P.SURFACE RACEWAYS: <br />1.INSTALL SURFACE RACEWAY WITH A MINIMUM 2-INCH RADIUS CONTROL AT BEND <br />POINTS. <br />2.SECURE SURFACE RACEWAY WITH SCREWS OR OTHER ANCHOR-TYPE DEVICES AT <br />INTERVALS NOT EXCEEDING 48 INCHES AND WITH NO LESS THAN TWO SUPPORTS <br />PER STRAIGHT RACEWAY SECTION. SUPPORT SURFACE RACEWAY IN ACCORDANCE <br />WITH MANUFACTURER'S WRITTEN INSTRUCTIONS. TAPE AND GLUE ARE NOT <br />ACCEPTABLE SUPPORT METHODS. <br />3.INSTALL A SEPARATE, GREEN, GROUND CONDUCTOR IN RACEWAYS FROM JUNCTION <br />BOX SUPPLYING RACEWAYS TO RECEPTACLE OR FIXTURE GROUND TERMINALS. <br />U.INSTALL RACEWAY SEALING FITTINGS AT ACCESSIBLE LOCATIONS IN ACCORDANCE WITH <br />CEC AND FILL THEM WITH LISTED SEALING COMPOUND. FOR CONCEALED RACEWAYS, <br />INSTALL EACH FITTING IN A FLUSH STEEL BOX WITH A BLANK COVER PLATE HAVING A <br />FINISH SIMILAR TO THAT OF ADJACENT PLATES OR SURFACES. INSTALL RACEWAY <br />SEALING FITTINGS IN ACCORDANCE WITH CEC. <br />V.INSTALL DEVICES TO SEAL RACEWAY INTERIORS AT ACCESSIBLE LOCATIONS. LOCATE <br />SEALS SO NO FITTINGS OR BOXES ARE BETWEEN THE SEAL AND THE FOLLOWING <br />CHANGES OF ENVIRONMENTS. SEAL THE INTERIOR OF ALL RACEWAYS AT THE <br />FOLLOWING POINTS: <br />1.WHERE CONDUITS PASS FROM WARM TO COLD LOCATIONS, SUCH AS BOUNDARIES <br />OF REFRIGERATED SPACES AND CONDITIONED VERSUS UNCONDITIONED INTERIOR <br />SPACES. <br />2.WHERE AN UNDERGROUND SERVICE RACEWAY ENTERS A BUILDING OR STRUCTURE. <br />3.CONDUIT EXTENDING FROM INTERIOR TO EXTERIOR OF BUILDING. <br />4.CONDUIT EXTENDING INTO PRESSURIZED DUCT AND EQUIPMENT. <br />5.CONDUIT EXTENDING INTO PRESSURIZED ZONES THAT ARE AUTOMATICALLY <br />CONTROLLED TO MAINTAIN DIFFERENT PRESSURE SET POINTS. <br />6.WHERE OTHERWISE REQUIRED BY CEC. <br />W.COMPLY WITH MANUFACTURER'S WRITTEN INSTRUCTIONS FOR SOLVENT WELDING RNC <br />AND FITTINGS. <br />X.EXPANSION-JOINT FITTINGS: <br />1.INSTALL IN EACH RUN OF ABOVEGROUND RNC THAT IS LOCATED WHERE <br />ENVIRONMENTAL TEMPERATURE CHANGE MAY EXCEED 30°F AND THAT HAS <br />STRAIGHT-RUN LENGTH THAT EXCEEDS 25 FEET. INSTALL IN EACH RUN OF <br />ABOVEGROUND RMC AND EMT CONDUIT THAT IS LOCATED WHERE ENVIRONMENTAL <br />TEMPERATURE CHANGE MAY EXCEED 100°F AND THAT HAS STRAIGHT-RUN LENGTH <br />THAT EXCEEDS 100 FEET. <br />2.INSTALL FITTING(S) THAT PROVIDE EXPANSION AND CONTRACTION FOR AT LEAST <br />0.00041 IN/FT-°F OF TEMPERATURE CHANGE FOR PVC CONDUITS. INSTALL FITTING(S) <br />THAT PROVIDE EXPANSION AND CONTRACTION FOR AT LEAST 0.000078 IN/FT-°F OF <br />TEMPERATURE CHANGE FOR METAL CONDUITS. <br />3.INSTALL EXPANSION FITTINGS AT ALL LOCATIONS WHERE CONDUITS CROSS <br />BUILDING OR STRUCTURE EXPANSION OR SEISMIC JOINTS. <br />4.INSTALL EACH EXPANSION-JOINT FITTING WITH POSITION, MOUNTING, AND PISTON <br />SETTING SELECTED IN ACCORDANCE WITH MANUFACTURER'S WRITTEN <br />INSTRUCTIONS FOR CONDITIONS AT SPECIFIC LOCATION AT TIME OF INSTALLATION. <br />INSTALL CONDUIT SUPPORTS TO ALLOW FOR EXPANSION MOVEMENT. <br />Y.FLEXIBLE CONDUIT CONNECTIONS: COMPLY WITH NEMA RV 3. USE A MINIMUM OF 36 <br />INCHES AND MAXIMUM OF 72 INCHES OF FLEXIBLE CONDUIT FOR RECESSED AND <br />SEMI-RECESSED LUMINAIRES, EQUIPMENT SUBJECT TO VIBRATION, NOISE <br />TRANSMISSION, OR MOVEMENT; AND FOR TRANSFORMERS AND MOTORS. <br />1.USE LFMC IN DAMP OR WET LOCATIONS, MECHANICAL ROOMS, AND ELECTRIC <br />ROOMS. INSTALL SEPARATE GROUND CONDUCTOR ACROSS FLEXIBLE <br />CONNECTIONS. <br />Z.MOUNT BOXES AT HEIGHTS INDICATED ON DRAWINGS. IF MOUNTING HEIGHTS OF BOXES <br />ARE NOT INDIVIDUALLY INDICATED, GIVE PRIORITY TO ADA REQUIREMENTS. INSTALL <br />BOXES WITH HEIGHT MEASURED TO CENTER OF BOX UNLESS OTHERWISE INDICATED. <br />AA.HORIZONTALLY SEPARATE BOXES MOUNTED ON OPPOSITE SIDES OF WALLS SO THEY <br />ARE NOT IN THE SAME VERTICAL CHANNEL. <br />BB.LOCATE BOXES SO THAT COVER OR PLATE WILL NOT SPAN DIFFERENT BUILDING <br />FINISHES. <br />CC.SUPPORT BOXES OF THREE GANGS OR MORE FROM MORE THAN ONE SIDE BY SPANNING <br />TWO FRAMING MEMBERS OR MOUNTING ON BRACKETS SPECIFICALLY DESIGNED FOR <br />THE PURPOSE. <br />DD.FASTEN JUNCTION AND PULL BOXES TO OR SUPPORT FROM BUILDING STRUCTURE. DO <br />NOT SUPPORT BOXES BY CONDUITS. <br />EE.INSTALL TEMPORARY CLOSURES TO PREVENT FOREIGN MATTER FROM ENTERING <br />RACEWAYS. <br />FF.PROTECT STUB-UPS FROM DAMAGE WHERE CONDUITS RISE THROUGH FLOOR SLABS. <br />GG.TIGHTEN SET SCREWS OF THREAD LESS FITTINGS WITH SUITABLE TOOLS. <br />HH.TERMINATIONS: <br />1.WHERE RACEWAYS ARE TERMINATED WITH THREADED HUBS, SCREW RACEWAYS OR <br />FITTINGS TIGHTLY INTO HUB SO END BEARS AGAINST WIRE PROTECTION SHOULDER. <br />WHERE CHASE NIPPLES ARE USED, ALIGN RACEWAYS SO COUPLING IS SQUARE TO <br />BOX; TIGHTEN CHASE NIPPLE SO NO THREADS ARE EXPOSED. <br />II.TELEPHONE AND SIGNAL SYSTEM RACEWAYS, 2-INCH TRADE SIZE AND SMALLER: IN <br />ADDITION TO ABOVE REQUIREMENTS, INSTALL RACEWAYS IN MAXIMUM LENGTHS OF 150 <br />FEET AND WITH A MAXIMUM OF TWO 90-DEGREE BENDS OR EQUIVALENT. SEPARATE <br />LENGTHS WITH PULL OR JUNCTION BOXES WHERE NECESSARY TO COMPLY WITH THESE <br />REQUIREMENTS. <br />JJ.STUB-UP CONNECTIONS: EXTEND CONDUITS THROUGH CONCRETE FLOOR FOR <br />CONNECTION TO FREESTANDING EQUIPMENT. INSTALL WITH AN ADJUSTABLE TOP OR <br />COUPLING THREADED INSIDE FOR PLUGS SET FLUSH WITH FINISHED FLOOR. <br />KK.INSTALL HINGED-COVER ENCLOSURES AND CABINETS PLUMB. SUPPORT AT EACH <br />CORNER. <br />3.03 FIRESTOPPING <br />A.INSTALL FIRESTOPPING AT PENETRATIONS OF FIRE-RATED FLOOR AND WALL <br />ASSEMBLIES. COMPLY WITH REQUIREMENTS IN SECTION 07 8413 "PENETRATION <br />FIRESTOPPING." <br />3.04 PROTECTION <br />A.PROVIDE FINAL PROTECTION AND MAINTAIN CONDITIONS THAT ENSURE COATINGS, <br />FINISHES, AND CABINETS ARE WITHOUT DAMAGE OR DETERIORATION AT TIME OF <br />SUBSTANTIAL COMPLETION. <br />1.REPAIR DAMAGE TO GALVANIZED FINISHES WITH ZINC-RICH PAINT RECOMMENDED <br />BY MANUFACTURER. <br />2.REPAIR DAMAGE TO PVC OR PAINT FINISHES WITH MATCHING TOUCHUP COATING <br />RECOMMENDED BY MANUFACTURER. <br />3.05 CLEANING <br />A.AFTER COMPLETING INSTALLATION OF EXPOSED, FACTORY-FINISHED RACEWAYS AND <br />BOXES, INSPECT EXPOSED FINISHES AND REPAIR DAMAGED FINISHES. <br />SECTION 26 0553 <br />IDENTIFICATION FOR ELECTRICAL SYSTEMS <br />PART 1 - GENERAL <br />1.01 SUMMARY <br />A.SECTION INCLUDES: <br />1.IDENTIFICATION FOR RACEWAYS. <br />2.IDENTIFICATION OF POWER AND CONTROL CABLES. <br />3.IDENTIFICATION FOR CONDUCTORS. <br />4.EQUIPMENT IDENTIFICATION LABELS. <br />5.MISCELLANEOUS IDENTIFICATION PRODUCTS. <br />1.02 SUBMITTALS <br />A.PRODUCT DATA: NONE. <br />1.03 QUALITY ASSURANCE <br />A.COMPLY WITH ANSI A13.1 AND IEEE C2. <br />B.COMPLY WITH CEC. <br />C.COMPLY WITH 29 CFR 1910.144 AND 29 CFR 1910.145. <br />D.ADHESIVE-ATTACHED LABELING MATERIALS, INCLUDING LABEL STOCKS, LAMINATING <br />ADHESIVES, AND INKS USED BY LABEL PRINTERS, SHALL COMPLY WITH UL 969. <br />1.04 COORDINATION <br />A.COORDINATE IDENTIFICATION NAMES, ABBREVIATIONS, COLORS, AND