301 N Broadway – Plan Check Response <br />September 20, 2024 –Page 3 <br /> <br /> <br />the hourly rate of the fire-rated door (opening <br />protection) and the opening force for the doors <br />from the Corridor R07J11A accessing the common <br />toilet (R07H12C) and Fitness Studio (R07J13) – See <br />also 1-fr. Fire-partition on Sheet R2.LS1.107. Please <br />see Sheets R2.I5.175, R2.I5.177, etc. <br />improvement (TI) scope will <br />cover only the interior unit <br />doors and the interior amenity <br />door on levels 6 and 7, which <br />do not require fire rating. For <br />further details, please refer to <br />the updated door schedule on <br />sheet R2.I0.031. <br />9 Please provide the equipment layout at Fitness/Spin Room. <br />At least one of each type of exercise machine and equipment <br />shall comply with Section 11B-1004. (11B-236.1) <br />Refer to the fitness equipment <br />layout and ADA clearance <br />provided on the enlarged <br />fitness center plan 01 / <br />R2.I5.175. <br />10 Toilet compartment: <br />a. Side opening doors: When located at the side of a <br />toilet compartment, the toilet compartment door <br />opening shall provide a clear width of 34 inches <br />(864 mm) minimum. (CBC 11B-604.8.1.2, Exception) <br />– See Sheets R2.I5.173, R2.I5.177, etc. <br /> <br /> <br />Updated ADA toilet <br />compartment door opening to <br />be a minimum 34” clear <br />opening. Refer to the clouded <br />dimension on the enlarged <br />restroom plan 01 / R2.I5.173. <br /> <br />(End of Architectural Plan Check Response) <br />