P.SURFACE RACEWAYS:
<br />1.INSTALL SURFACE RACEWAY WITH A MINIMUM 2-INCH RADIUS CONTROL AT BEND
<br />POINTS.
<br />2.SECURE SURFACE RACEWAY WITH SCREWS OR OTHER ANCHOR-TYPE DEVICES AT
<br />INTERVALS NOT EXCEEDING 48 INCHES AND WITH NO LESS THAN TWO SUPPORTS
<br />PER STRAIGHT RACEWAY SECTION. SUPPORT SURFACE RACEWAY IN ACCORDANCE
<br />WITH MANUFACTURER'S WRITTEN INSTRUCTIONS. TAPE AND GLUE ARE NOT
<br />ACCEPTABLE SUPPORT METHODS.
<br />3.INSTALL A SEPARATE, GREEN, GROUND CONDUCTOR IN RACEWAYS FROM JUNCTION
<br />BOX SUPPLYING RACEWAYS TO RECEPTACLE OR FIXTURE GROUND TERMINALS.
<br />U.INSTALL RACEWAY SEALING FITTINGS AT ACCESSIBLE LOCATIONS IN ACCORDANCE WITH
<br />CEC AND FILL THEM WITH LISTED SEALING COMPOUND. FOR CONCEALED RACEWAYS,
<br />INSTALL EACH FITTING IN A FLUSH STEEL BOX WITH A BLANK COVER PLATE HAVING A
<br />FINISH SIMILAR TO THAT OF ADJACENT PLATES OR SURFACES. INSTALL RACEWAY
<br />SEALING FITTINGS IN ACCORDANCE WITH CEC.
<br />V.INSTALL DEVICES TO SEAL RACEWAY INTERIORS AT ACCESSIBLE LOCATIONS. LOCATE
<br />SEALS SO NO FITTINGS OR BOXES ARE BETWEEN THE SEAL AND THE FOLLOWING
<br />CHANGES OF ENVIRONMENTS. SEAL THE INTERIOR OF ALL RACEWAYS AT THE
<br />FOLLOWING POINTS:
<br />1.WHERE CONDUITS PASS FROM WARM TO COLD LOCATIONS, SUCH AS BOUNDARIES
<br />OF REFRIGERATED SPACES AND CONDITIONED VERSUS UNCONDITIONED INTERIOR
<br />SPACES.
<br />2.WHERE AN UNDERGROUND SERVICE RACEWAY ENTERS A BUILDING OR STRUCTURE.
<br />3.CONDUIT EXTENDING FROM INTERIOR TO EXTERIOR OF BUILDING.
<br />4.CONDUIT EXTENDING INTO PRESSURIZED DUCT AND EQUIPMENT.
<br />5.CONDUIT EXTENDING INTO PRESSURIZED ZONES THAT ARE AUTOMATICALLY
<br />CONTROLLED TO MAINTAIN DIFFERENT PRESSURE SET POINTS.
<br />6.WHERE OTHERWISE REQUIRED BY CEC.
<br />W.COMPLY WITH MANUFACTURER'S WRITTEN INSTRUCTIONS FOR SOLVENT WELDING RNC
<br />AND FITTINGS.
<br />X.EXPANSION-JOINT FITTINGS:
<br />1.INSTALL IN EACH RUN OF ABOVEGROUND RNC THAT IS LOCATED WHERE
<br />ENVIRONMENTAL TEMPERATURE CHANGE MAY EXCEED 30°F AND THAT HAS
<br />STRAIGHT-RUN LENGTH THAT EXCEEDS 25 FEET. INSTALL IN EACH RUN OF
<br />ABOVEGROUND RMC AND EMT CONDUIT THAT IS LOCATED WHERE ENVIRONMENTAL
<br />TEMPERATURE CHANGE MAY EXCEED 100°F AND THAT HAS STRAIGHT-RUN LENGTH
<br />THAT EXCEEDS 100 FEET.
<br />2.INSTALL FITTING(S) THAT PROVIDE EXPANSION AND CONTRACTION FOR AT LEAST
<br />0.00041 IN/FT-°F OF TEMPERATURE CHANGE FOR PVC CONDUITS. INSTALL FITTING(S)
<br />THAT PROVIDE EXPANSION AND CONTRACTION FOR AT LEAST 0.000078 IN/FT-°F OF
<br />TEMPERATURE CHANGE FOR METAL CONDUITS.
<br />3.INSTALL EXPANSION FITTINGS AT ALL LOCATIONS WHERE CONDUITS CROSS
<br />BUILDING OR STRUCTURE EXPANSION OR SEISMIC JOINTS.
<br />4.INSTALL EACH EXPANSION-JOINT FITTING WITH POSITION, MOUNTING, AND PISTON
<br />SETTING SELECTED IN ACCORDANCE WITH MANUFACTURER'S WRITTEN
<br />INSTRUCTIONS FOR CONDITIONS AT SPECIFIC LOCATION AT TIME OF INSTALLATION.
<br />INSTALL CONDUIT SUPPORTS TO ALLOW FOR EXPANSION MOVEMENT.
<br />Y.FLEXIBLE CONDUIT CONNECTIONS: COMPLY WITH NEMA RV 3. USE A MINIMUM OF 36
<br />INCHES AND MAXIMUM OF 72 INCHES OF FLEXIBLE CONDUIT FOR RECESSED AND
<br />SEMI-RECESSED LUMINAIRES, EQUIPMENT SUBJECT TO VIBRATION, NOISE
<br />TRANSMISSION, OR MOVEMENT; AND FOR TRANSFORMERS AND MOTORS.
<br />1.USE LFMC IN DAMP OR WET LOCATIONS, MECHANICAL ROOMS, AND ELECTRIC
<br />ROOMS. INSTALL SEPARATE GROUND CONDUCTOR ACROSS FLEXIBLE
<br />CONNECTIONS.
<br />Z.MOUNT BOXES AT HEIGHTS INDICATED ON DRAWINGS. IF MOUNTING HEIGHTS OF BOXES
<br />ARE NOT INDIVIDUALLY INDICATED, GIVE PRIORITY TO ADA REQUIREMENTS. INSTALL
<br />BOXES WITH HEIGHT MEASURED TO CENTER OF BOX UNLESS OTHERWISE INDICATED.
<br />AA.HORIZONTALLY SEPARATE BOXES MOUNTED ON OPPOSITE SIDES OF WALLS SO THEY
<br />ARE NOT IN THE SAME VERTICAL CHANNEL.
<br />BB.LOCATE BOXES SO THAT COVER OR PLATE WILL NOT SPAN DIFFERENT BUILDING
<br />FINISHES.
<br />CC.SUPPORT BOXES OF THREE GANGS OR MORE FROM MORE THAN ONE SIDE BY SPANNING
<br />TWO FRAMING MEMBERS OR MOUNTING ON BRACKETS SPECIFICALLY DESIGNED FOR
<br />THE PURPOSE.
<br />DD.FASTEN JUNCTION AND PULL BOXES TO OR SUPPORT FROM BUILDING STRUCTURE. DO
<br />NOT SUPPORT BOXES BY CONDUITS.
<br />EE.INSTALL TEMPORARY CLOSURES TO PREVENT FOREIGN MATTER FROM ENTERING
<br />RACEWAYS.
<br />FF.PROTECT STUB-UPS FROM DAMAGE WHERE CONDUITS RISE THROUGH FLOOR SLABS.
<br />GG.TIGHTEN SET SCREWS OF THREAD LESS FITTINGS WITH SUITABLE TOOLS.
<br />HH.TERMINATIONS:
<br />1.WHERE RACEWAYS ARE TERMINATED WITH THREADED HUBS, SCREW RACEWAYS OR
<br />FITTINGS TIGHTLY INTO HUB SO END BEARS AGAINST WIRE PROTECTION SHOULDER.
<br />WHERE CHASE NIPPLES ARE USED, ALIGN RACEWAYS SO COUPLING IS SQUARE TO
<br />BOX; TIGHTEN CHASE NIPPLE SO NO THREADS ARE EXPOSED.
<br />II.TELEPHONE AND SIGNAL SYSTEM RACEWAYS, 2-INCH TRADE SIZE AND SMALLER: IN
<br />ADDITION TO ABOVE REQUIREMENTS, INSTALL RACEWAYS IN MAXIMUM LENGTHS OF 150
<br />FEET AND WITH A MAXIMUM OF TWO 90-DEGREE BENDS OR EQUIVALENT. SEPARATE
<br />LENGTHS WITH PULL OR JUNCTION BOXES WHERE NECESSARY TO COMPLY WITH THESE
<br />REQUIREMENTS.
<br />JJ.STUB-UP CONNECTIONS: EXTEND CONDUITS THROUGH CONCRETE FLOOR FOR
<br />CONNECTION TO FREESTANDING EQUIPMENT. INSTALL WITH AN ADJUSTABLE TOP OR
<br />COUPLING THREADED INSIDE FOR PLUGS SET FLUSH WITH FINISHED FLOOR.
<br />KK.INSTALL HINGED-COVER ENCLOSURES AND CABINETS PLUMB. SUPPORT AT EACH
<br />CORNER.
<br />3.03 FIRESTOPPING
<br />A.INSTALL FIRESTOPPING AT PENETRATIONS OF FIRE-RATED FLOOR AND WALL
<br />ASSEMBLIES. COMPLY WITH REQUIREMENTS IN SECTION 07 8413 "PENETRATION
<br />FIRESTOPPING."
<br />3.04 PROTECTION
<br />A.PROVIDE FINAL PROTECTION AND MAINTAIN CONDITIONS THAT ENSURE COATINGS,
<br />FINISHES, AND CABINETS ARE WITHOUT DAMAGE OR DETERIORATION AT TIME OF
<br />SUBSTANTIAL COMPLETION.
<br />1.REPAIR DAMAGE TO GALVANIZED FINISHES WITH ZINC-RICH PAINT RECOMMENDED
<br />BY MANUFACTURER.
<br />2.REPAIR DAMAGE TO PVC OR PAINT FINISHES WITH MATCHING TOUCHUP COATING
<br />RECOMMENDED BY MANUFACTURER.
<br />3.05 CLEANING
<br />A.AFTER COMPLETING INSTALLATION OF EXPOSED, FACTORY-FINISHED RACEWAYS AND
<br />BOXES, INSPECT EXPOSED FINISHES AND REPAIR DAMAGED FINISHES.
