Laserfiche WebLink
SECTION 26 0500 <br />COMMON WORK RESULTS FOR ELECTRICAL <br />PART 1 - GENERAL <br />1.01 SUMMARY <br />A.SECTION INCLUDES THE FOLLOWING: <br />1.SUPPORTING DEVICES FOR ELECTRICAL COMPONENTS. <br />2.ELECTRICAL DEMOLITION. <br />1.02 QUALITY ASSURANCE <br />A.ELECTRICAL COMPONENTS, DEVICES, AND ACCESSORIES: LISTED AND LABELED AS <br />DEFINED IN CEC, ARTICLE 100, BY A TESTING AGENCY ACCEPTABLE TO THE OWNER, AND <br />MARKED FOR INTENDED USE. <br />B.COMPLY WITH CEC. <br />1.03 COORDINATION <br />A.COORDINATE CHASES, SLOTS, INSERTS, SLEEVES, AND OPENINGS WITH GENERAL <br />CONSTRUCTION WORK AND ARRANGE IN BUILDING STRUCTURE DURING PROGRESS OF <br />CONSTRUCTION TO FACILITATE THE ELECTRICAL INSTALLATIONS THAT FOLLOW. <br />B.SEQUENCE, COORDINATE, AND INTEGRATE INSTALLING ELECTRICAL MATERIALS AND <br />EQUIPMENT FOR EFFICIENT FLOW OF THE WORK. COORDINATE INSTALLING LARGE <br />EQUIPMENT REQUIRING POSITIONING BEFORE CLOSING IN THE BUILDING. <br />C.COORDINATE LOCATION OF ACCESS PANELS AND DOORS FOR ELECTRICAL ITEMS THAT <br />ARE CONCEALED BY FINISHED SURFACES. <br />PART 2 - PRODUCTS <br />2.01 MANUFACTURERS <br />A.IN OTHER PART 2 ARTICLES WHERE TITLES BELOW INTRODUCE LISTS, THE FOLLOWING <br />REQUIREMENTS APPLY TO PRODUCT SELECTION: <br />1.MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE <br />PRODUCTS BY ONE OF THE MANUFACTURERS SPECIFIED. <br />2.OR EQUAL: WHERE PRODUCTS ARE SPECIFIED BY MANUFACTURERS NAME AND <br />ACCOMPANIED BY THE TERM "OR EQUAL", COMPLY WITH PROVISIONS IN DIVISION 01. <br />SPECIFIC PROCEDURES MUST BE FOLLOWED BEFORE USE OF AN UNNAMED <br />PRODUCT OR MANUFACTURER. <br />2.02 SUPPORTING DEVICES <br />A.MATERIAL: COLD-FORMED STEEL, WITH CORROSION-RESISTANT COATING ACCEPTABLE <br />TO THE OWNER. <br />B.METAL ITEMS FOR USE OUTDOORS OR IN DAMP LOCATIONS: HOT-DIP GALVANIZED <br />STEEL OR STAINLESS STEEL. <br />C.SLOTTED-STEEL CHANNEL SUPPORTS: FLANGE EDGES TURNED TOWARD WEB, AND <br />9/16-INCH-DIAMETER SLOTTED HOLES AT A MAXIMUM OF 2 INCHES, ON CENTER, IN WEBS. <br />1.CHANNEL THICKNESS: SELECTED TO SUIT STRUCTURAL LOADING. <br />2.FITTINGS AND ACCESSORIES: PRODUCTS OF THE SAME MANUFACTURER AS <br />CHANNEL SUPPORTS. <br />D.RACEWAY AND CABLE SUPPORTS: MANUFACTURED CLEVIS HANGERS, RISER CLAMPS, <br />STRAPS, THREADED C-CLAMPS WITH RETAINERS, CEILING TRAPEZE HANGERS, WALL <br />BRACKETS, AND SPRING-STEEL CLAMPS OR CLICK-TYPE HANGERS. <br />E.PIPE SLEEVES: ASTM A53, TYPE E, GRADE A, SCHEDULE 40, GALVANIZED STEEL, PLAIN <br />ENDS. <br />F.CABLE SUPPORTS FOR VERTICAL CONDUIT: FACTORY-FABRICATED ASSEMBLY <br />CONSISTING OF THREADED BODY AND INSULATING WEDGING PLUG FOR NON-ARMORED <br />ELECTRICAL CABLES IN RISER CONDUITS. PLUGS HAVE NUMBER AND SIZE OF <br />CONDUCTOR GRIPPING HOLES AS REQUIRED TO SUIT INDIVIDUAL RISERS. BODY <br />CONSTRUCTED OF MALLEABLE-IRON CASTING WITH HOT-DIP GALVANIZED FINISH. <br />G.EXPANSION ANCHORS: CARBON-STEEL WEDGE OR SLEEVE TYPE. <br />H.TOGGLE BOLTS: STEEL SPRINGHEAD TYPE. <br />I.POWDER-ACTUATED FASTENERS: ARE PROHIBITED EXCEPT WHEN EXECUTED IN <br />ACCORDANCE WITH DIVISION 01. <br />PART 3 - EXECUTION <br />3.01 ELECTRICAL EQUIPMENT INSTALLATION <br />A.HEADROOM MAINTENANCE: IF MOUNTING HEIGHTS OR OTHER LOCATION CRITERIA ARE <br />NOT INDICATED, ARRANGE AND INSTALL COMPONENTS AND EQUIPMENT TO PROVIDE <br />THE MAXIMUM POSSIBLE HEADROOM AND IN NO CASE LESS THAN 84 INCHES. <br />B.MATERIALS AND COMPONENTS: INSTALL LEVEL, PLUMB, AND PARALLEL AND <br />PERPENDICULAR TO OTHER BUILDING SYSTEMS AND COMPONENTS, UNLESS <br />OTHERWISE INDICATED. <br />C.EQUIPMENT: INSTALL TO FACILITATE SERVICE, MAINTENANCE, AND REPAIR OR <br />REPLACEMENT OF COMPONENTS. CONNECT FOR EASE OF DISCONNECTING, WITH <br />MINIMUM INTERFERENCE WITH OTHER INSTALLATIONS. <br />D.RIGHT OF WAY: GIVE TO RACEWAYS AND PIPING SYSTEMS INSTALLED AT A REQUIRED <br />SLOPE. <br />3.02 WIRING INSTALLATION <br />A.INSTALL SPLICES AND TAPS THAT ARE COMPATIBLE WITH CONDUCTOR MATERIAL AND <br />THAT POSSESS EQUIVALENT OR BETTER MECHANICAL STRENGTH AND INSULATION <br />RATINGS THAN THE UNSPLICED CONDUCTORS. <br />B.INSTALL WIRING AT OUTLETS OF SUFFICIENT LENGTH TO EXTEND A MINIMUM OF <br />6 INCHES OUTSIDE OF THE OPENING. <br />C.CONNECT OUTLET AND COMPONENT CONNECTIONS TO WIRING SYSTEMS AND TO <br />GROUND. TIGHTEN ELECTRICAL CONNECTORS AND TERMINALS, IN ACCORDANCE WITH <br />MANUFACTURER'S PUBLISHED TORQUE-TIGHTENING VALUES. IF MANUFACTURER'S <br />TORQUE VALUES ARE NOT INDICATED, USE THOSE SPECIFIED IN UL 486A. <br />3.03 ELECTRICAL SUPPORTING DEVICE APPLICATION <br />A.DAMP LOCATIONS AND OUTDOORS: HOT-DIP GALVANIZED MATERIALS, U-CHANNEL <br />SYSTEM COMPONENTS. <br />B.DRY LOCATIONS: ELECTRO-PLATED STEEL MATERIALS. <br />C.SUPPORT CLAMPS FOR PVC RACEWAYS: CLICK-TYPE CLAMP SYSTEM. <br />D.SELECTION OF SUPPORTS: COMPLY WITH MANUFACTURER'S WRITTEN INSTRUCTIONS. <br />E.STRENGTH OF SUPPORTS: ADEQUATE TO CARRY PRESENT AND FUTURE LOADS, TIMES <br />A SAFETY FACTOR OF AT LEAST FOUR; MINIMUM OF 200-LB DESIGN LOAD. <br />3.04 SUPPORT INSTALLATION <br />A.INSTALL SUPPORT DEVICES TO SECURELY AND PERMANENTLY FASTEN AND SUPPORT <br />ELECTRICAL COMPONENTS. <br />B.INSTALL INDIVIDUAL AND MULTIPLE RACEWAY HANGERS AND RISER CLAMPS TO <br />SUPPORT RACEWAYS. PROVIDE U-BOLTS, CLAMPS, ATTACHMENTS, AND OTHER <br />HARDWARE NECESSARY FOR HANGER ASSEMBLIES AND FOR SECURING HANGER RODS <br />AND CONDUITS. <br />C.SUPPORT PARALLEL RUNS OF HORIZONTAL RACEWAYS TOGETHER ON TRAPEZE OR <br />BRACKET-TYPE HANGERS. <br />D.SIZE SUPPORTS FOR MULTIPLE RACEWAY INSTALLATIONS SO CAPACITY CAN BE <br />INCREASED BY 25 PERCENT MINIMUM IN THE FUTURE. <br />E.SUPPORT INDIVIDUAL HORIZONTAL RACEWAYS WITH SEPARATE, PIPE HANGERS, OR <br />CLAMPS. <br />F.INSTALL 1/4-INCH DIAMETER OR LARGER THREADED STEEL HANGER RODS. <br />G.ARRANGE SUPPORTS IN VERTICAL RUNS SO THE WEIGHT OF RACEWAYS AND ENCLOSED <br />CONDUCTORS IS CARRIED ENTIRELY BY RACEWAY SUPPORTS, WITH NO WEIGHT LOAD <br />ON RACEWAY TERMINALS. <br />H.SIMULTANEOUSLY INSTALL VERTICAL CONDUCTOR SUPPORTS WITH CONDUCTORS. <br />I.SEPARATELY SUPPORT CAST BOXES THAT ARE THREADED TO RACEWAYS AND USED <br />FOR FIXTURE SUPPORT. SUPPORT SHEET-METAL BOXES DIRECTLY FROM THE BUILDING <br />STRUCTURE OR BY BAR HANGERS. IF BAR HANGERS ARE USED, ATTACH BAR TO <br />RACEWAYS ON OPPOSITE SIDES OF THE BOX AND SUPPORT THE RACEWAY WITH AN <br />APPROVED FASTENER NOT MORE THAN 24 INCHES FROM THE BOX. <br />J.INSTALL METAL CHANNEL RACKS FOR MOUNTING CABINETS, PANEL BOARDS; <br />DISCONNECT SWITCHES, CONTROL