Laserfiche WebLink
STRUCTURAL NOTES <br />FOUNDATION <br />1. <br />2. <br />3. <br />4. <br />5. <br />6. <br />7. <br />8. <br />9. <br />10. <br />11. <br />FOUNDATION DESIGN IS BASED ON THE GEOTECHNICAL INVESTIGATION REPORT BY ASSOCIATED <br />SOILS ENGINEER, INC. <br />FOOTINGS ARE DESIGNED BASED ON THE FOLLOWING INFORMATION: <br />ALLOWABLE NET BEARING = 3000 PSF (2500 PSF MAX) <br />PASSIVE EARTH PRESSURE = 200 PSF/FT (2000 PSF MAX) <br />COEFFICIENT OF FRICTION = 0.35 <br />MODULUS OF SUBGRADE REACTION = 100 PCI <br />ALLOWABLE BEARING AND PASSIVE PRESSURE VALUES MAY BE INCREASED BY 1/3 FOR WIND AND <br />SEISMIC WHEN ALTERNATIVE BASIC LOAD COMBINATIONS ARE USED. ALLOWABLE BEARING MAY BE <br />INCREASED BY 1/3 FOR WIND AND SEISMIC. MINIMUM DEPTH OF FOOTING BELOW LOWEST ADJACENT <br />FINAL GRADE SHALL BE 1'-6". MINIMUM WIDTH OF FOOTING SHALL BE 2'-0" FOR ISOLATED FOOTINGS <br />AND 1'-3" FOR CONTINUOUS FOOTINGS. ALLOWABLE BEARING PRESSURE MAY BE INCREASED 300 <br />PSF PER EACH ADDITIONAL FOOT OF DEPTH AND 100 PSF PER EACH ADDITIONAL FOOT OF WIDTH TO <br />A MAX VALUE OF 3000 PSF. FRICTIONAL RESISTANCE AND PASSIVE RESISTANCE MAY BE COMBINED <br />PROVIDED THE PASSIVE IS REDUCED BY ONE-THIRD. TO DETERMINE COMPOSITE LATERAL <br />RESISTANCE, WHICH MAY BE INCREASED BY 1/3 UNDER SHORT TERM, TRANSIENT WIND/SEISMIC <br />LOADING. <br />FOR ANY NEW FOOTINGS THAT ARE WITHIN A LATERAL DISTANCE FROM ANY EXISTING BUILDING <br />FOOTING EQUAL TO THE DEPTH OF THE NEW FOOTING (D), THE FOLLOWING TABULATED REDUCTION <br />FACTORS SHOULD BE APPLIED TO THE CORRESPONDING ALLOWABLE SOILS BEARING CAPACITY <br />VALUES. <br />CONTRACTOR SHALL PROVIDE FOR DESIGN AND INSTALLATION OF ALL CRIBBING, SHEATHING AND <br />SHORING REQUIRED AND SHALL BE SOLELY RESPONSIBLE FOR ALL EXCAVATION PROCEDURES <br />INCLUDING LAGGING, SHORING AND PROTECTION OF ADJACENT PROPERTY, STRUCTURES, STREETS <br />AND UTILITIES IN ACCORDANCE WITH ALL NATIONAL, STATE AND LOCAL SAFETY ORDINANCES. <br />EXCAVATION FOR FOOTINGS SHALL BE APPROVED BY THE INSPECTOR AND SOILS ENGINEER PRIOR <br />TO PLACING THE CONCRETE AND REINFORCING. CONTRACTOR TO NOTIFY THE INSPECTOR WHEN <br />INSPECTION OF EXCAVATION IS READY. INSPECTOR TO SUBMIT LETTER OF COMPLIANCE. <br />ALL EXCAVATIONS SHALL BE PROPERLY BACKFILLED. DO NOT PLACE BACKFILL BEHIND RETAINING <br />WALLS BEFORE CONCRETE OR GROUT HAS ATTAINED FULL DESIGN STRENGTH. CONTRACTORS <br />SHALL BRACE OR PROTECT ALL BUILDING AND PIT WALLS BELOW GRADE FROM LATERAL LOADS <br />UNTIL ATTACHING FLOORS ARE COMPLETELY IN PLACE AND HAVE ATTAINED FULL STRENGTH. <br />CONTRACTOR SHALL PROVIDE FOR DESIGN, PERMITS AND INSTALLATION OF SUCH BRACING. <br />FOUNDATIONS SHALL BE PLACED AND ESTIMATED ACCORDING TO DEPTHS SHOWN ON DRAWINGS. <br />SHOULD SOIL ENCOUNTERED AT THESE DEPTHS NOT BE APPROVED BY THE INSPECTOR OR SOILS <br />ENGINEER, FOUNDATION ELEVATIONS/DIMENSIONS MAY NEED TO BE MODIFIED BY THE ENGINEER. <br />FOOTING BACKFILL AND UTILITY TRENCH BACKFILL WITHIN BUILDING AREA SHALL BE MECHANICALLY <br />COMPACTED IN LAYERS IN ACCORDANCE WITH THE SOILS REPORT AND APPROVED BY THE SOILS <br />ENGINEER. FLOODING WILL NOT BE PERMITTED. ALL FILLS USED TO SUPPORT FOUNDATIONS SHALL <br />BE INSPECTED BY THE SOILS ENGINEER REPRESENTATIVE PER CODE SECTION 1704.7. <br />ALL ABANDONED FOOTINGS, UTILITIES, ETC. SHALL BE REMOVED UNLESS NOTED OTHERWISE. NEW <br />FOOTINGS MUST EXTEND INTO UNDISTURBED SOILS OR FOUNDED ON STRUCTURALLY CERTIFIED <br />FILL PER THE SOILS REPORT. <br />SLABS ON GRADE SHALL BE SUPPORTED ON UNDISTURBED