Laserfiche WebLink
1. <br />a. <br />a. <br />b. <br />c. <br />a. <br />b. <br />c. <br />d. <br />1. <br />a. <br />a. <br />b. <br />c. <br />1. <br />a. <br />a. <br />b. <br />1. <br />a. <br />a. <br />A. <br />1. <br />2. <br />MASTER SPECIFICATIONS - ELECTRICAL SPECIFICATIONS (CONTINUED) <br />SECTION 261323 - MEDIUM-VOLTAGE, SWITCHGEAR <br />2. ELECTRICAL TESTS: <br />a. INSPECT BOLTED ELECTRICAL CONNECTIONS USING A LOW RESISTANCE OHMMETER TO COMPARE BOLTED RESISTANCE VALUES TO VALUES OF SIMILAR CONNECTIONS. INVESTIGATE VALUES <br />THAT DEVIATE FROM THOSE OF SIMILAR BOLTED CONNECTIONS BY MORE THAN 50 PERCENT OF THE LOWEST VALUE. <br />b. PERFORM DC VOLTAGE INSULATION-RESISTANCE TESTS ON EACH BUS SECTION, PHASE TO PHASE AND PHASE TO GROUND, FOR ONE MINUTE. IF THE TEMPERATURE OF THE BUS IS OTHER <br />THAN PLUS OR MINUS 20 DEG C, ADJUST THE RESULTING RESISTANCE AS PROVIDED IN NETA ATS, TABLE 100.11. <br />1. INSULATION-RESISTANCE VALUES OF BUS INSULATION SHALL BE ACCORDING TO MANUFACTURER'S PUBLISHED DATA. IN THE ABSENCE OF MANUFACTURER'S PUBLISHED DATA, <br />COMPLY WITH NETA ATS, TABLE 100.1. INVESTIGATE AND CORRECT VALUES OF INSULATION RESISTANCE LESS THAN MANUFACTURER'S RECOMMENDATIONS OR NETA ATS, TABLE 100.1. <br />2. DO NOT PROCEED TO THE DIELECTRIC WITHSTAND VOLTAGE TESTS UNTIL INSULATION-RESISTANCE LEVELS ARE RAISED ABOVE MINIMUM VALUES. <br />c. PERFORM A DIELECTRIC WITHSTAND VOLTAGE TEST ON EACH BUS SECTION, EACH PHASE TO GROUND WITH PHASES NOT UNDER TEST GROUNDED, ACCORDING TO MANUFACTURER'S <br />PUBLISHED DATA. IF MANUFACTURER HAS NO RECOMMENDATION FOR THIS TEST, IT SHALL BE CONDUCTED ACCORDING TO NETA ATS, TABLE <br />100.2. APPLY THE TEST VOLTAGE FOR ONE MINUTE. <br />1. IF NO EVIDENCE OF DISTRESS OR INSULATION FAILURE IS OBSERVED BY THE END OF THE TOTAL TIME OF VOLTAGE APPLICATION DURING THE DIELECTRIC WITHSTAND TEST, THE <br />TEST SPECIMEN IS CONSIDERED TO HAVE PASSED THE TEST. <br />d. PERFORM INSULATION-RESISTANCE TESTS ON CONTROL WIRING WITH RESPECT TO GROUND. APPLIED POTENTIAL SHALL BE 500 VOLTS DC FOR 300-VOLT RATED CABLE AND 1000 V DC FOR 600- <br />V RATED CABLE. TEST DURATION SHALL BE ONE MINUTE. FOR UNITS WITH SOLID-STATE COMPONENTS OR CONTROL DEVICES THAT CANNOT TOLERATE THE APPLIED VOLTAGE, FOLLOW THE <br />MANUFACTURER'S RECOMMENDATION. <br />1. MINIMUM INSULATION-RESISTANCE VALUES OF CONTROL WIRING SHALL NOT BE LESS THAN TWO MEGOHMS. <br />e. CONTROL POWER TRANSFORMERS: <br />1. PERFORM INSULATION-RESISTANCE TESTS. PERFORM MEASUREMENTS FROM WINDING TO WINDING AND EACH WINDING TO GROUND. INSULATION-RESISTANCE VALUES OF WINDING <br />INSULATION SHALL BE ACCORDING TO MANUFACTURER'S PUBLISHED DATA. IN THE ABSENCE OF MANUFACTURER'S PUBLISHED DATA, COMPLY WITH NETA ATS, TABLE 100.1. <br />INVESTIGATE AND CORRECT VALUES OF INSULATION RESISTANCE LESS THAN MANUFACTURER'S RECOMMENDATIONS OR NETA ATS, TABLE 100.1. <br />2. PERFORM SECONDARY WIRING INTEGRITY TEST. DISCONNECT TRANSFORMER AT SECONDARY TERMINALS AND CONNECT SECONDARY WIRING TO A RATED SECONDARY VOLTAGE <br />SOURCE. VERIFY CORRECT POTENTIAL AT ALL DEVICES. <br />3. VERIFY CORRECT SECONDARY VOLTAGE BY ENERGIZING THE PRIMARY WINDING WITH SYSTEM VOLTAGE. MEASURE SECONDARY VOLTAGE WITH THE SECONDARY WIRING <br />DISCONNECTED. <br />4. VERIFY CORRECT FUNCTION OF CONTROL TRANSFER RELAYS LOCATED IN THE SWITCHGEAR WITH MULTIPLE CONTROL POWER SOURCES. <br />f. PERFORM SYSTEM FUNCTION TESTS ACCORDING TO "SYSTEM FUNCTION TESTS" ARTICLE. <br />g. VERIFY OPERATION OF SPACE HEATERS. <br />h. PERFORM PHASING CHECKS ON DOUBLE-ENDED OR DUAL-SOURCE SWITCHGEAR TO ENSURE CORRECT BUS PHASING FROM EACH SOURCE. <br />E. INSTRUMENT TRANSFORMER FIELD TESTS: <br />VISUAL AND MECHANICAL INSPECTION: <br />VERIFY THAT EQUIPMENT NAMEPLATE DATA COMPLIES WITH CONTRACT DOCUMENTS. <br />b. INSPECT PHYSICAL AND MECHANICAL CONDITION. <br />c. VERIFY CORRECT CONNECTION OF TRANSFORMERS WITH SYSTEM REQUIREMENTS. <br />d. VERIFY THAT ADEQUATE CLEARANCES EXIST BETWEEN PRIMARY AND SECONDARY CIRCUIT WIRING. <br />e. VERIFY THE UNIT IS CLEAN. <br />f.INSPECT BOLTED ELECTRICAL CONNECTIONS USING CALIBRATED TORQUE-WRENCH METHOD ACCORDING TO MANUFACTURER'S PUBLISHED DATA OR NETA ATS, TABLE 100.12. BOLT- <br />TORQUE LEVELS SHALL BE ACCORDING TO MANUFACTURER'S PUBLISHED DATA. IN THE ABSENCE OF MANUFACTURER'S PUBLISHED DATA, USE NETA ATS, TABLE 100.12. INVESTIGATE <br />VALUES THAT DEVIATE FROM THOSE OF SIMILAR BOLTED CONNECTIONS BY MORE THAN 50 PERCENT OF THE LOWEST VALUE. <br />g. VERIFY TIGHTNESS OF ACCESSIBLE BOLTED