OTHER FEATURES <br />WITH REQUIREMENTS IN OTHER SECTIONS REQUIRING IDENTIFICATION APPLICATIONS, <br />DRAWINGS, SHOP DRAWINGS, MANUFACTURER'S WIRING DIAGRAMS, AND THE <br />OPERATION AND MAINTENANCE MANUAL; AND WITH THOSE REQUIRED BY CODES, <br />STANDARDS, AND 29 CFR 1910.145. USE CONSISTENT DESIGNATIONS THROUGHOUT <br />PROJECT. <br />B.COORDINATE INSTALLATION OF IDENTIFYING DEVICES WITH COMPLETION OF COVERING <br />AND PAINTING OF SURFACES WHERE DEVICES ARE TO BE APPLIED. <br />C.COORDINATE INSTALLATION OF IDENTIFYING DEVICES WITH LOCATION OF ACCESS <br />PANELS AND DOORS. <br />D.INSTALL IDENTIFYING DEVICES BEFORE INSTALLING ACOUSTICAL CEILINGS AND SIMILAR <br />CONCEALMENT. <br />PART 2 - PRODUCTS <br />2.01 MATERIALS <br />A.FOR FIXTURE DESCRIPTIONS IN OTHER PART 2 ARTICLES WHERE THE SUBPARAGRAPH <br />TITLES "PRODUCTS," AND "MANUFACTURERS" INTRODUCE A LIST OF MANUFACTURERS <br />AND THEIR PRODUCTS OR MANUFACTURERS ONLY, THE FOLLOWING REQUIREMENTS <br />APPLY FOR PRODUCT SELECTION: <br />1.PRODUCTS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE ONE OF THE <br />PRODUCTS SPECIFIED IN OTHER PART 2 ARTICLES. <br />2.MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE <br />PRODUCTS BY THE MANUFACTURERS SPECIFIED IN OTHER PART 2 ARTICLES. <br />3.OR EQUAL: WHERE PRODUCTS ARE SPECIFIED BY MANUFACTURERS NAME AND <br />ACCOMPANIED BY THE TERM "OR EQUAL", COMPLY WITH PROVISIONS IN DIVISION 01. <br />SPECIFIC PROCEDURES MUST BE FOLLOWED BEFORE USE OF AN UNNAMED <br />PRODUCT OR MANUFACTURER. <br />2.02 POWER RACEWAY IDENTIFICATION MATERIALS <br />A.COLORS FOR RACEWAYS CARRYING CIRCUITS AT 600 V OR LESS: <br />1.BLACK LETTERS ON AN ORANGE FIELD <br />2.LEGEND: INDICATE VOLTAGE AND SYSTEM OR SERVICE TYPE. <br />B.WRITE-ON TAGS: POLYESTER TAG, 0.015 INCH THICK, WITH CORROSION-RESISTANT <br />GROMMET AND CABLE TIE FOR ATTACHMENT TO CONDUCTOR OR CABLE. <br />1.MARKER FOR TAGS: PERMANENT, WATERPROOF, BLACK INK MARKER <br />RECOMMENDED BY TAG MANUFACTURER. <br />2.03 ARMORED AND METAL-CLAD CABLE IDENTIFICATION MATERIALS <br />A.COMPLY WITH ANSI A13.1 FOR MINIMUM SIZE OF LETTERS FOR LEGEND AND FOR <br />MINIMUM LENGTH OF COLOR FIELD FOR EACH RACEWAY AND CABLE SIZE. <br />B.COLORS FOR RACEWAYS CARRYING CIRCUITS AT 600 V AND LESS: <br />1.BLACK LETTERS ON AN ORANGE FIELD <br />2.LEGEND: INDICATE VOLTAGE AND SYSTEM OR SERVICE TYPE. <br />C.SELF-ADHESIVE VINYL TAPE: COLORED, HEAVY DUTY, WATERPROOF, FADE RESISTANT; 2 <br />INCHES WIDE; COMPOUNDED FOR OUTDOOR USE. <br />2.04 POWER AND CONTROL CABLE IDENTIFICATION MATERIALS <br />A.COMPLY WITH ANSI A13.1 FOR MINIMUM SIZE OF LETTERS FOR LEGEND AND FOR <br />MINIMUM LENGTH OF COLOR FIELD FOR EACH RACEWAY AND CABLE SIZE. <br />B.SELF-ADHESIVE VINYL LABELS: PREPRINTED, FLEXIBLE LABEL LAMINATED WITH A CLEAR, <br />WEATHER- AND CHEMICAL-RESISTANT COATING AND MATCHING WRAPAROUND <br />ADHESIVE TAPE FOR SECURING ENDS OF LEGEND LABEL. <br />C.WRITE-ON TAGS: POLYESTER TAG, 0.015 INCH THICK, WITH CORROSION-RESISTANT <br />GROMMET AND CABLE TIE FOR ATTACHMENT TO CONDUCTOR OR CABLE. <br />1.MARKER FOR TAGS: MACHINE-PRINTED, PERMANENT, WATERPROOF, BLACK INK <br />MARKER RECOMMENDED BY PRINTER MANUFACTURER. <br />D.SNAP-AROUND LABELS: SLIT, PRETENSIONED, FLEXIBLE, PREPRINTED, COLOR-CODED <br />ACRYLIC SLEEVE, WITH DIAMETER SIZED TO SUIT DIAMETER OF RACEWAY OR CABLE IT <br />IDENTIFIES AND TO STAY IN PLACE BY GRIPPING ACTION. <br />2.05 CONDUCTOR IDENTIFICATION MATERIALS <br />A.COLOR-CODING CONDUCTOR TAPE: COLORED, SELF-ADHESIVE VINYL TAPE NOT LESS <br />THAN 3 MILS THICK BY 1 TO 2 INCHES WIDE. <br />B.SNAP-AROUND LABELS: SLIT, PRETENSIONED, FLEXIBLE, PREPRINTED, COLOR-CODED <br />ACRYLIC SLEEVE, WITH DIAMETER SIZED TO SUIT DIAMETER OF RACEWAY OR CABLE IT <br />IDENTIFIES AND TO STAY IN PLACE BY GRIPPING ACTION. <br />C.SNAP-AROUND, COLOR-CODING BANDS: SLIT, PRETENSIONED, FLEXIBLE, <br />SOLID-COLORED ACRYLIC SLEEVE, 2 INCHES LONG, WITH DIAMETER SIZED TO SUIT <br />DIAMETER OF RACEWAY OR CABLE IT IDENTIFIES AND TO STAY IN PLACE BY GRIPPING <br />ACTION. <br />D.WRITE-ON TAGS: POLYESTER TAG, 0.015 INCH THICK, WITH CORROSION-RESISTANT <br />GROMMET AND CABLE TIE FOR ATTACHMENT TO CONDUCTOR OR CABLE. <br />2.06 EQUIPMENT IDENTIFICATION LABELS <br />A.ADHESIVE FILM LABEL WITH CLEAR PROTECTIVE OVERLAY: MACHINE PRINTED, IN BLACK, <br />BY THERMAL TRANSFER OR EQUIVALENT PROCESS. MINIMUM LETTER HEIGHT SHALL BE <br />⅜ INCH. CLEAR PROTECTIVE OVERLAY SHALL PROVIDE A WEATHERPROOF AND <br />UV-RESISTANT SEAL FOR LABEL. <br />B.ENGRAVED, LAMINATED ACRYLIC OR MELAMINE LABEL: PUNCHED OR DRILLED FOR <br />SCREW MOUNTING. BLACK LETTERS ON A LIGHT-GRAY BACKGROUND. MINIMUM LETTER <br />HEIGHT SHALL BE ⅜ INCH. <br />2.07 CABLE TIES <br />A.GENERAL-PURPOSE CABLE TIES: FUNGUS INERT, SELF-EXTINGUISHING, ONE PIECE, <br />SELF-LOCKING, TYPE 6/6 NYLON. <br />1.MINIMUM WIDTH: 3/16 INCH. <br />2.TENSILE STRENGTH AT 73°F, IN ACCORDANCE WITH ASTM D638: 12,000 PSI. <br />3.TEMPERATURE RANGE: MINUS 40 TO PLUS 185°F. <br />4.COLOR: BLACK EXCEPT WHERE USED FOR COLOR-CODING. <br />B.PLENUM-RATED CABLE TIES: SELF-EXTINGUISHING, UV STABILIZED, ONE PIECE, <br />SELF-LOCKING. <br />1.MINIMUM WIDTH: 3/16 INCH. <br />2.TENSILE STRENGTH AT 73°F IN ACCORDANCE WITH ASTM D638: 7000 PSI. <br />3.UL 94 FLAME RATING: 94V-0. <br />4.TEMPERATURE RANGE: MINUS 50 TO PLUS 284°F. <br />5.COLOR: BLACK. <br />PART 3 - EXECUTION <br />3.01 INSTALLATION <br />A.VERIFY IDENTITY OF EACH ITEM BEFORE INSTALLING IDENTIFICATION PRODUCTS. <br />B.LOCATION: INSTALL IDENTIFICATION MATERIALS AND DEVICES AT LOCATIONS FOR MOST <br />CONVENIENT VIEWING WITHOUT INTERFERENCE WITH OPERATION AND MAINTENANCE <br />OF EQUIPMENT. <br />C.APPLY IDENTIFICATION DEVICES TO SURFACES THAT REQUIRE FINISH AFTER <br />COMPLETING FINISH WORK. <br />D.SECURE NAMEPLATES TO EQUIPMENT FRONTS USING SCREWS, RIVETS OR ADHESIVE. <br />SECURE NAMEPLATE TO INSIDE FACE OF RECESSED PANEL BOARD DOORS IN FINISHED <br />LOCATIONS. USE WEATHERPROOF ADHESIVE FOR OUTDOOR INSTALLATION. DO NOT USE <br />TAPE FOR NAMEPLATES OR LEGEND PLATES. <br />E.LETTERING, COLORS, AND GRAPHICS: COORDINATE NAMES, ABBREVIATIONS, COLORS, <br />AND OTHER DESIGNATIONS WITH CORRESPONDING DESIGNATIONS. USE CONSISTENT <br />DESIGNATIONS THROUGHOUT PROJECT. <br />F.SELF-ADHESIVE IDENTIFICATION PRODUCTS: CLEAN SURFACES BEFORE APPLYING. <br />G.INSTALL NAMEPLATES AND LABELS PARALLEL TO EQUIPMENT LINES. <br />H.JUNCTION BOXES FOR FIRE ALARM SYSTEM SHALL BE RED. <br />I.CAUTION LABELS FOR INDOOR BOXES AND ENCLOSURES FOR POWER AND LIGHTING: <br />INSTALL LABELS IDENTIFYING SYSTEM VOLTAGE WITH BLACK LETTERS ON ORANGE <br />BACKGROUND. INSTALL ON EXTERIOR OF DOOR OR COVER. <br />J.CIRCUIT IDENTIFICATION LABELS ON RECEPTACLES: <br />1.PUBLIC VIEW AREAS (LOBBIES, ATRIUM, PUBLIC CONFERENCE AND MEETING ROOMS, <br />CLASSROOMS, ETC.): PERMANENTLY ENGRAVE CIRCUIT INFORMATION ON BACK OF <br />PLATE. <br />2.OTHER AREAS: ENGRAVED