<br />SECTION 26 0553
<br />IDENTIFICATION FOR ELECTRICAL SYSTEMS
<br />PART 1 - GENERAL
<br />1.01 SUMMARY
<br />A.SECTION INCLUDES:
<br />1.IDENTIFICATION FOR RACEWAYS.
<br />2.IDENTIFICATION OF POWER AND CONTROL CABLES.
<br />3.IDENTIFICATION FOR CONDUCTORS.
<br />4.EQUIPMENT IDENTIFICATION LABELS.
<br />5.MISCELLANEOUS IDENTIFICATION PRODUCTS.
<br />1.02 SUBMITTALS
<br />A.PRODUCT DATA: NONE.
<br />1.03 QUALITY ASSURANCE
<br />A.COMPLY WITH ANSI A13.1 AND IEEE C2.
<br />B.COMPLY WITH CEC.
<br />C.COMPLY WITH 29 CFR 1910.144 AND 29 CFR 1910.145.
<br />D.ADHESIVE-ATTACHED LABELING MATERIALS, INCLUDING LABEL STOCKS, LAMINATING
<br />ADHESIVES, AND INKS USED BY LABEL PRINTERS, SHALL COMPLY WITH UL 969.
<br />1.04 COORDINATION
<br />A.COORDINATE IDENTIFICATION NAMES, ABBREVIATIONS, COLORS, AND OTHER FEATURES
<br />WITH REQUIREMENTS IN OTHER SECTIONS REQUIRING IDENTIFICATION APPLICATIONS,
<br />DRAWINGS, SHOP DRAWINGS, MANUFACTURER'S WIRING DIAGRAMS, AND THE
<br />OPERATION AND MAINTENANCE MANUAL; AND WITH THOSE REQUIRED BY CODES,
<br />STANDARDS, AND 29 CFR 1910.145. USE CONSISTENT DESIGNATIONS THROUGHOUT
<br />PROJECT.
<br />B.COORDINATE INSTALLATION OF IDENTIFYING DEVICES WITH COMPLETION OF COVERING
<br />AND PAINTING OF SURFACES WHERE DEVICES ARE TO BE APPLIED.
<br />C.COORDINATE INSTALLATION OF IDENTIFYING DEVICES WITH LOCATION OF ACCESS
<br />PANELS AND DOORS.
<br />D.INSTALL IDENTIFYING DEVICES BEFORE INSTALLING ACOUSTICAL CEILINGS AND SIMILAR
<br />CONCEALMENT.
<br />PART 2 - PRODUCTS
<br />2.01 MATERIALS
<br />A.FOR FIXTURE DESCRIPTIONS IN OTHER PART 2 ARTICLES WHERE THE SUBPARAGRAPH
<br />TITLES "PRODUCTS," AND "MANUFACTURERS" INTRODUCE A LIST OF MANUFACTURERS
<br />AND THEIR PRODUCTS OR MANUFACTURERS ONLY, THE FOLLOWING REQUIREMENTS
<br />APPLY FOR PRODUCT SELECTION:
<br />1.PRODUCTS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE ONE OF THE
<br />PRODUCTS SPECIFIED IN OTHER PART 2 ARTICLES.
<br />2.MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE
<br />PRODUCTS BY THE MANUFACTURERS SPECIFIED IN OTHER PART 2 ARTICLES.
<br />3.OR EQUAL: WHERE PRODUCTS ARE SPECIFIED BY MANUFACTURERS NAME AND
<br />ACCOMPANIED BY THE TERM "OR EQUAL", COMPLY WITH PROVISIONS IN DIVISION 01.
<br />SPECIFIC PROCEDURES MUST BE FOLLOWED BEFORE USE OF AN UNNAMED
<br />PRODUCT OR MANUFACTURER.
<br />2.02 POWER RACEWAY IDENTIFICATION MATERIALS
<br />A.COLORS FOR RACEWAYS CARRYING CIRCUITS AT 600 V OR LESS:
<br />1.BLACK LETTERS ON AN ORANGE FIELD
<br />2.LEGEND: INDICATE VOLTAGE AND SYSTEM OR SERVICE TYPE.
<br />B.WRITE-ON TAGS: POLYESTER TAG, 0.015 INCH THICK, WITH CORROSION-RESISTANT
<br />GROMMET AND CABLE TIE FOR ATTACHMENT TO CONDUCTOR OR CABLE.
<br />1.MARKER FOR TAGS: PERMANENT, WATERPROOF, BLACK INK MARKER
<br />RECOMMENDED BY TAG MANUFACTURER.
<br />2.03 ARMORED AND METAL-CLAD CABLE IDENTIFICATION MATERIALS
<br />A.COMPLY WITH ANSI A13.1 FOR MINIMUM SIZE OF LETTERS FOR LEGEND AND FOR
<br />MINIMUM LENGTH OF COLOR FIELD FOR EACH RACEWAY AND CABLE SIZE.
<br />B.COLORS FOR RACEWAYS CARRYING CIRCUITS AT 600 V AND LESS:
<br />1.BLACK LETTERS ON AN ORANGE FIELD
<br />2.LEGEND: INDICATE VOLTAGE AND SYSTEM OR SERVICE TYPE.
<br />C.SELF-ADHESIVE VINYL TAPE: COLORED, HEAVY DUTY, WATERPROOF, FADE RESISTANT; 2
<br />INCHES WIDE; COMPOUNDED FOR OUTDOOR USE.
<br />2.04 POWER AND CONTROL CABLE IDENTIFICATION MATERIALS
<br />A.COMPLY WITH ANSI A13.1 FOR MINIMUM SIZE OF LETTERS FOR LEGEND AND FOR
<br />MINIMUM LENGTH OF COLOR FIELD FOR EACH RACEWAY AND CABLE SIZE.
<br />B.SELF-ADHESIVE VINYL LABELS: PREPRINTED, FLEXIBLE LABEL LAMINATED WITH A CLEAR,
<br />WEATHER- AND CHEMICAL-RESISTANT COATING AND MATCHING WRAPAROUND
<br />ADHESIVE TAPE FOR SECURING ENDS OF LEGEND LABEL.
<br />C.WRITE-ON TAGS: POLYESTER TAG, 0.015 INCH THICK, WITH CORROSION-RESISTANT
<br />GROMMET AND CABLE TIE FOR ATTACHMENT TO CONDUCTOR OR CABLE.
<br />1.MARKER FOR TAGS: MACHINE-PRINTED, PERMANENT, WATERPROOF, BLACK INK
<br />MARKER RECOMMENDED BY PRINTER MANUFACTURER.
<br />D.SNAP-AROUND LABELS: SLIT, PRETENSIONED, FLEXIBLE, PREPRINTED, COLOR-CODED
<br />ACRYLIC SLEEVE, WITH DIAMETER SIZED TO SUIT DIAMETER OF RACEWAY OR CABLE IT
<br />IDENTIFIES AND TO STAY IN PLACE BY GRIPPING ACTION.
<br />2.05 CONDUCTOR IDENTIFICATION MATERIALS
<br />A.COLOR-CODING CONDUCTOR TAPE: COLORED, SELF-ADHESIVE VINYL TAPE NOT LESS
<br />THAN 3 MILS THICK BY 1 TO 2 INCHES WIDE.
<br />B.SNAP-AROUND LABELS: SLIT, PRETENSIONED, FLEXIBLE, PREPRINTED, COLOR-CODED
<br />ACRYLIC SLEEVE, WITH DIAMETER SIZED TO SUIT DIAMETER OF RACEWAY OR CABLE IT
<br />IDENTIFIES AND TO STAY IN PLACE BY GRIPPING ACTION.
<br />C.SNAP-AROUND, COLOR-CODING BANDS: SLIT, PRETENSIONED, FLEXIBLE,
<br />SOLID-COLORED ACRYLIC SLEEVE, 2 INCHES LONG, WITH DIAMETER SIZED TO SUIT
<br />DIAMETER OF RACEWAY OR CABLE IT IDENTIFIES AND TO STAY IN PLACE BY GRIPPING
<br />ACTION.
<br />D.WRITE-ON TAGS: POLYESTER TAG, 0.015 INCH THICK, WITH CORROSION-RESISTANT
<br />GROMMET AND CABLE TIE FOR ATTACHMENT TO CONDUCTOR OR CABLE.
<br />2.06 EQUIPMENT IDENTIFICATION LABELS
<br />A.ADHESIVE FILM LABEL WITH CLEAR PROTECTIVE OVERLAY: MACHINE PRINTED, IN BLACK,
<br />BY THERMAL TRANSFER OR EQUIVALENT PROCESS. MINIMUM LETTER HEIGHT SHALL BE
<br />⅜ INCH. CLEAR PROTECTIVE OVERLAY SHALL PROVIDE A WEATHERPROOF AND
<br />UV-RESISTANT SEAL FOR LABEL.
<br />B.ENGRAVED, LAMINATED ACRYLIC OR MELAMINE LABEL: PUNCHED OR DRILLED FOR
<br />SCREW MOUNTING. BLACK LETTERS ON A LIGHT-GRAY BACKGROUND. MINIMUM LETTER
<br />HEIGHT SHALL BE ⅜ INCH.
<br />2.07 CABLE TIES
<br />A.GENERAL-PURPOSE CABLE TIES: FUNGUS INERT, SELF-EXTINGUISHING, ONE PIECE,
<br />SELF-LOCKING, TYPE 6/6 NYLON.
<br />1.MINIMUM WIDTH: 3/16 INCH.
<br />2.TENSILE STRENGTH AT 73°F, IN ACCORDANCE WITH ASTM D638: 12,000 PSI.
<br />3.TEMPERATURE RANGE: MINUS 40 TO PLUS 185°F.
<br />4.COLOR: BLACK EXCEPT WHERE USED FOR COLOR-CODING.
<br />B.PLENUM-RATED CABLE TIES: SELF-EXTINGUISHING, UV STABILIZED, ONE PIECE,
<br />SELF-LOCKING.
<br />1.MINIMUM WIDTH: 3/16 INCH.
<br />2.TENSILE STRENGTH AT 73°F IN ACCORDANCE WITH ASTM D638: 7000 PSI.
<br />3.UL 94 FLAME RATING: 94V-0.
<br />4.TEMPERATURE RANGE: MINUS 50 TO PLUS 284°F.
<br />5.COLOR: BLACK.
<br />PART 3 - EXECUTION
<br />3.01 INSTALLATION
<br />A.VERIFY IDENTITY OF EACH ITEM BEFORE INSTALLING IDENTIFICATION PRODUCTS.