ELECTRICAL CONNECTIONS BY CALIBRATED TORQUE-WRENCH METHOD ACCORDING TO MANUFACTURER'S PUBLISHED DATA OR NETA ATS, <br />TABLE 100.12. BOLT-TORQUE LEVELS SHALL BE ACCORDING TO MANUFACTURER'S PUBLISHED DATA. IN THE ABSENCE OF MANUFACTURER'S PUBLISHED DATA, USE NETA ATS, TABLE <br />100.12. <br />h. VERIFY THAT REQUIRED GROUNDING AND SHORTING CONNECTIONS PROVIDE CONTACT. <br />i.VERIFY CORRECT OPERATION OF TRANSFORMER WITHDRAWAL MECHANISM AND GROUNDING OPERATION. <br />j.VERIFY CORRECT PRIMARY AND SECONDARY FUSE SIZES FOR VOLTAGE TRANSFORMERS. <br />k.VERIFY APPROPRIATE LUBRICATION ON MOVING CURRENT-CARRYING PARTS AND ON MOVING AND SLIDING SURFACES. <br />2. ELECTRICAL TESTS OF CURRENT TRANSFORMERS: <br />INSPECT BOLTED ELECTRICAL CONNECTIONS USING A LOW RESISTANCE OHMMETER TO COMPARE BOLTED RESISTANCE VALUES TO VALUES OF SIMILAR CONNECTIONS. INVESTIGATE <br />VALUES THAT DEVIATE FROM THOSE OF SIMILAR BOLTED CONNECTIONS BY MORE THAN 50 PERCENT OF THE LOWEST VALUE. <br />PERFORM INSULATION-RESISTANCE TEST OF EACH CURRENT TRANSFORMER AND ITS SECONDARY WIRING WITH RESPECT TO GROUND AT 1000 V DC FOR ONE MINUTE. FOR UNITS <br />WITH SOLID-STATE COMPONENTS THAT CANNOT TOLERATE THE APPLIED VOLTAGE, FOLLOW MANUFACTURER'S WRITTEN RECOMMENDATIONS. INVESTIGATE AND CORRECT VALUES OF <br />INSULATION RESISTANCE LESS THAN MANUFACTURER'S RECOMMENDATIONS OR NETA ATS, TABLE 100.5. <br />PERFORM A POLARITY TEST OF EACH CURRENT TRANSFORMER ACCORDING TO IEEE C57.13.1. POLARITY RESULTS SHALL AGREE WITH TRANSFORMER MARKINGS. <br />d. PERFORM A RATIO-VERIFICATION TEST USING THE VOLTAGE OR CURRENT METHOD ACCORDING TO IEEE C57.13.1. RATIO ERRORS SHALL BE ACCORDING TO IEEE C57.13. <br />e. PERFORM AN EXCITATION TEST ON TRANSFORMERS USED FOR RELAYING APPLICATIONS ACCORDING TO IEEE C57.13.1. EXCITATION RESULTS SHALL MATCH THE CURVE SUPPLIED BY <br />THE MANUFACTURER OR BE ACCORDING TO IEEE C57.13.1. <br />f.MEASURE CURRENT CIRCUIT BURDENS AT TRANSFORMER TERMINALS ACCORDING TO IEEE C57.13.1. MEASURED BURDENS SHALL BE COMPARED WITH AND SHALL MATCH INSTRUMENT <br />TRANSFORMER RATINGS. <br />g. PERFORM INSULATION-RESISTANCE TESTS ON THE PRIMARY WINDING WITH THE SECONDARY GROUNDED. TEST VOLTAGES SHALL BE ACCORDING TO TABLE 100.5. <br />h. PERFORM DIELECTRIC WITHSTAND TESTS ON THE PRIMARY WINDING WITH THE SECONDARY GROUNDED. TEST VOLTAGES SHALL BE ACCORDING TO TABLE 100.9. <br />i.PERFORM POWER-FACTOR OR DISSIPATION-FACTOR TESTS ACCORDING TO TEST EQUIPMENT MANUFACTURER'S PUBLISHED DATA. <br />j.VERIFY THAT CURRENT TRANSFORMER SECONDARY CIRCUITS ARE GROUNDED AND HAVE ONLY ONE GROUNDING POINT ACCORDING TO IEEE C57.13.3. THAT GROUNDING POINT <br />SHOULD BE LOCATED AS SPECIFIED BY THE ENGINEER IN THE PROJECT DRAWINGS. <br />3. ELECTRICAL TESTS OF VOLTAGE TRANSFORMERS: <br />INSPECT BOLTED ELECTRICAL CONNECTIONS USING A LOW RESISTANCE OHMMETER TO COMPARE BOLTED RESISTANCE VALUES TO VALUES OF SIMILAR CONNECTIONS. INVESTIGATE <br />VALUES THAT DEVIATE FROM THOSE OF SIMILAR BOLTED CONNECTIONS BY MORE THAN 50 PERCENT OF THE LOWEST VALUE. <br />PERFORM INSULATION-RESISTANCE TESTS WINDING-TO-WINDING AND EACH WINDING TO GROUND. TEST VOLTAGES SHALL BE APPLIED FOR ONE MINUTE ACCORDING TO TABLE 100.5. <br />FOR UNITS WITH SOLID-STATE COMPONENTS THAT CANNOT TOLERATE THE APPLIED VOLTAGE, FOLLOW MANUFACTURER'S RECOMMENDATIONS. INVESTIGATE AND CORRECT VALUES <br />OF INSULATION RESISTANCE LESS THAN MANUFACTURER'S RECOMMENDATIONS OR NETA ATS, TABLE 100.5. <br />PERFORM A POLARITY TEST ON EACH TRANSFORMER TO VERIFY THE POLARITY MARKS OR H1- X1 RELATIONSHIP AS APPLICABLE. POLARITY RESULTS SHALL AGREE WITH <br />TRANSFORMER MARKINGS. <br />PERFORM A TURNS-RATIO TEST ON ALL TAP POSITIONS. RATIO ERRORS SHALL BE ACCORDING TO IEEE C57.13. <br />e. MEASURE VOLTAGE CIRCUIT BURDENS AT TRANSFORMER TERMINALS. MEASURED BURDENS SHALL BE COMPARED WITH AND SHALL MATCH INSTRUMENT TRANSFORMER RATINGS. <br />f.PERFORM A DIELECTRIC WITHSTAND TEST ON THE PRIMARY WINDINGS WITH THE SECONDARY WINDINGS CONNECTED TO GROUND. THE DIELECTRIC VOLTAGE SHALL BE ACCORDING <br />TO TABLE 100.9. THE TEST VOLTAGE SHALL BE APPLIED FOR ONE MINUTE. IF NO EVIDENCE OF DISTRESS OR INSULATION FAILURE IS OBSERVED BY THE END OF THE TOTAL TIME OF <br />VOLTAGE APPLICATION DURING THE DIELECTRIC WITHSTAND TEST, THE PRIMARY WINDINGS ARE CONSIDERED TO HAVE PASSED THE TEST. <br />g. PERFORM POWER-FACTOR OR DISSIPATION-FACTOR TESTS ACCORDING TO TEST EQUIPMENT MANUFACTURER'S PUBLISHED DATA. POWER-FACTOR OR DISSIPATION-FACTOR VALUES <br />SHALL BE ACCORDING TO MANUFACTURER'S