CIRCUIT INFORMATION ON FRONT OF PLATE. <br />K.CONDUIT INSTALLED BELOW GRADE SHALL HAVE UNDERGROUND HAZARD TAPE <br />(NON-ADHESIVE) INSTALLED A MINIMUM OF 12 INCHES ABOVE THE CONDUIT OR TOP <br />LAYER OF CONDUITS IN A DUCT BANK. THE TAPE SHALL BE 6 INCHES WIDE AND 4 <br />MILLIMETERS THICK YELLOW POLYETHYLENE FOR LOW VOLTAGE CONDUITS AND RED <br />FOR MEDIUM VOLTAGE CONDUITS. THE TAPE SHALL BE MARKED “CAUTION BURIED <br />ELECTRIC LINE” FOR LOW VOLTAGE AND “DANGER HIGH VOLTAGE LINE” FOR MEDIUM <br />VOLTAGE. TRACER WIRE SHALL BE USED FOR PVC CONDUITS AND NON-METALLIC TAPE <br />FOR METALLIC CONDUITS. THE TAPE SHALL BE INSTALLED THE ENTIRE LENGTH OF <br />CONDUIT BELOW GRADE. <br />L.COLOR-CODING OF SECONDARY PHASE CONDUCTORS: USE THE FOLLOWING COLORS <br />FOR SERVICE FEEDER AND BRANCH-CIRCUIT PHASE CONDUCTORS. WIRING SHALL BE <br />COLOR CODED, SEE SECTION 26 0519, “LOW VOLTAGE ELECTRICAL POWER <br />CONDUCTORS AND CABLES”. LOW VOLTAGE WIRE MARKERS SHALL BE ADHERING, <br />PREPRINTED, SELF-LAMINATING VINYL WRAP-AROUND STRIPS. WIRE SHALL BE MARKED <br />WITH OPPOSITE END TERMINATION AND SHALL INCLUDE PANEL SOURCE AND CIRCUIT <br />NUMBERS. PHASING SHALL BE INDICATED BY COLORED WIRE OR TAPE. FOR OTHER <br />SYSTEM VOLTAGES CONSULT THE EEOR: <br />1.208/120-V CONDUCTORS: <br />a.PHASE A: BLACK. <br />b.PHASE B: RED. <br />c.PHASE C: BLUE. <br />d.SWITCH LEG: PINK. <br />e.SWITCH TRAVELER: SAME AS HOT LEG. <br />2.480/277-V CONDUCTORS: <br />a.PHASE A: BROWN. <br />b.PHASE B: ORANGE. <br />c.PHASE C: YELLOW. <br />d.SWITCH LEG: PURPLE <br />e.SWITCH TRAVELER: SAME AS HOT LEG. <br />3.NEUTRAL AND GROUND CONDUCTORS: <br />a.NEUTRAL: WHITE. <br />b.GROUND: GREEN. <br />4.FACTORY APPLY COLOR THE ENTIRE LENGTH OF CONDUCTORS, EXCEPT THE <br />FOLLOWING FIELD-APPLIED, COLOR-CODING METHODS MAY BE USED INSTEAD OF <br />FACTORY-CODED WIRE FOR SIZES LARGER THAN NO. 10 AWG: <br />a.COLORED, PRESSURE-SENSITIVE PLASTIC TAPE IN HALF-LAPPED TURNS FOR A <br />DISTANCE OF 6 INCHES FROM TERMINAL POINTS AND IN BOXES WHERE SPLICES <br />OR TAPS ARE MADE. APPLY LAST TWO TURNS OF TAPE WITH NO TENSION TO <br />PREVENT POSSIBLE UNWINDING. USE 1-INCH-WIDE TAPE IN COLORS SPECIFIED. <br />ADJUST TAPE BANDS TO AVOID OBSCURING CABLE IDENTIFICATION MARKINGS. <br />b.COLORED CABLE TIES APPLIED IN GROUPS OF THREE TIES OF SPECIFIED COLOR <br />TO EACH WIRE AT EACH TERMINAL OR SPLICE POINT STARTING 3 INCHES FROM <br />THE TERMINAL AND SPACED 3 INCHES APART. APPLY WITH A SPECIAL TOOL OR <br />PLIERS, TIGHTEN TO A SNUG FIT, AND CUT OFF EXCESS LENGTH. <br />M.POWER-CIRCUIT IDENTIFICATION: BRASS TAGS WITH WRAPAROUND MARKER BANDS <br />FOR CABLES, FEEDERS, AND POWER CIRCUITS IN VAULTS, PULL AND JUNCTION BOXES, <br />MANHOLES, AND SWITCHBOARD ROOMS. <br />1.LEGEND: ¼-INCH STEEL LETTER AND NUMBER STAMPING OR EMBOSSING WITH <br />LEGEND CORRESPONDING TO INDICATE CIRCUIT DESIGNATIONS. <br />2.TAG FASTENERS: NYLON CABLE TIES. <br />3.BAND FASTENERS: INTEGRAL EARS. <br />N.APPLY IDENTIFICATION TO CONDUCTORS AS FOLLOWS: <br />1.MULTIPLE POWER OR LIGHTING CIRCUITS IN THE SAME ENCLOSURE: IDENTIFY EACH <br />CONDUCTOR WITH SOURCE, VOLTAGE, CIRCUIT NUMBER, AND PHASE. USE <br />COLOR-CODING TO IDENTIFY CIRCUITS' VOLTAGE AND PHASE. <br />2.MULTIPLE CONTROL AND COMMUNICATION CIRCUITS IN THE SAME ENCLOSURE: <br />IDENTIFY EACH CONDUCTOR BY ITS SYSTEM AND CIRCUIT DESIGNATION. USE A <br />CONSISTENT SYSTEM OF TAGS, COLOR-CODING, OR CABLE MARKING TAPE. <br />O.LOW VOLTAGE IDENTIFICATION <br />1.EQUIPMENT NAMEPLATES SHALL BE ENGRAVED THREE-LAYER LAMINATED PLASTIC <br />WITH WHITE BACKGROUND AND BLACK LETTERS. LETTERS SHALL BE ¼” MINIMUM <br />SIZE. IDENTIFICATIONS SHALL MATCH PLAN DESIGNATIONS AND BASED UPON THE <br />OWNER'S NUMBERING SCHEME. <br />2.LEGEND PLATES FOR CONTROL PANELS AND INDICATORS SHALL BE PROVIDED ON <br />DISCONNECT AND SAFETY SWITCHES AND INDICATING LIGHTS. THE PLATES SHALL <br />BE DIE-STAMPED METAL WITH MOUNTING HOLE AND POSITIONING KEY. <br />3.FOR PANEL BOARD DIRECTORIES PROVIDE THE FOLLOWING: <br />a.PROVIDE TYPEWRITTEN DIRECTORIES ARRANGED IN NUMERICAL ORDER <br />SHOWING NUMBER OF ROOM IN WHICH EACH DEVICE IS LOCATED. <br />b.VERIFY ROOM NUMBERS TO BE USED WITH THE OWNER'S REPRESENTATIVE <br />PRIOR TO TYPING, SINCE ROOM NUMBERS WILL MOST LIKELY NOT BE THOSE <br />SHOWN ON THE DRAWINGS. <br />c.MOUNT DIRECTORIES UNDER A CLEAR PLASTIC COVER INSIDE EACH <br />PANELBOARD DOOR. <br />4.THE FOLLOWING LOW VOLTAGE EQUIPMENT NUMBERING SCHEME SHALL BE <br />FOLLOWED: <br />USE NUMBERING CONVENTION AS FOLLOWS: <br />a.FIRST LETTER OR NUMBER = FLOOR DESIGNATION; B = BASEMENT, 1, 2, 3, ETC. <br />(B). <br />b.SUBSEQUENT LOWER CASE LETTER = PANEL NUMBER ON EACH FLOOR; A, B, C, <br />ETC. (BA). <br />1)EXAMPLE: EMERGENCY 277/480V DISTRIBUTION PANELBOARD INSTALLED IN <br />BASEMENT IS “EHDP-B”. <br />2)EXAMPLE: SECOND 480/277VPANELBOARD INSTALLED ON THIRD FLOOR FOR <br />LIGHTING IS “HLP-3B”. <br />P.TELECOMMUNICATION, SIGNAL ALARM AND CONTROL WIRING: <br />1.CONDUCTORS TERMINATED OR SPLICED SHALL BE LABELED AT EACH END WITH <br />TAPE MARKERS. <br />SECTION 26 0943 <br />DIGITAL LIGHTING CONTROLS <br />PART 1 - GENERAL <br />1.01 SUMMARY <br />A.SECTION INCLUDES: <br />1.DIGITAL LIGHTING CONTROLS <br />2.RELAY PANELS <br />3.EMERGENCY LIGHTING CONTROL <br />B.CONTROL INTENT - CONTROL INTENT INCLUDES, BUT IS NOT LIMITED TO: <br />1.DEFAULTS AND INITIAL CALIBRATION SETTINGS FOR SUCH ITEMS AS TIME DELAY, <br />SENSITIVITY, FADE RATES, ETC. <br />2.INITIAL SENSOR AND SWITCHING ZONES <br />3.INITIAL TIME SWITCH SETTINGS <br />4.EMERGENCY LIGHTING CONTROL <br />1.02 SYSTEM DESCRIPTION & OPERATION <br />A.THE LIGHTING CONTROL AND AUTOMATION SYSTEM AS DEFINED UNDER THIS SECTION <br />COVERS THE FOLLOWING EQUIPMENT: <br />1.DIGITAL OCCUPANCY SENSORS - SELF-CONFIGURING, DIGITALLY ADDRESSABLE, AND <br />CALIBRATED OCCUPANCY SENSORS WITH LCD DISPLAY AND TWO-WAY ACTIVE <br />INFRARED (IR) COMMUNICATIONS. <br />2.DIGITAL SWITCHES - SELF-CONFIGURING, DIGITALLY ADDRESSABLE PUSHBUTTON <br />ON/OFF, DIMMING, AND SCENE SWITCHES WITH TWO-WAY ACTIVE INFRARED (IR) <br />COMMUNICATIONS. <br />3.DIGITAL DAYLIGHTING SENSORS - SINGLE-ZONE CLOSED LOOP, MULTI-ZONE OPEN <br />LOOP AND SINGLE-ZONE DUAL-LOOP DAYLIGHTING SENSORS WITH TWO-WAY ACTIVE <br />INFRARED (IR) COMMUNICATIONS CAN PROVIDE SWITCHING, BI-LEVEL, TRI-LEVEL, OR <br />DIMMING CONTROL FOR DAYLIGHT HARVESTING. <br />4.DIGITAL ROOM CONTROLLERS - SELF-CONFIGURING, DIGITALLY ADDRESSABLE ONE, <br />TWO, OR THREE RELAY PLENUM-RATED CONTROLLERS FOR ON/OFF CONTROL. <br />SELECTED MODELS INCLUDE 0-10 VOLT OR LINE VOLTAGE FORWARD PHASE <br />CONTROL DIMMING OUTPUTS AND INTEGRAL CURRENT MONITORING CAPABILITIES. <br />5.CONFIGURATION TOOLS - HANDHELD REMOTE FOR ROOM CONFIGURATION AND <br />RELAY PANEL PROGRAMMING PROVIDES TWO WAY INFRARED (IR) COMMUNICATIONS <br />TO DIGITAL DEVICES AND ALLOWS COMPLETE CONFIGURATION AND <br />RECONFIGURATION OF THE DEVICE / ROOM FROM UP TO 30 FEET AWAY. UNIT TO <br />HAVE ORGANIC LED DISPLAY, SIMPLE PUSHBUTTON INTERFACE, AND ALLOW <br />BI-DIRECTIONAL COMMUNICATION OF ROOM VARIABLES AND OCCUPANCY SENSOR <br />SETTINGS. COMPUTER SOFTWARE ALSO CUSTOMIZES ROOM SETTINGS. <br />6.EMERGENCY LIGHTING CONTROL UNIT (ELCU) - ALLOWS A STANDARD LIGHTING <br />CONTROL DEVICE TO CONTROL EMERGENCY LIGHTING IN CONJUNCTION WITH <br />NORMAL LIGHTING IN ANY AREA WITHIN A BUILDING. <br />1.03 LIGHTING CONTROL APPLICATIONS <br />A.UNLESS RELEVANT PROVISIONS OF THE APPLICABLE LOCAL ENERGY CODES ARE MORE <br />STRINGENT, PROVIDE A MINIMUM APPLICATION OF LIGHTING CONTROLS AS FOLLOWS: <br />1.SPACE CONTROL REQUIREMENTS - PROVIDE OCCUPANCY (VACANCY) SENSORS WITH <br />MANUAL- OR PARTIAL-ON FUNCTIONALITY IN SPACES EXCEPT TOILET ROOMS, <br />STOREROOMS OR OTHER APPLICATIONS WHERE HANDS-FREE OPERATION IS <br />DESIRABLE AND AUTOMATIC-ON OCCUPANCY SENSORS ARE MORE APPROPRIATE. <br />PROVIDE MANUAL-ON OCCUPANCY (VACANCY) SENSORS FOR ANY ENCLOSED <br />OFFICE, CONFERENCE ROOM, MEETING ROOM, OPEN PLAN SYSTEM, AND TRAINING <br />ROOM. FOR SPACES WITH MULTIPLE OCCUPANTS, OR WHERE LINE-OF-SIGHT MAY BE <br />OBSCURED, PROVIDE CEILING- OR CORNER-MOUNTED SENSORS AND MANUAL-ON <br />SWITCHES. <br />2.BI-LEVEL LIGHTING - PROVIDE MULTI-LEVEL CONTROLS IN SPACES EXCEPT TOILET <br />ROOMS, STOREROOMS, LIBRARY STACKS, OR APPLICATIONS WHERE VARIABLE <br />DIMMING IS USED. <br />3.DAY-LIGHTED AREAS - PROVIDE DAYLIGHT-RESPONSIVE AUTOMATIC CONTROL IN <br />SPACES CONDITIONED OR UNCONDITIONED WHERE DAYLIGHT CONTRIBUTION IS <br />AVAILABLE AS DEFINED BY RELEVANT LOCAL BUILDING ENERGY CODE: <br />a.LUMINAIRES WITHIN CODE-DEFINED DAYLIGHT ZONES SHALL BE CONTROLLED <br />SEPARATELY FROM LUMINAIRES OUTSIDE OF DAYLIGHT ZONES. <br />b.DAYTIME SETPOINTS FOR TOTAL AMBIENT ILLUMINATION (COMBINED DAYLIGHT <br />AND ELECTRIC LIGHT) LEVELS THAT INITIATE DIMMING SHALL BE PROGRAMMED IN <br />COMPLIANCE WITH RELEVANT LOCAL BUILDING ENERGY CODES. <br />c.MULTIPLE-LEVELED SWITCHED DAYLIGHT HARVESTING CONTROLS MAY BE USED <br />FOR AREAS MARKED ON DRAWINGS. <br />d.PROVIDE SMOOTH AND CONTINUOUS DAYLIGHT DIMMING FOR AREAS MARKED ON <br />DRAWINGS. DAYLIGHTING CONTROL SYSTEM MAY BE DESIGNED TO TURN OFF <br />ELECTRIC LIGHTING WHEN DAYLIGHT IS AT OR ABOVE REQUIRED LIGHTING <br />LEVELS, ONLY IF SYSTEM FUNCTIONS TO TURN LAMPS BACK ON AT DIMMED <br />LEVEL, INSTEAD OF TURNING FULL-ON PRIOR TO DIMMING. <br />1.04 SUBMITTALS <br />A.SUBMITTALS PACKAGE: SUBMIT THE SHOP DRAWINGS, AND THE PRODUCT DATA <br />SPECIFIED BELOW AT THE SAME TIME AS A PACKAGE. <br />B.SHOP DRAWINGS: SHOW INSTALLATION DETAILS FOR OCCUPANCY AND LIGHT-LEVEL <br />SENSORS. <br />4.LIGHTING PLAN SHOWING LOCATION, ORIENTATION, AND COVERAGE AREA OF EACH <br />SENSOR. <br />5.INTERCONNECTION DIAGRAMS SHOWING FIELD-INSTALLED WIRING. <br />1.05 QUALITY ASSURANCE <br />A.MANUFACTURER: MINIMUM 10 YEARS' EXPERIENCE IN MANUFACTURE OF LIGHTING <br />CONTROLS. <br />1.06 WARRANTY <br />A.PROVIDE A FIVE YEAR LIMITED MANUFACTURER'S WARRANTY ON ROOM CONTROL <br />DEVICES AND PANELS. <br />PART 2 - PRODUCTS <br />2.01 MANUFACTURERS <br />A.IN OTHER PART 2 ARTICLES THE FOLLOWING REQUIREMENTS APPLY TO PRODUCT <br />SELECTION: <br />1.BASIS OF DESIGN PRODUCT: ACUITY N-LIGHT DIGITAL LIGHTING MANAGEMENT (DLM). <br />SUBJECT TO COMPLIANCE WITH SPECIFIED REQUIREMENTS OF THIS SECTION, OR <br />EQUAL, PRIOR OWNER'S APPROVAL IS RECOMMENDED. <br />2.OR EQUAL: WHERE PRODUCTS ARE SPECIFIED BY MANUFACTURERS NAME AND <br />ACCOMPANIED BY THE TERM "OR EQUAL", COMPLY WITH PROVISIONS IN DIVISION 01 <br />SECTION “PRODUCT OPTIONS AND SUBSTITUTIONS”. SPECIFIC PROCEDURES MUST <br />BE FOLLOWED BEFORE USE OF AN UNNAMED PRODUCT OR MANUFACTURER. <br />2.02 DIGITAL LIGHTING CONTROLS <br />A.FURNISH THE COMPANY'S SYSTEM WHICH ACCOMMODATES THE SQUARE-FOOTAGE <br />COVERAGE REQUIREMENTS FOR EACH AREA CONTROLLED, UTILIZING ROOM <br />CONTROLLERS, DIGITAL OCCUPANCY SENSORS, SWITCHES, DAYLIGHTING SENSORS AND <br />ACCESSORIES WHICH SUIT THE LIGHTING AND ELECTRICAL SYSTEM PARAMETERS. <br />2.03 DIGITAL WALL SWITCH OCCUPANCY SENSORS <br />A.WALL BOX MOUNTED PASSIVE INFRARED PIR OR DUAL TECHNOLOGY (PASSIVE INFRARED <br />AND ULTRASONIC) DIGITAL OCCUPANCY SENSOR WITH 1 OR 2 SWITCH BUTTONS. <br />B.DIGITAL OCCUPANCY SENSORS SHALL PROVIDE SCROLLING LCD DISPLAY FOR DIGITAL <br />CALIBRATION AND ELECTRONIC DOCUMENTATION. FEATURES INCLUDE THE FOLLOWING: <br />1.DIGITAL CALIBRATION AND PUSHBUTTON CONFIGURATION FOR THE FOLLOWING <br />VARIABLES: <br />a.SENSITIVITY - 0-100% IN 10% INCREMENTS <br />b.TIME DELAY - 1-30 MINUTES IN 1 MINUTE INCREMENTS, FOR LED LIGHT FIXTURES <br />SET FOR 2 MINUTES UNLESS OTHERWISE DIRECTED. <br />c.TEST MODE - FIVE SECOND TIME DELAY <br />d.DETECTION TECHNOLOGY - PIR, DUAL TECHNOLOGY ACTIVATION AND/OR <br />RE-ACTIVATION. <br />e.WALK-THROUGH MODE <br />f.LOAD PARAMETERS INCLUDING AUTO/MANUAL-ON, BLINK WARNING, AND <br />DAYLIGHT ENABLE/DISABLE WHEN PHOTOSENSORS ARE INCLUDED IN THE DLM <br />LOCAL NETWORK. <br />2.PROGRAMMABLE CONTROL FUNCTIONALITY INCLUDING: <br />a.EACH SENSOR MAY BE PROGRAMMED TO CONTROL SPECIFIC LOADS WITHIN A <br />LOCAL NETWORK. <br />b.SENSOR SHALL BE CAPABLE OF ACTIVATING ONE OF 16 USER-DEFINABLE <br />LIGHTING SCENES. <br />c.ADJUSTABLE RETRIGGER TIME PERIOD FOR MANUAL-ON LOADS. LOAD WILL <br />RETRIGGER (TURN ON) AUTOMATICALLY DURING THE CONFIGURABLE PERIOD OF <br />TIME (DEFAULT 10 SECONDS) AFTER TURNING OFF. <br />d.ON DUAL TECHNOLOGY SENSORS, INDEPENDENTLY CONFIGURABLE TRIGGER <br />MODES ARE AVAILABLE FOR BOTH NORMAL (NH) AND AFTER-HOURS (AH) TIME <br />PERIODS. THE RETRIGGER MODE CAN BE PROGRAMMED TO USE THE FOLLOWING <br />TECHNOLOGIES: <br />1)ULTRASONIC AND PASSIVE INFRARED <br />2)ULTRASONIC OR PASSIVE INFRARED <br />3)ULTRASONIC ONLY <br />4)PASSIVE INFRARED ONLY <br />3.INDEPENDENTLY CONFIGURABLE SENSITIVITY SETTINGS FOR PASSIVE INFRARED <br />AND ULTRASONIC TECHNOLOGIES (ON DUAL TECHNOLOGY SENSORS) FOR BOTH <br />NORMAL (NH) AND AFTER HOUR (AH) TIME PERIODS. <br />4.TWO RJ-45 PORTS FOR CONNECTION TO DLM LOCAL NETWORK. <br />5.TWO-WAY INFRARED (IR) TRANSCEIVER TO ALLOW REMOTE PROGRAMMING <br />THROUGH HANDHELD CONFIGURATION TOOL AND CONTROL BY REMOTE PERSONAL <br />CONTROLS. <br />6.DEVICE STATUS LEDS INCLUDING: <br />a.PIR DETECTION <br />b.ULTRASONIC DETECTION <br />c.CONFIGURATION MODE <br />d.LOAD BINDING <br />7.ASSIGNMENT OF OCCUPANCY SENSOR TO A SPECIFIC LOAD WITHIN THE ROOM <br />WITHOUT WIRING OR SPECIAL TOOLS. <br />8.ASSIGNMENT OF LOCAL BUTTONS TO SPECIFIC LOADS WITHIN THE ROOM WITHOUT <br />WIRING OR SPECIAL TOOLS <br />9.MANUAL OVERRIDE OF CONTROLLED LOADS. <br />10.DIGITAL PARAMETER DATA PROGRAMMED INTO AN INDIVIDUAL WALL SWITCH <br />SENSOR SHALL BE RETAINED IN NON-VOLATILE FLASH MEMORY WITHIN THE WALL <br />SWITCH SENSOR ITSELF. MEMORY SHALL HAVE AN EXPECTED LIFE OF NO LESS THAN <br />10 YEARS. <br />C.PROHIBITED: UNITS WITH