ENCLOSURES, PULL AND JUNCTION BOXES, <br />TRANSFORMERS, AND OTHER DEVICES UNLESS COMPONENTS ARE MOUNTED DIRECTLY <br />TO STRUCTURAL ELEMENTS OF ADEQUATE STRENGTH. <br />K.INSTALL SLEEVES FOR CABLE AND RACEWAY PENETRATIONS OF CONCRETE SLABS AND <br />WALLS UNLESS CORE-DRILLED HOLES ARE USED. INSTALL SLEEVES FOR CABLE AND <br />RACEWAY PENETRATIONS OF MASONRY AND FIRE-RATED GYPSUM WALLS AND OTHER <br />FIRE-RATED FLOOR AND WALL ASSEMBLIES. INSTALL SLEEVES DURING ERECTION OF <br />CONCRETE AND MASONRY WALLS. <br />L.SECURELY FASTEN ELECTRICAL ITEMS AND THEIR SUPPORTS TO THE BUILDING <br />STRUCTURE, UNLESS OTHERWISE INDICATED. PERFORM FASTENING IN ACCORDANCE <br />WITH THE FOLLOWING UNLESS OTHER FASTENING METHODS ARE INDICATED: <br />1.WOOD: FASTEN WITH WOOD SCREWS OR LAG BOLTS. <br />2.MASONRY: TOGGLE BOLTS ON HOLLOW MASONRY UNITS AND EXPANSION BOLTS ON <br />SOLID MASONRY UNITS. <br />3.NEW CONCRETE: CONCRETE INSERTS WITH MACHINE SCREWS AND BOLTS. <br />4.EXISTING CONCRETE: EXPANSION BOLTS. <br />a.INSTEAD OF EXPANSION BOLTS, THREADED STUDS DRIVEN BY A POWDER <br />CHARGE AND PROVIDED WITH LOCK WASHERS MAY BE USED IN EXISTING <br />CONCRETE WHEN EXECUTED IN ACCORDANCE WITH DIVISION 01 REQUIREMENTS. <br />5.STEEL: WELDED THREADED STUDS OR SPRING-TENSION CLAMPS ON STEEL. <br />a.FIELD WELDING: COMPLY WITH AWS D1.1. <br />6.WELDING TO STEEL STRUCTURE MAY BE USED ONLY FOR THREADED STUDS, NOT <br />FOR CONDUITS, PIPE STRAPS, OR OTHER ITEMS. <br />7.LIGHT STEEL: SHEET-METAL SCREWS. <br />8.FASTENERS: SELECT SO THE LOAD APPLIED TO EACH FASTENER DOES NOT EXCEED <br />25 PERCENT OF ITS PROOF-TEST LOAD. <br />3.05 FIRESTOPPING <br />A.APPLY FIRESTOPPING TO CABLE AND RACEWAY PENETRATIONS OF FIRE-RATED FLOOR <br />AND WALL ASSEMBLIES TO ACHIEVE FIRE-RESISTANCE RATING OF THE ASSEMBLY. FIRE <br />STOPPING MATERIALS AND INSTALLATION REQUIREMENTS ARE SPECIFIED IN DIVISION 07 <br />SECTION "PENETRATION FIRESTOPPING." <br />3.06 DEMOLITION <br />A.PROTECT EXISTING ELECTRICAL EQUIPMENT AND INSTALLATIONS INDICATED TO REMAIN. <br />IF DAMAGED OR DISTURBED IN THE COURSE OF THE WORK, REMOVE DAMAGED <br />PORTIONS AND INSTALL NEW PRODUCTS OF EQUAL CAPACITY, QUALITY, AND <br />FUNCTIONALITY. <br />B.ACCESSIBLE WORK: REMOVE EXPOSED ELECTRICAL EQUIPMENT AND INSTALLATIONS, <br />INDICATED TO BE DEMOLISHED, IN THEIR ENTIRETY. <br />C.ABANDONED WORK: CUT AND REMOVE BURIED RACEWAY AND WIRING. WHEN <br />APPROVED BY THE OWNER'S REPRESENTATIVE RACEWAY CAN BE ABANDONED IN PLACE <br />A MINIMUM OF 4 INCHES BELOW THE SURFACE OF ADJACENT CONSTRUCTION. CAP <br />RACEWAYS AND PATCH SURFACE TO MATCH EXISTING FINISH. <br />D.REMOVE DEMOLISHED MATERIAL FROM PROJECT SITE. <br />E.REMOVE, STORE, CLEAN, REINSTALL, RECONNECT, AND MAKE OPERATIONAL <br />COMPONENTS INDICATED FOR RELOCATION. <br />3.07 FIELD QUALITY CONTROL <br />A.INSPECT INSTALLED COMPONENTS FOR DAMAGE AND FAULTY WORK, INCLUDING THE <br />FOLLOWING: <br />1.SUPPORTING DEVICES FOR ELECTRICAL COMPONENTS. <br />2.ELECTRICAL DEMOLITION. <br />3.08 CLEANING AND PROTECTION <br />A.ON COMPLETION OF INSTALLATION, INCLUDING OUTLETS, FITTINGS, AND DEVICES, <br />INSPECT EXPOSED FINISH. REMOVE BURRS, DIRT, PAINT SPOTS, AND CONSTRUCTION <br />DEBRIS. <br />B.PROTECT EQUIPMENT AND INSTALLATIONS AND MAINTAIN CONDITIONS TO ENSURE THAT <br />COATINGS, FINISHES, AND CABINETS ARE WITHOUT DAMAGE OR DETERIORATION AT <br />TIME OF SUBSTANTIAL COMPLETION. <br />SECTION 26 0519 <br />LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES <br />PART 1 - GENERAL <br />1.01 SUMMARY <br />A.SECTION INCLUDES BUILDING WIRES AND CABLES AND ASSOCIATED CONNECTORS, <br />SPLICES, AND TERMINATIONS FOR WIRING SYSTEMS RATED AT 600 VOLTS AND LOWER. <br />1.02 SUBMITTALS <br />A.PRODUCT DATA: FOR EACH TYPE OF PRODUCT INDICATED. <br />1.03 QUALITY ASSURANCE <br />A.ELECTRICAL COMPONENTS, DEVICES, AND ACCESSORIES: LISTED AND LABELED AS <br />DEFINED IN CEC, ARTICLE 100, BY A TESTING AGENCY ACCEPTABLE TO THE OWNER, AND <br />MARKED FOR INTENDED USE. <br />B.COMPLY WITH CEC. <br />PART 2 - PRODUCTS <br />2.01 MANUFACTURERS <br />A.IN OTHER PART 2 ARTICLES WHERE SUBPARAGRAPH TITLES BELOW INTRODUCE LISTS, <br />THE FOLLOWING REQUIREMENTS APPLY FOR PRODUCT SELECTION: <br />1.MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE <br />PRODUCTS BY THE MANUFACTURERS SPECIFIED. <br />2.OR EQUAL: WHERE PRODUCTS ARE SPECIFIED BY MANUFACTURERS NAME AND <br />ACCOMPANIED BY THE TERM "OR EQUAL", COMPLY WITH PROVISIONS IN DIVISION 01. <br />SPECIFIC PROCEDURES MUST BE FOLLOWED BEFORE USE OF AN UNNAMED <br />PRODUCT OR MANUFACTURER. <br />2.02 COPPER CONDUCTORS AND CABLES <br />A.MANUFACTURERS (BUILDING WIRE AND CABLE): <br />1.AMERICAN INSULATED WIRE CORP.; A LEVITON COMPANY. <br />2.CERRO WIRE LLC. <br />3.ENCORE WIRE CORPORATION. <br />4.GENERAL CABLE CORPORATION. <br />5.OKONITE COMPANY <br />6.REPUBLIC WIRE INC. <br />7.SERVICE WIRE COMPANY. <br />8.SOUTHWIRE COMPANY. <br />9.WESCO. <br />10.OR EQUAL <br />B.MANUFACTURERS (CONTROL CABLE): <br />1.ALPHA. <br />2.BELDEN. <br />3.CONNECTAIR <br />4.OR EQUAL. <br />C.MANUFACTURERS (MC CABLE): <br />1.AFC CABLE SYSTEMS. <br />2.SOUTHWIRE COMPANY. <br />3.OR EQUAL. <br />D.REFER TO PART 3 "CONDUCTOR AND INSULATION APPLICATIONS" ARTICLE FOR <br />INSULATION TYPE, CABLE CONSTRUCTION, AND RATINGS. <br />E.CONDUCTOR MATERIAL: COPPER COMPLYING WITH ICEA S-95-658 / NEMA WC 70 <br />UNSHIELDED 0 TO 2 KV CABLES. <br />F.CONDUCTOR INSULATION TYPES: TYPE THW, THHN-THWN, XHHW, UF, USE, AND SO <br />COMPLYING WITH NEMA WC 70. <br />G.MULTICONDUCTOR CABLE: METAL-CLAD CABLE, TYPE MC, THHN COPPER CONDUCTORS <br />WITH INTEGRAL GREEN GROUND WIRE, LIGHTWEIGHT STEEL CLAD, UL STANDARD 1569 <br />TYPE SO AND TYPE USE WITH GROUND WIRE. <br />2.03 CONNECTORS AND SPLICES <br />A.MANUFACTURERS: <br />1.AMP INCORPORATED/JOHNSON CONTROLS. <br />2.HUBBELL/ANDERSON. <br />3.O-Z/GEDNEY; EGS ELECTRICAL GROUP LLC. <br />4.3M COMPANY; ELECTRICAL PRODUCTS DIVISION. <br />5.OR EQUAL. <br />B.DESCRIPTION: FACTORY-FABRICATED INLINE CONNECTOR KITS AND SPLICES OF SIZE, <br />AMPACITY RATING, MATERIAL, TYPE, AND CLASS FOR APPLICATION AND SERVICE <br />INDICATED AND FOR SHIELD OR UNSHIELDED CABLES. PROVIDE INSULATING AND <br />SEALING COMPOUND. <br />PART 3 - EXECUTION <br />3.01 CONDUCTOR AND INSULATION APPLICATIONS <br />A.WIRING IN PATIENT CARE AREAS SHALL COMPLY WITH NEC 571.13(A) AND (B). <br />B.ALL PATIENT CARE AREAS USING 'MC' CABLES SHALL BE TYPE HCF-90 OR EQUAL, <br />ARMOURED HEALTH CARE FACILITY MC (FLEX) CABLE. THE CABLE MUST