<br />B.LOCATION: INSTALL IDENTIFICATION MATERIALS AND DEVICES AT LOCATIONS FOR MOST
<br />CONVENIENT VIEWING WITHOUT INTERFERENCE WITH OPERATION AND MAINTENANCE
<br />OF EQUIPMENT.
<br />C.APPLY IDENTIFICATION DEVICES TO SURFACES THAT REQUIRE FINISH AFTER
<br />COMPLETING FINISH WORK.
<br />D.SECURE NAMEPLATES TO EQUIPMENT FRONTS USING SCREWS, RIVETS OR ADHESIVE.
<br />SECURE NAMEPLATE TO INSIDE FACE OF RECESSED PANEL BOARD DOORS IN FINISHED
<br />LOCATIONS. USE WEATHERPROOF ADHESIVE FOR OUTDOOR INSTALLATION. DO NOT USE
<br />TAPE FOR NAMEPLATES OR LEGEND PLATES.
<br />E.LETTERING, COLORS, AND GRAPHICS: COORDINATE NAMES, ABBREVIATIONS, COLORS,
<br />AND OTHER DESIGNATIONS WITH CORRESPONDING DESIGNATIONS. USE CONSISTENT
<br />DESIGNATIONS THROUGHOUT PROJECT.
<br />F.SELF-ADHESIVE IDENTIFICATION PRODUCTS: CLEAN SURFACES BEFORE APPLYING.
<br />G.INSTALL NAMEPLATES AND LABELS PARALLEL TO EQUIPMENT LINES.
<br />H.JUNCTION BOXES FOR FIRE ALARM SYSTEM SHALL BE RED.
<br />I.CAUTION LABELS FOR INDOOR BOXES AND ENCLOSURES FOR POWER AND LIGHTING:
<br />INSTALL LABELS IDENTIFYING SYSTEM VOLTAGE WITH BLACK LETTERS ON ORANGE
<br />BACKGROUND. INSTALL ON EXTERIOR OF DOOR OR COVER.
<br />J.CIRCUIT IDENTIFICATION LABELS ON RECEPTACLES:
<br />1.PUBLIC VIEW AREAS (LOBBIES, ATRIUM, PUBLIC CONFERENCE AND MEETING ROOMS,
<br />CLASSROOMS, ETC.): PERMANENTLY ENGRAVE CIRCUIT INFORMATION ON BACK OF
<br />PLATE.
<br />2.OTHER AREAS: ENGRAVED CIRCUIT INFORMATION ON FRONT OF PLATE.
<br />K.CONDUIT INSTALLED BELOW GRADE SHALL HAVE UNDERGROUND HAZARD TAPE
<br />(NON-ADHESIVE) INSTALLED A MINIMUM OF 12 INCHES ABOVE THE CONDUIT OR TOP
<br />LAYER OF CONDUITS IN A DUCT BANK. THE TAPE SHALL BE 6 INCHES WIDE AND 4
<br />MILLIMETERS THICK YELLOW POLYETHYLENE FOR LOW VOLTAGE CONDUITS AND RED
<br />FOR MEDIUM VOLTAGE CONDUITS. THE TAPE SHALL BE MARKED “CAUTION BURIED
<br />ELECTRIC LINE” FOR LOW VOLTAGE AND “DANGER HIGH VOLTAGE LINE” FOR MEDIUM
<br />VOLTAGE. TRACER WIRE SHALL BE USED FOR PVC CONDUITS AND NON-METALLIC TAPE
<br />FOR METALLIC CONDUITS. THE TAPE SHALL BE INSTALLED THE ENTIRE LENGTH OF
<br />CONDUIT BELOW GRADE.
<br />L.COLOR-CODING OF SECONDARY PHASE CONDUCTORS: USE THE FOLLOWING COLORS
<br />FOR SERVICE FEEDER AND BRANCH-CIRCUIT PHASE CONDUCTORS. WIRING SHALL BE
<br />COLOR CODED, SEE SECTION 26 0519, “LOW VOLTAGE ELECTRICAL POWER
<br />CONDUCTORS AND CABLES”. LOW VOLTAGE WIRE MARKERS SHALL BE ADHERING,
<br />PREPRINTED, SELF-LAMINATING VINYL WRAP-AROUND STRIPS. WIRE SHALL BE MARKED
<br />WITH OPPOSITE END TERMINATION AND SHALL INCLUDE PANEL SOURCE AND CIRCUIT
<br />NUMBERS. PHASING SHALL BE INDICATED BY COLORED WIRE OR TAPE. FOR OTHER
<br />SYSTEM VOLTAGES CONSULT THE EEOR:
<br />1.208/120-V CONDUCTORS:
<br />a.PHASE A: BLACK.
<br />b.PHASE B: RED.
<br />c.PHASE C: BLUE.
<br />d.SWITCH LEG: PINK.
<br />e.SWITCH TRAVELER: SAME AS HOT LEG.
<br />2.480/277-V CONDUCTORS:
<br />a.PHASE A: BROWN.
<br />b.PHASE B: ORANGE.
<br />c.PHASE C: YELLOW.
<br />d.SWITCH LEG: PURPLE
<br />e.SWITCH TRAVELER: SAME AS HOT LEG.
<br />3.NEUTRAL AND GROUND CONDUCTORS:
<br />a.NEUTRAL: WHITE.
<br />b.GROUND: GREEN.
<br />4.FACTORY APPLY COLOR THE ENTIRE LENGTH OF CONDUCTORS, EXCEPT THE
<br />FOLLOWING FIELD-APPLIED, COLOR-CODING METHODS MAY BE USED INSTEAD OF
<br />FACTORY-CODED WIRE FOR SIZES LARGER THAN NO. 10 AWG:
<br />a.COLORED, PRESSURE-SENSITIVE PLASTIC TAPE IN HALF-LAPPED TURNS FOR A
<br />DISTANCE OF 6 INCHES FROM TERMINAL POINTS AND IN BOXES WHERE SPLICES
<br />OR TAPS ARE MADE. APPLY LAST TWO TURNS OF TAPE WITH NO TENSION TO
<br />PREVENT POSSIBLE UNWINDING. USE 1-INCH-WIDE TAPE IN COLORS SPECIFIED.
<br />ADJUST TAPE BANDS TO AVOID OBSCURING CABLE IDENTIFICATION MARKINGS.
<br />b.COLORED CABLE TIES APPLIED IN GROUPS OF THREE TIES OF SPECIFIED COLOR
<br />TO EACH WIRE AT EACH TERMINAL OR SPLICE POINT STARTING 3 INCHES FROM
<br />THE TERMINAL AND SPACED 3 INCHES APART. APPLY WITH A SPECIAL TOOL OR
<br />PLIERS, TIGHTEN TO A SNUG FIT, AND CUT OFF EXCESS LENGTH.
<br />M.POWER-CIRCUIT IDENTIFICATION: BRASS TAGS WITH WRAPAROUND MARKER BANDS
<br />FOR CABLES, FEEDERS, AND POWER CIRCUITS IN VAULTS, PULL AND JUNCTION BOXES,
<br />MANHOLES, AND SWITCHBOARD ROOMS.
<br />1.LEGEND: ¼-INCH STEEL LETTER AND NUMBER STAMPING OR EMBOSSING WITH
<br />LEGEND CORRESPONDING TO INDICATE CIRCUIT DESIGNATIONS.
<br />2.TAG FASTENERS: NYLON CABLE TIES.
<br />3.BAND FASTENERS: INTEGRAL EARS.
<br />N.APPLY IDENTIFICATION TO CONDUCTORS AS FOLLOWS:
<br />1.MULTIPLE POWER OR LIGHTING CIRCUITS IN THE SAME ENCLOSURE: IDENTIFY EACH
<br />CONDUCTOR WITH SOURCE, VOLTAGE, CIRCUIT NUMBER, AND PHASE. USE
<br />COLOR-CODING TO IDENTIFY CIRCUITS' VOLTAGE AND PHASE.
<br />2.MULTIPLE CONTROL AND COMMUNICATION CIRCUITS IN THE SAME ENCLOSURE:
<br />IDENTIFY EACH CONDUCTOR BY ITS SYSTEM AND CIRCUIT DESIGNATION. USE A
<br />CONSISTENT SYSTEM OF TAGS, COLOR-CODING, OR CABLE MARKING TAPE.
<br />O.LOW VOLTAGE IDENTIFICATION
<br />1.EQUIPMENT NAMEPLATES SHALL BE ENGRAVED THREE-LAYER LAMINATED PLASTIC
<br />WITH WHITE BACKGROUND AND BLACK LETTERS. LETTERS SHALL BE ¼” MINIMUM
<br />SIZE. IDENTIFICATIONS SHALL MATCH PLAN DESIGNATIONS AND BASED UPON THE
<br />OWNER'S NUMBERING SCHEME.
<br />2.LEGEND PLATES FOR CONTROL PANELS AND INDICATORS SHALL BE PROVIDED ON
<br />DISCONNECT AND SAFETY SWITCHES AND INDICATING LIGHTS. THE PLATES SHALL
<br />BE DIE-STAMPED METAL WITH MOUNTING HOLE AND POSITIONING KEY.
<br />3.FOR PANEL BOARD DIRECTORIES PROVIDE THE FOLLOWING:
<br />a.PROVIDE TYPEWRITTEN DIRECTORIES ARRANGED IN NUMERICAL ORDER
<br />SHOWING NUMBER OF ROOM IN WHICH EACH DEVICE IS LOCATED.
<br />b.VERIFY ROOM NUMBERS TO BE USED WITH THE OWNER'S REPRESENTATIVE
<br />PRIOR TO TYPING, SINCE ROOM NUMBERS WILL MOST LIKELY NOT BE THOSE
<br />SHOWN ON THE DRAWINGS.
<br />c.MOUNT DIRECTORIES UNDER A CLEAR PLASTIC COVER INSIDE EACH
<br />PANELBOARD DOOR.
<br />4.THE FOLLOWING LOW VOLTAGE EQUIPMENT NUMBERING SCHEME SHALL BE
<br />FOLLOWED:
<br />USE NUMBERING CONVENTION AS FOLLOWS:
<br />a.FIRST LETTER OR NUMBER = FLOOR DESIGNATION; B = BASEMENT, 1, 2, 3, ETC.
<br />(B).
<br />b.SUBSEQUENT LOWER CASE LETTER = PANEL NUMBER ON EACH FLOOR; A, B, C,
<br />ETC. (BA).