PUBLISHED DATA. IN THE ABSENCE OF MANUFACTURER'S PUBLISHED DATA, USE TEST EQUIPMENT MANUFACTURER'S PUBLISHED DATA. <br />h. VERIFY THAT VOLTAGE TRANSFORMER SECONDARY CIRCUITS ARE GROUNDED AND HAVE ONLY ONE GROUNDING POINT ACCORDING TO IEEE C57.13.3. TEST RESULTS SHALL INDICATE <br />THAT THE CIRCUITS ARE GROUNDED AT ONLY ONE POINT. <br />F.GROUND RESISTANCE TEST: <br />VISUAL AND MECHANICAL INSPECTION: <br />VERIFY GROUND SYSTEM COMPLIES WITH THE CONTRACT DOCUMENTS AND NFPA 70 ARTICLE 250, "GROUNDING AND BONDING." <br />b. INSPECT PHYSICAL AND MECHANICAL CONDITION. GROUNDING SYSTEM ELECTRICAL AND MECHANICAL CONNECTIONS SHALL BE FREE OF CORROSION. <br />c. INSPECT BOLTED ELECTRICAL CONNECTIONS USING A CALIBRATED TORQUE-WRENCH METHOD ACCORDING TO MANUFACTURER'S PUBLISHED DATA OR NETA ATS, TABLE 100.12. BOLT- <br />TORQUE LEVELS SHALL BE ACCORDING TO MANUFACTURER'S PUBLISHED DATA. IN THE ABSENCE OF MANUFACTURER'S PUBLISHED DATA, USE NETA ATS, TABLE 100.12. INVESTIGATE <br />VALUES THAT DEVIATE FROM THOSE OF SIMILAR BOLTED CONNECTIONS BY MORE THAN 50 PERCENT OF THE LOWEST VALUE. <br />d. INSPECT ANCHORAGE. <br />2. ELECTRICAL TESTS: <br />PERFORM FALL-OF-POTENTIAL OR ALTERNATIVE TEST ACCORDING TO IEEE 81 ON THE MAIN GROUNDING ELECTRODE OR SYSTEM. THE RESISTANCE BETWEEN THE MAIN GROUNDING <br />ELECTRODE AND GROUND SHALL BE NO MORE THAN [5 OHMS] [MAXIMUM GROUND RESISTANCE VALUE SPECIFIED IN "EXAMINATION" ARTICLE]. <br />PERFORM POINT-TO-POINT TESTS TO DETERMINE THE RESISTANCE BETWEEN THE MAIN GROUNDING SYSTEM AND ALL MAJOR ELECTRICAL EQUIPMENT FRAMES, SYSTEM NEUTRAL, <br />AND DERIVED NEUTRAL POINTS. INVESTIGATE POINT-TO-POINT RESISTANCE VALUES THAT EXCEED 0.5 OHMS. COMPARE EQUIPMENT NAMEPLATE DATA WITH CONTRACT DOCUMENTS. <br />INSPECT PHYSICAL AND MECHANICAL CONDITION. <br />d. INSPECT BOLTED ELECTRICAL CONNECTIONS FOR HIGH RESISTANCE USING A LOW-RESISTANCE OHMMETER TO COMPARE BOLTED CONNECTION RESISTANCE VALUES TO VALUES OF <br />SIMILAR CONNECTIONS. INVESTIGATE VALUES THAT DEVIATE FROM THOSE OF SIMILAR BOLTED CONNECTIONS BY MORE THAN 50 PERCENT OF THE LOWEST VALUE. <br />G. MEDIUM-VOLTAGE SURGE ARRESTER FIELD TESTS: <br />VISUAL AND MECHANICAL INSPECTION: <br />VERIFY THAT EQUIPMENT NAMEPLATE DATA COMPLIES WITH CONTRACT DOCUMENTS. <br />b. INSPECT PHYSICAL AND MECHANICAL CONDITION. <br />c. INSPECT ANCHORAGE, ALIGNMENT, GROUNDING, AND CLEARANCES. <br />d. VERIFY THE ARRESTERS ARE CLEAN. <br />e. VERIFY THAT THE GROUND LEAD ON EACH DEVICE IS INDIVIDUALLY ATTACHED TO A GROUND BUS OR GROUND ELECTRODE. <br />f.VERIFY THAT THE STROKE COUNTER IS CORRECTLY MOUNTED AND ELECTRICALLY CONNECTED IF APPLICABLE. RECORD THE STROKE COUNTER READING. <br />2. ELECTRICAL TEST: <br />PERFORM AN INSULATION-RESISTANCE TEST ON EACH ARRESTER, PHASE TERMINAL TO GROUND. APPLY VOLTAGE ACCORDING TO MANUFACTURER'S PUBLISHED DATA. IN THE <br />ABSENCE OF MANUFACTURER'S PUBLISHED DATA, COMPLY WITH NETA ATS, TABLE 100.1. REPLACE UNITS THAT FAIL TO MEET RECOMMENDED MINIMUM INSULATION RESISTANCE <br />LISTED IN THE TABLE. <br />PERFORM A WATTS-LOSS TEST. EVALUATE WATTS-LOSS VALUES BY COMPARISON WITH SIMILAR UNITS AND TEST EQUIPMENT MANUFACTURER'S PUBLISHED DATA. <br />c. TEST GROUNDING CONNECTIONS. RESISTANCE BETWEEN THE ARRESTER GROUND TERMINAL AND THE GROUND SYSTEM SHALL BE LESS THAN 0.5 OHM. <br />H. MICROPROCESSOR-BASED PROTECTIVE RELAY FIELD TESTS: <br />VISUAL AND MECHANICAL INSPECTION: <br />RECORD MODEL NUMBER, STYLE NUMBER, SERIAL NUMBER, FIRMWARE REVISION, SOFTWARE REVISION, AND RATED CONTROL VOLTAGE. <br />b. VERIFY OPERATION OF LIGHT-EMITTING DIODES, DISPLAY, AND TARGETS. <br />c. RECORD PASSWORDS FOR EACH ACCESS LEVEL. <br />d. CLEAN THE FRONT PANEL AND REMOVE FOREIGN MATERIAL FROM THE CASE. <br />e. CHECK TIGHTNESS OF CONNECTIONS. <br />f.VERIFY THAT THE FRAME IS GROUNDED ACCORDING TO MANUFACTURER'S INSTRUCTIONS. <br />g. SET THE RELAY ACCORDING TO RESULTS IN SECTION 260573.16 "COORDINATION STUDIES" AND IN SECTION 260573.19 "ARC-FLASH HAZARD ANALYSIS." <br />h. DOWNLOAD SETTINGS FROM THE RELAY. PRINT A COPY OF THE SETTINGS FOR THE REPORT AND COMPARE THE SETTINGS TO THOSE SPECIFIED IN THE COORDINATION STUDY. <br />2. ELECTRICAL TESTS: <br />PERFORM INSULATION-RESISTANCE TESTS FROM EACH CIRCUIT TO THE GROUNDED FRAME ACCORDING TO MANUFACTURER'S PUBLISHED DATA. <br />b. APPLY VOLTAGE OR CURRENT TO ANALOG INPUTS, AND VERIFY CORRECT REGISTRATION OF THE RELAY METER FUNCTIONS. <br />c. FUNCTIONAL OPERATION: CHECK FUNCTIONAL OPERATION OF EACH ELEMENT USED IN THE PROTECTION SCHEME. <br />I.SWITCHGEAR