE LINE DENOTES RECESSED MOUNTED.
<br />HATCH DENOTES EMERGENCY POWER. PROVIDE 90 MIN BATTERY PACK OR ON
<br />EMERGENCY CIRCUIT CONNECTION. REFER TO EMERGENCY SYSTEM FOR EXACT
<br />REQUIREMENT.
<br />LV CAMERA. PROVIDE DEDICATED CAT 6 CABLE PER CAMERA. MAXIMUM CABLE
<br />LENGTH SHALL BE 225'-0"
<br />SD SMOKE DETECTOR. PROVIDE LOCK-ON DEVICE IN PANEL BREAKER.
<br />DEDICATED 208/240V OUTLET SINGLE PHASE 2 POLE. VERIFY NEUTRAL WIRE REQUIREMENT
<br />WITH EQUIPMENT SUBMITTAL
<br />DENOTES EQUIPMENT NUMBER. REFER TO EQUIPMENT SCHEDULE FOR DETAILS
<br />MSB SWITCHBOARD/DISTRIBUTION BOARD TAG, "MSB" INDICATES EQUIPMENT DESIGNATION.
<br />PANEL TAG, "A" INDICATES PANELBOARD OR EQUIPMENT DESIGNATION.
<br />1
<br />WALL MOUNTED OCCUPANCY SENSOR LOWER CASE LETTERS INDICATES SWITCH LEG
<br />CEILING MOUNTED OCCUPANCY SENSOR LOWER CASE LETTERS INDICATES SWITCH LEG
<br />PCI CEILING MOUNTED DAYLITE PHOTOCELL CONTROL.
<br />4S/DP 4" SQUARE BY 2-1/8" DEEP BOX
<br />ADA AMERICAN WITH DISABILITIES ACT
<br />A.F.F. ABOVE FINISH FLOOR
<br />A.F.G. ABOVE FINISH GRADE
<br />AWG AMERICAN WIRE GAUGE
<br />AMP AMPERE
<br />A.I.C.AMPERES INTERRUPTING CAPACITY
<br />AF/AT AMP FRAME, AMP TRIP
<br />AHJ AUTHORITY HAVING JURISDICTION
<br />AS/AF AMPERE SWITCH, AMPERE FUSE
<br />ATS AUTOMATIC TRANSFER SWITCH
<br />AVG AVERAGE
<br />BR BRANCH
<br />BLDG BUILDING
<br />CBC CALIFORNIA BUILDING CODE
<br />CEC CALIFORNIA ELECTRICAL CODE
<br />CIRC CIRCUIT
<br />CKT. CB CIRCUIT BREAKER
<br />CSFD COMBINATION SMOKE FIRE DAMPER
<br />C CONDUIT
<br />C.O. CONDUIT ONLY, COMPLETE WITH PULLSTRING
<br />CONN CONNECTED
<br />CT CURRENT TRANSFORMER
<br />(D)EXISTING DEVICE TO BE DEMOLISHED.
<br />DIA DIAMETER
<br />DISC DISCONNECT
<br />DIST DISTRIBUTION
<br />E.C.ELECTRICAL CONTRACTOR
<br />EMS ENERGY MANAGEMENT CONTROL SYSTEM
<br />EMT ELECTRICAL METALLIC TUBING
<br />ENT ELECTRICAL NON-METALLIC TUBING
<br />EWC ELECTRIC WATER COOLER
<br />EPO EMERGENCY POWER OFF
<br />EOL END OF LINE CIRCUIT TERMINATOR
<br />EF EXHAUST FAN
<br />E, (E) EXISTING DEVICE TO REMAIN
<br />EP EXPLOSION PROOF
<br />(ER)EXISTING DEVICE TO BE RELOCATED
<br />FT or 'FEET
<br />FA FIRE ALARM
<br />FLA FULL LOAD AMPS
<br />GRD GROUND
<br />GFCI GROUND FAULT CIRCUIT INTERRUPTER
<br />GFP GROUND FAULT PROTECTION
<br />GEC GROUNDING ELECTRODE CONDUCTOR
<br />HACR HEATING AIR CONDITIONING REFRIGERATION
<br />HOA HAND-OFF-AUTO
<br />HVAC HEATING, VENTILATING AND AIR CONDITIONING
<br />H.,W.,D.,L.HEIGHT, WIDTH, DEPTH, LENGTH
<br />HP HORSEPOWER
<br />HPS HIGH PRESSURE SODIUM
<br />IN.or ''INCHES
<br />I/G ISOLATED GROUND
<br />IBC INTERNATIONAL BUILDING CODE
<br />JBOX JUNCTION BOX
<br />K DEGREE KELVIN
<br />KCMIL THOUSAND CIRCULAR MILS
<br />KVA KILOVOLT AMPERES
<br />KW KILOWATT
<br />KWH KILOWATT HOUR
<br />LCL LONG CONTINUOUS LOAD
<br />L.F LINEAR FEET
<br />LTG LIGHTING
<br />MAX.MAXIMUM
<br />MCB MAIN CIRCUIT BREAKER
<br />MLO MAIN LUGS ONLY
<br />MCB MECHANICAL CONTRACTOR
<br />M METER
<br />M/M METER MAIN
<br />MIN.MINIMUM
<br />MCA MINIMUM CIRCUIT AMPS
<br />MCC MOTOR CONTROL CENTER
<br />MCM THOUSAND CIRCULAR MILS
<br />MCP MOTOR CIRCUIT PROTECTOR
<br />MFR MANUFACTURER
<br />MTD MOUNTED
<br />MW MICROWAVE
<br />NATS NON AUTOMATIC DISCONNECT
<br />NEC NATIONAL ELECTRICAL CODE
<br />NEMA NATIONAL ELECTRICAL MANUFACTURERS'
<br />ASSOCIATION
<br />NC NORMALLY CLOSED
<br />NO NORMALLY OPENED
<br />NF NON-FUSED
<br />NIC NOT IN CONTRACT
<br />N.T.S.NOT TO SCALE
<br />NL NIGHT LIGHT
<br />NO.or #NUMBER
<br />OFCI OWNER FURNISHED, CONTRACTOR
<br />INSTALLED
<br />%Z PERCENT IMPEDANCE
<br />PH.or ø PHASE
<br />PC PHOTOCELL
<br />P.C.A PLUMBING CONTRACTOR
<br />P POLE
<br />PVC POLY VINYL CHLORIDE
<br />PDU POWER DISTRIBUTION UNIT
<br />PT POTENTIAL TRANSFORMER
<br />PA PUBLIC ADDRESS
<br />(R)DENOTES RELOCATED DEVICE LOCATION.