<br />1)EXAMPLE: EMERGENCY 277/480V DISTRIBUTION PANELBOARD INSTALLED IN
<br />BASEMENT IS “EHDP-B”.
<br />2)EXAMPLE: SECOND 480/277VPANELBOARD INSTALLED ON THIRD FLOOR FOR
<br />LIGHTING IS “HLP-3B”.
<br />P.TELECOMMUNICATION, SIGNAL ALARM AND CONTROL WIRING:
<br />1.CONDUCTORS TERMINATED OR SPLICED SHALL BE LABELED AT EACH END WITH
<br />TAPE MARKERS.
<br />SECTION 26 0943
<br />DIGITAL LIGHTING CONTROLS
<br />PART 1 - GENERAL
<br />1.01 SUMMARY
<br />A.SECTION INCLUDES:
<br />1.DIGITAL LIGHTING CONTROLS
<br />2.RELAY PANELS
<br />3.EMERGENCY LIGHTING CONTROL
<br />B.CONTROL INTENT - CONTROL INTENT INCLUDES, BUT IS NOT LIMITED TO:
<br />1.DEFAULTS AND INITIAL CALIBRATION SETTINGS FOR SUCH ITEMS AS TIME DELAY,
<br />SENSITIVITY, FADE RATES, ETC.
<br />2.INITIAL SENSOR AND SWITCHING ZONES
<br />3.INITIAL TIME SWITCH SETTINGS
<br />4.EMERGENCY LIGHTING CONTROL
<br />1.02 SYSTEM DESCRIPTION & OPERATION
<br />A.THE LIGHTING CONTROL AND AUTOMATION SYSTEM AS DEFINED UNDER THIS SECTION
<br />COVERS THE FOLLOWING EQUIPMENT:
<br />1.DIGITAL OCCUPANCY SENSORS - SELF-CONFIGURING, DIGITALLY ADDRESSABLE, AND
<br />CALIBRATED OCCUPANCY SENSORS WITH LCD DISPLAY AND TWO-WAY ACTIVE
<br />INFRARED (IR) COMMUNICATIONS.
<br />2.DIGITAL SWITCHES - SELF-CONFIGURING, DIGITALLY ADDRESSABLE PUSHBUTTON
<br />ON/OFF, DIMMING, AND SCENE SWITCHES WITH TWO-WAY ACTIVE INFRARED (IR)
<br />COMMUNICATIONS.
<br />3.DIGITAL DAYLIGHTING SENSORS - SINGLE-ZONE CLOSED LOOP, MULTI-ZONE OPEN
<br />LOOP AND SINGLE-ZONE DUAL-LOOP DAYLIGHTING SENSORS WITH TWO-WAY ACTIVE
<br />INFRARED (IR) COMMUNICATIONS CAN PROVIDE SWITCHING, BI-LEVEL, TRI-LEVEL, OR
<br />DIMMING CONTROL FOR DAYLIGHT HARVESTING.
<br />4.DIGITAL ROOM CONTROLLERS - SELF-CONFIGURING, DIGITALLY ADDRESSABLE ONE,
<br />TWO, OR THREE RELAY PLENUM-RATED CONTROLLERS FOR ON/OFF CONTROL.
<br />SELECTED MODELS INCLUDE 0-10 VOLT OR LINE VOLTAGE FORWARD PHASE
<br />CONTROL DIMMING OUTPUTS AND INTEGRAL CURRENT MONITORING CAPABILITIES.
<br />5.CONFIGURATION TOOLS - HANDHELD REMOTE FOR ROOM CONFIGURATION AND
<br />RELAY PANEL PROGRAMMING PROVIDES TWO WAY INFRARED (IR) COMMUNICATIONS
<br />TO DIGITAL DEVICES AND ALLOWS COMPLETE CONFIGURATION AND
<br />RECONFIGURATION OF THE DEVICE / ROOM FROM UP TO 30 FEET AWAY. UNIT TO
<br />HAVE ORGANIC LED DISPLAY, SIMPLE PUSHBUTTON INTERFACE, AND ALLOW
<br />BI-DIRECTIONAL COMMUNICATION OF ROOM VARIABLES AND OCCUPANCY SENSOR
<br />SETTINGS. COMPUTER SOFTWARE ALSO CUSTOMIZES ROOM SETTINGS.
<br />6.EMERGENCY LIGHTING CONTROL UNIT (ELCU) - ALLOWS A STANDARD LIGHTING
<br />CONTROL DEVICE TO CONTROL EMERGENCY LIGHTING IN CONJUNCTION WITH
<br />NORMAL LIGHTING IN ANY AREA WITHIN A BUILDING.
<br />1.03 LIGHTING CONTROL APPLICATIONS
<br />A.UNLESS RELEVANT PROVISIONS OF THE APPLICABLE LOCAL ENERGY CODES ARE MORE
<br />STRINGENT, PROVIDE A MINIMUM APPLICATION OF LIGHTING CONTROLS AS FOLLOWS:
<br />1.SPACE CONTROL REQUIREMENTS - PROVIDE OCCUPANCY (VACANCY) SENSORS WITH
<br />MANUAL- OR PARTIAL-ON FUNCTIONALITY IN SPACES EXCEPT TOILET ROOMS,
<br />STOREROOMS OR OTHER APPLICATIONS WHERE HANDS-FREE OPERATION IS
<br />DESIRABLE AND AUTOMATIC-ON OCCUPANCY SENSORS ARE MORE APPROPRIATE.
<br />PROVIDE MANUAL-ON OCCUPANCY (VACANCY) SENSORS FOR ANY ENCLOSED
<br />OFFICE, CONFERENCE ROOM, MEETING ROOM, OPEN PLAN SYSTEM, AND TRAINING
<br />ROOM. FOR SPACES WITH MULTIPLE OCCUPANTS, OR WHERE LINE-OF-SIGHT MAY BE
<br />OBSCURED, PROVIDE CEILING- OR CORNER-MOUNTED SENSORS AND MANUAL-ON
<br />SWITCHES.
<br />2.BI-LEVEL LIGHTING - PROVIDE MULTI-LEVEL CONTROLS IN SPACES EXCEPT TOILET
<br />ROOMS, STOREROOMS, LIBRARY STACKS, OR APPLICATIONS WHERE VARIABLE
<br />DIMMING IS USED.
<br />3.DAY-LIGHTED AREAS - PROVIDE DAYLIGHT-RESPONSIVE AUTOMATIC CONTROL IN
<br />SPACES CONDITIONED OR UNCONDITIONED WHERE DAYLIGHT CONTRIBUTION IS
<br />AVAILABLE AS DEFINED BY RELEVANT LOCAL BUILDING ENERGY CODE:
<br />a.LUMINAIRES WITHIN CODE-DEFINED DAYLIGHT ZONES SHALL BE CONTROLLED
<br />SEPARATELY FROM LUMINAIRES OUTSIDE OF DAYLIGHT ZONES.
<br />b.DAYTIME SETPOINTS FOR TOTAL AMBIENT ILLUMINATION (COMBINED DAYLIGHT
<br />AND ELECTRIC LIGHT) LEVELS THAT INITIATE DIMMING SHALL BE PROGRAMMED IN
<br />COMPLIANCE WITH RELEVANT LOCAL BUILDING ENERGY CODES.
<br />c.MULTIPLE-LEVELED SWITCHED DAYLIGHT HARVESTING CONTROLS MAY BE USED
<br />FOR AREAS MARKED ON DRAWINGS.
<br />d.PROVIDE SMOOTH AND CONTINUOUS DAYLIGHT DIMMING FOR AREAS MARKED ON
<br />DRAWINGS. DAYLIGHTING CONTROL SYSTEM MAY BE DESIGNED TO TURN OFF
<br />ELECTRIC LIGHTING WHEN DAYLIGHT IS AT OR ABOVE REQUIRED LIGHTING
<br />LEVELS, ONLY IF SYSTEM FUNCTIONS TO TURN LAMPS BACK ON AT DIMMED
<br />LEVEL, INSTEAD OF TURNING FULL-ON PRIOR TO DIMMING.
<br />1.04 SUBMITTALS
<br />A.SUBMITTALS PACKAGE: SUBMIT THE SHOP DRAWINGS, AND THE PRODUCT DATA
<br />SPECIFIED BELOW AT THE SAME TIME AS A PACKAGE.
<br />B.SHOP DRAWINGS: SHOW INSTALLATION DETAILS FOR OCCUPANCY AND LIGHT-LEVEL
<br />SENSORS.
<br />4.LIGHTING PLAN SHOWING LOCATION, ORIENTATION, AND COVERAGE AREA OF EACH
<br />SENSOR.
<br />5.INTERCONNECTION DIAGRAMS SHOWING FIELD-INSTALLED WIRING.
<br />1.05 QUALITY ASSURANCE
<br />A.MANUFACTURER: MINIMUM 10 YEARS' EXPERIENCE IN MANUFACTURE OF LIGHTING
<br />CONTROLS.
<br />1.06 WARRANTY
<br />A.PROVIDE A FIVE YEAR LIMITED MANUFACTURER'S WARRANTY ON ROOM CONTROL
<br />DEVICES AND PANELS.
<br />PART 2 - PRODUCTS
<br />2.01 MANUFACTURERS
<br />A.IN OTHER PART 2 ARTICLES THE FOLLOWING REQUIREMENTS APPLY TO PRODUCT
<br />SELECTION:
<br />1.BASIS OF DESIGN PRODUCT: ACUITY N-LIGHT DIGITAL LIGHTING MANAGEMENT (DLM).
<br />SUBJECT TO COMPLIANCE WITH SPECIFIED REQUIREMENTS OF THIS SECTION, OR
<br />EQUAL, PRIOR OWNER'S APPROVAL IS RECOMMENDED.
<br />2.OR EQUAL: WHERE PRODUCTS ARE SPECIFIED BY MANUFACTURERS NAME AND
<br />ACCOMPANIED BY THE TERM "OR EQUAL", COMPLY WITH PROVISIONS IN DIVISION 01
<br />SECTION “PRODUCT OPTIONS AND SUBSTITUTIONS”. SPECIFIC PROCEDURES MUST
<br />BE FOLLOWED BEFORE USE OF AN UNNAMED PRODUCT OR MANUFACTURER.
<br />2.02 DIGITAL LIGHTING CONTROLS
<br />A.FURNISH THE COMPANY'S SYSTEM WHICH ACCOMMODATES THE SQUARE-FOOTAGE
<br />COVERAGE REQUIREMENTS FOR EACH AREA CONTROLLED, UTILIZING ROOM
<br />CONTROLLERS, DIGITAL OCCUPANCY SENSORS, SWITCHES, DAYLIGHTING SENSORS AND
<br />ACCESSORIES WHICH SUIT THE LIGHTING AND ELECTRICAL SYSTEM PARAMETERS.