WILL BE CONSIDERED DEFECTIVE IF IT DOES NOT PASS TESTS AND INSPECTIONS. <br />J. REMOVE AND REPLACE DEFECTIVE UNITS AND RETEST. <br />K. PREPARE TEST AND INSPECTION REPORTS. RECORD AS-LEFT SET POINTS OF ADJUSTABLE DEVICES. <br />3.5 SYSTEM FUNCTION TESTS <br />SYSTEM FUNCTION TESTS SHALL PROVE THE CORRECT INTERACTION OF SENSING, PROCESSING, AND ACTION DEVICES. PERFORM SYSTEM FUNCTION TESTS AFTER FIELD QUALITY <br />CONTROL TESTS HAVE BEEN COMPLETED AND ALL COMPONENTS HAVE PASSED SPECIFIED TESTS. <br />DEVELOP TEST PARAMETERS AND PERFORM TESTS FOR THE PURPOSE OF EVALUATING PERFORMANCE OF INTEGRAL COMPONENTS AND THEIR FUNCTIONING AS A <br />COMPLETE UNIT WITHIN DESIGN REQUIREMENTS AND MANUFACTURER'S PUBLISHED DATA. <br />VERIFY THE CORRECT OPERATION OF INTERLOCK SAFETY DEVICES FOR FAIL-SAFE FUNCTIONS IN ADDITION TO DESIGN FUNCTION. <br />3. VERIFY THE CORRECT OPERATION OF SENSING DEVICES, ALARMS, AND INDICATING DEVICES. <br />END OF SECTION 261323 <br />1. <br />1. <br />2. <br />3. <br />4. <br />1. <br />A. <br />B. <br />C. <br />1. <br />A. <br />1. <br />a. <br />b. <br />A. <br />1. <br />A. <br />A. <br />A. <br />B. <br />A. <br />1. <br />A. <br />B. <br />C. <br />D. <br />E. <br />A. <br />1. <br />1. <br />2. <br />A. <br />A. <br />A. <br />1. <br />A. <br />1. <br />A. <br />SECTION 262413 - SWITCHBOARDS <br />PART 1 - GENERAL <br />1.1 SUMMARY <br />A. SECTION INCLUDES: <br />DISTRIBUTION SWITCHBOARDS RATED 600 V AND LESS. <br />2. SURGE PROTECTION DEVICES. <br />3. DISCONNECTING AND OVERCURRENT PROTECTIVE DEVICES. <br />4. INSTRUMENTATION. <br />5. CONTROL POWER. <br />6. ACCESSORY COMPONENTS AND FEATURES. <br />7. IDENTIFICATION. <br />1.2 SUBMITTALS <br />A. SHOP DRAWINGS: EQUIPMENT PROCURED BY OWNER. EQUIPMENT SUBMITTAL DRAWINGS PROVIDED FOR COORDINATION DURING CONSTRUCTION. <br />PART 2 - PRODUCTS <br />2.1 PERFORMANCE REQUIREMENTS <br />A. EQUIPMENT PROCURED AND PROVIDED BY OWNER. <br />2.2 IDENTIFICATION <br />A. SERVICE EQUIPMENT LABEL: NRTL LABELED FOR USE AS SERVICE EQUIPMENT FOR SWITCHBOARDS WITH ONE OR MORE SERVICE DISCONNECTING AND OVERCURRENT PROTECTIVE DEVICES. <br />PART 3 - EXECUTION <br />3.1 INSTALLATION <br />A. RECEIVE, INSPECT, HANDLE, AND STORE SWITCHBOARDS ACCORDING TO NEMA PB 2.1. <br />B. INSTALL SWITCHBOARDS AND ACCESSORIES ACCORDING TO NEMA PB 2.1. <br />C. EQUIPMENT MOUNTING: INSTALL SWITCHBOARDS ON CONCRETE BASE, 4-INCH (100-MM) NOMINAL THICKNESS. COMPLY WITH REQUIREMENTS FOR CONCRETE BASE SPECIFIED IN SECTION 033000 "CAST-IN- <br />PLACE CONCRETE." <br />INSTALL CONDUITS ENTERING UNDERNEATH THE SWITCHBOARD, ENTERING UNDER THE VERTICAL SECTION WHERE THE CONDUCTORS WILL TERMINATE. INSTALL WITH <br />COUPLINGS FLUSH WITH THE CONCRETE BASE. EXTEND 2 INCHES (50-MM) ABOVE CONCRETE BASE AFTER SWITCHBOARD IS ANCHORED IN PLACE. <br />FOR SUPPORTED EQUIPMENT, INSTALL EPOXY-COATED ANCHOR BOLTS THAT EXTEND THROUGH CONCRETE BASE AND ANCHOR INTO STRUCTURAL CONCRETE FLOOR. <br />PLACE AND SECURE ANCHORAGE DEVICES. USE SETTING DRAWINGS, TEMPLATES, DIAGRAMS, INSTRUCTIONS, AND DIRECTIONS FURNISHED WITH ITEMS TO BE EMBEDDED. <br />INSTALL ANCHOR BOLTS TO ELEVATIONS REQUIRED FOR PROPER ATTACHMENT TO SWITCHBOARDS. <br />D. TEMPORARY LIFTING PROVISIONS: REMOVE TEMPORARY LIFTING EYES, CHANNELS, STRAPS AND BRACKETS, AND TEMPORARY BLOCKING OF MOVING PARTS FROM SWITCHBOARD UNITS AND <br />COMPONENTS. <br />E. COMPLY WITH MOUNTING AND ANCHORING REQUIREMENTS SPECIFIED IN SECTION 260548.16 "SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS." <br />F. OPERATING INSTRUCTIONS: FRAME AND MOUNT THE PRINTED BASIC OPERATING INSTRUCTIONS FOR SWITCHBOARDS, INCLUDING CONTROL AND KEY INTERLOCKING SEQUENCES AND EMERGENCY <br />PROCEDURES. FABRICATE FRAME OF FINISHED WOOD OR METAL AND COVER INSTRUCTIONS WITH CLEAR ACRYLIC PLASTIC. MOUNT ON FRONT OF SWITCHBOARDS. <br />G. INSTALL FILLER PLATES IN UNUSED SPACES OF PANEL-MOUNTED SECTIONS. <br />H. INSTALL OVERCURRENT PROTECTIVE DEVICES, SURGE PROTECTION DEVICES, AND INSTRUMENTATION. <br />SET FIELD-ADJUSTABLE SWITCHES AND CIRCUIT-BREAKER TRIP RANGES. <br />I. COMPLY WITH NECA 1. <br />3.2 IDENTIFICATION <br />IDENTIFY FIELD-INSTALLED CONDUCTORS, INTERCONNECTING WIRING, AND COMPONENTS; PROVIDE WARNING SIGNS COMPLYING WITH REQUIREMENTS FOR IDENTIFICATION <br />SPECIFIED IN SECTION 260553 "IDENTIFICATION FOR ELECTRICAL SYSTEMS." <br />SWITCHBOARD NAMEPLATES: LABEL EACH SWITCHBOARD COMPARTMENT WITH A NAMEPLATE COMPLYING WITH REQUIREMENTS FOR IDENTIFICATION SPECIFIED IN SECTION 260553 <br />"IDENTIFICATION FOR