Laserfiche WebLink
ST. BARBARA CATHOLIC SCHOOL TASK 2 75-24272-01 <br />DIOCESE OF ORANGE SEPTEMBER 12TH, 2024 <br />SANTA ANA, CA BID & PERMIT SET <br /> <br />LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519 - 5 <br />b. Instrument: Use an infrared scanning device designed to measure temperature or <br />to detect significant deviations from normal values. Provide calibration record for <br />device. <br />c. Record of Infrared Scanning: Prepare a certified report that identifies splices <br />checked and that describes scanning results. Include notation of deficiencies <br />detected, remedial action taken, and observations after remedial action. <br />D. Test Reports: Prepare a written report to record the following: <br />1. Test procedures used. <br />2. Test results that comply with requirements. <br />3. Test results that do not comply with requirements and corrective action taken to achieve <br />compliance with requirements. <br />E. Remove and replace malfunctioning units and retest as specified above. <br />END OF SECTION 260519