DIP SWITCHES OR POTENTIOMETERS FOR FIELD SETTINGS. <br />D.MULTIPLE OCCUPANCY SENSORS MAY BE INSTALLED IN A ROOM BY SIMPLY CONNECTING <br />THEM TO THE FREE TOPOLOGY DLM LOCAL NETWORK. NO ADDITIONAL CONFIGURATION <br />WILL BE REQUIRED. <br />E.TWO-BUTTON WALL SWITCH OCCUPANCY SENSORS, WHEN CONNECTED TO A SINGLE <br />RELAY DIMMING ROOM CONTROLLER, SHALL OPERATE IN THE FOLLOWING SEQUENCE AS <br />A FACTORY DEFAULT: <br />1.LEFT BUTTON <br />a.PRESS AND RELEASE - TURN LOAD ON <br />b.PRESS AND HOLD - RAISE DIMMING LOAD <br />2.RIGHT BUTTON <br />a.PRESS AND RELEASE - TURN LOAD OFF <br />b.PRESS AND HOLD - LOWER DIMMING LOAD <br />G.LOW VOLTAGE MOMENTARY PUSHBUTTONS SHALL INCLUDE THE FOLLOWING FEATURES: <br />1.LOAD/SCENE STATUS LED ON EACH SWITCH BUTTON WITH THE FOLLOWING <br />CHARACTERISTICS: <br />a.BI-LEVEL LED <br />b.DIM LOCATOR LEVEL INDICATES POWER TO SWITCH <br />c.BRIGHT STATUS LEVEL INDICATES THAT LOAD OR SCENE IS ACTIVE <br />2.THE FOLLOWING BUTTON ATTRIBUTES MAY BE CHANGED OR SELECTED USING A <br />WIRELESS CONFIGURATION TOOL: <br />a.LOAD AND SCENE BUTTON FUNCTION MAY BE RECONFIGURED FOR INDIVIDUAL <br />BUTTONS (FROM LOAD TO SCENE, AND VICE VERSA). <br />b.INDIVIDUAL BUTTON FUNCTION MAY BE CONFIGURED TO TOGGLE, ON ONLY OR <br />OFF ONLY. <br />c.INDIVIDUAL SCENES MAY BE LOCKED TO PREVENT UNAUTHORIZED CHANGE. <br />d.FADE UP AND FADE DOWN TIMES FOR INDIVIDUAL SCENES MAY BE ADJUSTED <br />FROM 0 SECONDS TO 18 HOURS. <br />e.RAMP RATE MAY BE ADJUSTED FOR EACH DIMMER SWITCH. <br />f.SWITCH BUTTONS MAY BE BOUND TO ANY LOAD ON A ROOM CONTROLLER AND <br />ARE NOT LOAD TYPE DEPENDENT; EACH BUTTON MAY BE BOUND TO MULTIPLE <br />LOADS. <br />H.PROVIDE WHITE WALL PLATES UNLESS DIRECTED OTHERWISE. <br />2.04 DIGITAL WALL OR CEILING MOUNTED OCCUPANCY SENSOR <br />A.WALL OR CEILING MOUNTED (TO SUIT INSTALLATION) PASSIVE INFRARED (PIR), <br />ULTRASONIC OR DUAL TECHNOLOGY DIGITAL (PASSIVE INFRARED AND ULTRASONIC) <br />OCCUPANCY SENSOR. <br />B.DIGITAL OCCUPANCY SENSORS SHALL PROVIDE GRAPHIC LCD DISPLAY FOR DIGITAL <br />CALIBRATION AND ELECTRONIC DOCUMENTATION. FEATURES INCLUDE THE FOLLOWING: <br />1.DIGITAL CALIBRATION AND PUSHBUTTON CONFIGURATION FOR THE FOLLOWING <br />VARIABLES: <br />a.SENSITIVITY - 0-100% IN 10% INCREMENTS <br />b.TIME DELAY - 1-30 MINUTES IN 1 MINUTE INCREMENTS, FOR LED LIGHT FIXTURES <br />SET FOR 2 MINUTES UNLESS OTHERWISE DIRECTED. <br />c.TEST MODE - FIVE SECOND TIME DELAY <br />d.DETECTION TECHNOLOGY - PIR, ULTRASONIC OR DUAL TECHNOLOGY ACTIVATION <br />AND/OR RE-ACTIVATION. <br />e.WALK-THROUGH MODE <br />f.LOAD PARAMETERS INCLUDING AUTO/MANUAL-ON, BLINK WARNING, AND <br />DAYLIGHT ENABLE/DISABLE WHEN PHOTOSENSORS ARE INCLUDED IN THE DLM <br />LOCAL NETWORK. <br />2.PROGRAMMABLE CONTROL FUNCTIONALITY INCLUDING: <br />a.EACH SENSOR MAY BE PROGRAMMED TO CONTROL SPECIFIC LOADS WITHIN A <br />LOCAL NETWORK. <br />b.SENSOR SHALL BE CAPABLE OF ACTIVATING ONE OF 16 USER-DEFINABLE <br />LIGHTING SCENES. <br />c.ADJUSTABLE RETRIGGER TIME PERIOD FOR MANUAL-ON LOADS. LOAD WILL <br />RETRIGGER (TURN ON) AUTOMATICALLY WITHIN A CONFIGURABLE PERIOD OF <br />TIME (DEFAULT 10 SECONDS) AFTER TURNING OFF. <br />d.ON DUAL TECHNOLOGY SENSORS, INDEPENDENTLY CONFIGURABLE TRIGGER <br />MODES ARE AVAILABLE FOR BOTH NORMAL (NH) AND AFTER-HOURS (AH) TIME <br />PERIODS. THE RETRIGGER MODE CAN BE PROGRAMMED TO USE THE <br />FOLLOWING TECHNOLOGIES: <br />1)ULTRASONIC AND PASSIVE INFRARED <br />2)ULTRASONIC OR PASSIVE INFRARED <br />3)ULTRASONIC ONLY <br />4)PASSIVE INFRARED ONLY <br />3.INDEPENDENTLY CONFIGURABLE SENSITIVITY SETTINGS FOR PASSIVE INFRARED <br />AND ULTRASONIC TECHNOLOGIES (ON DUAL TECHNOLOGY SENSORS) FOR BOTH <br />NORMAL (NH) AND AFTER HOUR (AH) TIME PERIODS. <br />4.ONE OR TWO RJ-45 PORT(S) FOR CONNECTION TO DLM LOCAL NETWORK. <br />5.TWO-WAY INFRARED (IR) TRANSCEIVER TO ALLOW REMOTE PROGRAMMING <br />THROUGH HANDHELD COMMISSIONING TOOL AND CONTROL BY REMOTE PERSONAL <br />CONTROLS. <br />6.DEVICE STATUS LEDS, WHICH MAY BE DISABLED FOR SELECTED APPLICATIONS, <br />INCLUDING: <br />a.PIR DETECTION <br />b.ULTRASONIC DETECTION <br />c.CONFIGURATION MODE <br />d.LOAD BINDING <br />7.ASSIGNMENT OF OCCUPANCY SENSOR TO A SPECIFIC LOAD WITHIN THE ROOM <br />WITHOUT WIRING OR SPECIAL TOOLS. <br />8.MANUAL OVERRIDE OF CONTROLLED LOADS. <br />9.DIGITAL PARAMETER DATA PROGRAMMED INTO AN INDIVIDUAL OCCUPANCY SENSOR <br />SHALL BE RETAINED IN NON-VOLATILE FLASH MEMORY WITHIN THE SENSOR ITSELF. <br />MEMORY SHALL HAVE AN EXPECTED LIFE OF NO LESS THAN 10 YEARS. <br />C.PROHIBITED: UNITS WITH DIP SWITCHES OR POTENTIOMETERS FOR FIELD SETTINGS. <br />D.MULTIPLE OCCUPANCY SENSORS MAY BE INSTALLED IN A ROOM BY SIMPLY CONNECTING <br />THEM TO THE FREE TOPOLOGY DLM LOCAL NETWORK. NO ADDITIONAL CONFIGURATION <br />WILL BE REQUIRED. <br />2.05 DIGITAL WALL SWITCHES <br />A.LOW VOLTAGE MOMENTARY PUSHBUTTON SWITCHES IN 1, 2, 3, 4, 5, AND 8 BUTTON <br />CONFIGURATION. WALL SWITCHES SHALL INCLUDE THE FOLLOWING FEATURES: <br />1.TWO-WAY INFRARED (IR) TRANSCEIVER FOR USE WITH PERSONAL AND <br />CONFIGURATION REMOTE CONTROLS. <br />2.REMOVABLE BUTTONS FOR FIELD REPLACEMENT WITH ENGRAVED BUTTONS AND/OR <br />ALTERNATE COLOR BUTTONS. BUTTON REPLACEMENT MAY BE COMPLETED WITHOUT <br />REMOVING THE SWITCH FROM THE WALL. <br />3.CONFIGURATION LED ON EACH SWITCH THAT BLINKS TO INDICATE DATA <br />TRANSMISSION. <br />4. LOAD/SCENE STATUS LED ON EACH SWITCH BUTTON WITH THE FOLLOWING <br />CHARACTERISTICS: <br />a.BI-LEVEL LED <br />b.DIM LOCATOR LEVEL INDICATES POWER TO SWITCH <br />c.BRIGHT STATUS LEVEL INDICATES THAT LOAD OR SCENE IS ACTIVE <br />5.DIMMING SWITCHES SHALL INCLUDE SEVEN BI-LEVEL LEDS TO INDICATE LOAD <br />LEVELS USING 14 STEPS. <br />6.PROGRAMMABLE CONTROL FUNCTIONALITY INCLUDING: <br />a.BUTTON PRIORITY MAY BE CONFIGURED TO ANY BACNET PRIORITY LEVEL, FROM <br />1-16, CORRESPONDING TO NETWORKED OPERATION ALLOWING LOCAL ACTIONS <br />TO USE LIFE SAFETY PRIORITY <br />b.SCENE PATTERNS MAY BE SAVED TO ANY BUTTON OTHER THAN DIMMING <br />ROCKERS. ONCE SET, BUTTONS MAY BE DIGITALLY LOCKED TO PREVENT <br />OVERWRITING OF THE PRESET LEVELS. <br />7.DIGITAL PARAMETER DATA PROGRAMMED INTO AN INDIVIDUAL WALL SWITCH SHALL <br />BE RETAINED IN NON-VOLATILE FLASH MEMORY WITHIN THE WALL SWITCH ITSELF. <br />MEMORY SHALL HAVE AN EXPECTED LIFE OF NO LESS THAN 10 YEARS. <br />C.TWO RJ-45 PORTS FOR CONNECTION TO DLM LOCAL NETWORK. <br />D.MULTIPLE DIGITAL WALL SWITCHES MAY BE INSTALLED IN A ROOM BY SIMPLY <br />CONNECTING THEM TO THE FREE TOPOLOGY DLM LOCAL NETWORK. NO ADDITIONAL <br />CONFIGURATION SHALL BE REQUIRED TO ACHIEVE MULTI-WAY SWITCHING. <br />E.THE FOLLOWING SWITCH ATTRIBUTES MAY BE CHANGED OR SELECTED USING A <br />WIRELESS CONFIGURATION TOOL: <br />1.LOAD AND SCENE BUTTON FUNCTION MAY BE RECONFIGURED FOR INDIVIDUAL <br />BUTTONS (FROM LOAD TO SCENE, AND VICE VERSA). <br />2.INDIVIDUAL BUTTON FUNCTION MAY BE CONFIGURED TO TOGGLE, ON ONLY