<br />REC, RECEPT RECEPTACLE
<br />REF REFRIGERATOR
<br />RGS RIGID GALVANIZED STEEL
<br />RMS ROOT MEAN SQUARE
<br />SCC SHORT CIRCUIT CURRENT
<br />SCS STRUCTURED CABLING SYSTEM
<br />SFD SMOKE FIRE DAMPER
<br />TC TIMECLOCK
<br />TEL/DATA TELEPHONE AND DATA
<br />TV TELEVISION
<br />T.V..S.TRANSIENT VOLTAGE SURGE
<br />SUPPRESSION
<br />TYP TYPICAL
<br />TTB TELEPHONE TERMINAL BOARD
<br />U.G.P.S.UNDERGROUND PULL SECTION
<br />U.O.N.UNLESS OTHERWISE NOTED
<br />U.P.S.UNINTERRUPTABLE POWER SYSTEM
<br />VAV VARIABLE AIR VOLUME
<br />V VOLTS
<br />VA VOLT AMPERES
<br />VD VOLTAGE DROP
<br />VL VERIFY EXACT LOCATION IN
<br />FIELD/OWNER/ARCHITECT AND OTHER
<br />TRADE
<br />WP WEATHERPROOF
<br />W WIRE
<br />XFMR TRANSFORMER
<br />ABBREVIATIONS BRANCH CIRCUIT SYMBOLS
<br />C
<br />B
<br />A
<br />D
<br />SHUNT= PROVIDE SHUNT TRIP MECHANISM
<br />HACR= PROVIDE HACR-RATED BREAKER
<br />GFP= GROUND FAULT PROTECTION
<br />CLCB= CURRENT LIMITING CIRCUIT BREAKER
<br />SS= PROVIDE SOLID STATE CIRCUIT BREAKER
<br />LO= PROVIDE PERMANENT LOCK-OPEN (OFF) HARDWARE
<br />LC= PROVIDE PERMANENT LOCK-CLOSED (ON) HARDWARE
<br />SHUNT= PROVIDE SHUNT TRIP MECHANISM
<br />GFP= GROUND FAULT PROTECTION
<br />CLF= CURRENT LIMITING FUSE
<br />D - DIMMER
<br />LV - LOW VOLTAGE
<br />VC - VACANCY SENSOR
<br />M - MOTOR RATED
<br />OS - OCCUPANCY SENSOR
<br />K - KEY OPERATED
<br />4 - FOUR WAY
<br />3 - THREE WAY
<br />2 - DOUBLE POLE
<br />a,b. - DENOTES SWITCH LEG.
<br />LIGHTING
<br />TELEPHONE/DATA
<br />POWER
<br />2X4 LED LIGHT.
<br />DOUBLE LINE DENOTES RECESSED MOUNTED.
<br />HATCH DENOTES EMERGENCY POWER. PROVIDE 90 MIN BATTERY PACK OR ON
<br />EMERGENCY CIRCUIT CONNECTION. REFER TO EMERGENCY SYSTEM FOR EXACT
<br />REQUIREMENT.
<br />Scale
<br />Date
<br />Drawn By
<br />Checked By
<br />Project Number
<br />14
<br />3
<br />0
<br />
<br />E
<br />
<br />E
<br />D
<br />I
<br />N
<br />G
<br />E
<br />R
<br />
<br />A
<br />V
<br />E
<br />,
<br />
<br />S
<br />A
<br />N
<br />T
<br />A
<br />
<br />A
<br />N
<br />A
<br />,
<br />
<br />C
<br />A
<br />
<br />9
<br />2
<br />7
<br />0
<br />5
<br />NOVUM
<br />A R C H I T E C T U R E, Inc
<br />www.novumarchitecture.com
<br />OFFICES: SOUTH BAY / ORANGE COUNTY
<br />116 S CATALINA AVE. STE. 122,
<br />REDONDO BEACH, CA 90277
<br />TEL: 310-383-1827 / 310-709-4476
<br />N
<br />AS SHOWN
<br />TO
<br />M
<br />'
<br />S
<br />
<br />J
<br />R
<br />CAD
<br />Author
<br />9-1-2023
<br />tom's2023
<br />Mr
<br />.
<br />
<br />S
<br />p
<br />i
<br />r
<br />o
<br />s
<br />
<br />P
<br />o
<br />l
<br />i
<br />t
<br />i
<br />s
<br />No.Description Date
<br />1 PC Comments 08/08/2024
<br />2 HlthDep.Corr.2 09/03/2024
<br />SYMBOLS LIST &
<br />ABBREVIATIONS
<br />E-102
<br />1430 E Edinger Ave
<br />3/27/2025
|