HAVE AN <br />APPROVED/EFFECTIVE REDUNDANT GROUND-FAULT CURRENT RETURN PATH <br />EQUIPMENT GROUND CONDUCTOR (EGC) WITH A BRANCH CIRCUIT OR FEEDER <br />CIRCUIT GROUND CONDUCTOR. ALUMINUM MC (FLEX) CABLE PROVIDED WITH (2) <br />GREEN BRANCH CIRCUIT OR FEEDER CIRCUIT GROUND CONDUCTOR IS NOT <br />ACCEPTABLE. <br />C.FEEDERS CONCEALED IN CEILINGS, WALLS, AND PARTITIONS: TYPE THHN-THWN, SINGLE <br />CONDUCTORS IN RACEWAY. <br />D.EXPOSED BRANCH CIRCUITS: TYPE THHN-THWN, SINGLE CONDUCTORS IN RACEWAY. <br />E.BRANCH CIRCUITS FOR WET AND DRY LABORATORIES CONCEALED IN CEILINGS, WALLS <br />AND PARTITIONS: LIGHTWEIGHT STEEL METAL-CLAD CABLE, TYPE MC WITH TWO EXTRA <br />SPARE CIRCUITS TO RACEWAY OR TYPE THHN-THWN, SINGLE CONDUCTORS IN <br />RACEWAY. <br />F.BRANCH CIRCUITS CONCEALED IN CEILINGS, WALLS, AND PARTITIONS: LIGHTWEIGHT <br />STEEL METAL-CLAD CABLE TYPE MC OR TYPE THHN-THWN, SINGLE CONDUCTORS IN <br />RACEWAY. <br />G.LIGHTING CIRCUITS CONCEALED IN CEILING, WALLS, AND PARTITIONS: LIGHTWEIGHT <br />STEEL METAL-CLAD CABLE, OR TYPE MC TYPE THHN-THWN, SINGLE CONDUCTORS IN <br />RACEWAY. <br />H.FIRE ALARM CIRCUITS: TYPE THHN-THWN, IN RACEWAY, POWER-LIMITED, <br />FIRE-PROTECTIVE, SIGNALING CIRCUIT CABLE. <br />I.CLASS 1 CONTROL CIRCUITS: TYPE THHN-THWN, IN RACEWAY. <br />J.CLASS 2 CONTROL CIRCUITS: TYPE THHN-THWN, IN RACEWAY. <br />3.02 INSTALLATION <br />A.CONCEAL CABLES IN FINISHED WALLS, CEILINGS, AND FLOORS, UNLESS OTHERWISE <br />INDICATED. <br />B.USE MANUFACTURER-APPROVED PULLING COMPOUND OR LUBRICANT WHERE <br />NECESSARY; COMPOUND USED MUST NOT DETERIORATE CONDUCTOR OR INSULATION. <br />DO NOT USE OIL, GREASE, GRAPHITE, OR SIMILAR SUBSTANCES. DO NOT EXCEED <br />MANUFACTURER'S RECOMMENDED MAXIMUM PULLING TENSIONS AND SIDEWALL <br />PRESSURE VALUES. <br />C.USE PULLING MEANS; INCLUDING FISH TAPE, CABLE, ROPE, AND BASKET-WEAVE <br />WIRE/CABLE GRIPS THAT WILL NOT DAMAGE CABLES OR RACEWAY. PULLING OF LARGE <br />CONDUCTORS IN RACEWAYS SHALL BE DONE WITH AN APPROVED CABLE PULLING <br />MACHINE. OTHER METHODS SUCH AS BLOCK AND TACKLE TO INSTALL CONDUCTORS <br />ARE PROHIBITED. <br />D.INSTALL EXPOSED CABLES PARALLEL AND PERPENDICULAR TO SURFACES OF EXPOSED <br />STRUCTURAL MEMBERS AND FOLLOW SURFACE CONTOURS WHERE POSSIBLE. <br />E.SUPPORT CABLES IN ACCORDANCE WITH DIVISION 26 SECTION "COMMON WORK <br />RESULTS FOR ELECTRICAL." <br />F.SEAL AROUND CABLES PENETRATING FIRE-RATED ELEMENTS IN ACCORDANCE WITH <br />DIVISION 07 SECTION "PENETRATION FIRESTOPPING.". PROVIDE SEPARATE SLEEVES <br />AND/OR FIRE BARRIERS FOR CABLE FIRE WALL PENETRATION, UNLESS CABLE IS UL <br />LISTED FOR THE APPLICATION. <br />G.IDENTIFY AND COLOR-CODE CONDUCTORS AND CABLES IN ACCORDANCE WITH <br />DIVISION 26 SECTION "IDENTIFICATION FOR ELECTRICAL SYSTEM. COLOR-CODED <br />CONDUCTOR SLEEVES ARE NOT PERMITTED." <br />H.METAL CLAD (MC) CABLE INSTALLATION REQUIREMENTS: <br />1.PROVIDE J-BOX ABOVE CEILING BEFORE RUNNING MC CABLE DOWN WITH <br />PARTITIONS OR WALLS. <br />2.OVERHEAD MC CABLE RUNS SHALL GENERALLY FOLLOW BUILDING LINES TO <br />PROVIDE A NEAT AND WORKMANLIKE INSTALLATION. <br />3.OVERSIZE J-BOX TO ACCOMMODATE MC CABLE SPLICING. <br />4.MC CABLE MAY BE RUN DOWN DIRECTLY INTO PANELBOARDS TO AVOID EXTRA <br />SPLICE INTO J-BOX ABOVE PANELBOARD AS LONG AS CONCEALED. INSTALLED IN A <br />NEAT ORDERLY MANNER USING UNISTRUT® OR EQUAL TO SPACE AND HOLD MC <br />CABLE IN PLACE <br />5.MC CABLE RUNS SHALL NOT REST ON CEILING STRUCTURES. DO NOT SUPPORT MC <br />CABLE ON HUNG CEILING OR CEILING SUPPORT WIRES. DO NOT SUPPORT CABLES <br />OR ALLOW CONTACT WITH MECHANICAL PIPING. THE USE OF CABLE TIES TO <br />SUPPORT MC CABLE IS NOT ALLOWED. <br />6.USE LOCK OR SPRING NUT FITTINGS. <br />7.SECURELY SUPPORT MC CABLE WITH CABLE HANGERS, INDIVIDUAL SPRING STEEL <br />SUPPORT CLIPS, STEEL TRAPEZE HANGERS, THREADED RODS, OR DEDICATED NO. 8 <br />AWG DROP WIRE. CABLE SUPPORTS SHALL BE FASTENED TO CONCRETE SLABS, <br />BEAMS, JOISTS OR OTHER STRUCTURAL MEMBERS OF THE BUILDING. <br />8.MC CABLE SHALL BE SUPPORTED EVERY 6 FEET AND SECURED WITHIN 12 INCHES <br />FROM TERMINATION. <br />9.LIMIT #12 WIRE HOMERUNS TO CODE VOLTAGE DROP REQUIREMENTS. <br />10.DO NOT MAKE SPLICES IN HOME RUN CIRCUITS, EXCEPT DIRECTLY ABOVE THE <br />PANELBOARD. <br />11.CABLE RUNS SHALL BE CONTINUOUS FROM OUTLET TO OUTLET. <br />12.WHEN TERMINATING OR SPLICING AT A JUNCTION, OUTLET, OR SWITCH BOX, CUT <br />THE CABLE SUCH THAT 6-INCHES OF FREE CONDUCTORS REMAIN FOR CONNECTIONS <br />OR SPLICES. USE SCREW-IN OR SPRING LOCK CONNECTOR AND ENSURE A PROPER <br />BONDING BY FIRMLY TIGHTENING THE CONNECTOR TO BOTH THE BOX AND CABLE. <br />13.MC CABLE SHALL BE CUT WITH AN ARMORED CABLE ROTARY CUTTER. <br />14.INSERT AN ANTI-SHORT BUSHING AT CABLE ENDS TO PROTECT CONDUCTORS FROM <br />ABRASION OR USE INSULATED CONNECTORS. <br />15.BEND RADIUS SHALL BE LESS THAN 7 TIMES THE EXTERNAL DIAMETER OF THE <br />CABLE. <br />16.MC CABLES PASSING THROUGH FIRE-RATED WALLS OR ELECTRICAL <br />/TELECOMMUNICATION ROOM WALLS SHALL BE PROVIDED WITH A UL LISTED, FIRE <br />RATED PENETRATION ASSEMBLY. <br />17.PROVIDE #10 NEUTRAL WIRE, OR ONE NEUTRAL PER PHASE FOR THREE-PHASE, <br />FOUR WIRE POWER SUPPLY SYSTEMS TO COMPUTERS, OFFICE MACHINES, <br />PROGRAMMABLE CONTROLS, ELECTRONIC DISCHARGE EQUIPMENT. <br />18.DO NOT EXCEED CODE REQUIREMENTS FOR TOTAL NUMBER OF CURRENT-CARRYING <br />CONDUCTORS IN MULTIPLE MC CABLE RUNS BUNDLED TOGETHER INTO A SINGLE MC <br />CABLE HANGER OR STRAP. NEUTRALS SHALL BE COUNTED AS CURRENT CARRYING <br />CONDUCTORS. <br />19.MAINTAIN A CLEARANCE OF AT LEAST 6 INCHES FROM HOT WATER AND OTHER HIGH <br />TEMPERATURE PIPES. <br />20.MAINTAIN AT LEAST 12 INCHES FROM TELECOMMUNICATION CONDUITS AND <br />UNSHIELDED TWISTED-PAIR TELECOMMUNICATION CABLES. <br />3.03 CONNECTIONS <br />A.PROVIDE STEEL CABLE CONNECTORS WITH INSULATED THROAT, OZ/GEDNEY AMC <br />SERIES OR EQUAL. DIE CAST OR PRESSURE CAST FITTINGS ARE PROHIBITED. <br />B.TIGHTEN ELECTRICAL CONNECTORS AND TERMINALS IN ACCORDANCE WITH <br />MANUFACTURER'S PUBLISHED TORQUE-TIGHTENING VALUES. IF MANUFACTURER'S <br />TORQUE VALUES ARE NOT INDICATED, USE THOSE SPECIFIED IN UL 486A. <br />C.MAKE SPLICES AND TAPS THAT ARE COMPATIBLE WITH CONDUCTOR MATERIAL AND <br />THAT POSSESS EQUIVALENT OR BETTER MECHANICAL STRENGTH AND INSULATION <br />RATINGS THAN UNSPLICED CONDUCTORS. <br />D.WIRING AT OUTLETS: INSTALL WIRING AT OUTLETS OF SUFFICIENT LENGTH TO EXTEND <br />A MINIMUM OF 6 INCHES OUTSIDE OF THE OPENING. <br />3.04 FIELD QUALITY CONTROL <br />A.PERFORM TESTS AND INSPECTIONS. <br />1.PERFORM EACH OF THE FOLLOWING VISUAL AND ELECTRICAL TESTS: <br />a.INSPECT EXPOSED SECTIONS OF CONDUCTOR AND CABLE FOR PHYSICAL <br />DAMAGE AND CORRECT CONNECTION. <br />B.CABLES WILL BE CONSIDERED DEFECTIVE IF THEY DO NOT PASS TESTS AND <br />INSPECTIONS. <br />C.PREPARE TEST AND INSPECTION REPORTS TO RECORD THE FOLLOWING: <br />1.PROCEDURES USED. <br />2.RESULTS THAT COMPLY WITH REQUIREMENTS. <br />3.RESULTS THAT DO NOT COMPLY WITH REQUIREMENTS, AND CORRECTIVE ACTION <br />TAKEN TO ACHIEVE COMPLIANCE WITH REQUIREMENTS. <br />SECTION 26 0526 <br />GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS <br />PART 1 - GENERAL <br />1.01 SUMMARY <br />A.SECTION INCLUDES GROUNDING OF ELECTRICAL SYSTEMS AND EQUIPMENT. <br />GROUNDING REQUIREMENTS SPECIFIED IN THIS SECTION MAY BE SUPPLEMENTED BY <br />SPECIAL REQUIREMENTS OF SYSTEMS DESCRIBED IN OTHER SECTIONS. <br />B.GROUNDING TO WATER PIPING WHETHER UNDERGROUND, OR INDOORS IS STRICTLY <br />PROHIBITED. <br />1.02 SUBMITTALS <br />A.PRODUCT DATA: FOR EACH TYPE OF PRODUCT INDICATED. <br />B.PRODUCT DATA: NONE <br />1.03 QUALITY ASSURANCE <br />A.ELECTRICAL COMPONENTS, DEVICES, AND ACCESSORIES: LISTED AND LABELED AS <br />DEFINED IN CEC, ARTICLE 100, BY A TESTING AGENCY ACCEPTABLE TO AUTHORITIES <br />HAVING JURISDICTION, AND MARKED FOR INTENDED USE. <br />1.COMPLY WITH UL 467. <br />B.COMPLY WITH CEC; FOR MEDIUM-VOLTAGE UNDERGROUND CONSTRUCTION, COMPLY <br />WITH IEEE C2. <br />PART 2 - PRODUCTS <br />2.01 MANUFACTURERS <br />A.MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE <br />PRODUCTS BY ONE OF THE FOLLOWING: <br />1.GROUNDING CONDUCTORS, CABLES, CONNECTORS, AND RODS: <br />a.APPLETON <br />b.BURNDY ELECTRICAL. <br />c.COOPER POWER SYSTEMS. <br />d.COPPERWELD CORP. <br />e.ERICO INC. <br />f.HUBBELL. <br />g.O-Z/GEDNEY CO. <br />h.THOMAS & BETTS <br />i.OR EQUAL. <br />B.OR EQUAL: WHERE PRODUCTS ARE SPECIFIED BY MANUFACTURERS NAME AND <br />ACCOMPANIED BY THE TERM "OR EQUAL", COMPLY WITH PROVISIONS IN DIVISION 01. <br />SPECIFIC PROCEDURES MUST BE FOLLOWED BEFORE USE OF AN UNNAMED PRODUCT <br />OR MANUFACTURER. <br />2.02 GROUNDING CONDUCTORS <br />A.FOR INSULATED CONDUCTORS, COMPLY WITH DIVISION 26 SECTION "LOW-VOLTAGE <br />ELECTRICAL POWER CONDUCTORS AND CABLES.” <br />B.MATERIAL: COPPER. <br />C.EQUIPMENT GROUNDING CONDUCTORS: INSULATED WITH GREEN-COLORED <br />INSULATION. <br />D.ISOLATED GROUND CONDUCTORS: INSULATED WITH GREEN-COLORED INSULATION WITH <br />YELLOW STRIPE. ON FEEDERS WITH ISOLATED GROUND, USE COLORED TAPE, <br />ALTERNATING BANDS OF GREEN AND YELLOW TAPE TO PROVIDE A MINIMUM OF THREE <br />BANDS OF GREEN AND TWO BANDS OF YELLOW. <br />E.GROUNDING ELECTRODE CONDUCTORS: STRANDED CABLE. <br />F.UNDERGROUND CONDUCTORS: BARE, TINNED, STRANDED, UNLESS OTHERWISE <br />INDICATED. <br />G.BARE COPPER CONDUCTORS: COMPLY WITH THE FOLLOWING: <br />1.SOLID CONDUCTORS: ASTM B3. <br />2.ASSEMBLY OF STRANDED CONDUCTORS: ASTM B8. <br />3.TINNED CONDUCTORS: ASTM B33. <br />H.COPPER BONDING CONDUCTORS: AS FOLLOWS: <br />1.BONDING CABLE: 28 KCMIL, 14 STRANDS OF NO. 17 AWG COPPER CONDUCTOR, AND <br />¼ INCH IN DIAMETER. <br />2.BONDING CONDUCTOR: NO. 4 OR NO. 6 AWG, STRANDED COPPER CONDUCTOR. <br />3.BONDING JUMPER: BARE COPPER TAPE, BRAIDED BARE COPPER CONDUCTORS, <br />TERMINATED WITH COPPER FERRULES; 1⅝ INCHES WIDE AND 1/16 INCH THICK. <br />4.TINNED BONDING JUMPER: TINNED-COPPER TAPE, BRAIDED COPPER CONDUCTORS, <br />TERMINATED WITH COPPER FERRULES; 1⅝ INCHES WIDE AND 1/16 INCH THICK. <br />I.GROUNDING BUS: BARE, ANNEALED COPPER BARS OF RECTANGULAR CROSS SECTION, <br />WITH INSULATORS. <br />2.03 CONNECTOR PRODUCTS <br />A.COMPLY WITH IEEE 837 AND UL 467; LISTED FOR USE FOR SPECIFIC TYPES, SIZES, AND <br />COMBINATIONS OF CONDUCTORS AND CONNECTED ITEMS. <br />B.WELDED CONNECTORS: EXOTHERMIC-WELDED TYPE, IN KIT FORM, AND SELECTED PER <br />MANUFACTURER'S WRITTEN INSTRUCTIONS. <br />PART 3 - EXECUTION <br />3.01 APPLICATION <br />A.USE ONLY COPPER CONDUCTORS FOR BOTH INSULATED AND BARE GROUNDING <br />CONDUCTORS. <br />B.IN RACEWAYS, USE INSULATED EQUIPMENT GROUNDING CONDUCTORS. <br />C.EXOTHERMIC-WELDED CONNECTIONS: USE FOR CONNECTIONS TO STRUCTURAL STEEL <br />AND FOR UNDERGROUND CONNECTIONS, EXCEPT THOSE AT TEST WELLS. <br />D.EQUIPMENT GROUNDING CONDUCTOR TERMINATIONS: USE BOLTED PRESSURE CLAMPS. <br />E.GROUNDING BUS: INSTALL AS INDICATED. <br />1.USE INSULATED SPACER; SPACE 1 INCH FROM WALL AND SUPPORT FROM WALL 6 <br />INCHES ABOVE FINISHED FLOOR, UNLESS OTHERWISE INDICATED. <br />2.AT DOORS, ROUTE THE BUS UP TO THE TOP OF THE DOOR FRAME, ACROSS THE TOP <br />OF THE DOORWAY, AND DOWN TO THE SPECIFIED HEIGHT ABOVE THE FLOOR. <br />F.UNDERGROUND GROUNDING CONDUCTORS: USE COPPER CONDUCTOR, NO. 2/0 AWG, <br />MINIMUM. BURY AT LEAST 24 INCHES BELOW GRADE OR BURY 12 INCHES ABOVE DUCT <br />BANK WHEN INSTALLED AS PART OF THE DUCT BANK. <br />3.02 EQUIPMENT GROUNDING CONDUCTORS <br />A.COMPLY WITH CEC, ARTICLE 250, FOR TYPES, SIZES, AND QUANTITIES OF EQUIPMENT <br />GROUNDING CONDUCTORS, UNLESS SPECIFIC TYPES, LARGER SIZES, OR MORE <br />CONDUCTORS THAN REQUIRED BY CEC ARE INDICATED. <br />B.INSTALL EQUIPMENT GROUNDING CONDUCTORS IN FEEDERS AND CIRCUITS. <br />C.INSTALL INSULATED EQUIPMENT GROUNDING CONDUCTOR WITH CIRCUIT CONDUCTORS <br />FOR THE FOLLOWING ITEMS, IN ADDITION TO THOSE REQUIRED BY NEC: <br />1.FEEDERS AND BRANCH CIRCUITS. <br />2.LIGHTING CIRCUITS. <br />3.RECEPTACLE CIRCUITS. <br />4.SINGLE-PHASE MOTOR AND APPLIANCE BRANCH CIRCUITS. <br />5.THREE-PHASE MOTOR AND APPLIANCE BRANCH CIRCUITS. <br />6.FLEXIBLE RACEWAY RUNS. <br />7.ARMORED AND METAL-CLAD CABLE RUNS. <br />D.AIR-DUCT EQUIPMENT CIRCUITS: INSTALL AN EQUIPMENT GROUNDING CONDUCTOR TO <br />DUCT-MOUNTED ELECTRICAL DEVICES OPERATING AT 120 V AND MORE, INCLUDING AIR <br />CLEANERS AND HEATERS. BOND CONDUCTOR TO EACH UNIT AND TO AIR DUCT. <br />3.03 INSTALLATION <br />A.GROUNDING CONDUCTORS: ROUTE ALONG SHORTEST AND STRAIGHTEST PATHS <br />POSSIBLE, UNLESS OTHERWISE INDICATED. AVOID OBSTRUCTING ACCESS OR PLACING <br />CONDUCTORS WHERE THEY MAY BE SUBJECTED TO STRAIN, IMPACT, OR DAMAGE. <br />B.BONDING STRAPS AND JUMPERS: INSTALL SO VIBRATION BY EQUIPMENT MOUNTED ON <br />VIBRATION ISOLATION HANGERS AND SUPPORTS IS NOT TRANSMITTED TO RIGIDLY <br />MOUNTED EQUIPMENT. USE EXOTHERMIC-WELDED CONNECTORS FOR OUTDOOR <br />LOCATIONS, UNLESS A DISCONNECT-TYPE CONNECTION IS REQUIRED; THEN, USE A <br />BOLTED CLAMP. BOND STRAPS DIRECTLY TO THE BASIC STRUCTURE