OR OFF <br />ONLY. <br />3.INDIVIDUAL SCENES MAY BE LOCKED TO PREVENT UNAUTHORIZED CHANGE. <br />4.FADE UP AND FADE DOWN TIMES FOR INDIVIDUAL SCENES MAY BE ADJUSTED FROM 0 <br />SECONDS TO 18 HOURS. <br />5.RAMP RATE MAY BE ADJUSTED FOR EACH DIMMER SWITCH. <br />6.SWITCH BUTTONS MAY BE BOUND TO ANY LOAD ON A ROOM CONTROLLER AND ARE <br />NOT LOAD TYPE DEPENDENT; EACH BUTTON MAY BE BOUND TO MULTIPLE LOADS. <br />F.PROVIDE WHITE WALL PLATES WITH DECORATOR OPENING UNLESS OTHERWISE <br />DIRECTED. <br />2.06 DIGITAL DAYLIGHTING SENSORS <br />A.DIGITAL DAYLIGHTING SENSORS SHALL WORK WITH ROOM CONTROLLERS TO PROVIDE <br />AUTOMATIC SWITCHING, BI-LEVEL, OR TRI-LEVEL OR DIMMING DAYLIGHT HARVESTING <br />CAPABILITIES FOR ANY LOAD TYPE CONNECTED TO A ROOM CONTROLLER. DAYLIGHTING <br />SENSORS SHALL BE INTERCHANGEABLE WITHOUT THE NEED FOR REWIRING. <br />1.CLOSED LOOP SENSORS MEASURE THE AMBIENT LIGHT IN THE SPACE AND CONTROL <br />A SINGLE LIGHTING ZONE. <br />2.OPEN LOOP SENSORS MEASURE INCOMING DAYLIGHT IN THE SPACE, AND ARE <br />CAPABLE OF CONTROLLING UP TO THREE LIGHTING ZONES. <br />3.DUAL LOOP SENSORS MEASURE BOTH AMBIENT AND INCOMING DAYLIGHT IN THE <br />SPACE TO INSURE THAT PROPER LIGHT LEVELS ARE MAINTAINED AS CHANGES TO <br />REFLECTIVE MATERIALS ARE MADE IN A SINGLE ZONE. <br />B.DIGITAL DAYLIGHTING SENSORS SHALL INCLUDE THE FOLLOWING FEATURES: <br />1.THE SENSOR'S INTERNAL PHOTODIODE SHALL ONLY MEASURE LIGHT WAVES WITHIN <br />THE VISIBLE SPECTRUM. THE PHOTODIODE'S SPECTRAL RESPONSE CURVE SHALL <br />CLOSELY MATCH THE ENTIRE PHOTOPIC CURVE. THE PHOTODIODE SHALL NOT <br />MEASURE ENERGY IN EITHER THE ULTRAVIOLET OR INFRARED SPECTRUMS. THE <br />PHOTOCELL SHALL HAVE A SENSITIVITY OF LESS THAN 5% FOR ANY WAVELENGTHS <br />LESS THAN 400 NANOMETERS OR GREATER THAN 700 NANOMETERS. <br />2.SENSOR LIGHT LEVEL RANGE SHALL BE FROM 1-6,553 FOOT-CANDLES (FC). <br />3.THE CAPABILITY OF ON/OFF, BI-LEVEL OR TRI-LEVEL SWITCHING, OR DIMMING, FOR <br />EACH CONTROLLED ZONE, DEPENDING ON THE SELECTION OF ROOM <br />CONTROLLER(S) AND LOAD BINDING TO ROOM CONTROLLER(S). <br />4.FOR SWITCHING DAYLIGHT HARVESTING, THE PHOTOSENSOR SHALL PROVIDE A <br />FIELD-SELECTABLE DEAD BAND, OR A SEPARATION, BETWEEN THE “ON SETPOINT” <br />AND THE “OFF SETPOINT” THAT WILL PREVENT THE LIGHTS FROM CYCLING <br />EXCESSIVELY AFTER THEY TURN OFF. <br />5.FOR DIMMING DAYLIGHT HARVESTING, THE PHOTOSENSOR SHALL PROVIDE THE <br />OPTION, WHEN THE DAYLIGHT CONTRIBUTION IS SUFFICIENT, OF TURNING LIGHTS <br />OFF OR DIMMING LIGHTS TO A FIELD-SELECTABLE MINIMUM LEVEL. <br />6.PHOTOSENSORS SHALL HAVE A DIGITAL, INDEPENDENTLY CONFIGURABLE FADE <br />RATE FOR BOTH INCREASING AND DECREASING LIGHT LEVEL IN UNITS OF PERCENT <br />PER SECOND. <br />7.PHOTOSENSORS SHALL PROVIDE ADJUSTABLE CUT-OFF TIME. CUT-OFF TIME IS <br />DEFINED BY THE NUMBER OF SELECTED MINUTES THE LOAD IS AT THE MINIMUM <br />OUTPUT BEFORE THE LOAD TURNS OFF. SELECTABLE RANGE BETWEEN 0-240 <br />MINUTES INCLUDING OPTION TO NEVER CUT-OFF. <br />8.OPTIONAL WALL SWITCH OVERRIDE SHALL ALLOW OCCUPANTS TO REDUCE LIGHTING <br />LEVEL TO INCREASE ENERGY SAVINGS OR, IF PERMITTED BY SYSTEM <br />ADMINISTRATOR, RAISE LIGHTING LEVELS FOR A SELECTABLE PERIOD OF TIME OR <br />CYCLE OF OCCUPANCY. <br />9.INTEGRAL INFRARED (IR) TRANSCEIVER FOR CONFIGURATION AND/OR <br />COMMISSIONING WITH A HANDHELD CONFIGURATION TOOL, TO TRANSMIT DETECTED <br />LIGHT LEVEL TO WIRELESS CONFIGURATION TOOL, AND FOR COMMUNICATION WITH <br />PERSONAL REMOTE CONTROLS. <br />10.CONFIGURATION LED STATUS LIGHT ON DEVICE THAT BLINKS TO INDICATE DATA <br />TRANSMISSION. <br />11.STATUS LED INDICATES TEST MODE, OVERRIDE MODE AND LOAD BINDING. <br />12.RECESSED SWITCH ON DEVICE TO TURN CONTROLLED LOAD(S) ON AND OFF. <br />13.A CHOICE OF ACCESSORIES TO ACCOMMODATE MULTIPLE MOUNTING METHODS AND <br />BUILDING MATERIALS. THE PHOTOSENSORS MAY BE MOUNTED ON A CEILING TILE, <br />SKYLIGHT LIGHT WELL, SUSPENDED LIGHTING FIXTURE, OR BACK BOX. ANY LOAD OR <br />GROUP OF LOADS IN THE ROOM CAN BE ASSIGNED TO A DAYLIGHTING ZONE <br />14.EACH LOAD WITHIN A DAYLIGHTING ZONE CAN BE INDIVIDUALLY ENABLED OR <br />DISABLED FOR DISCRETE CONTROL (LOAD INDEPENDENCE). <br />15.DIGITAL PARAMETER DATA PROGRAMMED INTO A PHOTOSENSOR SHALL BE <br />RETAINED IN NON-VOLATILE FLASH MEMORY WITHIN THE PHOTOSENSOR ITSELF. <br />MEMORY SHALL HAVE AN EXPECTED LIFE OF 10 YEARS, MINIMUM. <br />C.CLOSED LOOP DIGITAL PHOTOSENSORS SHALL INCLUDE THE FOLLOWING ADDITIONAL <br />FEATURES: <br />1.AN INTERNAL PHOTODIODE THAT MEASURES LIGHT IN A 100-DEGREE ANGLE, <br />CUTTING OFF THE UNWANTED LIGHT FROM BRIGHT SOURCES OUTSIDE OF THIS <br />CONE. <br />2.AUTOMATIC SELF-CALIBRATION, INITIATED FROM THE PHOTOSENSOR, A WIRELESS <br />CONFIGURATION TOOL OR A PC WITH APPROPRIATE SOFTWARE. <br />3.AUTOMATICALLY ESTABLISHES APPLICATION-SPECIFIC SETPOINTS FOLLOWING <br />SELF-CALIBRATION. FOR SWITCHING OPERATION, AN ADEQUATE DEAD BAND <br />BETWEEN THE ON AND OFF SETPOINTS SHALL PREVENT THE LIGHTS FROM CYCLING; <br />FOR DIMMING OPERATION A SLIDING SETPOINT CONTROL ALGORITHM WITH <br />SEPARATE DAY AND NIGHT SETPOINTS SHALL PREVENT ABRUPT RAMPING OF LOADS. <br />4.WATTSTOPPER PRODUCT NUMBER: LMLS-400, LMLS-400-L. <br />D.OPEN LOOP DIGITAL PHOTOSENSORS SHALL INCLUDE THE FOLLOWING ADDITIONAL <br />FEATURES: <br />1.AN INTERNAL PHOTODIODE THAT MEASURES LIGHT IN A 60-DEGREE ANGLE CUTTING <br />OFF THE UNWANTED LIGHT FROM THE INTERIOR OF THE ROOM. <br />2.AUTOMATICALLY ESTABLISHES APPLICATION-SPECIFIC SETPOINTS FOLLOWING <br />MANUAL CALIBRATION USING A WIRELESS CONFIGURATION TOOL OR A PC WITH <br />APPROPRIATE SOFTWARE. FOR SWITCHING OPERATION, AN ADEQUATE DEAD BAND <br />BETWEEN THE ON AND OFF SETPOINTS FOR EACH ZONE SHALL PREVENT THE LIGHTS <br />FROM CYCLING; FOR DIMMING OPERATION, A PROPORTIONAL CONTROL ALGORITHM <br />SHALL MAINTAIN THE DESIGN LIGHTING LEVEL IN EACH ZONE. <br />3.EACH OF THE THREE DISCRETE DAYLIGHT ZONES CAN INCLUDE ANY <br />NON-OVERLAPPING GROUP OF LOADS IN THE ROOM. <br />4.WATTSTOPPER PRODUCT NUMBER: LMLS-500, LMLS-500-L. <br />E.DUAL LOOP DIGITAL PHOTOSENSORS SHALL INCLUDE THE FOLLOWING ADDITIONAL <br />FEATURES: <br />1.CLOSE LOOP PORTION OF DUAL LOOP DEVICE MUST HAVE AN INTERNAL <br />PHOTODIODE THAT MEASURES LIGHT IN A 100 DEGREE ANGLE, CUTTING OFF THE <br />UNWANTED LIGHT FROM SOURCES OUTSIDE OF THIS CON <br />2.OPEN LOOP PORTION OF DUAL LOOP DEVICE MUST HAVE AN INTERNAL PHOTODIODE <br />THAT CAN MEASURE LIGHT IN A 60 DEGREE ANGLE, CUTTING OFF THE UNWANTED <br />LIGHT FROM THE INTERIOR OF THE ROOM. <br />3.AUTOMATICALLY ESTABLISHES APPLICATION-SPECIFIC SET-POINTS FOLLOWING <br />SELF-CALIBRATION. FOR SWITCHING OPERATION, AN ADEQUATE DEAD BAND <br />BETWEEN THE ON AND OFF SETPOINTS SHALL PREVENT THE LIGHTS FROM CYCLING; <br />FOR DIMMING OPERATION A SLIDING SETPOINT CONTROL ALGORITHM WITH <br />SEPARATE DAY AND NIGHT SETPOINTS SHALL PREVENT ABRUPT RAMPING OF LOAD. <br />4.DEVICE MUST