NATURAL EARTH MATERIALS OR <br />PROPERLY CONTROLLED FILL MATERIALS AS PER THE RECOMMENDATIONS OF THE SOILS REPORT. <br />REINFORCING STEEL <br />1. <br />2. <br />3. <br />4. <br />5. <br />6. <br />7. <br />8. <br />9. <br />10. <br />11. <br />12. <br />13. <br />REINFORCING BARS SHALL CONFORM TO THE REQUIREMENTS OF CHAPTER 19 OF THE <br />CODE, ASTM A615, GRADE 60 UNO. DEFORMATIONS SHALL BE IN ACCORDANCE WITH <br />ASTM A-305. <br />BARS SHALL BE CLEAN OF RUST, GREASE, OR OTHER MATERIALS LIKELY TO IMPAIR <br />BOND. ALL REINFORCING BAR BENDS SHALL BE MADE COLD. <br />WELDED WIRE FABRIC SHALL CONFORM TO ASTM A-185. PROVIDE LAPS AS PER ACI <br />318-14 SECTION 25.5, 8" MINIMUM. WWF SHALL BE SUPPORTED ON APPROVED CHAIRS. <br />REINFORCING BAR SPLICES SHALL BE MADE AS INDICATED ON THE DRAWINGS. <br />MINIMUM SPLICE LENGTH FOR REINFORCING STEEL BARS IN MASONRY SHALL BE 48 <br />BAR DIAMETERS, 24" MINIMUM. MINIMUM SPLICE LENGTH FOR REINFORCING STEEL <br />BARS IN CONCRETE SHALL BE PER ACI 318. LAP ALL HORIZONTAL BARS AT CORNERS <br />AND INTERSECTIONS. <br />ALL BARS SHALL BE MARKED SO THEIR IDENTIFICATION CAN BE MADE WHEN THE FINAL <br />IN-PLACE INSPECTION IS MADE. <br />WHERE WELDING OF REINFORCING IS APPROVED BY THE STRUCTURAL ENGINEER, IT <br />SHALL BE DONE BY AWS CERTIFIED WELDERS USING E90XX OR APPROVED ELECTRODES. WELDING <br />PROCEDURES SHALL CONFORM TO THE REQUIREMENTS OF STRUCTURAL WELDING CODE- <br />REINFORCING STEEL", AWS-D1.4, LATEST REVISION. REINFORCING BARS TO BE WELDED SHALL <br />CONFORM TO THE REQUIREMENTS OF ASTM A-706. <br />BARS IN SLABS SHALL BE SECURELY SUPPORTED ON WELL-CURED CONCRETE BLOCKS OR <br />APPROVED METAL CHAIRS, PRIOR TO PLACING CONCRETE. <br />REINFORCING STEEL SHALL BE DETAILED IN ACCORDANCE WITH THE "ACI MANUAL OF <br />STANDARD PRACTICE FOR DETAILING REINFORCED CONCRETE STRUCTURES", LATEST EDITION. <br />COMPLETE AND DETAILED REINFORCING PLACEMENT DRAWINGS SHALL BE PREPARED <br />AND SUBMITTED TO THE ARCHITECT FOR REVIEW BY THE STRUCTURAL ENGINEER PRIOR <br />TO FABRICATION IN ACCORDANCE WITH THE SPECIFICATIONS AND APPLICABLE CODES. <br />THESE DRAWINGS SHALL BE AVAILABLE ON THE JOB SITE PRIOR TO PLACING OF CONCRETE. <br />MILL TEST REPORTS FOR GRADE 60 BARS SHALL BE SUBMITTED PRIOR TO PLACEMENT <br />OF CONCRETE. <br />CONTINUOUS INSPECTION OF CONCRETE SHALL INCLUDE INSPECTION DURING <br />INSTALLATION OF REINFORCING STEEL. INSPECTION SHALL BE SCHEDULED SO THAT <br />PLACEMENT OF REINFORCING STEEL, CONDUIT, SLEEVES, AND EMBEDDED ITEMS MAY BE <br />CORRECTED PRIOR TO PLACEMENT OF OVERLYING GRIDS OR REINFORCING STEEL. <br />ALL GRADE 60 REINFORCING STEEL SHALL BE CLEARLY MARKED TO DIFFERENTIATE <br />THEM FROM GRADE 40 REINFORCING STEEL IF CONCURRENTLY ON SITE. <br />CONCRETE PROTECTION FOR REINFORCEMENT <br />THE FOLLOWING MINIMUM CONCRETE COVER SHALL BE MINIMUM <br />PROVIDED FOR REINFORCEMENT: COVER, IN. <br /> <br />A. CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH 3 <br />B, CONCRETE EXPOSED TO EARTH OR WEATHER: <br />NO. 6 THROUGH NO. 18 BAR 2 <br />NO 5 BAR, W31 OR D31 WIRE & SMALLER 1 1/2 <br />C. CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT WITH GROUND: <br />SLABS, WALLS, JOISTS: <br /> NO. 14 AND NO. 18 BAR 1 1/2 <br /> NO. 11 BAR & SMALLER 3/4 <br />BEAMS, COLUMNS: <br /> PRIMARY REINFORCEMENT TIES, STIRRUPS, SPIRALS 1 1/2 <br />ALL CONCRETE CONSTRUCTION SHALL CONFORM WITH CHAPTER 19 OF THE CODE AND <br />WITH THE PROVISIONS OF ACI 318-19. <br />REINFORCED CONCRETE WAS DESIGNED BY THE "ULTIMATE STRENGTH DESIGN METHOD". <br />CONCRETE MIXES SHALL BE DESIGNED BY AN APPROVED TESTING LABORATORY AND <br />REVIEWED BY THE STRUCTURAL ENGINEER. THE COMPRESSIVE STRENGTH AND <br />DURABILITY OF THE CONCRETE SHALL BE PROPORTIONED BASED ACI 318-19 AND CBC <br />CHAPTER 19. <br />SCHEDULE OF STRUCTURAL CONCRETE 28-DAY STRENGTH AND TYPES (UNO): <br />PORTLAND CEMENT SHALL CONFORM TO ASTM C-150, TYPE II/V. <br />AGGREGATE FOR HARDROCK CONCRETE SHALL CONFORM TO ALL REQUIREMENTS AND <br />TESTS OF ASTM C-33 AND PROJECT SPECIFICATIONS. EXCEPTIONS MAY BE USED ONLY <br />WITH PERMISSION OF THE STRUCTURAL ENGINEER. <br />AGGREGATE FOR LIGHT WEIGHT (110PCF) CONCRETE SHALL BE EXPANDED CONFORMING <br />TO ASTM C330 AND PROJECT SPECIFICATIONS. EXCEPTIONS MAY BE USED ONLY WITH <br />PERMISSION OF THE STRUCTURAL ENGINEER. <br />CONCRETE MIXING OPERATION, ETC. SHALL CONFORM TO ASTM C-94. <br />PLACEMENT OF CONCRETE SHALL CONFORM TO CODE SECTION 1905 AND PROJECT <br />SPECIFICATIONS. CLEAN AND ROUGHEN TO 1/4" AMPLITUDE ALL CONCRETE SURFACES <br />AGAINST WHICH NEW CONCRETE IS TO BE PLACED. <br />ALL REINFORCING BARS, ANCHOR BOLTS AND OTHER CONCRETE INSERTS SHALL BE WELL <br />SECURED IN POSITION PRIOR TO PLACING CONCRETE. <br />PROVIDE SLEEVES FOR PLUMBING AND ELECTRICAL OPENINGS IN CONCRETE BEFORE <br />PLACING. DO NOT CUT ANY REINFORCING WHICH MAY CONFLICT. CORING IN CONCRETE <br />IS NOT PERMITTED. NOTIFY THE STRUCTURAL ENGINEER IN ADVANCE OF CONDITIONS <br />NOT SHOWN ON THE DRAWINGS. SEE THESE DRAWINGS FOR ADDITIONAL RESTRICTIONS <br />ON THE PLACEMENT OF OPENINGS IN SLABS AND WALLS. <br />PIPES LARGER THAN 1-1/2" DIAMETER SHALL NOT BE EMBEDDED IN STRUCTURAL <br />CONCRETE EXCEPT WHERE SPECIFICALLY APPROVED BY STRUCTURAL ENGINEER. PIPES <br />SHALL NOT DISPLACE OR INTERRUPT REINFORCING BARS, SPACE EMBEDDED PIPES AND <br />SLEEVES AT A MINIMUM OF 3 DIAMETERS. <br />CONCRETE <br />1. <br />2. <br />3. <br />4. <br />5. <br />6. <br />7. <br />8. <br />9. <br />10. <br />11. <br />12. <br /> MIN MAX MAX MAX MAX <br />LOCATION IN STRUCTURE STRENGTH DENSITY SLUMP WATER/CEMENT AGGREGATE <br />(PSI) (PCF) (IN) RATIO SIZE (IN) <br />ALL CONCRETE FOOTINGS 5000 145 4 0.5 1 <br />SLAB ON GRADE, CURBS 4000 145 4 0.5 3/4 <br />LWC FILLED METAL DECK 4000 115 4 0.45 3/4 <br />CONCRETE SHEAR WALL 5000 145 4 0.5 1 <br />FLOOR AND ROOF LIVE LOADS: <br />ROOF 20 PSF (REDUCIBLE) <br />CLASSROOM AREA 50 PSF <br />SNOW LOADS: <br />SNOW LOADS ARE IN ACCORDANCE WITH SECTION 1608 OF THE CODE. <br />GROUND SNOW LOAD, Pg = ZERO <br />WIND LOADS: <br />WIND LOADS ARE IN ACCORDANCE WITH SECTION 1609 OF THE CBC AND ASCE 7-16. <br />BASIC WIND SPEED, V = 95 MPH (3-SECOND GUST) <br />WIND EXPOSURE C <br />WIND RISK CATEGORY = II <br />BUILDING HEIGHT < 60 FT <br />ENCLOSED BUILDING, GCpi = +/- 0.18 <br />EARTHQUAKE LOADS ON PRIMARY STRUCTURE: <br />EARTHQUAKE LOADS ARE IN ACCORDANCE WITH SECTION 1613 OF THE CBC AND <br />ASCE 7-16. <br />SEISMIC LOADING IS PER THE EQUIVALENT LATERAL FORCE PROCEDURE IN <br />ACCORDANCE WITH ASCE 7-16 SECTION 12.8. <br />LOCATION: 34.18618 LAT, -118.58325 LON <br />SS = 1.284g <br />S1 = 0.458g <br />Fa = 1.0 <br />Fv = 1.842 <br />SMS = 1.284g <br />SM1 = 0.844g <br />SDS = 0.856g <br />SD1 = 0.562g <br />RISK CATEGORY II <br />SITE CLASS D <br />SEISMIC DESIGN CATEGORY D <br />SPECIAL RC SHEAR WALL <br />le = 1.0 <br />R = 5 <br />Ωo = 2.5 <br />Cd = 5 <br />rho = 1.3 <br />WOOD SHEAR WALL <br />le = 1.0 <br />R = 6.5 <br />Ωo = 3 <br />Cd = 4 <br />rho = 1.3 <br />DESIGN <br />1. <br />2. <br />3. <br />4. <br />5.EARTHQUAKE LOADS