<br />2.03 DIGITAL WALL SWITCH OCCUPANCY SENSORS
<br />A.WALL BOX MOUNTED PASSIVE INFRARED PIR OR DUAL TECHNOLOGY (PASSIVE INFRARED
<br />AND ULTRASONIC) DIGITAL OCCUPANCY SENSOR WITH 1 OR 2 SWITCH BUTTONS.
<br />B.DIGITAL OCCUPANCY SENSORS SHALL PROVIDE SCROLLING LCD DISPLAY FOR DIGITAL
<br />CALIBRATION AND ELECTRONIC DOCUMENTATION. FEATURES INCLUDE THE FOLLOWING:
<br />1.DIGITAL CALIBRATION AND PUSHBUTTON CONFIGURATION FOR THE FOLLOWING
<br />VARIABLES:
<br />a.SENSITIVITY - 0-100% IN 10% INCREMENTS
<br />b.TIME DELAY - 1-30 MINUTES IN 1 MINUTE INCREMENTS, FOR LED LIGHT FIXTURES
<br />SET FOR 2 MINUTES UNLESS OTHERWISE DIRECTED.
<br />c.TEST MODE - FIVE SECOND TIME DELAY
<br />d.DETECTION TECHNOLOGY - PIR, DUAL TECHNOLOGY ACTIVATION AND/OR
<br />RE-ACTIVATION.
<br />e.WALK-THROUGH MODE
<br />f.LOAD PARAMETERS INCLUDING AUTO/MANUAL-ON, BLINK WARNING, AND
<br />DAYLIGHT ENABLE/DISABLE WHEN PHOTOSENSORS ARE INCLUDED IN THE DLM
<br />LOCAL NETWORK.
<br />2.PROGRAMMABLE CONTROL FUNCTIONALITY INCLUDING:
<br />a.EACH SENSOR MAY BE PROGRAMMED TO CONTROL SPECIFIC LOADS WITHIN A
<br />LOCAL NETWORK.
<br />b.SENSOR SHALL BE CAPABLE OF ACTIVATING ONE OF 16 USER-DEFINABLE
<br />LIGHTING SCENES.
<br />c.ADJUSTABLE RETRIGGER TIME PERIOD FOR MANUAL-ON LOADS. LOAD WILL
<br />RETRIGGER (TURN ON) AUTOMATICALLY DURING THE CONFIGURABLE PERIOD OF
<br />TIME (DEFAULT 10 SECONDS) AFTER TURNING OFF.
<br />d.ON DUAL TECHNOLOGY SENSORS, INDEPENDENTLY CONFIGURABLE TRIGGER
<br />MODES ARE AVAILABLE FOR BOTH NORMAL (NH) AND AFTER-HOURS (AH) TIME
<br />PERIODS. THE RETRIGGER MODE CAN BE PROGRAMMED TO USE THE FOLLOWING
<br />TECHNOLOGIES:
<br />1)ULTRASONIC AND PASSIVE INFRARED
<br />2)ULTRASONIC OR PASSIVE INFRARED
<br />3)ULTRASONIC ONLY
<br />4)PASSIVE INFRARED ONLY
<br />3.INDEPENDENTLY CONFIGURABLE SENSITIVITY SETTINGS FOR PASSIVE INFRARED
<br />AND ULTRASONIC TECHNOLOGIES (ON DUAL TECHNOLOGY SENSORS) FOR BOTH
<br />NORMAL (NH) AND AFTER HOUR (AH) TIME PERIODS.
<br />4.TWO RJ-45 PORTS FOR CONNECTION TO DLM LOCAL NETWORK.
<br />5.TWO-WAY INFRARED (IR) TRANSCEIVER TO ALLOW REMOTE PROGRAMMING
<br />THROUGH HANDHELD CONFIGURATION TOOL AND CONTROL BY REMOTE PERSONAL
<br />CONTROLS.
<br />6.DEVICE STATUS LEDS INCLUDING:
<br />a.PIR DETECTION
<br />b.ULTRASONIC DETECTION
<br />c.CONFIGURATION MODE
<br />d.LOAD BINDING
<br />7.ASSIGNMENT OF OCCUPANCY SENSOR TO A SPECIFIC LOAD WITHIN THE ROOM
<br />WITHOUT WIRING OR SPECIAL TOOLS.
<br />8.ASSIGNMENT OF LOCAL BUTTONS TO SPECIFIC LOADS WITHIN THE ROOM WITHOUT
<br />WIRING OR SPECIAL TOOLS
<br />9.MANUAL OVERRIDE OF CONTROLLED LOADS.
<br />10.DIGITAL PARAMETER DATA PROGRAMMED INTO AN INDIVIDUAL WALL SWITCH
<br />SENSOR SHALL BE RETAINED IN NON-VOLATILE FLASH MEMORY WITHIN THE WALL
<br />SWITCH SENSOR ITSELF. MEMORY SHALL HAVE AN EXPECTED LIFE OF NO LESS THAN
<br />10 YEARS.
<br />C.PROHIBITED: UNITS WITH DIP SWITCHES OR POTENTIOMETERS FOR FIELD SETTINGS.
<br />D.MULTIPLE OCCUPANCY SENSORS MAY BE INSTALLED IN A ROOM BY SIMPLY CONNECTING
<br />THEM TO THE FREE TOPOLOGY DLM LOCAL NETWORK. NO ADDITIONAL CONFIGURATION
<br />WILL BE REQUIRED.
<br />E.TWO-BUTTON WALL SWITCH OCCUPANCY SENSORS, WHEN CONNECTED TO A SINGLE
<br />RELAY DIMMING ROOM CONTROLLER, SHALL OPERATE IN THE FOLLOWING SEQUENCE AS
<br />A FACTORY DEFAULT:
<br />1.LEFT BUTTON
<br />a.PRESS AND RELEASE - TURN LOAD ON
<br />b.PRESS AND HOLD - RAISE DIMMING LOAD
<br />2.RIGHT BUTTON
<br />a.PRESS AND RELEASE - TURN LOAD OFF
<br />b.PRESS AND HOLD - LOWER DIMMING LOAD
<br />G.LOW VOLTAGE MOMENTARY PUSHBUTTONS SHALL INCLUDE THE FOLLOWING FEATURES:
<br />1.LOAD/SCENE STATUS LED ON EACH SWITCH BUTTON WITH THE FOLLOWING
<br />CHARACTERISTICS:
<br />a.BI-LEVEL LED
<br />b.DIM LOCATOR LEVEL INDICATES POWER TO SWITCH
<br />c.BRIGHT STATUS LEVEL INDICATES THAT LOAD OR SCENE IS ACTIVE
<br />2.THE FOLLOWING BUTTON ATTRIBUTES MAY BE CHANGED OR SELECTED USING A
<br />WIRELESS CONFIGURATION TOOL:
<br />a.LOAD AND SCENE BUTTON FUNCTION MAY BE RECONFIGURED FOR INDIVIDUAL
<br />BUTTONS (FROM LOAD TO SCENE, AND VICE VERSA).
<br />b.INDIVIDUAL BUTTON FUNCTION MAY BE CONFIGURED TO TOGGLE, ON ONLY OR
<br />OFF ONLY.
<br />c.INDIVIDUAL SCENES MAY BE LOCKED TO PREVENT UNAUTHORIZED CHANGE.
<br />d.FADE UP AND FADE DOWN TIMES FOR INDIVIDUAL SCENES MAY BE ADJUSTED
<br />FROM 0 SECONDS TO 18 HOURS.
<br />e.RAMP RATE MAY BE ADJUSTED FOR EACH DIMMER SWITCH.
<br />f.SWITCH BUTTONS MAY BE BOUND TO ANY LOAD ON A ROOM CONTROLLER AND
<br />ARE NOT LOAD TYPE DEPENDENT; EACH BUTTON MAY BE BOUND TO MULTIPLE
<br />LOADS.
<br />H.PROVIDE WHITE WALL PLATES UNLESS DIRECTED OTHERWISE.
<br />2.04 DIGITAL WALL OR CEILING MOUNTED OCCUPANCY SENSOR
<br />A.WALL OR CEILING MOUNTED (TO SUIT INSTALLATION) PASSIVE INFRARED (PIR),
<br />ULTRASONIC OR DUAL TECHNOLOGY DIGITAL (PASSIVE INFRARED AND ULTRASONIC)
<br />OCCUPANCY SENSOR.
<br />B.DIGITAL OCCUPANCY SENSORS SHALL PROVIDE GRAPHIC LCD DISPLAY FOR DIGITAL
<br />CALIBRATION AND ELECTRONIC DOCUMENTATION. FEATURES INCLUDE THE FOLLOWING:
<br />1.DIGITAL CALIBRATION AND PUSHBUTTON CONFIGURATION FOR THE FOLLOWING
<br />VARIABLES:
<br />a.SENSITIVITY - 0-100% IN 10% INCREMENTS
<br />b.TIME DELAY - 1-30 MINUTES IN 1 MINUTE INCREMENTS, FOR LED LIGHT FIXTURES
<br />SET FOR 2 MINUTES UNLESS OTHERWISE DIRECTED.
<br />c.TEST MODE - FIVE SECOND TIME DELAY
<br />d.DETECTION TECHNOLOGY - PIR, ULTRASONIC OR DUAL TECHNOLOGY ACTIVATION
<br />AND/OR RE-ACTIVATION.
<br />e.WALK-THROUGH MODE
<br />f.LOAD PARAMETERS INCLUDING AUTO/MANUAL-ON, BLINK WARNING, AND
<br />DAYLIGHT ENABLE/DISABLE WHEN PHOTOSENSORS ARE INCLUDED IN THE DLM
<br />LOCAL NETWORK.
<br />2.PROGRAMMABLE CONTROL FUNCTIONALITY INCLUDING:
<br />a.EACH SENSOR MAY BE PROGRAMMED TO CONTROL SPECIFIC LOADS WITHIN A
<br />LOCAL NETWORK.
<br />b.SENSOR SHALL BE CAPABLE OF ACTIVATING ONE OF 16 USER-DEFINABLE
<br />LIGHTING SCENES.
