P-1
<br />P-1 POOL CIRCULATION PUMP
<br />PENTAIR WHISPERFLOXF VS #022035
<br />5 HP, 208V, THREE PHASE, 13 AMPS
<br />SET AT 75 GPM
<br />MAIN DRAIN SYSTEM
<br />TRUNK: 2.5" PVC, 75 GPM @ 5.7 FPS
<br />EACH WAY: 2" PVC, 37.5 GPM @ 4.4 FPS
<br /> (QTY. 2)
<br />SUCTION LOOP
<br />2" PVC, 37.5 GPM @ 4.4 FPS
<br />PENTAIR TR-100C SAND FILTER
<br />4.91 SQFT EACH (QTY. 1)
<br />PSI RELIEF
<br />3/4" GAS
<br />CONDENSATE DRAIN
<br />GUTTER GRATE SUCTION SYSTEM
<br />TRUNK: 2.5" PVC, 75 GPM @ 5.7 FPS
<br />LOOP: 2" PVC, 37.5 GPM @ 4.4 FPS
<br />RISERS: 2" PVC, 7.5 GPM @ .87 FPS (QTY. 10)
<br />RETURN LOOP
<br />2" PVC, 37.5 GPM @ 4.4 FPS
<br />WALL INLET SYSTEM
<br />TRUNK: 2.5" PVC, 75 GPM @ 5.7 FPS
<br />LOOP: 2" PVC, 37.5 GPM @ 4.4 FPS
<br />RISERS: 1.5" PVC, 7.5 GPM @ 1.5 FPS (QTY. 10)
<br />ORP PH
<br />CHEMICAL CONTROLLER TO BE ELECTRICALLY
<br />INTERLOCKED WITH CIRCULATION PUMP
<br />THROUGH RELAY IN INTELLICENTER
<br />CHLORINE TANKACID TANKEZPOOL PRO SYSTEM
<br />(POOL & SPA)
<br />OPTIONAL BYPASS FOR
<br />FUTURE SOLAR HEATING
<br />TO BACKWASH
<br />RISER
<br />1" (POOL)
<br />1" (POOL)
<br />J-BOX
<br />TRANS
<br />POOL LIGHTING SYSTEM
<br />18W, 12V LIGHTS (QTY. 2)
<br />INTELLICENTER
<br />ADA LIFT BATTERY
<br />PROVIDE DEDICATED
<br />OUTLET FOR CHARGING
<br />115V GFCI OUTLET
<br />1" (SPA)
<br />HEAVY DUTY FLOAT VALVE
<br />IN GUTTER W/ BYPASS FILL
<br />2.5" PVC, 75 GPM @ 5.7 FPS
<br />P-2
<br />P-2 SPA CIRCULATION PUMP
<br />PENTAIR WHISPERFLOXF VS #022035
<br />5 HP, 208V, THREE PHASE, 13 AMPS
<br />SET AT 150 GPM
<br />MAIN DRAIN SYSTEM
<br />TRUNK: 4" PVC, 150 GPM @ 4.2 FPS
<br />EACH WAY: 4" PVC, 75 GPM @ 2.1 FPS
<br /> (QTY. 2)
<br />SUCTION LOOP
<br />2.5" PVC, 75 GPM @ 5.7 FPS
<br />PENTAIR TR-140C SAND FILTER
<br />7.06 SQFT EACH (QTY. 1)
<br />PSI RELIEF
<br />3/4" GAS
<br />CONDENSATE DRAIN
<br />RETURN LOOP
<br />2.5" PVC, 75 GPM @ 5.7 FPS
<br />ORP PH
<br />CHEMICAL CONTROLLER TO BE ELECTRICALLY
<br />INTERLOCKED WITH CIRCULATION PUMP
<br />THROUGH RELAY IN INTELLICENTER
<br />CHLORINE TANKACID TANK
<br />3" PVC, 150 GPM @ 7.3 FPS
<br />EZPOOL PRO SYSTEM
<br />(POOL & SPA)
<br />3" PVC, 150 GPM @ 7.3 FPS
<br />OPTIONAL BYPASS FOR
<br />FUTURE SOLAR HEATING
<br />TO BACKWASH
<br />RISER
<br />1" (POOL)
<br />1" (POOL)
<br />J-BOX
<br />TRANS
<br />SPA LIGHTING SYSTEM
<br />18W, 12V LIGHTS (QTY. 1)
<br />INTELLICENTER
<br />1" (SPA)
<br />HEAVY DUTY FLOAT VALVE
<br />IN GUTTER W/ BYPASS FILL