ON NON-STRUCTURAL COMPONENTS: <br />EARTHQUAKE LOADS ARE IN ACCORDANCE WITH SECTION 1613 OF THE CODE. <br />Ip = 1.0 FOR ALL NONSTRUCTURAL COMPONENTS EARTHQUAKE LOADS ON NONSTRUCTURAL <br />COMPONENTS, SHALL BE DETERMINED IN ACCORDANCE WITH THE FOLLOWING PROCEDURE: <br />CALCULATE Fp BASED ON ASCE 7-16 EQUATION 13.3-1 <br />THE MAXIMUM AND MINIMUM VALUES FOR Fp SHALL BE DETERMINED FROM ASCE 7-16 <br />EQUATIONS 13.3-2 AND 13.3-3, RESPECTIVELY. <br />ALL EARTHQUAKE LOADS ON NONSTRUCTURAL COMPONENTS SHALL BE BASED ON THE <br />VALUES OF ap AND Rp FROM ASCE 7-16 TABLES 13.5-1 AND 13.6-1. <br />PER THE GEOTECHNICAL INVESTIGATION REPORT THE PROJECT IS LOCATED WITHIN A <br />LIQUEFACTION HAZARD ZONE. IT IS NOT WITHIN A STATE OF CALIFORNIA ALQUIST PRIOLO <br />EARTHQUAKE FAULT ZONE. <br />STRUCTURAL STEEL <br />1. <br />2. <br />3. <br />4. <br />5. <br />6. <br />7. <br />8. <br />9. <br />10. <br />11. <br />12. <br />13. <br />STRUCTURAL STEEL SHALL BE DETAILED, FABRICATED AND ERECTED BY AN APPROVED AND <br />LICENSED FABRICATOR IN ACCORDANCE WITH THE AISC SPECIFICATION FOR DESIGN, <br />FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS (LATEST EDITION), AND <br />WITH CHAPTER 22 OF THE CODE. <br />ALL STRUCTURAL STEEL SHALL CONFORM WITH THE ASTM DESIGNATION AS INDICATED BELOW <br />(UNO): <br />WF SHAPES, WT SHAPES A992 OR A572, GRADE 50 <br />(MULTI CERT) <br />PLATES, CONNECTION PLATES,A-36, UNO <br />AND MISC, UNO. <br />PIPE COLUMNS A-53, GRADE B <br />TUBE SECTIONS A-500, GRADE B <br />BOLTS A-325 / A-490, AS NOTED ON DWGS <br />ANCHOR BOLTS IN CONCRETE/MASONRY F-1554, GRADE 36 <br />ANGLES, CHANNELS A-36 <br />THE STRUCTURAL STEEL FABRICATOR SHALL FURNISH SHOP DRAWINGS TO THE ARCHITECT <br />OF ALL STEEL FOR ARCHITECTS AND STRUCTURAL ENGINEERS TO REVIEW AND APPROVAL <br />BEFORE FABRICATION. <br />BOLT HOLES USED IN STEEL SHALL BE 1/16" LARGER IN DIAMETER THAN NORMAL SIZE OF BOLT <br />USED, EXCEPT AS NOTED. <br />ALL STRUCTURAL STEEL SURFACES THAT ARE ENCASED IN CONCRETE, OR MASONRY, SPRAY <br />ON FIREPROOFING, OR ARE ENCASED BY BUILDING FINISH, SHALL BE LEFT UNPAINTED. <br />ALL WELDING IS TO BE DONE BY CERTIFIED WELDERS USING E70XX ELECTRODES (UNO). ALL <br />WELDS SHALL BE IN CONFORMITY WITH THE PROJECTS SPECIFICATIONS AND FOR THE CODE <br />FOR WELDING IN BUILDING CONSTRUCTION (AWS D1.1 LATEST REVISION) OF THE AMERICAN <br />WELDING SOCIETY. SEE SPECIAL INSPECTIONS SECTION FOR WELDING INSPECTION <br />REQUIREMENTS. <br />WELD LENGTHS CALLED FOR ON PLANS ARE THE NET EFFECTIVE LENGTH REQUIRED. WHERE <br />FILLET WELD SYMBOL IS GIVEN WITHOUT INDICATION OF SIZE, USE MINIMUM SIZE WELDS AS <br />SPECIFIED IN AISC MANUAL OF STEEL CONSTRUCTION 15TH EDITION, SECTION J2.4. <br />ALL STRUCTURAL STEEL AND MISCELLANEOUS METAL EXPOSED TO THE WEATHER SHALL BE <br />HOT DIP GALVANIZED AFTER FABRICATION, UNLESS NOTED OTHERWISE ON THE <br />CONSTRUCTION DOCUMENTS. REFER TO ARCH DRAWINGS FOR STEEL FINISH. PROTECT FIELD <br />WELDS EXPOSED TO THE WEATHER SHALL RECEIVE PRIME AND PAINT OR BRUSH / COLD <br />GALVANIZING. FOR EXPOSED STRUCTURAL STEEL CALLED OUT TO RECEIVE COATINGS SEE <br />SPECIFICATION 05 1200 SECTION 2.03J, ITEM 4 FOR PREPARATION AND PRIMING.FOR EXPOSED, <br />GALVANIZED MISCELLANEOUS METAL CALLED OUT TO RECEIVE COATINGS, SEE SPECIFICATION <br />09 9600 SECTION 2.5 FOR PREPARATION AND PRIMING. <br />THE USE OF E70T-4 WELDING WIRE IS NOT PERMITTED. <br />ALL WELD FILLER MATERIAL SPECIFIED AS "NOTCH TOUGH" SHALL HAVE A MINIMUM CHARPY-V <br />NOTCH (CVN) VALUE OF 20 FT-LBS AT A TEMPERATURE