<br />c.ADJUSTABLE RETRIGGER TIME PERIOD FOR MANUAL-ON LOADS. LOAD WILL
<br />RETRIGGER (TURN ON) AUTOMATICALLY WITHIN A CONFIGURABLE PERIOD OF
<br />TIME (DEFAULT 10 SECONDS) AFTER TURNING OFF.
<br />d.ON DUAL TECHNOLOGY SENSORS, INDEPENDENTLY CONFIGURABLE TRIGGER
<br />MODES ARE AVAILABLE FOR BOTH NORMAL (NH) AND AFTER-HOURS (AH) TIME
<br />PERIODS. THE RETRIGGER MODE CAN BE PROGRAMMED TO USE THE
<br />FOLLOWING TECHNOLOGIES:
<br />1)ULTRASONIC AND PASSIVE INFRARED
<br />2)ULTRASONIC OR PASSIVE INFRARED
<br />3)ULTRASONIC ONLY
<br />4)PASSIVE INFRARED ONLY
<br />3.INDEPENDENTLY CONFIGURABLE SENSITIVITY SETTINGS FOR PASSIVE INFRARED
<br />AND ULTRASONIC TECHNOLOGIES (ON DUAL TECHNOLOGY SENSORS) FOR BOTH
<br />NORMAL (NH) AND AFTER HOUR (AH) TIME PERIODS.
<br />4.ONE OR TWO RJ-45 PORT(S) FOR CONNECTION TO DLM LOCAL NETWORK.
<br />5.TWO-WAY INFRARED (IR) TRANSCEIVER TO ALLOW REMOTE PROGRAMMING
<br />THROUGH HANDHELD COMMISSIONING TOOL AND CONTROL BY REMOTE PERSONAL
<br />CONTROLS.
<br />6.DEVICE STATUS LEDS, WHICH MAY BE DISABLED FOR SELECTED APPLICATIONS,
<br />INCLUDING:
<br />a.PIR DETECTION
<br />b.ULTRASONIC DETECTION
<br />c.CONFIGURATION MODE
<br />d.LOAD BINDING
<br />7.ASSIGNMENT OF OCCUPANCY SENSOR TO A SPECIFIC LOAD WITHIN THE ROOM
<br />WITHOUT WIRING OR SPECIAL TOOLS.
<br />8.MANUAL OVERRIDE OF CONTROLLED LOADS.
<br />9.DIGITAL PARAMETER DATA PROGRAMMED INTO AN INDIVIDUAL OCCUPANCY SENSOR
<br />SHALL BE RETAINED IN NON-VOLATILE FLASH MEMORY WITHIN THE SENSOR ITSELF.
<br />MEMORY SHALL HAVE AN EXPECTED LIFE OF NO LESS THAN 10 YEARS.
<br />C.PROHIBITED: UNITS WITH DIP SWITCHES OR POTENTIOMETERS FOR FIELD SETTINGS.
<br />D.MULTIPLE OCCUPANCY SENSORS MAY BE INSTALLED IN A ROOM BY SIMPLY CONNECTING
<br />THEM TO THE FREE TOPOLOGY DLM LOCAL NETWORK. NO ADDITIONAL CONFIGURATION
<br />WILL BE REQUIRED.
<br />2.05 DIGITAL WALL SWITCHES
<br />A.LOW VOLTAGE MOMENTARY PUSHBUTTON SWITCHES IN 1, 2, 3, 4, 5, AND 8 BUTTON
<br />CONFIGURATION. WALL SWITCHES SHALL INCLUDE THE FOLLOWING FEATURES:
<br />1.TWO-WAY INFRARED (IR) TRANSCEIVER FOR USE WITH PERSONAL AND
<br />CONFIGURATION REMOTE CONTROLS.
<br />2.REMOVABLE BUTTONS FOR FIELD REPLACEMENT WITH ENGRAVED BUTTONS AND/OR
<br />ALTERNATE COLOR BUTTONS. BUTTON REPLACEMENT MAY BE COMPLETED WITHOUT
<br />REMOVING THE SWITCH FROM THE WALL.
<br />3.CONFIGURATION LED ON EACH SWITCH THAT BLINKS TO INDICATE DATA
<br />TRANSMISSION.
<br />4. LOAD/SCENE STATUS LED ON EACH SWITCH BUTTON WITH THE FOLLOWING
<br />CHARACTERISTICS:
<br />a.BI-LEVEL LED
<br />b.DIM LOCATOR LEVEL INDICATES POWER TO SWITCH
<br />c.BRIGHT STATUS LEVEL INDICATES THAT LOAD OR SCENE IS ACTIVE
<br />5.DIMMING SWITCHES SHALL INCLUDE SEVEN BI-LEVEL LEDS TO INDICATE LOAD
<br />LEVELS USING 14 STEPS.
<br />6.PROGRAMMABLE CONTROL FUNCTIONALITY INCLUDING:
<br />a.BUTTON PRIORITY MAY BE CONFIGURED TO ANY BACNET PRIORITY LEVEL, FROM
<br />1-16, CORRESPONDING TO NETWORKED OPERATION ALLOWING LOCAL ACTIONS
<br />TO USE LIFE SAFETY PRIORITY
<br />b.SCENE PATTERNS MAY BE SAVED TO ANY BUTTON OTHER THAN DIMMING
<br />ROCKERS. ONCE SET, BUTTONS MAY BE DIGITALLY LOCKED TO PREVENT
<br />OVERWRITING OF THE PRESET LEVELS.
<br />7.DIGITAL PARAMETER DATA PROGRAMMED INTO AN INDIVIDUAL WALL SWITCH SHALL
<br />BE RETAINED IN NON-VOLATILE FLASH MEMORY WITHIN THE WALL SWITCH ITSELF.
<br />MEMORY SHALL HAVE AN EXPECTED LIFE OF NO LESS THAN 10 YEARS.
<br />C.TWO RJ-45 PORTS FOR CONNECTION TO DLM LOCAL NETWORK.
<br />D.MULTIPLE DIGITAL WALL SWITCHES MAY BE INSTALLED IN A ROOM BY SIMPLY
<br />CONNECTING THEM TO THE FREE TOPOLOGY DLM LOCAL NETWORK. NO ADDITIONAL
<br />CONFIGURATION SHALL BE REQUIRED TO ACHIEVE MULTI-WAY SWITCHING.
<br />E.THE FOLLOWING SWITCH ATTRIBUTES MAY BE CHANGED OR SELECTED USING A
<br />WIRELESS CONFIGURATION TOOL:
<br />1.LOAD AND SCENE BUTTON FUNCTION MAY BE RECONFIGURED FOR INDIVIDUAL
<br />BUTTONS (FROM LOAD TO SCENE, AND VICE VERSA).
<br />2.INDIVIDUAL BUTTON FUNCTION MAY BE CONFIGURED TO TOGGLE, ON ONLY OR OFF
<br />ONLY.
<br />3.INDIVIDUAL SCENES MAY BE LOCKED TO PREVENT UNAUTHORIZED CHANGE.
<br />4.FADE UP AND FADE DOWN TIMES FOR INDIVIDUAL SCENES MAY BE ADJUSTED FROM 0
<br />SECONDS TO 18 HOURS.
<br />5.RAMP RATE MAY BE ADJUSTED FOR EACH DIMMER SWITCH.
<br />6.SWITCH BUTTONS MAY BE BOUND TO ANY LOAD ON A ROOM CONTROLLER AND ARE
<br />NOT LOAD TYPE DEPENDENT; EACH BUTTON MAY BE BOUND TO MULTIPLE LOADS.
<br />F.PROVIDE WHITE WALL PLATES WITH DECORATOR OPENING UNLESS OTHERWISE
<br />DIRECTED.
<br />2.06 DIGITAL DAYLIGHTING SENSORS
<br />A.DIGITAL DAYLIGHTING SENSORS SHALL WORK WITH ROOM CONTROLLERS TO PROVIDE
<br />AUTOMATIC SWITCHING, BI-LEVEL, OR TRI-LEVEL OR DIMMING DAYLIGHT HARVESTING
<br />CAPABILITIES FOR ANY LOAD TYPE CONNECTED TO A ROOM CONTROLLER. DAYLIGHTING
<br />SENSORS SHALL BE INTERCHANGEABLE WITHOUT THE NEED FOR REWIRING.
<br />1.CLOSED LOOP SENSORS MEASURE THE AMBIENT LIGHT IN THE SPACE AND CONTROL
<br />A SINGLE LIGHTING ZONE.
<br />2.OPEN LOOP SENSORS MEASURE INCOMING DAYLIGHT IN THE SPACE, AND ARE
<br />CAPABLE OF CONTROLLING UP TO THREE LIGHTING ZONES.
<br />3.DUAL LOOP SENSORS MEASURE BOTH AMBIENT AND INCOMING DAYLIGHT IN THE
<br />SPACE TO INSURE THAT PROPER LIGHT LEVELS ARE MAINTAINED AS CHANGES TO
<br />REFLECTIVE MATERIALS ARE MADE IN A SINGLE ZONE.
<br />B.DIGITAL DAYLIGHTING SENSORS SHALL INCLUDE THE FOLLOWING FEATURES:
<br />1.THE SENSOR'S INTERNAL PHOTODIODE SHALL ONLY MEASURE LIGHT WAVES WITHIN
<br />THE VISIBLE SPECTRUM. THE PHOTODIODE'S SPECTRAL RESPONSE CURVE SHALL
<br />CLOSELY MATCH THE ENTIRE PHOTOPIC CURVE. THE PHOTODIODE SHALL NOT
<br />MEASURE ENERGY IN EITHER THE ULTRAVIOLET OR INFRARED SPECTRUMS. THE
<br />PHOTOCELL SHALL HAVE A SENSITIVITY OF LESS THAN 5% FOR ANY WAVELENGTHS
<br />LESS THAN 400 NANOMETERS OR GREATER THAN 700 NANOMETERS.
<br />2.SENSOR LIGHT LEVEL RANGE SHALL BE FROM 1-6,553 FOOT-CANDLES (FC).
<br />3.THE CAPABILITY OF ON/OFF, BI-LEVEL OR TRI-LEVEL SWITCHING, OR DIMMING, FOR
<br />EACH CONTROLLED ZONE, DEPENDING ON THE SELECTION OF ROOM
<br />CONTROLLER(S) AND LOAD BINDING TO ROOM CONTROLLER(S).