ELECTRICAL SYSTEMS." <br />DEVICE NAMEPLATES: LABEL EACH DISCONNECTING AND OVERCURRENT PROTECTIVE DEVICE AND EACH METER AND CONTROL DEVICE MOUNTED IN COMPARTMENT DOORS WITH A <br />NAMEPLATE COMPLYING WITH REQUIREMENTS FOR IDENTIFICATION SPECIFIED IN SECTION 260553 "IDENTIFICATION FOR ELECTRICAL SYSTEMS." <br />FIELD QUALITY CONTROL <br />PERFORM THE FOLLOWING TESTS AND INSPECTIONS WITH THE ASSISTANCE OF A FACTORY-AUTHORIZED SERVICE REPRESENTATIVE: <br />ACCEPTANCE TESTING: <br />TEST INSULATION RESISTANCE FOR EACH SWITCHBOARD BUS, COMPONENT, CONNECTING SUPPLY, FEEDER, AND CONTROL CIRCUIT. OPEN CONTROL AND <br />METERING CIRCUITS WITHIN THE SWITCHBOARD, AND REMOVE NEUTRAL CONNECTION TO SURGE PROTECTION AND OTHER ELECTRONIC DEVICES PRIOR TO <br />INSULATION TEST. RECONNECT AFTER TEST. <br />TEST CONTINUITY OF EACH CIRCUIT. <br />2. TEST GROUND-FAULT PROTECTION OF EQUIPMENT FOR SERVICE EQUIPMENT PER NFPA 70. <br />3. PERFORM EACH VISUAL AND MECHANICAL INSPECTION AND ELECTRICAL TEST STATED IN NETA ACCEPTANCE TESTING SPECIFICATION. CERTIFY COMPLIANCE WITH TEST <br />PARAMETERS. <br />4. CORRECT MALFUNCTIONING UNITS ON-SITE WHERE POSSIBLE, AND RETEST TO DEMONSTRATE COMPLIANCE; OTHERWISE, REPLACE WITH NEW UNITS AND RETEST. <br />5. TEST AND ADJUST CONTROLS, REMOTE MONITORING, AND SAFETIES. REPLACE DAMAGED AND MALFUNCTIONING CONTROLS AND EQUIPMENT. <br />B. SWITCHBOARD WILL BE CONSIDERED DEFECTIVE IF IT DOES NOT PASS TESTS AND INSPECTIONS. <br />C. PREPARE TEST AND INSPECTION REPORTS, INCLUDING A CERTIFIED REPORT THAT IDENTIFIES SWITCHBOARDS INCLUDED AND THAT DESCRIBES SCANNING RESULTS. INCLUDE <br />NOTATION OF DEFICIENCIES DETECTED, REMEDIAL ACTION TAKEN, AND OBSERVATIONS AFTER REMEDIAL ACTION. <br />SECTION 262416 - PANELBOARDS <br />PART 1 - GENERAL <br />1.1 SUMMARY <br />SECTION INCLUDES: <br />DISTRIBUTION PANELBOARDS. <br />1.2 SUBMITTALS <br />SHOP DRAWINGS: EQUIPMENT PROCURED BY OWNER. EQUIPMENT SUBMITTAL DRAWINGS PROVIDED FOR COORDINATION DURING CONSTRUCTION. <br />PART 2 - PRODUCTS <br />2.1 PERFORMANCE REQUIREMENTS <br />EQUIPMENT PROCURED AND PROVIDED BY OWNER. <br />2.2 IDENTIFICATION <br />PANELBOARD LABEL: MANUFACTURER'S NAME AND TRADEMARK, VOLTAGE, AMPERAGE, NUMBER OF PHASES, AND NUMBER OF POLES SHALL BE LOCATED ON THE INTERIOR OF THE <br />PANELBOARD DOOR. <br />BREAKER LABELS: FACEPLATE SHALL LIST CURRENT RATING, UL AND IEC CERTIFICATION STANDARDS, AND AIC RATING. <br />C. CIRCUIT DIRECTORY: DIRECTORY CARD INSIDE PANELBOARD DOOR, MOUNTED IN METAL FRAME WITH TRANSPARENT PROTECTIVE COVER. <br />PART 3 - EXECUTION <br />3.1 INSTALLATION <br />COMPLY WITH NECA 1. <br />B. INSTALL PANELBOARDS AND ACCESSORIES ACCORDING TO NEMA PB 1.1. <br />C. COMPLY WITH MOUNTING AND ANCHORING REQUIREMENTS SPECIFIED IN SECTION 260548.16 "SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS." <br />D. MOUNT TOP OF TRIM 90 INCHES (2286 MM) ABOVE FINISHED FLOOR OR FINISHED GRADE UNLESS OTHERWISE INDICATED. <br />E. MOUNT PANELBOARD CABINET PLUMB AND RIGID WITHOUT DISTORTION OF BOX. <br />F. INSTALL OVERCURRENT PROTECTIVE DEVICES AND CONTROLLERS NOT ALREADY FACTORY INSTALLED. <br />SET FIELD-ADJUSTABLE, CIRCUIT-BREAKER TRIP RANGES. <br />G. MAKE GROUNDING CONNECTIONS AND BOND NEUTRAL FOR SERVICES AND SEPARATELY DERIVED SYSTEMS TO GROUND. MAKE CONNECTIONS TO GROUNDING ELECTRODES, <br />SEPARATE GROUNDS FOR ISOLATED GROUND BARS, AND CONNECTIONS TO SEPARATE GROUND BARS. <br />H. INSTALL FILLER PLATES IN UNUSED SPACES. <br />I.STUB FOUR 1-INCH (27-EMT) EMPTY CONDUITS FROM PANELBOARD INTO ACCESSIBLE CEILING SPACE OR SPACE DESIGNATED TO BE CEILING SPACE AT A LATER DATE FOR INTERIOR <br />MOUNTED PANELBOARDS. <br />J.ARRANGE CONDUCTORS IN GUTTERS INTO GROUPS AND BUNDLE AND WRAP WITH WIRE TIES. <br />3.2 IDENTIFICATION <br />IDENTIFY FIELD-INSTALLED CONDUCTORS, INTERCONNECTING WIRING, AND COMPONENTS; INSTALL WARNING SIGNS COMPLYING WITH REQUIREMENTS IN SECTION 260553 <br />"IDENTIFICATION FOR ELECTRICAL SYSTEMS." <br />CREATE A DIRECTORY TO INDICATE INSTALLED CIRCUIT LOADS; INCORPORATE OWNER'S FINAL DESIGNATIONS. OBTAIN APPROVAL BEFORE INSTALLING. HANDWRITTEN DIRECTORIES <br />ARE NOT ACCEPTABLE. INSTALL DIRECTORY INSIDE PANELBOARD DOOR. <br />PANELBOARD NAMEPLATES: LABEL EACH PANELBOARD WITH A NAMEPLATE COMPLYING WITH REQUIREMENTS FOR IDENTIFICATION SPECIFIED IN SECTION 260553 "IDENTIFICATION FOR <br />ELECTRICAL SYSTEMS." <br />DEVICE NAMEPLATES: LABEL EACH BRANCH CIRCUIT DEVICE IN POWER PANELBOARDS WITH A NAMEPLATE COMPLYING WITH REQUIREMENTS FOR IDENTIFICATION SPECIFIED IN <br />SECTION 260553 "IDENTIFICATION FOR ELECTRICAL SYSTEMS." <br />INSTALL WARNING SIGNS COMPLYING WITH REQUIREMENTS IN SECTION 260553 "IDENTIFICATION FOR ELECTRICAL SYSTEMS" IDENTIFYING SOURCE OF REMOTE CIRCUIT. <br />3.3 FIELD QUALITY CONTROL <br />PERFORM TESTS AND INSPECTIONS. <br />B. ACCEPTANCE TESTING PREPARATION: <br />TEST INSULATION RESISTANCE FOR EACH PANELBOARD BUS, COMPONENT, CONNECTING SUPPLY, FEEDER, AND CONTROL CIRCUIT. <br />2. TEST CONTINUITY OF EACH CIRCUIT. <br />C. TESTS AND INSPECTIONS: <br />PERFORM EACH VISUAL AND MECHANICAL INSPECTION AND ELECTRICAL TEST FOR LOW-VOLTAGE AIR CIRCUIT BREAKERS STATED IN NETA ATS. CERTIFY COMPLIANCE WITH <br />TEST PARAMETERS. <br />CORRECT MALFUNCTIONING UNITS ON-SITE, WHERE POSSIBLE, AND RETEST TO DEMONSTRATE COMPLIANCE; OTHERWISE, REPLACE WITH NEW UNITS AND RETEST. <br />D. PANELBOARDS WILL BE CONSIDERED DEFECTIVE IF THEY DO NOT PASS TESTS AND INSPECTIONS. <br />E. PREPARE TEST AND INSPECTION REPORTS, INCLUDING A CERTIFIED REPORT THAT IDENTIFIES PANELBOARDS INCLUDED AND THAT DESCRIBES SCANNING RESULTS, WITH <br />COMPARISONS OF THE TWO SCANS. INCLUDE NOTATION OF DEFICIENCIES DETECTED, REMEDIAL ACTION TAKEN, AND OBSERVATIONS AFTER REMEDIAL ACTION. <br />END OF SECTION 262416 <br />SECTION 262743 - ELECTRIC-VEHICLE SERVICE EQUIPMENT <br />PART 1 - GENERAL <br />1.1 SUMMARY <br />SECTION INCLUDES EVSE THAT PROVIDES AC LEVEL 2 AND LEVEL 3 EV CHARGING. <br />1.2 SUBMITTALS <br />SHOP DRAWINGS: EQUIPMENT PROCURED BY OWNER. EQUIPMENT SUBMITTAL DRAWINGS PROVIDED FOR COORDINATION DURING CONSTRUCTION. <br />B. PRODUCT SCHEDULE: USE SAME DESIGNATIONS INDICATED ON DRAWINGS. <br />PART 2 - PRODUCTS <br />2.1 PERFORMANCE REQUIREMENTS <br />EQUIPMENT PROCURED AND PROVIDED BY OWNER. <br />B. EV CHARGING LEVELS: <br />SINGLE OR DUAL VEHICLE, AC LEVEL 2 AT UP TO 10 KW PER VEHICLE. <br />2. SINGLE OR DUAL VEHICLE, AC LEVEL 3 AT UP TO 50 KW PER VEHICLE. <br />PART 3 - EXECUTION <br />3.1 INSTALLATION <br />COMPLY WITH NECA 1 AND NECA 413. <br />B. CONCRETE BASE MOUNTING: <br />INSTALL EVSE ON 6-INCH (150-MM) NOMINAL-THICKNESS CONCRETE BASE. COMPLY WITH REQUIREMENTS FOR CONCRETE BASE SPECIFIED IN SECTION 033000 "CAST-IN- <br />PLACE CONCRETE." <br />3.2 CONNECTIONS <br />CONNECT WIRING ACCORDING TO SECTION 260519 "LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES." <br />B. COMPLY WITH GROUNDING REQUIREMENTS IN SECTION 260526 "GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS." <br />C. COMPLY WITH REQUIREMENTS FOR INSTALLATION OF CONDUIT IN SECTION 260533 "RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS." DRAWINGS INDICATE GENERAL ARRANGEMENT <br />OF CONDUIT, FITTINGS, AND SPECIALTIES. <br />D. TIGHTEN ELECTRICAL CONNECTORS AND TERMINALS ACCORDING TO MANUFACTURER'S PUBLISHED TORQUE-TIGHTENING VALUES. IF MANUFACTURER'S TORQUE VALUES ARE NOT <br />INDICATED, USE THOSE SPECIFIED IN UL 486A-486B. <br />E. VERIFY THAT ALL ELECTRICAL CONNECTIONS HAVE BEEN MADE ACCORDING TO THE MANUFACTURER'S INSTRUCTIONS. REMOVE ALL BURRS, SHAVINGS, AND DETRITUS FROM INSIDE <br />THE ENCLOSURE. <br />F.AFTER CONFIRMING ALL CONNECTIONS, INSTALL COVERS AND TIGHTEN FASTENERS TO ACCORDING TO MANUFACTURER'S INSTRUCTIONS. <br />A. <br />A. <br />B. <br />1. <br />a. <br />A. <br />1. <br />A. <br />A. <br />1. <br />A. <br />A. <br />1. <br />1. <br />A. <br />B. <br />C. <br />1. <br />A. <br />1. <br />A. <br />B. <br />A. <br />1. <br />A. <br />1. <br />a. <br />1. <br />a. <br />1. <br />a. <br />a. <br />b. <br />c. <br />d. <br />1. <br />SECTION 262743 - ELECTRIC-VEHICLE SERVICE EQUIPMENT (CONTINUED) <br />3.3 IDENTIFICATION <br />IDENTIFY SYSTEM COMPONENTS, WIRING, CABLING, AND TERMINALS. COMPLY WITH REQUIREMENTS FOR IDENTIFICATION SPECIFIED IN SECTION 260553 "IDENTIFICATION FOR <br />ELECTRICAL SYSTEMS." <br />3.4 FIELD QUALITY CONTROL <br />MANUFACTURER'S FIELD SERVICE: ENGAGE A FACTORY-AUTHORIZED SERVICE REPRESENTATIVE TO TEST AND INSPECT COMPONENTS, ASSEMBLIES, AND EQUIPMENT INSTALLATIONS, <br />INCLUDING CONNECTIONS. <br />PERFORM TESTS AND INSPECTIONS WITH THE ASSISTANCE OF A FACTORY-AUTHORIZED SERVICE REPRESENTATIVE. <br />C. TESTS AND INSPECTIONS: <br />FOR EACH UNIT OF EVSE, PERFORM THE FOLLOWING TESTS AND INSPECTIONS: <br />UNIT SELF-TEST. <br />b. OPERATION TEST WITH LOAD BANK. <br />D. EVSE WILL BE CONSIDERED DEFECTIVE IF IT DOES NOT PASS TESTS AND INSPECTIONS. <br />E. PREPARE TEST AND INSPECTION REPORTS. <br />END OF SECTION 262743 <br />SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS <br />PART 1 - GENERAL <br />1.1 SUMMARY <br />SECTION INCLUDES: <br />FUSIBLE SWITCHES. <br />2. NONFUSIBLE SWITCHES. <br />3. ENCLOSURES. <br />1.2 SUBMITTALS <br />PRODUCT DATA: FOR EACH TYPE OF ENCLOSED SWITCH, ACCESSORY, AND COMPONENT INDICATED. INCLUDE NAMEPLATE RATINGS, DIMENSIONED ELEVATIONS, SECTIONS, WEIGHTS, <br />AND MANUFACTURERS' TECHNICAL DATA ON FEATURES, PERFORMANCE, ELECTRICAL CHARACTERISTICS, RATINGS, ACCESSORIES, AND FINISHES. <br />1.3 WARRANTY <br />MANUFACTURER'S WARRANTY: MANUFACTURER AND INSTALLER AGREE TO REPAIR OR REPLACE COMPONENTS THAT FAIL IN MATERIALS OR WORKMANSHIP WITHIN SPECIFIED <br />WARRANTY PERIOD. <br />WARRANTY PERIOD: ONE YEAR FROM DATE OF SUBSTANTIAL COMPLETION. <br />PART 2 - PRODUCTS <br />2.1 GENERAL REQUIREMENTS <br />SOURCE LIMITATIONS: OBTAIN ENCLOSED SWITCHES, COMPONENTS, AND ACCESSORIES, WITHIN SAME PRODUCT CATEGORY, FROM SINGLE MANUFACTURER. <br />B. ELECTRICAL COMPONENTS, DEVICES, AND ACCESSORIES: LISTED AND LABELED AS DEFINED IN NFPA 70, BY AN NRTL, AND MARKED FOR INTENDED LOCATION AND APPLICATION. <br />C. COMPLY WITH NFPA 70. <br />2.2 FUSIBLE SWITCHES <br />TYPE HD, HEAVY DUTY: <br />SINGLE THROW. <br />2. THREE POLE. <br />3. 600-V AC. <br />4. 200 A AND SMALLER. <br />5. UL 98 AND NEMA KS 1, HORSEPOWER RATED, WITH CLIPS OR BOLT PADS TO ACCOMMODATE SPECIFIED FUSES. <br />6. LOCKABLE HANDLE WITH CAPABILITY TO ACCEPT THREE PADLOCKS, AND INTERLOCKED WITH COVER IN CLOSED POSITION. <br />B. ACCESSORIES: <br />EQUIPMENT GROUND KIT: INTERNALLY MOUNTED AND LABELED FOR COPPER AND ALUMINUM GROUND CONDUCTORS. <br />2. NEUTRAL KIT: INTERNALLY MOUNTED; INSULATED, CAPABLE OF BEING GROUNDED AND BONDED; LABELED FOR COPPER AND ALUMINUM NEUTRAL CONDUCTORS. <br />3. SERVICE-RATED SWITCHES: LABELED FOR USE AS SERVICE EQUIPMENT. <br />2.3 NONFUSIBLE SWITCHES <br />TYPE GD, GENERAL DUTY, THREE POLE, SINGLE THROW, 240-V AC, 600 A AND SMALLER: UL 98 AND NEMA KS 1, HORSEPOWER RATED, LOCKABLE HANDLE WITH CAPABILITY TO ACCEPT <br />TWO PADLOCKS, AND INTERLOCKED WITH COVER IN CLOSED POSITION. <br />TYPE HD, HEAVY DUTY, SIX POLE, SINGLE THROW, 600-V AC, 200 A AND SMALLER: UL 98 AND NEMA KS 1, HORSEPOWER RATED, LOCKABLE HANDLE WITH CAPABILITY TO ACCEPT THREE <br />PADLOCKS, AND INTERLOCKED WITH COVER IN CLOSED POSITION. <br />ACCESSORIES: <br />EQUIPMENT GROUND KIT: INTERNALLY MOUNTED AND LABELED FOR COPPER AND ALUMINUM GROUND CONDUCTORS. <br />2. NEUTRAL KIT: INTERNALLY MOUNTED; INSULATED, CAPABLE OF BEING GROUNDED AND BONDED; LABELED FOR COPPER AND ALUMINUM NEUTRAL CONDUCTORS. <br />3. SERVICE-RATED SWITCHES: LABELED FOR USE AS SERVICE EQUIPMENT. <br />PART 3 - EXECUTION <br />3.1 ENCLOSURE ENVIRONMENTAL RATING APPLICATIONS <br />ENCLOSED SWITCHES AND CIRCUIT BREAKERS: PROVIDE ENCLOSURES AT INSTALLED LOCATIONS WITH THE FOLLOWING ENVIRONMENTAL RATINGS. <br />INDOOR, DRY AND CLEAN LOCATIONS: NEMA 250, TYPE 1. <br />2. OUTDOOR LOCATIONS: NEMA 250, TYPE 3R. <br />3.2 INSTALLATION <br />COORDINATE LAYOUT AND INSTALLATION OF SWITCHES AND COMPONENTS WITH EQUIPMENT SERVED AND ADJACENT SURFACES. MAINTAIN REQUIRED WORKSPACE CLEARANCES AND <br />REQUIRED CLEARANCES FOR EQUIPMENT ACCESS DOORS AND PANELS. <br />INSTALL INDIVIDUAL WALL-MOUNTED SWITCHES WITH TOPS AT UNIFORM HEIGHT UNLESS OTHERWISE INDICATED. <br />C. COMPLY WITH MOUNTING AND ANCHORING REQUIREMENTS SPECIFIED IN SECTION 260548.16 "SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS." <br />D. INSTALL FUSES IN FUSIBLE DEVICES. <br />E. COMPLY WITH NFPA 70 AND NECA 1. <br />3.3 IDENTIFICATION <br />COMPLY WITH REQUIREMENTS IN SECTION 260553 "IDENTIFICATION FOR ELECTRICAL SYSTEMS." <br />IDENTIFY FIELD-INSTALLED CONDUCTORS, INTERCONNECTING WIRING, AND COMPONENTS; PROVIDE WARNING SIGNS. <br />2. LABEL EACH ENCLOSURE WITH ENGRAVED METAL OR LAMINATED-PLASTIC NAMEPLATE. <br />3.4 FIELD QUALITY CONTROL <br />PERFORM TESTS AND INSPECTIONS. <br />B. TESTS AND INSPECTIONS FOR SWITCHES: <br />VISUAL AND MECHANICAL INSPECTION: <br />INSPECT PHYSICAL AND MECHANICAL CONDITION. <br />b. INSPECT ANCHORAGE, ALIGNMENT, GROUNDING, AND CLEARANCES. <br />c. VERIFY THAT THE UNIT IS CLEAN. <br />d. VERIFY BLADE ALIGNMENT, BLADE PENETRATION, TRAVEL STOPS, AND MECHANICAL OPERATION. <br />e. VERIFY THAT FUSE SIZES AND TYPES MATCH THE DRAWINGS. <br />f.VERIFY THAT EACH FUSE HAS ADEQUATE MECHANICAL SUPPORT AND CONTACT INTEGRITY. <br />g. INSPECT BOLTED ELECTRICAL CONNECTIONS FOR HIGH RESISTANCE USING ONE OF THE TWO FOLLOWING METHODS: <br />USE A LOW-RESISTANCE OHMMETER. <br />COMPARE BOLTED CONNECTION RESISTANCE VALUES TO VALUES OF