Laserfiche WebLink
FACILITY  <br />GROUND <br />120/240 VAC <br />SINGLE PHASE <br />SERVICE  <br />EXISTING 225A <br />MAIN <br />BREAKER  <br />-END FED <br />EXISTING 225A <br />MAIN PANEL <br />225A  BUS <br />(E) FACILITY  <br />LOADS <br />M <br />  125A  <br />NEW 200A <br />BACKUP GATEWAY 3  <br />(1841000-X1-Y) <br />(N) INTERNAL PANELBOARD <br />WITH(1) 60A PV+ESS BREAKER <br />4 <br />A <br />A <br />NEW 225 A BACKUP <br />LOADS PANEL WITH  <br />125 A MAIN BREAKER <br />RELOCATED (E) LOADS <br />4 <br />60A <br />(N) IMO PE69-3020,  <br />DISCONNECT  <br />SWITCH, 3P, 16A <br />INVERTER: TESLA <br />POWERWALL 3 1707000-XX-Y, <br />ENERGY STORAGE: <br />TESLA:POWERWALL 3 <br />1707000-XX-Y 11500 WATT INVERTER <br />LOAD RATED DC DISCONNECT <br />WITH AFCI RAPID SHUTDOWN COMPLIANT, <br />POWER CONTROL SYSTEM <br />3 <br />J-BOX <br />12 <br />222012-776623 <br />CHARACTERISTICS INCLUDED IN SPEC SHEETS <br />INTERCONNECTION CALCULATIONS <br />(N)TESLA REMOTE METER <br />SITE  CURRENT <br />TRANSFORMER <br />13 SILFAB <br />SIL-440QD <br />STRING 1 WITH 13 MODULES <br />WITH 5 MCI COUNT , MODULE  <br />LEVEL RAPID SHUTDOWN  <br />DEVICES <br />(N) LOCKABLE <br />BLADE TYPE <br />AC DISCONNECT <br />SQUARE D <br />DU222RB <br />3R, 60A, 2P <br />120/240VAC <br />3 <br />5 <br />CONDUIT SCHEDULE <br />TAG CIRCUIT DESCRIPTION CONDUCTOR NEUTRAL GROUND CONDUIT <br />1 Inverter Input (2) 10 AWG  (PV WIRE)N/A 6 AWG  (BARE)Open Air <br />2 Inverter Input (2) 10 AWG  <br />THHN/THWN-2 N/A 8 AWG THHN/THWN-2 3/4 EMT <br />3 Inverter Output (2) 6 AWG  <br />THHN/THWN-2 <br />(1) 6 AWG  <br />THHN/THWN-2 8 AWG THHN/THWN-2 3/4 EMT <br />4 Backup Panel Feeder (2) 1 AWG  <br />THHN/THWN-2 <br />(1) 1 AWG  <br />THHN/THWN-2 6 AWG THHN/THWN-2 1 1/4 EMT <br />5 Backup loads <br />(22) 10 AWG  <br />THHN/THWN-2 <br />(22) 10 AWG  <br />THHN/THWN-2 8 AWG THHN/THWN-2 <br />2 EMT(2) 10 AWG  <br />THHN/THWN-2 <br />(1) 10 AWG  <br />THHN/THWN-2 8 AWG THHN/THWN-2 <br />(4) 8 AWG  <br />THHN/THWN-2 <br />(2) 8 AWG  <br />THHN/THWN-2 8 AWG THHN/THWN-2 <br />PAGE <br />REV: A 12/22/2025 <br />TED YAMADA <br />1925 W DEERFIELD RD, SANTA  <br />ANA, CA, 92704 <br />PROJECT NUMBER: <br />  109R-925YAMA  PR-3004737100 <br />SHEET <br />DESIGNER: <br />MEGHA S <br />CUSTOMER RESIDENCE: <br />TEL. (714) 550-6636 <br />APN: 412-531-54 <br />(415) 580-6920 ex3 <br />PV-4.0 <br />#ESTAMP#SSTAMP <br />2500 WHITE RD. SUITE A, IRVINE CA 92614 <br />PHONE 805.540.7603   <br />FAX 949.215.7778 <br />CA CL #750184 <br />GILBERT CORREIA, C10, C46 <br />ELECTRICAL <br />MODULE CHARACTERISTICS <br />SILFAB: SIL-440QD 440 W <br />OPEN CIRCUIT VOLTAGE 38.97 V <br />MAX POWER VOLTAGE 33.41 V <br />SHORT CIRCUIT CURRENT 14.29 A <br />INSTALLER MUST CHECK THE CONDITION,  <br />INSTALLABILITY AND CODE COMPLIANCE OF  <br />EXISTING EQUIPMENT. <br />POWER CONTROL SYSTEM (PCS):  <br />DOES NOT EXCEED THE RATING OF ANY BUSBAR OR CONDUCTOR SUPPLIED BY THE POWER PRODUCTION  <br />SOURCES <br />SHALL COMPLY WITH ARTICLE 705.12. <br />          - 180A - MAXIMUM TOTAL CURRENT ON THE CONTROLLED PANEL <br />          - 0A - FAIL SAFE GENERATION BACKFEED CURRENT SUPPLY (120% COMPLIANT) <br />General Notes: <br />COLD WATER GAS BOND <br />INTERCONNECTION DEVICE BREAKER CONDUCTORS IN TWO SEPARATE  <br />CONDUITS. <br />IF THE RELOCATED LOADS EXTEND MORE THAN 6 FEET, AFCI PROTECTION  <br />APPLIES PER 2019 CEC 210.12 <br />ANY MULTIWIRE BRANCH CIRCUITS RELOCATED ARE TO BE IDENTIFIED,  <br />GROUPED, AND EQUIPPED WITH A 2-POLE OCPD BREAKER PER CEC  <br />210.4(B,D).