TAKING CARE NOT <br />TO PENETRATE ANY ADJACENT PARTS. INSTALL STRAPS ONLY IN LOCATIONS <br />ACCESSIBLE FOR MAINTENANCE. <br />C.METAL WATER SERVICE AND METER PIPING: GROUNDING TO WATER PIPES IS <br />PROHIBITED ON SITE. SITE WATER MAINS ARE NON-CONDUCTING. BOND BUILDING PIPING <br />TO THE SEPARATE GROUNDING SYSTEM FOR THE BUILDING. <br />3.04 CONNECTIONS <br />A.GENERAL: MAKE CONNECTIONS SO GALVANIC ACTION OR ELECTROLYSIS POSSIBILITY IS <br />MINIMIZED. SELECT CONNECTORS, CONNECTION HARDWARE, CONDUCTORS, AND <br />CONNECTION METHODS SO METALS IN DIRECT CONTACT ARE COMPATIBLE. <br />1.USE ELECTROPLATED OR HOT-TIN-COATED MATERIALS TO ENSURE HIGH <br />CONDUCTIVITY AND TO MAKE CONTACT POINTS CLOSER TO ORDER OF GALVANIC <br />SERIES. <br />2.MAKE CONNECTIONS WITH CLEAN, BARE METAL AT POINTS OF CONTACT. <br />3.COAT AND SEAL CONNECTIONS HAVING DISSIMILAR METALS WITH INERT MATERIAL <br />TO PREVENT FUTURE PENETRATION OF MOISTURE TO CONTACT SURFACES. <br />B.EXOTHERMIC-WELDED CONNECTIONS: COMPLY WITH MANUFACTURER'S WRITTEN <br />INSTRUCTIONS. WELDS THAT ARE PUFFED UP OR THAT SHOW CONVEX SURFACES <br />INDICATING IMPROPER CLEANING ARE NOT ACCEPTABLE. <br />C.EQUIPMENT GROUNDING CONDUCTOR TERMINATIONS: FOR NO. 8 AWG AND LARGER, <br />USE PRESSURE-TYPE GROUNDING LUGS. NO. 10 AWG AND SMALLER GROUNDING <br />CONDUCTORS MAY BE TERMINATED WITH WINGED PRESSURE-TYPE CONNECTORS. <br />D.TIGHTEN SCREWS AND BOLTS FOR GROUNDING AND BONDING CONNECTORS AND <br />TERMINALS IN ACCORDANCE WITH MANUFACTURER'S PUBLISHED TORQUE-TIGHTENING <br />VALUES. IF MANUFACTURER'S TORQUE VALUES ARE NOT INDICATED, USE THOSE <br />SPECIFIED IN UL 486A. <br />E.COMPRESSION-TYPE CONNECTIONS: USE HYDRAULIC COMPRESSION TOOLS TO <br />PROVIDE CORRECT CIRCUMFERENTIAL PRESSURE FOR COMPRESSION CONNECTORS. <br />USE TOOLS AND DIES RECOMMENDED BY CONNECTOR MANUFACTURER. PROVIDE <br />EMBOSSING DIE CODE OR OTHER STANDARD METHOD TO MAKE A VISIBLE INDICATION <br />THAT A CONNECTOR HAS BEEN ADEQUATELY COMPRESSED ON GROUNDING <br />CONDUCTOR. <br />F.MOISTURE PROTECTION: IF INSULATED GROUNDING CONDUCTORS ARE CONNECTED TO <br />GROUND RODS OR GROUNDING BUSES, INSULATE ENTIRE AREA OF CONNECTION AND <br />SEAL AGAINST MOISTURE PENETRATION OF INSULATION AND CABLE. <br />G.GROUND BUS CONNECTIONS: SHALL BE ONE HOLE, COPPER CABLE TERMINATION TYPE <br />BURNDY HYLUG™, THOMAS & BETTS BLUE, OR EQUAL. INSTALL WITH ¼ TO ½-INCH <br />SILICON BRONZE HEX-HEAD MACHINE BOLTS WITH BRONZE WASHER EACH SIDE. <br />MACHINE BOLTS SHALL BE IN ACCORDANCE WITH ASTM F468 AND NUTS SHALL BE IN <br />ACCORDANCE WITH ASTM F467. <br />SECTION 26 0529 <br />HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS <br />PART 1 - GENERAL <br />1.01 SUMMARY <br />A.SECTION INCLUDES THE FOLLOWING: <br />1.HANGERS AND SUPPORTS FOR ELECTRICAL EQUIPMENT AND SYSTEMS. <br />1.02 DEFINITIONS <br />A.CEC: CALIFORNIA ELECTRIC CODE <br />B.EMT: ELECTRICAL METALLIC TUBING. <br />C.RMC: RIGID METAL CONDUIT. <br />D.SEISMIC RESTRAINT: A STRUCTURAL SUPPORT ELEMENT SUCH AS A METAL FRAMING <br />MEMBER, A CABLE, AN ANCHOR BOLT OR STUD, A FASTENING DEVICE, OR AN ASSEMBLY <br />OF THESE ITEMS USED TO TRANSMIT SEISMIC FORCES FROM AN ITEM OF EQUIPMENT OR <br />SYSTEM TO BUILDING STRUCTURE AND TO LIMIT MOVEMENT OF ITEM DURING A SEISMIC <br />EVENT. <br />1.03 SUBMITTALS <br />A.PRODUCT DATA: ILLUSTRATE AND INDICATE STYLE, MATERIAL, STRENGTH, FASTENING <br />PROVISION, AND FINISH FOR EACH TYPE AND SIZE OF ELECTRICAL SUPPORT AND <br />SEISMIC-RESTRAINT COMPONENT USED. <br />1.04 QUALITY ASSURANCE <br />A.COMPLY WITH SEISMIC-RESTRAINT REQUIREMENTS IN THE CALIFORNIA BUILDING CODE <br />B.STRUCTURAL SEISMIC PERFORMANCE: REFER TO DIVISION 26 SECTION “VIBRATION AND <br />SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS.” <br />PART 2 - PRODUCTS <br />2.01 MANUFACTURERS <br />A.IN OTHER PART 2 ARTICLES WHERE TITLES BELOW INTRODUCE LISTS, THE FOLLOWING <br />REQUIREMENTS APPLY TO PRODUCT SELECTION: <br />1.MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE <br />PRODUCTS BY ONE OF THE MANUFACTURERS SPECIFIED. <br />2.OR EQUAL: WHERE PRODUCTS ARE SPECIFIED BY MANUFACTURERS NAME AND <br />ACCOMPANIED BY THE TERM "OR EQUAL", COMPLY WITH PROVISIONS IN DIVISION 01. <br />SPECIFIC PROCEDURES MUST BE FOLLOWED BEFORE USE OF AN UNNAMED <br />PRODUCT OR MANUFACTURER. <br />2.02 SUPPORT, ANCHORAGE, AND ATTACHMENT COMPONENTS <br />A.RATED STRENGTH: ADEQUATE IN TENSION, SHEAR, AND PULLOUT FORCE TO RESIST <br />MAXIMUM LOADS CALCULATED OR IMPOSED UNDER THIS PROJECT, WITH A MINIMUM <br />STRUCTURAL SAFETY FACTOR OF FIVE TIMES THE APPLIED FORCE. <br />B.STEEL SLOTTED SUPPORT SYSTEMS: COMPLY WITH MFMA-4, FACTORY-FABRICATED <br />COMPONENTS FOR FIELD ASSEMBLY. <br />1.MANUFACTURERS: <br />a.ALLIED SUPPORT SYSTEMS; POWER-STRUT UNIT. <br />b.COOPER B-LINE; A DIVISION OF COOPER INDUSTRIES. <br />c.ERICO INTERNATIONAL CORPORATION. <br />d.GS METALS CORP. <br />e.MICHIGAN HANGER CO., INC.; O-STRUT DIV. <br />f.NATIONAL PIPE HANGER CORP. <br />g.THOMAS & BETTS CORPORATION. <br />h.UNISTRUT. <br />i.WESANCO, INC. <br />j.OR EQUAL. <br />2.FINISHES: <br />a.METALLIC COATINGS: HOT-DIP GALVANIZED AFTER FABRICATION AND APPLIED IN <br />ACCORDANCE WITH MFMA-4. <br />b.NONMETALLIC COATINGS: MANUFACTURER'S STANDARD PVC, POLYURETHANE, <br />OR POLYESTER COATING APPLIED IN ACCORDANCE WITH MFMA-4. <br />c.PAINTED COATINGS: MANUFACTURER'S STANDARD PAINTED COATING APPLIED IN <br />ACCORDANCE WITH MFMA-4. <br />3.CHANNEL DIMENSIONS: SELECTED FOR STRUCTURAL LOADING AND APPLICABLE <br />SEISMIC FORCES. <br />C.RACEWAY AND CABLE SUPPORTS: AS DESCRIBED IN NECA 1. <br />D.CONDUIT AND CABLE SUPPORT DEVICES: STEEL AND MALLEABLE-IRON HANGERS, <br />CLAMPS, AND ASSOCIATED FITTINGS, DESIGNED FOR TYPES AND SIZES OF RACEWAY OR <br />CABLE TO BE SUPPORTED. <br />E.SUPPORT FOR CONDUCTORS IN VERTICAL CONDUIT: FACTORY-FABRICATED ASSEMBLY <br />CONSISTING OF THREADED BODY AND INSULATING WEDGING PLUG OR PLUGS FOR <br />NON-ARMORED ELECTRICAL CONDUCTORS OR CABLES IN RISER CONDUITS. PLUGS <br />SHALL HAVE NUMBER, SIZE, AND SHAPE OF CONDUCTOR GRIPPING PIECES AS REQUIRED <br />TO SUIT INDIVIDUAL CONDUCTORS OR CABLES SUPPORTED. BODY SHALL BE MALLEABLE <br />IRON. <br />F.STRUCTURAL STEEL FOR FABRICATED SUPPORTS AND RESTRAINTS: ASTM A36, STEEL <br />PLATES, SHAPES, AND BARS; BLACK AND GALVANIZED. <br />G.MOUNTING, ANCHORING, AND ATTACHMENT COMPONENTS: ITEMS FOR FASTENING <br />ELECTRICAL ITEMS OR THEIR SUPPORTS TO BUILDING SURFACES INCLUDE THE <br />FOLLOWING: <br />1.POWDER-ACTUATED FASTENERS: ARE PROHIBITED EXCEPT WHEN EXECUTED IN <br />ACCORDANCE WITH DIVISION 01. <br />2.THREADED-STEEL STUD, FOR USE IN HARDENED PORTLAND CEMENT CONCRETE, <br />STEEL, OR WOOD, WITH TENSION, SHEAR, AND PULLOUT CAPACITIES APPROPRIATE <br />FOR SUPPORTED LOADS AND BUILDING MATERIALS WHERE USED. <br />a.MANUFACTURERS: <br />1)HILTI, INC. <br />2)ITW CONSTRUCTION PRODUCTS. <br />3)MKT FASTENING, LLC. <br />4)SIMPSON STRONG-TIE CO. INC. <br />5)OR EQUAL. <br />3.MECHANICAL-EXPANSION ANCHORS: INSERT-WEDGE-TYPE, HOT DIP GALVANIZED <br />STEEL OR STAINLESS STEEL, FOR USE IN HARDENED PORTLAND CEMENT CONCRETE <br />WITH TENSION, SHEAR, AND PULLOUT CAPACITIES APPROPRIATE FOR SUPPORTED <br />LOADS AND BUILDING MATERIALS IN WHICH USED. <br />a.MANUFACTURERS: <br />1)COOPER B-LINE; A DIVISION OF COOPER INDUSTRIES. <br />2)EMPIRE TOOL AND MANUFACTURING CO., INC <br />3)HILTI, INC. <br />4)ITW CONSTRUCTION PRODUCTS. <br />5)MKT FASTENING, LLC. <br />6)POWERS FASTENERS. <br />7)OR EQUAL. <br />4.CONCRETE INSERTS: STEEL OR MALLEABLE-IRON SLOTTED-SUPPORT-SYSTEM UNITS <br />SIMILAR TO MSS TYPE 18; COMPLYING WITH MFMA-4 OR MSS SP-58. <br />5.CLAMPS FOR ATTACHMENT TO STEEL STRUCTURAL ELEMENTS: MSS SP-58, TYPE <br />SUITABLE FOR ATTACHED STRUCTURAL ELEMENT. <br />6.THROUGH BOLTS: STRUCTURAL TYPE, HEX HEAD, HIGH STRENGTH. COMPLY WITH <br />ASTM A325. <br />7.TOGGLE BOLTS: STEEL SPRINGHEAD TYPE. <br />8.HANGER RODS: THREADED STEEL. <br />2.03 SEISMIC-RESTRAINT COMPONENTS <br />A.RATED STRENGTH, FEATURES, AND APPLICATION REQUIREMENTS FOR RESTRAINT <br />COMPONENTS: AS DEFINED IN REPORTS BY AN AGENCY ACCEPTABLE TO THE OWNER. <br />1.STRUCTURAL SAFETY FACTOR: STRENGTH IN TENSION, SHEAR, AND PULLOUT <br />FORCE OF COMPONENTS USED SHALL BE AT LEAST FIVE TIMES THE MAXIMUM <br />SEISMIC FORCES TO WHICH THEY WILL BE SUBJECTED. <br />B.ANGLE AND CHANNEL-TYPE BRACE ASSEMBLIES: STEEL ANGLES OR STEEL <br />SLOTTED-SUPPORT-SYSTEM COMPONENTS; WITH ACCESSORIES FOR ATTACHMENT TO <br />BRACED COMPONENT AT ONE END AND TO BUILDING STRUCTURE AT THE OTHER END. <br />C.CABLE RESTRAINTS: ASTM A603, ZINC-COATED, STEEL WIRE ROPE ATTACHED TO STEEL <br />OR STAINLESS-STEEL THIMBLES, BRACKETS, SWIVELS, AND BOLTS DESIGNED FOR <br />RESTRAINING CABLE SERVICE. <br />1.MANUFACTURERS: <br />a.AMBER/BOOTH COMPANY, INC. <br />b.LOOS & CO., INC. <br />c.MASON INDUSTRIES, INC. <br />d.OR EQUAL. <br />2.SEISMIC MOUNTINGS, ANCHORS, AND ATTACHMENTS: DEVICES AS SPECIFIED IN <br />PART 2 "SUPPORT, ANCHORAGE, AND ATTACHMENT COMPONENTS" ARTICLE, <br />SELECTED TO RESIST SEISMIC FORCES. <br />3.HANGER ROD STIFFENER: REINFORCING STEEL ANGLE CLAMPED TO HANGER ROD, <br />OF DESIGN RECOGNIZED BY AN AGENCY ACCEPTABLE TO THE OWNER. <br />4.BUSHINGS FOR FLOOR-MOUNTED EQUIPMENT ANCHORS: NEOPRENE UNITS <br />DESIGNED FOR SEISMICALLY RATED RIGID EQUIPMENT MOUNTINGS, AND MATCHED <br />TO TYPE AND SIZE OF ANCHOR BOLTS AND STUDS USED. <br />5.BUSHING ASSEMBLIES FOR WALL-MOUNTED EQUIPMENT ANCHORAGE: ASSEMBLIES <br />OF NEOPRENE ELEMENTS AND STEEL SLEEVES DESIGNED FOR SEISMICALLY RATED <br />RIGID EQUIPMENT MOUNTINGS, AND MATCHED TO TYPE AND SIZE OF ATTACHMENT <br />DEVICES USED. <br />PART 3 - EXECUTION <br />3.01 APPLICATION <br />A.COMPLY WITH NECA 1 FOR APPLICATION OF HANGERS AND SUPPORTS FOR ELECTRICAL <br />EQUIPMENT AND SYSTEMS, EXCEPT IF REQUIREMENTS IN THIS SECTION ARE MORE <br />STRINGENT. <br />B.MAXIMUM SUPPORT SPACING AND MINIMUM HANGER ROD SIZE FOR RACEWAY: SPACE <br />SUPPORTS FOR EMT, AND RMC AS SCHEDULED IN NECA 1, WHERE TABLE 1 LISTS <br />MAXIMUM SPACING LESS THAN STATED IN. MINIMUM ROD SIZE SHALL BE ¼ INCH IN <br />DIAMETER. <br />C.OUTSIDE OF CONDITIONED SPACES, PROVIDE HOT DIP GALVANIZED OR, IN CORROSIVE <br />AREAS, PROVIDE STAINLESS STEEL. <br />D.FOR INDIVIDUAL CONDUIT RUNS NOT DIRECTLY FASTENED TO THE STRUCTURE, USE ROD <br />HANGERS. <br />E.ARRANGE CONDUIT SUPPORTS TO PREVENT DISTORTION OF ALIGNMENT BY WIRE <br />PULLING OPERATIONS. FASTEN CONDUIT USING GALVANIZED STRAPS, LAY-IN <br />ADJUSTABLE HANGERS, CLEVIS HANGERS, OR BOLTED SPLIT GALVANIZED HANGERS. <br />F.CONDUIT FASTENED WITH WIRE OR PERFORATED PIPE STRAPS ARE PROHIBITED. <br />REMOVE WIRE USED FOR TEMPORARY CONDUIT SUPPORT DURING CONSTRUCTION <br />BEFORE CONDUCTORS ARE PULLED. DO NOT USE CEILING WIRE TO SUPPORT CONDUIT. <br />G.MULTIPLE RACEWAYS OR CABLES: INSTALL TRAPEZE-TYPE SUPPORTS FABRICATED <br />WITH STEEL SLOTTED SUPPORT SYSTEM, SIZED SO CAPACITY CAN BE INCREASED BY AT <br />LEAST 25 PERCENT IN FUTURE WITHOUT EXCEEDING SPECIFIED DESIGN LOAD LIMITS. <br />SUPPORTS SHOULD BE SPACED FOR MAXIMUM DEFLECTION OF CONDUIT NOT GREATER <br />THAN ⅛ INCH. <br />1.SECURE RACEWAYS AND CABLES TO TRAPEZE MEMBER WITH CLAMPS APPROVED <br />FOR APPLICATION BY AN AGENCY ACCEPTABLE TO THE OWNER. <br />3.02 SUPPORT AND SEISMIC-RESTRAINT INSTALLATION <br />A.COMPLY WITH NECA 1 FOR INSTALLATION REQUIREMENTS, EXCEPT AS SPECIFIED IN THIS <br />ARTICLE. <br />B.RACEWAY SUPPORT METHODS: IN ADDITION TO METHODS DESCRIBED IN NECA 1, EMT, <br />RMC MAY BE SUPPORTED BY OPENINGS THROUGH STRUCTURE MEMBERS, AS <br />PERMITTED IN CEC. <br />C.INSTALL SEISMIC-RESTRAINT COMPONENTS USING METHODS APPROVED BY THE <br />EVALUATION SERVICE PROVIDING REQUIRED SUBMITTALS FOR COMPONENT. <br />D.DRILL HOLES FOR EXPANSION ANCHORS IN CONCRETE AT LOCATIONS AND TO DEPTHS <br />THAT AVOID REINFORCING BARS. <br />3.03 INSTALLATION OF SEISMIC-RESTRAINT COMPONENTS <br />A.INSTALL BUSHING ASSEMBLIES FOR ANCHOR BOLTS FOR FLOOR-MOUNTED EQUIPMENT, <br />ARRANGED TO PROVIDE RESILIENT MEDIA BETWEEN ANCHOR BOLTS AND MOUNTING <br />HOLE IN CONCRETE BASE. <br />B.INSTALL BUSHING ASSEMBLIES FOR MOUNTING BOLTS FOR WALL-MOUNTED EQUIPMENT, <br />ARRANGED TO PROVIDE RESILIENT MEDIA WHERE EQUIPMENT OR <br />EQUIPMENT-MOUNTING CHANNELS ARE ATTACHED TO WALL. <br />C.RESTRAINT CABLES: PROVIDE SLACK WITHIN MAXIMUMS RECOMMENDED BY <br />MANUFACTURER. <br />D.ATTACHMENT TO STRUCTURE: IF SPECIFIC ATTACHMENT IS NOT INDICATED, ANCHOR <br />BRACING TO STRUCTURE AT FLANGES OF BEAMS, UPPER TRUSS CHORDS OF BAR <br />JOISTS, OR AT CONCRETE MEMBERS. <br />E.PROVIDE RACEWAY FIXTURES AND EQUIPMENT SYSTEMS WITH APPROPRIATE <br />LONGITUDINAL AND CROSS BRACING TO SATISFY SEISMIC REQUIREMENTS. <br />SECTION 26 0533 <br />RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS <br />PART 1 - GENERAL <br />1.01 SUMMARY <br />A.SECTION INCLUDES: <br />1.METAL CONDUITS AND FITTINGS. <br />2.METAL WIREWAYS AND AUXILIARY GUTTERS. <br />3.SURFACE RACEWAYS. <br />4.BOXES, ENCLOSURES, AND CABINETS. <br />1.02 