<br />P-3
<br />RETURN LOOP
<br />2.5" PVC, 75 GPM @ 5.7 FPS
<br />MAIN DRAIN SYSTEM
<br />TRUNK: 4" PVC, 150 GPM @ 4.2 FPS
<br />EACH WAY: 4" PVC, 75 GPM @ 2.1 FPS
<br /> (QTY. 2)
<br />P-3 SPA JET PUMP
<br />PENTAIR WHISPERFLOXF VS #022035
<br />5 HP, 208V, THREE PHASE, 13 AMPS
<br />SET AT 150 GPM
<br />JET INLET SYSTEM
<br />TRUNK: 3" PVC, 150 GPM @ 7.3 FPS
<br />LOOP: 2.5" PVC, 75 GPM @ 5.7 FPS
<br />RISERS: 1.5" PVC, 25 GPM @ 4.6 (QTY. 10)
<br />SPA WATER LINE
<br />2" REMOTE AIR
<br />RISER
<br />COORDINATE ALL PIPE
<br />PENETRATION LOCATIONS
<br />AND SLEEVED PENETRATION
<br />TYPE IN STRUCTURE VAULT
<br />G.C. BEFORE WORK
<br />PRESSURE GROUT WITH
<br />NON-SHRINK GROUT THEN USE
<br />LOW VISCOSITY EPOXY POLYGEM
<br />1001-SLV TO FILL REMAINING
<br />VOIDS. SUBMIT GROUT TO
<br />ARCHITECT FOR COORDINATION
<br />POOL VAULT WALL
<br />PIPE SIZE VARIES
<br />NOTE:
<br />1.DETAIL IS FOR COORDINATION ONLY, CONTRACTOR TO COORDINATE WITH G.C. AND BUILDING STRUCTURAL
<br />ENGINEER. POOL CONTRACTOR FINAL SUBMIT DESIGN. LINK SEALS WILL BE CONSIDERED AS ALTERNATE DESIGN.
<br />LINK SEAL PENETRATION SEAL
<br />WATER-PROOFING BY OTHERS
<br />VA
<br />R
<br />I
<br />E
<br />S
<br />WALL ASSEMBLY - STUDS
<br />& FIRE RATE GYPSUM PER
<br />ARCHITECTURAL SHEETS
<br />FILL, VOID, CAVITY WITH
<br />FIRE-STOP SYSTEM.
<br />INSTALL TO COMPLETELY
<br />FILL THE ANNULAR SPACE
<br />BETWEEN THE PIPES AND
<br />GYPSUM WALLBOARD ON
<br />BOTH SIDES OF WALL
<br />SECTION FRONT VIEW
<br />NOTE:
<br />1. PIPE SHALL BE RIGIDLY SUPPORTED ON BOTH SIDES OF THE FLOOR OR WALL ASSEMBLY.
<br />2. FILL VOID WITH FIRE-STOP SYSTEM SHALL BE EQUAL TO HOURLY FIRE RATED WALL ASSEMBLY
<br />FOR WHICH IT IS INSTALLED
<br />3/
<br />4
<br />"
<br />
<br />M
<br />I
<br />N
<br />
<br />-
<br />
<br />1
<br />-
<br />1
<br />/
<br />4
<br />"
<br />
<br />M
<br />A
<br />X
<br />.
<br />4" MAX.
<br />CONCRETE FLOOR - FIRE RATE
<br />PER ARCHITECTURAL SHEETS
<br />FILL, VOID, CAVITY WITH FIRE-STOP
<br />SYSTEM. INSTALL TO COMPLETELY FILL
<br />THE ANNULAR SPACE BETWEEN THE PIPES
<br />AND CONCRETE FLOOR ON BOTH SIDES
<br />NOTE:
<br />1. PIPE SHALL BE FIRE-STOP SYSTEM SHALL BE ON BOTH SIDES OF THE FLOOR OR WALL ASSEMBLY.
<br />2. FILL VOID WITH FIRE-STOP SYSTEM SHALL BE EQUAL TO HOURLY FIRE RATED FLOOR ASSEMBLY
<br />FOR WHICH IT IS INSTALLED.
<br />3/16" MIN - 5/16" MAX.
<br />4-
<br />1
<br />/
<br />2
<br />"
<br />
<br />M
<br />I
<br />N
<br />.
