Laserfiche WebLink
ST. BARBARA CATHOLIC SCHOOL TASK 2 75-24272-01 <br />DIOCESE OF ORANGE SEPTEMBER 12TH, 2024 <br />SANTA ANA, CA BID & PERMIT SET <br /> <br />IDENTIFICATION FOR ELECTRICAL SYSTEMS 260532 - 2 <br />schematic and interconnection diagrams equipment manufacturer's shop drawings for control <br />wiring. <br />3.3 NAMEPLATE ENGRAVING <br />A. Provide nameplates to identify all circuits in the service distribution and power distribution <br />panelboards; branch circuit panelboards; separately mounted starting switches; disconnecting <br />switches; motor control push-button stations; selector switches; terminal cabinets; telephone <br />cabinets, etc. Clearly identify on the nameplate the equipment such as "Air Handling Unit AH- <br />1" and "Hot Water Cir. Pump P-1" in lieu of abbreviated plan references such as "AH-1" or "P- <br />1". <br />B. Provide nameplates of minimum letter height as scheduled below. <br />C. Panelboards and Switchboards: 1/4 inch; identify equipment designation, voltage rating, and <br />source. <br />D. Individual Circuit Breakers In Panelboards and Switchboards: 1/8 inch; identify circuit and <br />load served, including location. <br />E. Individual Circuit Breakers, Enclosed Switches and Motor Starters: 1/8 inch; identify voltage <br />rating, ampere rating and load served including location. <br />F. HVAC and Plumbing Control Equipment: 1/8 inch; identify equipment designation and <br />equipment served including location. <br />G. Communication Terminal Cabinets: 1/4 inch; identify cabinet designation and type of system. <br />END OF SECTION 260532