SIMILAR CONNECTIONS. INVESTIGATE VALUES THAT DEVIATE FROM <br />THOSE OF SIMILAR BOLTED CONNECTIONS BY MORE THAN 50 PERCENT OF THE LOWEST VALUE. <br />VERIFY TIGHTNESS OF ACCESSIBLE BOLTED ELECTRICAL CONNECTIONS BY CALIBRATED TORQUE-WRENCH METHOD IN ACCORDANCE WITH <br />MANUFACTURER'S PUBLISHED DATA OR NETA ATS TABLE 100.12. <br />BOLT-TORQUE LEVELS SHALL BE IN ACCORDANCE WITH MANUFACTURER'S PUBLISHED DATA. IN THE ABSENCE OF MANUFACTURER'S <br />PUBLISHED DATA, USE NETA ATS TABLE 100.12. <br />h. VERIFY THAT OPERATION AND SEQUENCING OF INTERLOCKING SYSTEMS IS AS DESCRIBED IN THE SPECIFICATIONS AND SHOWN ON THE DRAWINGS. <br />i.VERIFY CORRECT PHASE BARRIER INSTALLATION. <br />j.VERIFY LUBRICATION OF MOVING CURRENT-CARRYING PARTS AND MOVING AND SLIDING SURFACES. <br />2. ELECTRICAL TESTS: <br />PERFORM RESISTANCE MEASUREMENTS THROUGH BOLTED CONNECTIONS WITH A LOW-RESISTANCE OHMMETER. COMPARE BOLTED CONNECTION RESISTANCE <br />VALUES TO VALUES OF SIMILAR CONNECTIONS. INVESTIGATE VALUES THAT DEVIATE FROM ADJACENT POLES OR SIMILAR SWITCHES BY MORE THAN 50 PERCENT <br />OF THE LOWEST VALUE. <br />MEASURE CONTACT RESISTANCE ACROSS EACH SWITCHBLADE FUSEHOLDER. DROP VALUES SHALL NOT EXCEED THE HIGH LEVEL OF THE MANUFACTURER'S <br />PUBLISHED DATA. IF MANUFACTURER'S PUBLISHED DATA ARE NOT AVAILABLE, INVESTIGATE VALUES THAT DEVIATE FROM ADJACENT POLES OR SIMILAR <br />SWITCHES BY MORE THAN 50 PERCENT OF THE LOWEST VALUE. <br />PERFORM INSULATION-RESISTANCE TESTS FOR ONE MINUTE ON EACH POLE, PHASE-TO-PHASE AND PHASE-TO-GROUND WITH SWITCH CLOSED, AND ACROSS <br />EACH OPEN POLE. APPLY VOLTAGE IN ACCORDANCE WITH MANUFACTURER'S PUBLISHED DATA. IN THE ABSENCE OF MANUFACTURER'S PUBLISHED DATA, USE <br />TABLE 100.1 FROM THE NETA ATS. INVESTIGATE VALUES OF INSULATION RESISTANCE LESS THAN THOSE PUBLISHED IN TABLE 100.1 OR AS RECOMMENDED IN <br />MANUFACTURER'S PUBLISHED DATA. <br />MEASURE FUSE RESISTANCE. INVESTIGATE FUSE-RESISTANCE VALUES THAT DEVIATE FROM EACH OTHER BY MORE THAN 15 PERCENT. <br />e. PERFORM GROUND FAULT TEST ACCORDING TO NETA ATS 7.14 "GROUND FAULT PROTECTION SYSTEMS, LOW-VOLTAGE." <br />C. ENCLOSED SWITCHES WILL BE CONSIDERED DEFECTIVE IF THEY DO NOT PASS TESTS AND INSPECTIONS. <br />D. PREPARE TEST AND INSPECTION REPORTS. <br />TEST PROCEDURES USED. <br />2. INCLUDE IDENTIFICATION OF EACH ENCLOSED SWITCH TESTED AND DESCRIBE TEST RESULTS. <br />3. LIST DEFICIENCIES DETECTED, REMEDIAL ACTION TAKEN, AND OBSERVATIONS AFTER REMEDIAL ACTION. <br />END OF SECTION 262816 <br />PH: <br />RE <br />V <br />I <br />S <br />I <br />O <br />N <br />DA <br />T <br />E <br />2/ <br />1 <br />9 <br />/ <br />2 <br />5 <br />Ci <br />t <br />y <br /> <br />o <br />f <br /> <br />C <br />a <br />r <br />l <br />s <br />b <br />a <br />d <br /> <br />C <br />o <br />m <br />m <br />e <br />n <br />t <br />s <br />A <br />45 <br />0 <br /> <br />L <br />A <br />M <br />B <br />E <br />R <br />T <br /> <br />A <br />V <br />E <br />, <br /> <br />P <br />A <br />L <br />O <br /> <br />A <br />L <br />T <br />O <br />, <br /> <br />C <br />A <br /> <br />9 <br />4 <br />3 <br />0 <br />6 <br />(8 <br />8 <br />8 <br />) <br /> <br />3 <br />4 <br />2 <br />- <br />7 <br />3 <br />8 <br />3 <br />ORIGINAL SIZE 24"X36" <br />REV: <br />PROJ: <br />DL <br />X <br />8 <br /> <br />E <br />L <br />E <br />C <br />T <br />R <br />I <br />C <br /> <br />V <br />E <br />H <br />I <br />C <br />L <br />E <br /> <br />C <br />H <br />A <br />R <br />G <br />I <br />N <br />G <br /> <br />S <br />T <br />A <br />T <br />I <br />O <br />N <br />S <br />51 <br />5 <br /> <br />E <br />A <br />S <br />T <br /> <br />D <br />Y <br />E <br />R <br /> <br />R <br />O <br />A <br />D <br />SA <br />N <br />T <br />A <br /> <br />A <br />N <br />A <br />, <br /> <br />C <br />A <br /> <br />9 <br />2 <br />7 <br />0 <br />7 <br />BSE14-2 <br />DLX8_EV_OSP <br />ALEXANDER SHORTS <br />PROFESSIONA L ENGINEER <br />ELECTRICALSTATE OF CALIFORNIA <br />E 21782 <br />7/ <br />1 <br />4 <br />/ <br />2 <br />5 <br />Ut <br />i <br />l <br />i <br />t <br />y <br /> <br />t <br />r <br />e <br />n <br />c <br />h <br /> <br />p <br />a <br />t <br />h <br />B <br />9/22/25 <br />SS <br />B <br />J <br /> <br />U <br />p <br />s <br />i <br />z <br />e <br />, <br /> <br />G <br />e <br />n <br />e <br />r <br />a <br />t <br />o <br />r <br /> <br />s <br />e <br />c <br />t <br />i <br />o <br />n <br />C <br />9/ <br />2 <br />2 <br />/ <br />2 <br />5 <br />ELECTRICAL <br />SPECIFICATIONS <br />E0.4 <br />IFP C