<br />3" MAX.PER STRUCTURAL
<br />EQUAL
<br />FL
<br />A
<br />N
<br />G
<br />E
<br />PI
<br />P
<br />E
<br />
<br />Ø
<br />SHOTCRETE WALL OR FLOOR
<br />HEAT OR SOLVENT WELDED
<br />PVC FLANGE TO COUPLING
<br />PIPE SIZES FLANGE WIDTH
<br />12" TO 3"
<br />4" TO 6"
<br />PER STRUCTURAL
<br />EQUAL
<br />FL
<br />A
<br />N
<br />G
<br />E
<br />PI
<br />P
<br />E
<br />
<br />Ø
<br />SHOTCRETE WALL OR FLOOR
<br />HEAT OR SOLVENT WELDED
<br />PVC FLANGE TO COUPLING
<br />PIPE SIZES FLANGE WIDTH
<br />12" TO 3"
<br />4" TO 6"1 12"
<br /> 12"
<br />POOL PIPE SHALL BE ATTACHED TO UNDERSIDE
<br />OF STRUCTURAL DECK, SUPPORT PIPE PER IPC.
<br />PIPE SHALL BE SUPPORTED IN ACCORDANCE
<br />WITH TABLE 308.5. THE CONTRACTOR SHALL
<br />SUBMIT SUPPORT SYSTEM DESIGN TO
<br />ARCHITECT BEFORE START OF THIS WORK.
<br />COORDINATE FINAL LOCATIONS OF PIPE
<br />PENETRATIONS THROUGH STRUCTURAL
<br />VAULT, COORDINATE PENETRATION
<br />DESIGN WITH STRUCTURAL ENGINEER.
<br />CAULK BOTH SIDES OF PENETRATION
<br />LEVEL (2) STRUCTURAL SLAB
<br />PIPE INSULATION AS
<br />REQUIRED PER CODE
<br />COORDINATE ANCHOR
<br />CONNECTION WITH
<br />BUILDING STRUCTURAL
<br />NOTE:
<br />1.POOL PIPE INSTALLED IN A PLENUM OR SUBJECT TO FREEZING SHALL BE INSULATED PER SPECIFICATION.
<br />2.POOL PIPE RUNNING THROUGH BUILDING EXPANSION JOINT AREAS SHALL BE INSTALLED WITH
<br />APPROVED RUBBER PIPE EXPANSION JOINTS WITHSTANDING CHEMICALLY TREATED WATER.
<br />HOLDRITE SILENCER
<br />CLAMPS ACOUSTICAL
<br />TRAPEZE MEMBER
<br />(DOUBLE STRUT)
<br />STRUCTURAL DECK ABOVE
<br />COORDINATE CONNECTION
<br />STRUCTURE ATTACHMENT
<br />PIPE SIZE VARIES
<br />NOTE:
<br />1.DETAIL IS FOR COORDINATION ONLY, CONTRACTOR TO SUBMIT DESIGN.
<br />2.CONTRACTOR TO SUBMIT DESIGN LOAD SIZING PER FINAL LAYOUT.
<br />3.THE PIPE OR CONDUIT LOADS ON THE TRAPEZE SYSTEM SHOULD BE RELATIVELY UNIFORM AND SYMMETRICAL
<br />ALONG THE LENGTH OF THE MEMBER.
<br />LON
<br />G
<br />I
<br />T
<br />U
<br />D
<br />I
<br />N
<br />A
<br />L
<br />
<br />B
<br />R
<br />A
<br />C
<br />E
<br />1/2" ALL THREAD ROD
<br />SIZE AS REQUIRED
<br />COORDINATE FINAL TRAPEZE LENGTH
<br />CO
<br />O
<br />R
<br />D
<br />I
<br />N
<br />A
<br />T
<br />E
<br />45
<br />°
<br />HOLDRITE
<br />ACOUSTICAL
<br />PIPE SUPPORT
<br />NOTE:
<br />1.DETAIL IS FOR COORDINATION ONLY, COORDINATE FINAL PIPE ROUTING WITH GENERAL CONTRACTOR AND SUBMIT
<br />SHOP DRAWING FOR FINAL DESIGN APPROVAL TO BUILDING STRUCTURAL ENGINEER.
<br />2.THE PIPE OR CONDUIT LOADS ON THE UNI-STRUT SYSTEM SHOULD BE RELATIVELY UNIFORM AND SYMMETRICAL
<br />ALONG THE LENGTH OF THE MEMBER.