OF -20° F. <br />100% UT TEST FOR ALL COMPLETE PENETRATION GROOVE WELDS. <br />DISCONTINUITIES IN WELD CREATED BY ERRORS OR BY FABRICATION OR ERECTION <br />OPERATIONS, SUCH AS TACK WELDS, ERECTION AIDS, AIR ARC GOUGING AND FLAME CUTTING, <br />SHALL BE REPAIRED AS REQUIRED BY THE ENGINEER OF RECORD. <br />WRITTEN WELDING PROCEDURE SPECIFICATIONS (WPS) PER THE RECOMMENDATIONS OF THE <br />AMERICAN WELDING SOCIETY (AWS) SHALL BE DEVELOPED BY THE FABRICATOR/ERECTOR <br />AND SUBMITTED FOR REVIEW TO THE ENGINEER PRIOR TO ANY WELDING OF THE STRUCTURAL <br />STEEL. THE WELDING PROCEDURES SHALL INCLUDE ALL THE WELDED JOINTS AND <br />CONFIGURATIONS TO BE USED ON THIS PROJECT-ONLY WPS WHICH ARE RELEVANT TO THIS <br />PROJECT SHALL BE SUBMITTED, ALL WELDED JOINTS SHALL BE PRE-QUALIFIED PER AWS OR <br />BE QUALIFIED BY TEST PER AWS. A PROCEDURE QUALIFICATION RECORD (PQR) SHALL BE <br />INCLUDED WITH THE WPS IF THE WELDING PROCEDURE OR JOINT IS QUALIFIED BY TESTING. <br />THE ELECTRODE MANUFACTURER AND PRODUCT/TRADE NAME SHALL BE IDENTIFIED IN THE <br />WPS IN ADDITION TO THE AWS ELECTRODE CLASSIFICATION NAME. A COPY OF THE <br />ELECTRODE MANUFACTURER'S TECHNICAL DATA SHEETS WITH THE RECOMMENDED WELDING <br />PARAMETERS SHALL BE SUBMITTED WITH THE WPS. <br />POWER DRIVEN FASTENERS / SHOT PINS <br />1. <br />2. <br />3. <br />4. <br />5. <br />6. <br />7. <br />ALL POWDER DRIVEN FASTENERS SHALL CONSIST OF HILTI 0.157 DIAM XU <br />(ICC ESR-2269) LOW VELOCITY POWDER DRIVEN FASTENERS. INSTALLATION OF ANCHORS <br />SHALL BE IN CONFORMANCE WITH THE ICC REPORT AND MANUFACTURER <br />RECOMMENDATIONS. <br />WHEN INSTALLING POWDER DRIVEN FASTENERS IN NON-PRESTRESSED REINFORCED <br />CONCRETE, USE CARE AND CAUTION TO AVOID CUTTING OR DAMAGING THE REINFORCING <br />BARS. <br />THE SPECIAL INSPECTOR MUST BE ON THE JOBSITE CONTINUOUSLY DURING ANCHOR <br />INSTALLATION TO VERIFY ANCHOR TYPE, ANCHOR DIMENSIONS, CONCRETE TYPE, <br />CONCRETE COMPRESSIVE STRENGTH, ANCHOR SPACING, EDGE DISTANCES, SLAB <br />THICKNESS AND ANCHOR EMBEDMENT. <br />POWDER DRIVEN FASTENERS ARE NOT PERMITTED FOR USE ON CONCRETE CURBS. <br />FASTENERS MAY BE USED FOR SHEAR LOADS AND THEY MAY BE USED IN TENSION TO <br />SUPPORT LOADS LESS THAN 100 POUNDS FOR MINOR LOADS LIKE ACOUSTICAL CEILINGS, <br />DUCT WORK, CONDUIT, ETC. <br />THE ALLOWABLE LOADS SHALL BE 100 POUNDS OR 80% OF ICC EVALUATION REPORT <br />APPROVED VALUES, WHICHEVER IS LESS. QUALIFICATION FOR USE OF ALL POWER <br />ACTUATED TOOLS MUST MEET ANSI A10.3 STANDARD AS REQUIRED BY THE <br />MANUFACTURER AND ALL OSHA REQUIREMENTS. <br />TESTING - THE OPERATOR, TOOL AND FASTENER SHALL BE PRE-QUALIFIED BY THE <br />PROJECT INSPECTOR. THE INSPECTOR SHALL OBSERVE THE TESTING OF THE FIRST 10 <br />FASTENER INSTALLATIONS. A TEST "PULL-OUT" LOAD OF NOT LESS THAN TWICE THE <br />DESIGN LOAD SHALL BE APPLIED TO THE PIN IN SUCH A MANNER AS NOT TO RESIST THE <br />SPALLING TENDENCY OF THE CONCRETE SURROUNDING THE PIN. THEREAFTER RANDOM <br />TESTS UNDER THE PROJECT INSPECTOR'S SUPERVISION SHALL BE MADE OF <br />APPROXIMATELY 1 IN 10 PINS. IF ANY PIN FAILS TESTING, TEST ALL PINS OF THE SAME <br />CATEGORY NOT PREVIOUSLY TESTED UNTIL TWENTY (20) CONSECUTIVE PASS, THEN <br />RESUME THE INITIAL TESTING FREQUENCY. <br />WELDED THREADED AND HEADED STUDS <br />1. <br />2. <br />3. <br />WELDED STUDS SHALL BE "TRUE-WELD STUDS", DIVISION OF TRU-FIT SCREW <br />CORPORATION, CLEVELAND, OHIO OR "NELSON STUD" OHIO, OR APPROVED EQUAL. <br />WELDED STUDS SHALL BE AUTOMATICALLY END WELDED IN SHOP OR FIELD WITH <br />EQUIPMENT RECOMMENDED BY MANUFACTURER OF STUDS. <br />WELDED STUD MATERIAL, WELDING AND INSPECTION, SHALL BE IN ACCORDANCE WITH <br />THE AWS "STRUCTURAL WELDING CODE", AWS D1.1, SECTION 7. <br />CONSTRUCTION JOINTS <br />1. <br />2. <br />3. <br />ALL CONSTRUCTION JOINTS SHALL BE CONSTRUCTED IN ACCORDANCE WITH CODE <br />SECTION 1906 AND THE TYPICAL CONSTRUCTION JOINT DETAILS SHOWN ON THE <br />STRUCTURAL DRAWINGS. <br />ALL SURFACES OF CONSTRUCTION JOINTS SHALL BE CLEANED TO REMOVE DUST, CHIPS <br />OR OTHER FOREIGN MATTER PRIOR TO PLACING THE ADJACENT CONCRETE. <br />THE CONTRACTOR SHALL SUBMIT THE PROPOSED LOCATIONS OF CONSTRUCTION <br />JOINTS TO THE STRUCTURAL ENGINEER FOR REVIEW BEFORE STARTING <br />CONSTRUCTION. <br />GENERAL <br />1. <br />2. <br />3. <br />4. <br />5. <br />6. <br />7. <br />8. <br />9. <br />10. <br />11. <br />12. <br />THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR TO STARTING CONSTRUCTION. <br />THE ARCHITECT SHALL BE NOTIFIED OF ANY DISCREPANCIES OR INCONSISTENCIES. <br />ALL DRAWINGS ARE CONSIDERED TO BE A PART OF THE CONTRACT DOCUMENTS. THE <br />CONTRACTOR SHALL BE RESPONSIBLE FOR THE REVIEW AND COORDINATION OF ALL <br />DRAWINGS AND SPECIFICATIONS PRIOR TO THE START OF CONSTRUCTION. ANY <br />DISCREPANCIES THAT OCCUR SHALL BE BROUGHT TO THE ATTENTION OF THE <br />ARCHITECT PRIOR TO START OF CONSTRUCTION SO THAT A CLARIFICATION CAN BE <br />ISSUED. ANY WORK PERFORMED IN CONFLICT WITH THE CONTRACT DOCUMENTS OR <br />ANY CODE REQUIREMENTS SHALL BE CORRECTED BY THE CONTRACTOR AT THEIR OWN <br />EXPENSE AND AT NO EXPENSE TO THE OWNER OR ARCHITECT. <br />NOTES AND DETAILS ON DRAWINGS SHALL TAKE PRECEDENCE OVER GENERAL NOTES <br />AND TYPICAL DETAILS. WHERE NO DETAILS ARE GIVEN, CONSTRUCTION SHALL BE AS <br />SHOWN FOR SIMILAR WORK. <br />ALL WORK SHALL CONFORM TO THE MINIMUM STANDARDS OF THE FOLLOWING: <br />2022 CALIFORNIA BUILDING CODE, VOLUME 2, REFERRED TO HERE AS "THE CODE", <br />AND ANY OTHER REGULATING AGENCIES WHICH HAVE AUTHORITY OVER WHICH ANY <br />PORTION OF THE WORK, INCLUDING THE STATE OF CALIFORNIA DIVISION OF <br />INDUSTRIAL SAFETY, AND THOSE CODES & STANDARDS LISTED IN THESE NOTES AND <br />SPECIFICATIONS. <br />SEE ARCHITECTURAL DRAWINGS FOR THE FOLLOWING: <br />a. SIZE AND LOCATION OF ALL DOOR AND WINDOW OPENINGS, EXCEPT AS NOTED <br />b. SIZE AND LOCATION OF ALL INTERIOR AND EXTERIOR NON-BEARING PARTITIONS. <br />c. SIZE AND LOCATION OF ALL CONCRETE CURBS, EQUIPMENT PADS, PITS, FLOOR <br />DRAINS, SLOPES, DEPRESSED AREAS, CHANGE IN LEVEL, CHAMFERS, GROOVES, <br />INSERTS, ETC. <br />d. SIZE AND LOCATION OF ALL FLOOR AND ROOF OPENINGS EXCEPT AS SHOWN. <br />e. FLOOR AND ROOF FINISHES. <br />f. DIMENSIONS NOT SHOWN ON STRUCTURAL DRAWINGS. <br />SEE MECHANICAL, PLUMBING AND ELECTRICAL DRAWINGS FOR THE FOLLOWING: <br />a. PIPE RUNS, SLEEVES, HANGERS, TRENCHES, WALL AND SLAB OPENINGS, ETC., <br />EXCEPT AS SHOWN OR NOTED. <br />b. ELECTRICAL CONDUIT RUNS, BOXES, OUTLETS IN WALLS AND SLABS. <br />c. CONCRETE INSERTS FOR ELECTRICAL, MECHANICAL OR PLUMBING FIXTURES. <br />d. SIZE AND LOCATION OF MACHINE OR EQUIPMENT BASES, ANCHOR BOLTS FOR <br />MOTOR MOUNTS. <br />THE CONTRACT STRUCTURAL DRAWINGS AND SPECIFICATIONS REPRESENT THE <br />FINISHED STRUCTURE. THEY DO NOT INDICATE THE METHOD OF CONSTRUCTION. THE <br />CONTRACTOR SHALL PROVIDE ALL MEASURES NECESSARY TO PROTECT THE <br />STRUCTURE DURING CONSTRUCTION. SUCH MEASURES SHALL INCLUDE, BUT NOT BE <br />LIMITED TO, BRACING, SHORING FOR LOADS DUE TO CONSTRUCTION EQUIPMENT, ETC. <br />OBSERVATION VISITS TO THE SITE BY THE STRUCTURAL ENGINEER SHALL NOT INCLUDE <br />INSPECTION OF THE ABOVE ITEMS. <br />OPENINGS, POCKETS, ETC., LARGER THAN 6" SHALL NOT BE PLACED IN CONCRETE <br />SLABS, DECKS, WALLS, UNLESS SPECIALLY DETAILED ON THE STRUCTURAL DRAWINGS. <br />NOTIFY THE STRUCTURAL ENGINEER WHEN DRAWINGS BY OTHERS SHOW OPENINGS, <br />POCKETS, ETC., LARGER THAN 6" NOT SHOWN ON THE STRUCTURAL DRAWINGS, BUT <br />WHICH ARE LOCATED IN STRUCTURAL MEMBERS. FOR ANY FURTHER RESTRICTIONS ON <br />OPENINGS IN STRUCTURAL ELEMENTS, SEE APPLICABLE SECTIONS BELOW. <br />PIPES LARGER THAN 1-1/2" DIAMETER SHALL NOT BE EMBEDDED IN STRUCTURAL <br />CONCRETE EXCEPT WHERE SPECIFICALLY APPROVED. <br />ASTM SPECIFICATIONS ON THE DRAWINGS SHALL BE OF THE LATEST REVISION. <br />CONTRACTOR SHALL INVESTIGATE SITE DURING CLEARING AND EARTHWORK <br />OPERATIONS FOR FILLED EXCAVATIONS OR BURIED STRUCTURES, SUCH AS CESSPOOLS, <br />CISTERNS, FOUNDATIONS, ETC. IF ANY SUCH STRUCTURES ARE FOUND, STRUCTURAL <br />ENGINEER SHALL BE NOTIFIED IMMEDIATELY. <br />CONSTRUCTION MATERIAL SHALL BE SPREAD OUT IF PLACED ON FRAMED ROOF OR <br />FLOOR. LOAD SHALL NOT EXCEED THE DESIGN LIVE LOAD PER SQUARE FOOT. PROVIDE <br />ADEQUATE SHORING AND/OR BRACING WHERE STRUCTURE HAS NOT ATTAINED DESIGN <br />STRENGTH. <br />1. FABRICATE AND INSTALL STEEL DECK ACCORDING TO THE FOLLOWING PROVISIONS: <br />A. ROOF DECK: ANSI/SDI RD-2017, "STANDARDS FOR STEEL ROOF DECK." <br />B. COMPOSITE FLOOR DECK: ANSI/SDI C-2017, "STANDARDS FOR COMPOSITE STEEL FLOOR DECK-SLAB." <br />C. WELDING OF STEEL DECK: AWS D1.3, "STRUCTURAL WELDING CODE - SHEET STEEL." <br />2. STEEL ROOF DECK: PROVIDE AND INSTALL ROOF AS NOTED ON THE DRAWINGS MINIMUM PROPERTIES ARE AS <br />FOLLOWS: <br />DECK PROFILE AND GAGE I (IN4) +S(IN3) -S(IN3) <br />HSB-36 x 18 GA DECK 0.306 0.314 0.331 <br />HSB-36 x 16 GA DECK 0.381 0.399 0.410 <br />PLN-24 x 18 GA DECK 1.369 0.652 0.753 <br />PLN-24 x 16 GA DECK 1.706 0.837 0.914 <br />3. COMPOSITE FLOOR DECK: PROVIDE AND INSTALL ROOF AS NOTED ON THE DRAWINGS MINIMUM PROPERTIES ARE AS <br />FOLLOWS: <br />DECK PROFILE AND GAGE I (IN4) +S(IN3) -S(IN3) <br />3" x 18GA DECK 1.213 0.752 0.768 <br />3" x 16GA DECK 1.516 0.968 0.966 <br />2" x 18GA DECK 0.564 0.471 0.481 <br />1 1/2" x 18GA DECK 0.381 0.399 0.410 <br />4. DESIGN OF ALL STEEL DECK SHALL BE IN ACCORDANCE WITH SECTION 2210 OF THE CODE. <br />5. ALL STEEL DECK CLOSURES AND FLASHING SHALL CONFORM TO ASTM A653 GR 33, FY 33,000 PSI MIN. <br />6. ACCEPTABLE STEEL DECK MANUFACTURERS ARE AS FOLLOWS: <br />VERCO MANUFACTURING IAPMO REPORT ER-2018 <br />ASC PROFILE IAPMO REPORT ER-0161 & ER-0329 <br />7. EXAMINE SUPPORTING FRAME AND FIELD CONDITIONS FOR COMPLIANCE WITH REQUIREMENTS FOR INSTALLATION <br />TOLERANCES AND OTHER CONDITIONS AFFECTING PERFORMANCE. PROCEED WITH INSTALLATION ONLY AFTER <br />UNSATISFACTORY CONDITIONS HAVE BEEN CORRECTED. <br />A. RUN UNITS CONTINUOUS OVER THREE OR MORE SPANS. <br />B. PROVIDE 2" MINIMUM DECK BEARING AT ALL SUPPORTS. <br />8. INSTALL DECK PANELS AND ACCESSORIES ACCORDING TO ANSI/SDI STANDARDS AND MANUFACTURER'S WRITTEN <br />INSTRUCTIONS. <br />9. INSTALL TEMPORARY SHORING BEFORE PLACING DECK PANELS AS REQUIRED TO MEET DEFLECTION LIMITATIONS. ALL <br />SHORING OF STEEL DECK SHALL BE PER MANUFACTURER'S RECOMMENDATIONS. <br />10. ALL WELDING OF STEEL DECK SHALL BE DONE BY CERTIFIED LIGHT GAGE WELDERS IN ACCORDANCE WITH AWS <br />"STRUCTURAL WELDING CODE - SHEET STEEL", AWS D1.3, LATEST EDITION. <br />11. UNITS SHALL BE FASTENED TO THE STEEL