REFERENCE CLOSED LOOP PHOTOSENSOR INFORMATION AS A BASE <br />LINE REFERENCE. THE DEVICE MUST BE ABLE TO ANALYZE THE OPEN LOOP <br />PHOTOSENSOR INFORMATION TO DETERMINE IF AN ADJUSTMENT IN LIGHT LEVELS IS <br />REQUIRED. <br />5.DEVICE MUST BE ABLE TO AUTOMATICALLY COMMISSION SETPOINTS EACH NIGHT TO <br />PROVIDE ADJUSTMENTS TO ELECTRICAL LIGHTING BASED ON CHANGES IN OVERALL <br />LIGHTING IN THE SPACE DUE TO CHANGES IN REFLECTANCE WITHIN THE SPACE OR <br />CHANGES TO DAYLIGHT CONTRIBUTION BASED ON SEASONAL CHANGES. <br />6.DEVICE MUST INCLUDE EXTENDABLE MOUNTING ARM TO PROPERLY POSITION <br />SENSOR WITHIN A SKYLIGHT WELL. <br />2.07 DIGITAL ROOM CONTROLLERS AND PLUG-LOAD CONTROLLERS <br />A.DIGITAL CONTROLLERS FOR LIGHTING AND PLUG LOADS AUTOMATICALLY BIND THE <br />ROOM LOADS TO THE CONNECTED DEVICES IN THE SPACE WITHOUT COMMISSIONING OR <br />THE USE OF ANY TOOLS. ROOM AND PLUG LOAD CONTROLLERS SHALL BE PROVIDED TO <br />MATCH THE ROOM LIGHTING AND PLUG LOAD CONTROL REQUIREMENTS. THE <br />CONTROLLERS SHALL BE SIMPLE TO INSTALL, AND PROVIDE STANDARD PLUG N' GO <br />APPLICATIONS. THE CONTROL UNITS SHALL INCLUDE THE FOLLOWING FEATURES: <br />1.AUTOMATIC ROOM CONFIGURATION TO THE MOST ENERGY-EFFICIENT SEQUENCE OF <br />OPERATION BASED UPON THE DEVICES IN THE ROOM. <br />2.SIMPLE REPLACEMENT - USING THE DEFAULT AUTOMATIC CONFIGURATION <br />CAPABILITIES, A ROOM CONTROLLER MAY BE REPLACED WITH AN OFF-THE-SHELF. <br />3.MULTIPLE ROOM CONTROLLERS CONNECTED TOGETHER IN A LOCAL NETWORK MUST <br />AUTOMATICALLY PRIORITIZE EACH ROOM CONTROLLER, WITHOUT REQUIRING ANY <br />CONFIGURATION OR SETUP, SO THAT LOADS ARE SEQUENTIALLY ASSIGNED USING <br />ROOM CONTROLLER DEVICE ID'S FROM HIGHEST TO LOWEST. <br />4.DEVICE STATUS LEDS TO INDICATE: <br />a.DATA TRANSMISSION <br />b.DEVICE HAS POWER <br />c.STATUS FOR EACH LOAD <br />d.CONFIGURATION STATUS <br />5.QUICK INSTALLATION FEATURES INCLUDING: <br />a.STANDARD JUNCTION BOX MOUNTING <br />b.QUICK LOW VOLTAGE CONNECTIONS USING STANDARD RJ-45 PATCH CABLE <br />6.BASED ON INDIVIDUAL CONFIGURATION, EACH LOAD SHALL BE CAPABLE OF THE <br />FOLLOWING BEHAVIOR ON POWER UP FOLLOWING THE LOSS OF NORMAL POWER: <br />a.TURN ON TO 100% <br />b.REMAIN OFF <br />c.TURN ON TO LAST LEVEL <br />7.EACH LOAD SHALL BE CONFIGURABLE TO OPERATE IN THE FOLLOWING SEQUENCES <br />BASED ON OCCUPANCY: <br />a.AUTO-ON/AUTO-OFF (FOLLOW ON AND OFF) <br />b.MANUAL-ON/AUTO-OFF (FOLLOW OFF ONLY) <br />8.THE POLARITY OF EACH LOAD OUTPUT SHALL BE REVERSIBLE, VIA DIGITAL <br />CONFIGURATION, SO THAT ON IS OFF AND OFF IS ON. <br />9.BACNET OBJECT INFORMATION SHALL BE AVAILABLE FOR THE FOLLOWING OBJECTS: <br />a.LOAD STATUS <br />b.ELECTRICAL CURRENT <br />c.TOTAL WATTS PER CONTROLLER <br />d.SCHEDULE STATE - NORMAL OR AFTER-HOURS <br />e.DEMAND RESPONSE CONTROL AND CAP LEVEL <br />f.ROOM OCCUPANCY STATUS <br />g.TOTAL ROOM LIGHTING AND PLUG LOADS WATTS <br />h.TOTAL ROOM WATTS/SQ. FT. <br />i.FORCE ON/OFF EVERY LOAD <br />10.UL 2043 PLENUM RATED <br />11.MANUAL OVERRIDE AND LED INDICATION FOR EACH LOAD <br />12.DUAL VOLTAGE (120/277 VAC, 60 HZ), OR 347 VAC, 60 HZ (SELECTED MODELS ONLY). <br />120/277 VOLT MODELS RATED FOR 20A TOTAL LOAD, DERATING TO 16A REQUIRED <br />FOR SOME DIMMED LOADS (FORWARD PHASE DIMMING); 347 VOLT MODELS RATED <br />FOR 15 AMPS TOTAL LOAD; PLUG LOAD CONTROLLERS CARRY <br />APPLICATION-SPECIFIC UL 20 RATING FOR RECEPTACLE CONTROL. <br />13.ZERO CROSS CIRCUITRY FOR EACH LOAD <br />14.DIGITAL PARAMETER DATA PROGRAMMED INTO AN INDIVIDUAL ROOM CONTROLLER <br />OR PLUG LOAD CONTROLLER SHALL BE RETAINED IN NON-VOLATILE FLASH MEMORY <br />WITHIN THE CONTROLLER ITSELF. MEMORY SHALL HAVE AN EXPECTED LIFE OF NO <br />LESS THAN 10 YEARS. <br />15.PROHIBITED: DIP SWITCHES OR POTENTIOMETERS, OR REQUIRE SPECIAL <br />CONFIGURATION FOR STANDARD PLUG N' GO APPLICATIONS <br />B.ON/OFF ROOM CONTROLLERS SHALL INCLUDE: <br />1.ONE OR TWO RELAY CONFIGURATION <br />2.EFFICIENT 150 MA SWITCHING POWER SUPPLY <br />3.THREE RJ-45 DLM LOCAL NETWORK PORTS WITH INTEGRAL STRAIN RELIEF AND DUST <br />COVER <br />4.WATTSTOPPER PRODUCT NUMBERS: LMRC-101, LMRC-102 <br />C.ON/OFF/DIMMING ENHANCED ROOM CONTROLLERS SHALL INCLUDE: <br />1.REAL TIME CURRENT MONITORING <br />2. MULTIPLE RELAY CONFIGURATIONS <br />a.ONE, TWO OR THREE RELAYS (LMRC-21X SERIES) <br />b.ONE OR TWO RELAYS (LMRC-22X SERIES) <br />3.EFFICIENT 250 MA SWITCHING POWER SUPPLY <br />4.FOUR RJ-45 DLM LOCAL NETWORK PORTS WITH INTEGRAL STRAIN RELIEF AND DUST <br />COVER <br />5.ONE DIMMING OUTPUT PER RELAY <br />a.0-10V DIMMING - WHERE INDICATED, ONE 0 TO 10 VOLT ANALOG OUTPUT PER <br />RELAY FOR CONTROL OF COMPATIBLE BALLASTS AND LED DRIVERS. THE <br />0 TO 10 VOLT OUTPUT SHALL AUTOMATICALLY OPEN UPON LOSS OF POWER TO <br />THE ROOM CONTROLLER TO ASSURE FULL LIGHT OUTPUT FROM THE <br />CONTROLLED LIGHTING. (LMRC-21X SERIES) <br />b.LINE VOLTAGE, FORWARD PHASE DIMMING - WHERE INDICATED, ONE FORWARD <br />PHASE CONTROL LINE VOLTAGE DIMMING OUTPUT PER RELAY FOR CONTROL OF <br />COMPATIBLE TWO-WIRE OR THREE-WIRE BALLASTS, LED DRIVERS, MLV, <br />FORWARD PHASE COMPATIBLE ELV, NEON/COLD CATHODE AND INCANDESCENT <br />LOADS. (LMRC-22X SERIES) <br />c.EACH DIMMING OUTPUT CHANNEL SHALL HAVE AN INDEPENDENTLY <br />CONFIGURABLE MINIMUM AND MAXIMUM CALIBRATION TRIM LEVEL TO SET THE <br />DIMMING RANGE TO MATCH THE TRUE DYNAMIC RANGE OF THE CONNECTED <br />BALLAST OR DRIVER. <br />d.THE LED LEVEL INDICATORS ON BOUND DIMMING SWITCHES SHALL USE THIS <br />NEW MAXIMUM AND MINIMUM TRIM. <br />e.EACH DIMMING OUTPUT CHANNEL SHALL HAVE AN INDEPENDENTLY <br />CONFIGURABLE MINIMUM AND MAXIMUM TRIM LEVEL TO SET THE DYNAMIC <br />RANGE OF THE OUTPUT WITHIN THE NEW 0-100% DIMMING RANGE DEFINED BY <br />THE MINIMUM AND MAXIMUM CALIBRATION TRIM. <br />f.CALIBRATION AND TRIM LEVELS MUST BE SET PER OUTPUT CHANNEL. <br />g.CONFIGURATION SHALL BE DIGITAL. <br />h.PROHIBITED: DEVICES THAT SET CALIBRATION OR TRIM LEVELS PER <br />CONTROLLER. <br />6.EACH LOAD SHALL HAVE AN INDEPENDENTLY CONFIGURABLE PRESET ON LEVEL FOR <br />NORMAL-HOURS AND AFTER-HOURS EVENTS TO ALLOW DIFFERENT DIMMED LEVELS <br />TO BE ESTABLISHED AT THE START OF BOTH NORMAL-HOURS AND AFTER-HOURS <br />EVENTS. <br />7.FADE RATES FOR DIMMING LOADS SHALL BE SPECIFIC TO BOUND SWITCH BUTTONS, <br />AND THE LOAD SHALL MAINTAIN A DEFAULT VALUE FOR ANY BOUND BUTTONS THAT <br />DO NOT SPECIFY A UNIQUE VALUE. <br />8.THE FOLLOWING DIMMING ATTRIBUTES MAY BE CHANGED OR SELECTED USING A <br />WIRELESS CONFIGURATION TOOL: <br />a.ESTABLISH PRESET LEVEL FOR EACH LOAD FROM 0-100% <br />b.SET HIGH AND LOW TRIM FOR EACH LOAD <br />c.SET LAMP BURN IN TIME FOR EACH LOAD UP TO 100 HOURS <br />9.OVERRIDE BUTTON FOR EACH LOAD PROVIDES THE FOLLOWING FUNCTIONS: <br />a.PRESS AND RELEASE FOR ON/OFF CONTROL <br />b.PRESS AND HOLD FOR DIMMING CONTROL <br />10.10.WATTSTOPPER PRODUCT NUMBERS: LMRC-211, LRMC-212, LRMC-213, LMRC-221, <br />LMRC-222. <br />2.09 