DEFINITIONS <br />A.ARC:ALUMINUM RIGID CONDUIT. <br />B.EMT: ELECTRICAL METALLIC TUBING. <br />C.FMC:FLEXIBLE METAL CONDUIT <br />D.GRC:GALVANIZED RIGID STEEL CONDUIT. <br />E.IMC:INTERMEDIATE METAL CONDUIT. <br />F.LFMC:LIQUIDTIGHT FLEXIBLE METAL CONDUIT. <br />G.RMC: RIGID METAL CONDUIT. <br />H.RNC:RIGID NONMETALLIC CONDUIT. <br />1.03 ACTION SUBMITTALS <br />A.PRODUCT DATA: FOR SURFACE RACEWAYS, WIREWAYS AND FITTINGS. <br />1.04 QUALITY ASSURANCE <br />A.LISTING AND LABELING: LISTED AND LABELED AS DEFINED IN CALIFORNIA ELECTRIC <br />CODE, BY A QUALIFIED TESTING AGENCY, AND MARKED FOR INTENDED LOCATION AND <br />APPLICATION. <br />B.COMPLY WITH CEC. <br />C.PROHIBITED: ELECTRICAL MATERIALS MADE IN CHINA. <br />1.05 COORDINATION <br />A.COORDINATE LAYOUT AND INSTALLATION OF RACEWAYS, BOXES, ENCLOSURES, <br />CABINETS, AND SUSPENSION SYSTEM WITH OTHER CONSTRUCTION THAT PENETRATES <br />CEILINGS OR IS SUPPORTED BY THEM, INCLUDING LIGHT FIXTURES, HVAC EQUIPMENT, <br />FIRE-SUPPRESSION SYSTEM, AND PARTITION ASSEMBLIES. <br />PART 2 - PRODUCTS <br />2.01 MANUFACTURERS <br />A.IN OTHER PART 2 ARTICLES WHERE SUBPARAGRAPH TITLES BELOW INTRODUCE LISTS, <br />THE FOLLOWING REQUIREMENTS APPLY FOR PRODUCT SELECTION: <br />1.MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE <br />PRODUCTS BY THE MANUFACTURERS SPECIFIED. <br />2.OR EQUAL: WHERE PRODUCTS ARE SPECIFIED BY MANUFACTURERS NAME AND <br />ACCOMPANIED BY THE TERM "OR EQUAL", COMPLY WITH PROVISIONS IN DIVISION 01 <br />SPECIFIC PROCEDURES MUST BE FOLLOWED BEFORE USE OF AN UNNAMED <br />PRODUCT OR MANUFACTURER. <br />2.02 METAL CONDUIT AND TUBING <br />A.METAL CONDUIT: <br />1.MANUFACTURERS: <br />a.AFC CABLE SYSTEMS, INC. <br />b.ALFLEX INC. <br />c.ALLIED TUBE AND CONDUIT <br />d.ANAMET ELECTRICAL, INC.; ANACONDA METAL HOSE. <br />e.ELECTRI-FLEX CO. <br />f.GRINNELL CO. <br />g.LTV STEEL TUBULAR PRODUCTS COMPANY. <br />h.MANHATTAN/CDT/COLE-FLEX. <br />i.O-Z GEDNEY. <br />j.SOUTHWIRE COMPANY. <br />k.WESTERN TUBE & CONDUIT CORPORATION <br />l.WHEATLAND TUBE CO. <br />m.OR EQUAL. <br />2.GRC: COMPLY WITH ANSI C80.1 AND UL 6. <br />3.ARC: COMPLY WITH ANSI C80.5 AND UL 6A. <br />4.IMC: COMPLY WITH ANSI C80.6 AND UL 1242. <br />5.PVC-COATED STEEL CONDUIT: PVC-COATED RIGID STEEL CONDUIT OR IMC. <br />a.COMPLY WITH NEMA RN 1. <br />b.COATING THICKNESS: 0.040 INCH, MINIMUM. <br />6.EMT: COMPLY WITH ANSI C80.3 AND UL 797. <br />7.FMC: COMPLY WITH UL 1; GALVANIZED STEEL. FULL WALL <br />8.LFMC: FLEXIBLE STEEL CONDUIT WITH PVC JACKET AND COMPLYING WITH UL 360. <br />B.METAL FITTINGS: <br />1.MANUFACTURERS: <br />a.BRIDGEPORT FITTINGS, INC. <br />b.RACO; DIVISION OF HUBBELL, INC. <br />c.THOMAS & BETTS <br />d.OR EQUAL. <br />2.COMPLY WITH NEMA FB 1 AND UL 514B. <br />3.FITTINGS, GENERAL: LISTED AND LABELED FOR TYPE OF CONDUIT, LOCATION, AND <br />USE. <br />4.CONDUIT FITTINGS FOR HAZARDOUS (CLASSIFIED) LOCATIONS: COMPLY WITH UL 1203 <br />AND CEC. <br />5.FITTINGS FOR EMT: <br />a.MATERIAL: STEEL OR DIE CAST. <br />b.TYPE: SETSCREW. <br />6.EXPANSION FITTINGS: PVC OR STEEL TO MATCH CONDUIT TYPE, COMPLYING WITH <br />UL 651, RATED FOR THE ENVIRONMENTAL CONDITIONS WHERE IT IS INSTALLED, AND <br />INCLUDING FLEXIBLE EXTERNAL BONDING JUMPER. <br />7.COATING FOR FITTINGS FOR PVC-COATED CONDUIT: MINIMUM THICKNESS OF 0.040 <br />INCH, WITH OVERLAPPING SLEEVES PROTECTING THREADED JOINTS. <br />C.JOINT COMPOUND FOR IMC, GRC, OR ARC: APPROVED, AS DEFINED IN CEC, BY <br />AUTHORITIES HAVING JURISDICTION FOR USE IN CONDUIT ASSEMBLIES, AND <br />COMPOUNDED FOR USE TO LUBRICATE AND PROTECT THREADED CONDUIT JOINTS FROM <br />CORROSION AND TO ENHANCE THEIR CONDUCTIVITY. <br />2.03 METAL WIREWAYS AND AUXILIARY GUTTERS <br />A.MANUFACTURERS: <br />1.EATON/COOPER/B-LINE <br />2.HOFFMAN. <br />3.SQUARE D. <br />4.OR EQUAL. <br />B.DESCRIPTION: SHEET METAL, COMPLYING WITH UL 870 AND NEMA 250, TYPE 1 FOR <br />INTERIOR USE, TYPE 3R FOR INTERIOR WET LOCATIONS AND TYPE 4 FOR EXTERIOR <br />INSTALLATION, UNLESS OTHERWISE INDICATED, AND SIZED IN ACCORDANCE WITH CEC. <br />1.METAL WIREWAYS INSTALLED IN WET LOCATIONS OR OUTDOORS SHALL BE LISTED <br />AND LABELED AS DEFINED IN CEC, BY A QUALIFIED TESTING AGENCY, AND MARKED <br />FOR INTENDED LOCATION AND APPLICATION. <br />C.FITTINGS AND ACCESSORIES: INCLUDE COVERS, COUPLINGS, OFFSETS, ELBOWS, <br />EXPANSION JOINTS, ADAPTERS, HOLD-DOWN STRAPS, END CAPS, AND OTHER FITTINGS <br />TO MATCH AND MATE WITH WIREWAYS AS REQUIRED FOR COMPLETE SYSTEM. <br />D.WIREWAY COVERS: HINGED TYPE FOR WIREWAYS LARGER THAN 24” X 24”, <br />SCREW-COVER TYPE FOR SMALL WIREWAYS, AND FLANGED-AND-GASKETED TYPE FOR <br />EXTERIOR INSTALLATION OR WET LOCATIONS, UNLESS OTHERWISE INDICATED. <br />E.FINISH: MANUFACTURER'S STANDARD ENAMEL FINISH. <br />2.04 BOXES, ENCLOSURES, AND CABINETS <br />A.MANUFACTURERS: <br />1.COOPER CROUSE-HINDS <br />2.EMERSON <br />3.HOFFMAN. <br />4.HUBBELL, INC. <br />5.O-Z/GEDNEY; <br />6.THOMAS & BETTS CORPORATION. <br />7.WIREMOLD COMPANY. <br />8.OR EQUAL <br />B.PROHIBITED: GANGABLE BOXES. <br />C.SHEET METAL OUTLET AND DEVICE BOXES: NEMA OS 1 AND UL 514A. <br />D.CAST-METAL OUTLET AND DEVICE BOXES: COMPLY WITH NEMA FB 1, FERROUS ALLOY, <br />TYPE FD, WITH GASKETED COVER. <br />E.LUMINAIRE OUTLET BOXES: NONADJUSTABLE, DESIGNED FOR ATTACHMENT OF <br />LUMINAIRE WEIGHING 50 POUNDS. OUTLET BOXES DESIGNED FOR ATTACHMENT OF <br />LUMINAIRES WEIGHING MORE THAN 50 POUNDS SHALL BE LISTED AND MARKED FOR THE <br />MAXIMUM ALLOWABLE WEIGHT. <br />F.SMALL SHEET METAL PULL AND JUNCTION BOXES: NEMA OS 1. <br />G.CAST-METAL ACCESS, PULL, AND JUNCTION BOXES: COMPLY WITH NEMA FB 1 AND <br />UL 1773, CAST ALUMINUM WITH GASKETED COVER. <br />H.BOX EXTENSIONS USED TO ACCOMMODATE NEW OR EXISTING BUILDING FINISHES SHALL <br />BE OF SAME MATERIAL AS RECESSED BOX. <br />I.DEVICE BOX DIMENSIONS: 4 X 2⅛ X 2⅛ INCHES DEEP. <br />J.HINGED-COVER ENCLOSURES: COMPLY WITH UL 50 AND NEMA 250, TYPE 1 FOR INTERIOR <br />USE, TYPE 3R FOR INTERIOR WET LOCATIONS AND TYPE 4 FOR EXTERIOR INSTALLATION, <br />WITH CONTINUOUS-HINGE COVER WITH FLUSH LATCH UNLESS OTHERWISE INDICATED. <br />1.METAL ENCLOSURES: STEEL, FINISHED INSIDE AND OUT WITH MANUFACTURER'S <br />STANDARD ENAMEL. <br />2.NONMETALLIC ENCLOSURES: FIBERGLASS. <br />3.INTERIOR PANELS: STEEL; ALL SIDES FINISHED WITH MANUFACTURER'S STANDARD <br />ENAMEL. <br />PART 3 - EXECUTION <br />3.01 RACEWAY APPLICATION <br />A.INDOORS: APPLY RACEWAY PRODUCTS AS SPECIFIED BELOW UNLESS OTHERWISE <br />INDICATED: <br />1.EXPOSED: EMT. <br />2.EXPOSED AND