<br />4.FOR SWITCHING DAYLIGHT HARVESTING, THE PHOTOSENSOR SHALL PROVIDE A
<br />FIELD-SELECTABLE DEAD BAND, OR A SEPARATION, BETWEEN THE “ON SETPOINT”
<br />AND THE “OFF SETPOINT” THAT WILL PREVENT THE LIGHTS FROM CYCLING
<br />EXCESSIVELY AFTER THEY TURN OFF.
<br />5.FOR DIMMING DAYLIGHT HARVESTING, THE PHOTOSENSOR SHALL PROVIDE THE
<br />OPTION, WHEN THE DAYLIGHT CONTRIBUTION IS SUFFICIENT, OF TURNING LIGHTS
<br />OFF OR DIMMING LIGHTS TO A FIELD-SELECTABLE MINIMUM LEVEL.
<br />6.PHOTOSENSORS SHALL HAVE A DIGITAL, INDEPENDENTLY CONFIGURABLE FADE
<br />RATE FOR BOTH INCREASING AND DECREASING LIGHT LEVEL IN UNITS OF PERCENT
<br />PER SECOND.
<br />7.PHOTOSENSORS SHALL PROVIDE ADJUSTABLE CUT-OFF TIME. CUT-OFF TIME IS
<br />DEFINED BY THE NUMBER OF SELECTED MINUTES THE LOAD IS AT THE MINIMUM
<br />OUTPUT BEFORE THE LOAD TURNS OFF. SELECTABLE RANGE BETWEEN 0-240
<br />MINUTES INCLUDING OPTION TO NEVER CUT-OFF.
<br />8.OPTIONAL WALL SWITCH OVERRIDE SHALL ALLOW OCCUPANTS TO REDUCE LIGHTING
<br />LEVEL TO INCREASE ENERGY SAVINGS OR, IF PERMITTED BY SYSTEM
<br />ADMINISTRATOR, RAISE LIGHTING LEVELS FOR A SELECTABLE PERIOD OF TIME OR
<br />CYCLE OF OCCUPANCY.
<br />9.INTEGRAL INFRARED (IR) TRANSCEIVER FOR CONFIGURATION AND/OR
<br />COMMISSIONING WITH A HANDHELD CONFIGURATION TOOL, TO TRANSMIT DETECTED
<br />LIGHT LEVEL TO WIRELESS CONFIGURATION TOOL, AND FOR COMMUNICATION WITH
<br />PERSONAL REMOTE CONTROLS.
<br />10.CONFIGURATION LED STATUS LIGHT ON DEVICE THAT BLINKS TO INDICATE DATA
<br />TRANSMISSION.
<br />11.STATUS LED INDICATES TEST MODE, OVERRIDE MODE AND LOAD BINDING.
<br />12.RECESSED SWITCH ON DEVICE TO TURN CONTROLLED LOAD(S) ON AND OFF.
<br />13.A CHOICE OF ACCESSORIES TO ACCOMMODATE MULTIPLE MOUNTING METHODS AND
<br />BUILDING MATERIALS. THE PHOTOSENSORS MAY BE MOUNTED ON A CEILING TILE,
<br />SKYLIGHT LIGHT WELL, SUSPENDED LIGHTING FIXTURE, OR BACK BOX. ANY LOAD OR
<br />GROUP OF LOADS IN THE ROOM CAN BE ASSIGNED TO A DAYLIGHTING ZONE
<br />14.EACH LOAD WITHIN A DAYLIGHTING ZONE CAN BE INDIVIDUALLY ENABLED OR
<br />DISABLED FOR DISCRETE CONTROL (LOAD INDEPENDENCE).
<br />15.DIGITAL PARAMETER DATA PROGRAMMED INTO A PHOTOSENSOR SHALL BE
<br />RETAINED IN NON-VOLATILE FLASH MEMORY WITHIN THE PHOTOSENSOR ITSELF.
<br />MEMORY SHALL HAVE AN EXPECTED LIFE OF 10 YEARS, MINIMUM.
<br />C.CLOSED LOOP DIGITAL PHOTOSENSORS SHALL INCLUDE THE FOLLOWING ADDITIONAL
<br />FEATURES:
<br />1.AN INTERNAL PHOTODIODE THAT MEASURES LIGHT IN A 100-DEGREE ANGLE,
<br />CUTTING OFF THE UNWANTED LIGHT FROM BRIGHT SOURCES OUTSIDE OF THIS
<br />CONE.
<br />2.AUTOMATIC SELF-CALIBRATION, INITIATED FROM THE PHOTOSENSOR, A WIRELESS
<br />CONFIGURATION TOOL OR A PC WITH APPROPRIATE SOFTWARE.
<br />3.AUTOMATICALLY ESTABLISHES APPLICATION-SPECIFIC SETPOINTS FOLLOWING
<br />SELF-CALIBRATION. FOR SWITCHING OPERATION, AN ADEQUATE DEAD BAND
<br />BETWEEN THE ON AND OFF SETPOINTS SHALL PREVENT THE LIGHTS FROM CYCLING;
<br />FOR DIMMING OPERATION A SLIDING SETPOINT CONTROL ALGORITHM WITH
<br />SEPARATE DAY AND NIGHT SETPOINTS SHALL PREVENT ABRUPT RAMPING OF LOADS.
<br />4.WATTSTOPPER PRODUCT NUMBER: LMLS-400, LMLS-400-L.
<br />D.OPEN LOOP DIGITAL PHOTOSENSORS SHALL INCLUDE THE FOLLOWING ADDITIONAL
<br />FEATURES:
<br />1.AN INTERNAL PHOTODIODE THAT MEASURES LIGHT IN A 60-DEGREE ANGLE CUTTING
<br />OFF THE UNWANTED LIGHT FROM THE INTERIOR OF THE ROOM.
<br />2.AUTOMATICALLY ESTABLISHES APPLICATION-SPECIFIC SETPOINTS FOLLOWING
<br />MANUAL CALIBRATION USING A WIRELESS CONFIGURATION TOOL OR A PC WITH
<br />APPROPRIATE SOFTWARE. FOR SWITCHING OPERATION, AN ADEQUATE DEAD BAND
<br />BETWEEN THE ON AND OFF SETPOINTS FOR EACH ZONE SHALL PREVENT THE LIGHTS
<br />FROM CYCLING; FOR DIMMING OPERATION, A PROPORTIONAL CONTROL ALGORITHM
<br />SHALL MAINTAIN THE DESIGN LIGHTING LEVEL IN EACH ZONE.
<br />3.EACH OF THE THREE DISCRETE DAYLIGHT ZONES CAN INCLUDE ANY
<br />NON-OVERLAPPING GROUP OF LOADS IN THE ROOM.
<br />4.WATTSTOPPER PRODUCT NUMBER: LMLS-500, LMLS-500-L.
<br />E.DUAL LOOP DIGITAL PHOTOSENSORS SHALL INCLUDE THE FOLLOWING ADDITIONAL
<br />FEATURES:
<br />1.CLOSE LOOP PORTION OF DUAL LOOP DEVICE MUST HAVE AN INTERNAL
<br />PHOTODIODE THAT MEASURES LIGHT IN A 100 DEGREE ANGLE, CUTTING OFF THE
<br />UNWANTED LIGHT FROM SOURCES OUTSIDE OF THIS CON
<br />2.OPEN LOOP PORTION OF DUAL LOOP DEVICE MUST HAVE AN INTERNAL PHOTODIODE
<br />THAT CAN MEASURE LIGHT IN A 60 DEGREE ANGLE, CUTTING OFF THE UNWANTED
<br />LIGHT FROM THE INTERIOR OF THE ROOM.
<br />3.AUTOMATICALLY ESTABLISHES APPLICATION-SPECIFIC SET-POINTS FOLLOWING
<br />SELF-CALIBRATION. FOR SWITCHING OPERATION, AN ADEQUATE DEAD BAND
<br />BETWEEN THE ON AND OFF SETPOINTS SHALL PREVENT THE LIGHTS FROM CYCLING;
<br />FOR DIMMING OPERATION A SLIDING SETPOINT CONTROL ALGORITHM WITH
<br />SEPARATE DAY AND NIGHT SETPOINTS SHALL PREVENT ABRUPT RAMPING OF LOAD.
<br />4.DEVICE MUST REFERENCE CLOSED LOOP PHOTOSENSOR INFORMATION AS A BASE
<br />LINE REFERENCE. THE DEVICE MUST BE ABLE TO ANALYZE THE OPEN LOOP
<br />PHOTOSENSOR INFORMATION TO DETERMINE IF AN ADJUSTMENT IN LIGHT LEVELS IS
<br />REQUIRED.
<br />5.DEVICE MUST BE ABLE TO AUTOMATICALLY COMMISSION SETPOINTS EACH NIGHT TO
<br />PROVIDE ADJUSTMENTS TO ELECTRICAL LIGHTING BASED ON CHANGES IN OVERALL
<br />LIGHTING IN THE SPACE DUE TO CHANGES IN REFLECTANCE WITHIN THE SPACE OR
<br />CHANGES TO DAYLIGHT CONTRIBUTION BASED ON SEASONAL CHANGES.
<br />6.DEVICE MUST INCLUDE EXTENDABLE MOUNTING ARM TO PROPERLY POSITION
<br />SENSOR WITHIN A SKYLIGHT WELL.
<br />2.07 DIGITAL ROOM CONTROLLERS AND PLUG-LOAD CONTROLLERS
<br />A.DIGITAL CONTROLLERS FOR LIGHTING AND PLUG LOADS AUTOMATICALLY BIND THE
<br />ROOM LOADS TO THE CONNECTED DEVICES IN THE SPACE WITHOUT COMMISSIONING OR
<br />THE USE OF ANY TOOLS. ROOM AND PLUG LOAD CONTROLLERS SHALL BE PROVIDED TO
<br />MATCH THE ROOM LIGHTING AND PLUG LOAD CONTROL REQUIREMENTS. THE
<br />CONTROLLERS SHALL BE SIMPLE TO INSTALL, AND PROVIDE STANDARD PLUG N' GO
<br />APPLICATIONS. THE CONTROL UNITS SHALL INCLUDE THE FOLLOWING FEATURES:
<br />1.AUTOMATIC ROOM CONFIGURATION TO THE MOST ENERGY-EFFICIENT SEQUENCE OF
<br />OPERATION BASED UPON THE DEVICES IN THE ROOM.
<br />2.SIMPLE REPLACEMENT - USING THE DEFAULT AUTOMATIC CONFIGURATION
<br />CAPABILITIES, A ROOM CONTROLLER MAY BE REPLACED WITH AN OFF-THE-SHELF.