SUPPORTS AT THE END OF THE UNITS AND INTERMEDIATE SUPPORTS AND <br />TO THE STEEL SUPPORTS AT THE SIDE BOUNDARIES BY 1/2" PUDDLE WELDS AT 12" OC. SHEAR STUDS WELDED <br />THROUGH DECK MAY BE USED IN PLACE OF 1/2" DIAMETER PUDDLE WELDS. <br />12. SIDE LAPS OF ADJACENT UNITS SHALL BE FASTENED BETWEEN SUPPORTS BY BUTTON PUNCHING AT 12" OC MAX OR <br />PER SPACING INDICATED IN DECK SCHEDULE, WHICHEVER IS LESS. CONTRACTOR MAY DECREASE SPACING OF SIDE <br />LAP ATTACHMENTS TO ACCOMMODATE CONSTRUCTION LOADING AS REQUIRED. <br />13. PROVIDE FLASHING AND CLOSURE PLATES AT ENDS OF ALL UNITS, AROUND COLUMNS, AND AT ALL PERIMETER <br />LOCATIONS REQUIRING CONCRETE. <br />14. ALL METAL DECK TO BE GALVANIZED. <br />15. PROVIDE PERFORATIONS OR SLOTS (1.5% MAXIMUM OPEN AREA) IN ALL ROOF AND FLOOR DECKING EXCEPT AT <br />LOCATION WHERE THE DECKING IS PROVIDING PROTECTION FROM RAIN WATER OR WHERE NOTED ON THE DRAWINGS. <br />STEEL DECK <br />LATERAL DISTANCE BETWEEN NEW <br />FOOTING AND EXISTING BUILDING <br />FOOTING EXPRESSED IN FRACTION <br />OF THE NEW FOOTING DEPTH, D <br />REDUCTION FACTOR TO ALLOWABLE <br />SOILS BEARING CAPACITY a 1.0 0.75 0.5 <br />≥ 1D 1/2D 0 <br />a. INTERPOLATION MAY BE USED FOR DERIVING REDUCTION FACTOR <br />FOR OTHER DISTANCE VALUE. <br />3 <br />PROJECT <br />COPYRIGHT LOC, INC <br />ORIGINAL SHEET SIZE: 42" X 30" <br />LOC <br />CLIEN <br />ARCHITEC <br />CONSULTANT <br />AC <br />C <br /> <br />R <br />e <br />v <br />i <br />t <br /> <br />2 <br />0 <br />2 <br />2 <br /> <br />h <br />o <br />s <br />t <br />e <br />d <br /> <br />b <br />y <br /> <br />L <br />O <br />C <br />2/ <br />1 <br />2 <br />/ <br />2 <br />0 <br />2 <br />5 <br /> <br />1 <br />2 <br />: <br />0 <br />3 <br />: <br />1 <br />9 <br /> <br />P <br />M <br />Au <br />t <br />o <br />d <br />e <br />s <br />k <br /> <br />D <br />o <br />c <br />s <br />: <br />/ <br />/ <br />2 <br />3 <br />0 <br />8 <br />_ <br />S <br />A <br />Z <br />_ <br />H <br />i <br />v <br />e <br />/ <br />2 <br />3 <br />0 <br />0 <br />1 <br />7 <br />5 <br />_ <br />S <br />A <br />Z <br />_ <br />K <br />P <br />F <br />F <br />_ <br />R <br />2 <br />2 <br />. <br />r <br />v <br />t <br />2308 <br />GENERAL <br />NOTES <br />FEBRUARY 13, 2025 <br />PLAN CHECK <br />SUBMITTAL 02 <br />S0.02 <br />SANTA ANA ZOO <br />1801 E CHESTNUT AVE, SANTA ANA, CA <br />92701 <br />KPFF <br />STRUCTURAL ENGINEER <br />LOC ARCHITECTS <br />KPFF <br />CIVIL ENGINEER <br />BORDER <br />LANDSCAPE ARCHITECT <br />ABRARI AND ASSOCIATES <br />MEP ENGINEER <br />ASSOCIATED SOILS ENGINEERING <br />GEOTECHNICAL ENGINEER <br />700 S. FLOWER, SUITE 2100 <br />LOS ANGELES, CA 90017 <br />213 372 5111 <br />Ramzi.hodali@kpff.com <br />700 S. FLOWER, SUITE 2100 <br />LOS ANGELES, CA 90017 <br />213 372 5111 <br />Sharad.Ganju@kpff.com <br />724 S. SPRING ST, SUITE 701 <br />LOS ANGELES, CA 90014 <br />213 372 5111 <br />Darren@border-la.com <br />1713 S. STANDARD AVE <br />GLENDALE, CA 91201 <br />818 956 1900 <br />Telma@abrari.com <br />2860 WALNUT AVE. <br />SIGNAL HILL, CA 90755 <br />562 897 2749 <br />Ted@associatedsoils.com <br />3203 E. 4TH ST <br />LOS ANGELES, CA 90063 <br />213 537 0480 <br />Office@loc-arch.com <br />1801 E. CHESTNUT AVE. <br />SANTA ANA, CA 92701 <br />714 647 6575 <br />Efisher@santa-ana.org <br />SANTA ANA ZOO <br />EDUCATION <br />HUB <br />No.Description Date <br />3 PLAN CHECK SUBMITTAL 02 02-13-2025 <br />REGISTERED PROFESSIONAL ENGINEERRAMZI S . HODAL <br />I <br />STRUC T URALSTATE OF CAL IFORNIA <br />2/13/2025