SUBJECT TO SEVERE PHYSICAL DAMAGE: GRC. RACEWAY LOCATIONS <br />INCLUDE THE FOLLOWING: <br />a.LOADING DOCKS. <br />b.CORRIDORS USED FOR TRAFFIC OF MECHANIZED CARTS, FORKLIFTS, AND <br />PALLET-HANDLING UNITS. <br />c.MECHANICAL ROOMS. <br />d.GYMNASIUMS. <br />3.CONCEALED IN CEILINGS AND INTERIOR WALLS AND PARTITIONS: EMT. <br />4.CONNECTION TO VIBRATING EQUIPMENT (INCLUDING TRANSFORMERS AND <br />HYDRAULIC, PNEUMATIC, ELECTRIC SOLENOID, OR MOTOR-DRIVEN EQUIPMENT): FMC, <br />EXCEPT USE LFMC IN DAMP OR WET LOCATIONS. <br />5.DAMP OR WET LOCATIONS: GRC OR IMC. <br />6.BOXES AND ENCLOSURES: NEMA 250, TYPE 1, EXCEPT USE NEMA 250, TYPE 4 <br />STAINLESS STEEL IN KITCHENS AND DAMP OR WET LOCATIONS. <br />B.MINIMUM RACEWAY SIZE: ¾-INCH TRADE SIZE <br />C.RACEWAY FITTINGS: COMPATIBLE WITH RACEWAYS AND SUITABLE FOR USE AND <br />LOCATION. <br />1.RIGID AND INTERMEDIATE STEEL CONDUIT: USE THREADED RIGID STEEL CONDUIT <br />FITTINGS. COMPLY WITH NEMA FB 2.10. <br />2.PVC EXTERNALLY COATED, RIGID STEEL CONDUITS: USE ONLY FITTINGS LISTED FOR <br />USE WITH THIS TYPE OF CONDUIT. PATCH AND SEAL JOINTS, NICKS, AND SCRAPES IN <br />PVC COATING AFTER INSTALLING CONDUITS AND FITTINGS. USE SEALANT <br />RECOMMENDED BY FITTING MANUFACTURER AND APPLY IN THICKNESS AND NUMBER <br />OF COATS RECOMMENDED BY MANUFACTURER. <br />3.EMT: USE SETSCREW, STEEL OR CAST-METAL FITTINGS. COMPLY WITH NEMA FB 2.10. <br />4.FLEXIBLE CONDUIT: USE ONLY FITTINGS LISTED FOR USE WITH FLEXIBLE CONDUIT. <br />COMPLY WITH NEMA FB 2.20. <br />D.INSTALL NONFERROUS CONDUIT OR TUBING FOR CIRCUITS OPERATING ABOVE 60 HZ. <br />WHERE ALUMINUM RACEWAYS ARE INSTALLED FOR SUCH CIRCUITS AND PASS THROUGH <br />CONCRETE, INSTALL IN NONMETALLIC SLEEVE. <br />E.DO NOT INSTALL ALUMINUM CONDUITS EMBEDDED IN OR IN CONTACT WITH CONCRETE <br />OR EARTH. <br />3.02 INSTALLATION <br />A.COMPLY WITH REQUIREMENTS IN SECTION 26 0529 "HANGERS AND SUPPORTS FOR <br />ELECTRICAL SYSTEMS" FOR HANGERS AND SUPPORTS. <br />B.COMPLY WITH NECA 1 AND NECA 101 FOR INSTALLATION REQUIREMENTS EXCEPT <br />WHERE REQUIREMENTS ON DRAWINGS OR IN THIS ARTICLE ARE STRICTER. COMPLY <br />WITH NECA 102 FOR ALUMINUM CONDUITS. COMPLY WITH CEC LIMITATIONS FOR TYPES <br />OF RACEWAYS ALLOWED IN SPECIFIC OCCUPANCIES AND NUMBER OF FLOORS. <br />C.DO NOT FASTEN CONDUITS ONTO THE BOTTOM SIDE OF A METAL DECK ROOF. <br />D.KEEP RACEWAYS AT LEAST 6 INCHES AWAY FROM PARALLEL RUNS OF FLUES AND <br />STEAM OR HOT-WATER PIPES. INSTALL HORIZONTAL RACEWAY RUNS ABOVE WATER AND <br />STEAM PIPING. <br />E.COMPLETE RACEWAY INSTALLATION BEFORE STARTING CONDUCTOR INSTALLATION. <br />F.ARRANGE STUB-UPS SO CURVED PORTIONS OF BENDS ARE NOT VISIBLE ABOVE <br />FINISHED SLAB. <br />G.INSTALL NO MORE THAN THE EQUIVALENT OF THREE 90-DEGREE BENDS IN ANY CONDUIT <br />RUN EXCEPT FOR CONTROL WIRING CONDUITS, FOR WHICH FEWER BENDS ARE <br />ALLOWED. SUPPORT WITHIN 12 INCHES OF CHANGES IN DIRECTION. <br />H.MAKE BENDS IN RACEWAY USING LARGE-RADIUS PREFORMED ELLS. FIELD BENDING <br />SHALL BE IN ACCORDANCE WITH CEC MINIMUM RADII REQUIREMENTS. USE ONLY <br />EQUIPMENT SPECIFICALLY DESIGNED FOR MATERIAL AND SIZE INVOLVED. <br />I.CONCEAL CONDUIT WITHIN FINISHED WALLS, CEILINGS, AND FLOORS UNLESS <br />OTHERWISE INDICATED. INSTALL CONDUITS PARALLEL OR PERPENDICULAR TO BUILDING <br />LINES. <br />1.INSTALL CONCEALED RACEWAYS WITH A MINIMUM OF BENDS IN THE SHORTEST <br />PRACTICAL DISTANCE, CONSIDERING TYPE OF BUILDING CONSTRUCTION AND <br />OBSTRUCTIONS, UNLESS OTHERWISE INDICATED. <br />J.SUPPORT CONDUIT WITHIN 12 INCHES OF ENCLOSURES TO WHICH ATTACHED. <br />K.PROHIBITED: INSTALLATION OF RACEWAYS EMBEDDED IN CONCRETE SLABS: <br />L.STUB-UPS TO ABOVE RECESSED CEILINGS: <br />1.USE EMT, IMC, OR RMC FOR RACEWAYS. <br />2.USE A CONDUIT BUSHING OR INSULATED FITTING TO TERMINATE STUB-UPS NOT <br />TERMINATED IN HUBS OR IN AN ENCLOSURE. <br />M.THREADED CONDUIT JOINTS, EXPOSED TO WET, DAMP, CORROSIVE, OR OUTDOOR <br />CONDITIONS: APPLY LISTED COMPOUND TO THREADS OF RACEWAY AND FITTINGS <br />BEFORE MAKING UP JOINTS. FOLLOW COMPOUND MANUFACTURER'S WRITTEN <br />INSTRUCTIONS. <br />N.COAT FIELD-CUT THREADS ON PVC-COATED RACEWAY WITH A CORROSION-PREVENTING <br />CONDUCTIVE COMPOUND PRIOR TO ASSEMBLY. <br />O.TERMINATE THREADED CONDUITS INTO THREADED HUBS OR WITH LOCKNUTS ON INSIDE <br />AND OUTSIDE OF BOXES OR CABINETS. INSTALL BUSHINGS ON CONDUITS UP TO 1¼-INCH <br />TRADE SIZE AND INSULATED THROAT METAL BUSHINGS ON 1½-INCH TRADE SIZE AND <br />LARGER CONDUITS TERMINATED WITH LOCKNUTS. INSTALL INSULATED THROAT METAL <br />GROUNDING BUSHINGS ON SERVICE CONDUITS. <br />P.INSTALL RACEWAYS SQUARE TO THE ENCLOSURE AND TERMINATE AT ENCLOSURES <br />WITH LOCKNUTS. INSTALL LOCKNUTS HAND TIGHT PLUS ¼ TURN MORE. <br />Q.DO NOT RELY ON LOCKNUTS TO PENETRATE NONCONDUCTIVE COATINGS ON <br />ENCLOSURES. REMOVE COATINGS IN THE LOCKNUT AREA PRIOR TO ASSEMBLING <br />CONDUIT TO ENCLOSURE TO ASSURE A CONTINUOUS GROUND PATH. <br />R.CUT CONDUIT PERPENDICULAR TO THE LENGTH. FOR CONDUITS 2-INCH TRADE SIZE AND <br />LARGER, USE ROLL CUTTER OR A GUIDE TO MAKE CUT STRAIGHT AND PERPENDICULAR <br />TO THE LENGTH. <br />S.INSTALL PULL WIRES IN EMPTY RACEWAYS. USE BRAIDED POLYPROPYLENE LINE WITH <br />NOT LESS THAN 200-LBF TENSILE STRENGTH. LEAVE AT LEAST 12 INCHES OF SLACK AT <br />EACH END OF PULL WIRE. CAP UNDERGROUND RACEWAYS DESIGNATED AS SPARE <br />ABOVE GRADE ALONGSIDE RACEWAYS IN USE. <br />Sheet No. <br />Project <br />Agency Plan Check / Permit No. <br />Petersen Design Project No. <br />Consultant <br />5082.1 <br />652 East Dyer Drive <br />Santa Ana, CA 92705 <br />DYER WAREHOUSE <br />Staging & Set-Up Space <br />Tenant Improvements <br />Sheet Title <br />Revision / Submittal History <br />Scale <br />Status <br />. <br />architecture + planning <br />Agency Approval <br />Petersen Design Architects, Inc. <br />17582 Fiesta Way, Tustin, CA 92780 <br />M: 714.904.6720 E: mike@mpdarch.com <br />www.mpdarch.com <br />Architect's Stamp <br />. <br />255 E. Rincon St., Suite 301 <br />Corona, CA 92879 <br />P 951.340.1977 | F 951.340.1090 <br />www.gossengineering.com <br />CALOFI <br />GI <br />RE <br />NG <br />A <br />E <br />S <br />No. E17083 <br />T <br />E <br />ET <br />SAT L CE A <br />F <br />RICL <br />ORNI <br />EPR <br />RAET <br />RED D.D <br />OF ONABR <br />L <br />SSI <br />NE <br />RE <br />IWD <br />UT <br />HCE <br />Project Number: 125-09-07 <br />Date Signed 01-09-2026 <br />1 01/09/2026 PLAN CHECK RESUBMITTAL <br />ELECTRICAL <br />SPECIFICATIONS <br />E7.1