<br />2-1/2
<br />
<br />S
<br />U
<br />C
<br />T
<br />I
<br />O
<br />N
<br />1" C
<br />O
<br />L
<br />D
<br />
<br />W
<br />A
<br />T
<br />E
<br />R
<br />2-1/2
<br />
<br />S
<br />U
<br />C
<br />T
<br />I
<br />O
<br />N
<br />2-1/2
<br />
<br />R
<br />E
<br />T
<br />U
<br />R
<br />N
<br />COORDINATE PENETRATION WITH
<br />BUILDING STRUCTURAL ENGINEER,
<br />SEE DETAIL 5 ON THIS SHEET
<br /> MOUNTING HARDWARE
<br />ON STRUCTURAL DECK
<br />POOL PLUMBING PER PLAN
<br />SECURE PIPING TO
<br />MOUNTING HARDWARE
<br />SEE PIPING PLAN FOR VAULT
<br />PENETRATION LOCATIONS
<br />DECK MOUNTING HARDWARE
<br />45° POOL PIPE AS
<br />NEEDED OVER
<br />PLUMBING LINES
<br />POOL VAULT PER STRUCTURAL
<br />BOTTOM OF SLAB
<br />LEVER-OPERATED
<br />BUTTERFLY VALVE
<br />TRUE UNION BALL VALVE
<br />GCFI POWER
<br />FLOW METER
<br />SOLENOID
<br />BACKFLOW PREVENTOR
<br />UNDERWATER LIGHT
<br />SCHEMATIC LEGEND
<br />CHECK VALVE
<br />PIPE CAP
<br />TEMPERATURE SENSOR
<br />NEUTRALIZER
<br />VACUUM RELIEF VALVE
<br />2-WAY MULTIPORT VALVE
<br />PRESSURE / VACUUM GAGUE
<br />3-WAY MULTIPORT VALVE
<br />WALL INLET SYSTEM
<br />TRUNK: 3" PVC, 150 GPM @ 7.3 FPS
<br />LOOP: 2.5" PVC, 75 GPM @ 5.7 FPS
<br />RISERS: 1.5" PVC, 25 GPM @ 4.6 FPS(QTY. 6)
<br />Scale: N.T.S.
<br />POOL - CIRCULATION SYSTEM (SCHEMATIC)9 Scale: NTS
<br />SPA - CIRCULATION SYSTEM (SCHEMATIC)10
<br />Scale: 1-1/2" = 1'
<br />VAULT PIPE PENETRATIONS4Scale: 1" = 1'
<br />PLASTIC PIPE THROUGH FIRE RATED WALL2Scale: NTS
<br />PLASTIC PIPE THROUGH CONCRETE FLOOR1 Scale: NTS
<br />CONCRETE PIPE FLANGES (SECTION)3
<br />Scale:3/4"= 1 FT.
<br />PIPE ROUTING (SECTION)6Scale: NTS
<br />PIPE HANGERS (SCHEMATIC)5 Scale: NTS
<br />PIPE & CONDUIT ROUTING (ISOMETRIC)8Scale: NTS
<br />SLAB MOUNTED PIPE ROUTING (SECTION)7
<br />© Gensler
<br />Date Description
<br />Project Name
<br />Project Number
<br />Description
<br />Scale
<br />Seal / Signature
<br />2021
<br />Tel 949.863.9434
<br />Fax 949-553-1676
<br />4675 MacArthur Court
<br />Suite 100
<br />Newport Beach, CA
<br />92600
<br />USA
<br />BI
<br />M
<br />
<br />3
<br />6
<br />0
<br />:
<br />/
<br />/
<br />0
<br />0
<br />7
<br />.
<br />3
<br />7
<br />5
<br />7
<br />.
<br />0
<br />0
<br />0
<br />
<br />-
<br />
<br />C
<br />a
<br />r
<br />i
<br />b
<br />o
<br />u
<br />
<br />I
<br />n
<br />d
<br />u
<br />s
<br />t
<br />r
<br />i
<br />e
<br />s
<br />
<br />-
<br />
<br />3
<br />r
<br />d
<br />
<br />&
<br />
<br />B
<br />r
<br />o
<br />a
<br />d
<br />w
<br />a
<br />y
<br />/
<br />3
<br />R
<br />D
<br />-
<br />B
<br />_
<br />A
<br />R
<br />C
<br />H
<br />_
<br />W
<br />E
<br />S
<br />T
<br />_
<br />R
<br />2
<br />0
<br />.
<br />r
<br />v
<br />t
<br />07.3757.000
<br />3rd & Broadway
<br />301 N. Broadway, Santa Ana, CA
<br />09/21/2021 Issue for Plan Check
<br />A 12/10/2021 Reissue for Plan Check
<br />B 07/11/2022 Reissue for Plan Check
<br />C 06/17/2024 REVISION TO PERMIT
<br />R1-SP-505CC
<br />Jun 04, 2024
<br />1/7/25
|