CONFIGURATION TOOLS <br />A.FEATURES AND FUNCTIONALITY OF THE WIRELESS CONFIGURATION TOOL SHALL <br />INCLUDE BUT NOT BE LIMITED TO: <br />1.TWO-WAY INFRARED (IR) COMMUNICATION WITH DLM IR-ENABLED DEVICES WITHIN A <br />RANGE OF APPROXIMATELY 30 FEET. <br />2.HIGH VISIBILITY ORGANIC LED (OLED) DISPLAY, PUSHBUTTON USER INTERFACE, AND <br />MENU-DRIVEN OPERATION. <br />3.MUST BE ABLE TO READ AND MODIFY PARAMETERS FOR ROOM CONTROLLERS, <br />OCCUPANCY SENSORS, WALL SWITCHES, DAYLIGHTING SENSORS, NETWORK <br />BRIDGES AND RELAY PANELS, AND IDENTIFY ROOM DEVICES BY TYPE AND SERIAL <br />NUMBER. <br />4.SAVE UP TO EIGHT OCCUPANCY SENSOR SETTING PROFILES, AND APPLY PROFILES <br />TO SELECTED SENSORS. <br />5.TEMPORARILY ADJUST LIGHT LEVEL OF ANY LOAD(S) ON THE LOCAL NETWORK, AND <br />INCORPORATE THOSE LEVELS IN SCENE SETTING. SET ROOM MODE FOR TESTING OF <br />NORMAL-HOURS (NH) AND AFTER-HOURS (AH) PARAMETER SETTINGS. <br />6.ADJUST OR FINE-TUNE DAYLIGHTING SETTINGS ESTABLISHED DURING <br />AUTO-CONFIGURATION, AND INPUT LIGHT LEVEL DATA TO COMPLETE <br />CONFIGURATION OF OPEN LOOP DAYLIGHTING CONTROLS. <br />7.SET ROOM MODE FOR TESTING OF NORMAL-HOURS (NH) AND AFTER-HOURS (AH) <br />PARAMETER SETTINGS. <br />8.VERIFY STATUS OF BUILDING LEVEL NETWORK DEVICES. <br />2.10 EMERGENCY LIGHTING CONTROL DEVICES <br />A.EMERGENCY LIGHTING CONTROL UNIT - A UL 924 LISTED DEVICE THAT MONITORS A <br />SWITCHED CIRCUIT PROVIDING NORMAL LIGHTING TO AN AREA. THE UNIT PROVIDES <br />NORMAL ON/OFF CONTROL OF EMERGENCY LIGHTING ALONG WITH THE NORMAL <br />LIGHTING. UPON NORMAL POWER FAILURE THE EMERGENCY LIGHTING CIRCUIT WILL <br />CLOSE, FORCING THE EMERGENCY LIGHTING ON UNTIL NORMAL POWER IS RESTORED. <br />FEATURES INCLUDE: <br />1.120/277 VOLTS, 50/60 HZ, 20 AMP BALLAST RATING <br />2.PUSH TO TEST BUTTON AUXILIARY CONTACT FOR REMOTE TEST OR FIRE ALARM <br />SYSTEM INTERFACE <br />PART 3 - EXECUTION <br />3.01 CONTRACTOR INSTALLATION AND SERVICES <br />A.INSTALL DEVICES AND WIRING IN A PROFESSIONAL MANNER. LINE VOLTAGE <br />CONNECTIONS TO BE TAGGED TO INDICATE CIRCUIT AND SWITCHED LEGS. <br />B.INSTALL ROOM/AREA DEVICES USING MANUFACTURER'S FACTORY-TESTED CAT 5E <br />CABLE WITH PRE-TERMINATED RJ-45 CONNECTORS. IF PRE-TERMINATED CABLE IS NOT <br />USED FOR ROOM/AREA WIRING, THE CONTRACTOR IS RESPONSIBLE FOR TESTING EACH <br />FIELD-TERMINATED CABLE FOLLOWING INSTALLATION, AND SHALL SUPPLY THE LIGHTING <br />CONTROLS MANUFACTURER WITH TEST RESULTS. <br />C.INSTALL THE WORK IN ACCORDANCE WITH MANUFACTURER'S PRINTED INSTRUCTIONS <br />UNLESS OTHERWISE INDICATED. BEFORE START UP, TEST EACH DEVICE TO ENSURE <br />PROPER COMMUNICATION. <br />D.CALIBRATE SENSOR TIME DELAYS AND SENSITIVITY TO GUARANTEE PROPER DETECTION <br />OF OCCUPANTS AND ENERGY SAVINGS. <br />E.ADJUST TIME DELAY SO THAT CONTROLLED AREA REMAINS LIGHTED WHILE OCCUPIED. <br />F.PROVIDE WRITTEN OR COMPUTER-GENERATED DOCUMENTATION ON THE <br />CONFIGURATION OF THE SYSTEM INCLUDING ROOM BY ROOM DESCRIPTION INCLUDING: <br />G.SENSOR PARAMETERS, TIME DELAYS, SENSITIVITIES, AND DAYLIGHTING SETPOINTS. <br />H.SEQUENCE OF OPERATION, (E.G. MANUAL ON, AUTO OFF. ETC.) <br />I.LOAD PARAMETERS (E.G. BLINK WARNING, ETC.) <br />J.POST START-UP TUNING - AFTER 30 DAYS FROM OCCUPANCY CONTRACTOR SHALL <br />ADJUST SENSOR TIME DELAYS AND SENSITIVITIES TO MEET THE INDUSTRY <br />REQUIREMENTS. PROVIDE A DETAILED REPORT TO THE OWNER'S REPRESENTATIVE OF <br />POST START-UP ACTIVITY. <br />3.02 FACTORY SERVICES (OPTIONAL) <br />A.UPON COMPLETION OF THE INSTALLATION, THE MANUFACTURER'S FACTORY <br />AUTHORIZED REPRESENTATIVE SHALL START UP AND VERIFY A COMPLETE FULLY <br />FUNCTIONAL SYSTEM. <br />B.THE ELECTRICAL CONTRACTOR SHALL PROVIDE BOTH THE MANUFACTURER AND THE <br />ELECTRICAL ENGINEER WITH THREE WEEKS WRITTEN NOTICE OF THE SYSTEM START UP <br />AND ADJUSTMENT DATE. <br />C.UPON COMPLETION OF THE SYSTEM START UP, THE FACTORY-AUTHORIZED TECHNICIAN <br />SHALL PROVIDE THE PROPER TRAINING TO THE OWNER'S PERSONNEL ON THE <br />ADJUSTMENT AND MAINTENANCE OF THE SYSTEM. <br />3.03 ACCEPTANCE TESTING SUPPORT SERVICES <br />A.A CERTIFIED LIGHTING CONTROLS ACCEPTANCE TEST TECHNICIAN (CLCATT) MUST <br />VERIFY THE INSTALLATION OF THE LIGHTING CONTROL SYSTEM. MANUFACTURER <br />SHOULD INCLUDE AN EXTRA DAY OF FACTORY TECHNICIAN'S TIME TO ASSIST THE <br />CLCATT REVIEW THE FUNCTIONALITY AND SETTINGS OF THE LIGHTING CONTROL <br />HARDWARE PER THE REQUIREMENTS IN THE CALIFORNIA STATE FORMS. IT WILL BE THE <br />CLCATT'S RESPONSIBILITY TO CREATE AND COMPLETE ANY FORMS REQUIRED FOR THE <br />COMMISSIONING PROCESS, ALTHOUGH THE MANUFACTURER OR CONTRACTOR MAY <br />OFFER SPREADSHEETS AND/OR PRINTOUTS TO ASSIST THE CLCATT WITH THIS TASK. <br />3.04 INSTALLATION <br />A.COMPLY WITH NECA 1. <br />B.WIRING METHOD: INSTALL CABLES IN RACEWAYS, EXCEPT IN ACCESSIBLE CEILING <br />SPACES AND IN GYPSUM BOARD PARTITIONS WHERE UNENCLOSED WIRING METHOD <br />MAY BE USED. CONCEAL RACEWAY AND CABLES EXCEPT IN UNFINISHED SPACES. <br />C.SPLICES, TAPS, AND TERMINATIONS: MAKE CONNECTIONS ONLY ON NUMBERED <br />TERMINAL STRIPS IN JUNCTION, PULL, AND OUTLET BOXES; TERMINAL CABINETS; AND <br />EQUIPMENT ENCLOSURES. <br />LABEL EACH SCENE-CONTROL BUTTON WITH APPROVED SCENE DESCRIPTION. <br />TYPE DESCRIPTION <br />DP 208/120V DISTRIBUTION PANELBOARD <br />LP 208/120V PANELBOARD - RECEPTACLES & LIGHTING <br />HDP 480/277V DISTRIBUTION PANELBOARD <br />HLP 480/277 V PANELBOARD - LIGHTING <br />ATS AUTOMATIC TRANSFER SWITCH <br />CB CIRCUIT BREAKER <br />DS DISCONNECT SWITCH <br />EDP EMERGENCY 208/120V DISTRIBUTION PANELBOARD <br />ELP EMERGENCY 208/120V PANELBOARD <br />EHDP EMERGENCY 480/277V DISTRIBUTION PANELBOARD <br />EMCC EMERGENCY MOTOR CONTROL CENTER <br />MSB MAIN SWITCHBOARD <br />MCC MOTOR CONTROL CENTER <br />T TRANSFORMER <br />US UNIT SUBSTATION <br />Sheet No. <br />Project <br />Agency Plan Check / Permit No. <br />Petersen Design Project No. <br />Consultant <br />5082.1 <br />652 East Dyer Drive <br />Santa Ana, CA 92705 <br />DYER WAREHOUSE <br />Staging & Set-Up Space <br />Tenant Improvements <br />Sheet Title <br />Revision / Submittal History <br />Scale <br />Status <br />. <br />architecture + planning <br />Agency Approval <br />Petersen Design Architects, Inc. <br />17582 Fiesta Way, Tustin, CA 92780 <br />M: 714.904.6720 E: mike@mpdarch.com <br />www.mpdarch.com <br />Architect's Stamp <br />. <br />255 E. Rincon St., Suite 301 <br />Corona, CA 92879 <br />P 951.340.1977 | F 951.340.1090 <br />www.gossengineering.com <br />CALOFI <br />GI <br />RE <br />NG <br />A <br />E <br />S <br />No. E17083 <br />T <br />E <br />ET <br />SAT L CE A <br />F <br />RIC L <br />ORNI <br />EPR <br />RAET <br />RED D.D <br />OF ONABR <br />L <br />SSI <br />NE <br />RE <br />IWD <br />UT <br />HCE <br />Project Number: 125-09-07 <br />Date Signed 01-09-2026 <br />1 01/09/2026 PLAN CHECK RESUBMITTAL <br />ELECTRICAL <br />SPECIFICATIONS <br />E7.2