<br />3.MULTIPLE ROOM CONTROLLERS CONNECTED TOGETHER IN A LOCAL NETWORK MUST
<br />AUTOMATICALLY PRIORITIZE EACH ROOM CONTROLLER, WITHOUT REQUIRING ANY
<br />CONFIGURATION OR SETUP, SO THAT LOADS ARE SEQUENTIALLY ASSIGNED USING
<br />ROOM CONTROLLER DEVICE ID'S FROM HIGHEST TO LOWEST.
<br />4.DEVICE STATUS LEDS TO INDICATE:
<br />a.DATA TRANSMISSION
<br />b.DEVICE HAS POWER
<br />c.STATUS FOR EACH LOAD
<br />d.CONFIGURATION STATUS
<br />5.QUICK INSTALLATION FEATURES INCLUDING:
<br />a.STANDARD JUNCTION BOX MOUNTING
<br />b.QUICK LOW VOLTAGE CONNECTIONS USING STANDARD RJ-45 PATCH CABLE
<br />6.BASED ON INDIVIDUAL CONFIGURATION, EACH LOAD SHALL BE CAPABLE OF THE
<br />FOLLOWING BEHAVIOR ON POWER UP FOLLOWING THE LOSS OF NORMAL POWER:
<br />a.TURN ON TO 100%
<br />b.REMAIN OFF
<br />c.TURN ON TO LAST LEVEL
<br />7.EACH LOAD SHALL BE CONFIGURABLE TO OPERATE IN THE FOLLOWING SEQUENCES
<br />BASED ON OCCUPANCY:
<br />a.AUTO-ON/AUTO-OFF (FOLLOW ON AND OFF)
<br />b.MANUAL-ON/AUTO-OFF (FOLLOW OFF ONLY)
<br />8.THE POLARITY OF EACH LOAD OUTPUT SHALL BE REVERSIBLE, VIA DIGITAL
<br />CONFIGURATION, SO THAT ON IS OFF AND OFF IS ON.
<br />9.BACNET OBJECT INFORMATION SHALL BE AVAILABLE FOR THE FOLLOWING OBJECTS:
<br />a.LOAD STATUS
<br />b.ELECTRICAL CURRENT
<br />c.TOTAL WATTS PER CONTROLLER
<br />d.SCHEDULE STATE - NORMAL OR AFTER-HOURS
<br />e.DEMAND RESPONSE CONTROL AND CAP LEVEL
<br />f.ROOM OCCUPANCY STATUS
<br />g.TOTAL ROOM LIGHTING AND PLUG LOADS WATTS
<br />h.TOTAL ROOM WATTS/SQ. FT.
<br />i.FORCE ON/OFF EVERY LOAD
<br />10.UL 2043 PLENUM RATED
<br />11.MANUAL OVERRIDE AND LED INDICATION FOR EACH LOAD
<br />12.DUAL VOLTAGE (120/277 VAC, 60 HZ), OR 347 VAC, 60 HZ (SELECTED MODELS ONLY).
<br />120/277 VOLT MODELS RATED FOR 20A TOTAL LOAD, DERATING TO 16A REQUIRED
<br />FOR SOME DIMMED LOADS (FORWARD PHASE DIMMING); 347 VOLT MODELS RATED
<br />FOR 15 AMPS TOTAL LOAD; PLUG LOAD CONTROLLERS CARRY
<br />APPLICATION-SPECIFIC UL 20 RATING FOR RECEPTACLE CONTROL.
<br />13.ZERO CROSS CIRCUITRY FOR EACH LOAD
<br />14.DIGITAL PARAMETER DATA PROGRAMMED INTO AN INDIVIDUAL ROOM CONTROLLER
<br />OR PLUG LOAD CONTROLLER SHALL BE RETAINED IN NON-VOLATILE FLASH MEMORY
<br />WITHIN THE CONTROLLER ITSELF. MEMORY SHALL HAVE AN EXPECTED LIFE OF NO
<br />LESS THAN 10 YEARS.
<br />15.PROHIBITED: DIP SWITCHES OR POTENTIOMETERS, OR REQUIRE SPECIAL
<br />CONFIGURATION FOR STANDARD PLUG N' GO APPLICATIONS
<br />B.ON/OFF ROOM CONTROLLERS SHALL INCLUDE:
<br />1.ONE OR TWO RELAY CONFIGURATION
<br />2.EFFICIENT 150 MA SWITCHING POWER SUPPLY
<br />3.THREE RJ-45 DLM LOCAL NETWORK PORTS WITH INTEGRAL STRAIN RELIEF AND DUST
<br />COVER
<br />4.WATTSTOPPER PRODUCT NUMBERS: LMRC-101, LMRC-102
<br />C.ON/OFF/DIMMING ENHANCED ROOM CONTROLLERS SHALL INCLUDE:
<br />1.REAL TIME CURRENT MONITORING
<br />2. MULTIPLE RELAY CONFIGURATIONS
<br />a.ONE, TWO OR THREE RELAYS (LMRC-21X SERIES)
<br />b.ONE OR TWO RELAYS (LMRC-22X SERIES)
<br />3.EFFICIENT 250 MA SWITCHING POWER SUPPLY
<br />4.FOUR RJ-45 DLM LOCAL NETWORK PORTS WITH INTEGRAL STRAIN RELIEF AND DUST
<br />COVER
<br />5.ONE DIMMING OUTPUT PER RELAY
<br />a.0-10V DIMMING - WHERE INDICATED, ONE 0 TO 10 VOLT ANALOG OUTPUT PER
<br />RELAY FOR CONTROL OF COMPATIBLE BALLASTS AND LED DRIVERS. THE
<br />0 TO 10 VOLT OUTPUT SHALL AUTOMATICALLY OPEN UPON LOSS OF POWER TO
<br />THE ROOM CONTROLLER TO ASSURE FULL LIGHT OUTPUT FROM THE
<br />CONTROLLED LIGHTING. (LMRC-21X SERIES)
<br />b.LINE VOLTAGE, FORWARD PHASE DIMMING - WHERE INDICATED, ONE FORWARD
<br />PHASE CONTROL LINE VOLTAGE DIMMING OUTPUT PER RELAY FOR CONTROL OF
<br />COMPATIBLE TWO-WIRE OR THREE-WIRE BALLASTS, LED DRIVERS, MLV,
<br />FORWARD PHASE COMPATIBLE ELV, NEON/COLD CATHODE AND INCANDESCENT
<br />LOADS. (LMRC-22X SERIES)
<br />c.EACH DIMMING OUTPUT CHANNEL SHALL HAVE AN INDEPENDENTLY
<br />CONFIGURABLE MINIMUM AND MAXIMUM CALIBRATION TRIM LEVEL TO SET THE
<br />DIMMING RANGE TO MATCH THE TRUE DYNAMIC RANGE OF THE CONNECTED
<br />BALLAST OR DRIVER.
<br />d.THE LED LEVEL INDICATORS ON BOUND DIMMING SWITCHES SHALL USE THIS
<br />NEW MAXIMUM AND MINIMUM TRIM.
<br />e.EACH DIMMING OUTPUT CHANNEL SHALL HAVE AN INDEPENDENTLY
<br />CONFIGURABLE MINIMUM AND MAXIMUM TRIM LEVEL TO SET THE DYNAMIC
<br />RANGE OF THE OUTPUT WITHIN THE NEW 0-100% DIMMING RANGE DEFINED BY
<br />THE MINIMUM AND MAXIMUM CALIBRATION TRIM.
<br />f.CALIBRATION AND TRIM LEVELS MUST BE SET PER OUTPUT CHANNEL.
<br />g.CONFIGURATION SHALL BE DIGITAL.
<br />h.PROHIBITED: DEVICES THAT SET CALIBRATION OR TRIM LEVELS PER
<br />CONTROLLER.
<br />6.EACH LOAD SHALL HAVE AN INDEPENDENTLY CONFIGURABLE PRESET ON LEVEL FOR
<br />NORMAL-HOURS AND AFTER-HOURS EVENTS TO ALLOW DIFFERENT DIMMED LEVELS
<br />TO BE ESTABLISHED AT THE START OF BOTH NORMAL-HOURS AND AFTER-HOURS
<br />EVENTS.
<br />7.FADE RATES FOR DIMMING LOADS SHALL BE SPECIFIC TO BOUND SWITCH BUTTONS,
<br />AND THE LOAD SHALL MAINTAIN A DEFAULT VALUE FOR ANY BOUND BUTTONS THAT
<br />DO NOT SPECIFY A UNIQUE VALUE.
<br />8.THE FOLLOWING DIMMING ATTRIBUTES MAY BE CHANGED OR SELECTED USING A
<br />WIRELESS CONFIGURATION TOOL:
<br />a.ESTABLISH PRESET LEVEL FOR EACH LOAD FROM 0-100%
<br />b.SET HIGH AND LOW TRIM FOR EACH LOAD
<br />c.SET LAMP BURN IN TIME FOR EACH LOAD UP TO 100 HOURS
<br />9.OVERRIDE BUTTON FOR EACH LOAD PROVIDES THE FOLLOWING FUNCTIONS:
<br />a.PRESS AND RELEASE FOR ON/OFF CONTROL
<br />b.PRESS AND HOLD FOR DIMMING CONTROL
<br />10.10.WATTSTOPPER PRODUCT NUMBERS: LMRC-211, LRMC-212, LRMC-213, LMRC-221,
<br />LMRC-222.
<br />2.09 CONFIGURATION TOOLS
<br />A.FEATURES AND FUNCTIONALITY OF THE WIRELESS CONFIGURATION TOOL SHALL
<br />INCLUDE BUT NOT BE LIMITED TO:
<br />1.TWO-WAY INFRARED (IR) COMMUNICATION WITH DLM IR-ENABLED DEVICES WITHIN A
<br />RANGE OF APPROXIMATELY 30 FEET.
<br />2.HIGH VISIBILITY ORGANIC LED (OLED) DISPLAY, PUSHBUTTON USER INTERFACE, AND
<br />MENU-DRIVEN OPERATION.
<br />3.MUST BE ABLE TO READ AND MODIFY PARAMETERS FOR ROOM CONTROLLERS,
<br />OCCUPANCY SENSORS, WALL SWITCHES, DAYLIGHTING SENSORS, NETWORK
<br />BRIDGES AND RELAY PANELS, AND IDENTIFY ROOM DEVICES BY TYPE AND SERIAL
<br />NUMBER.
<br />4.SAVE UP TO EIGHT OCCUPANCY SENSOR SETTING PROFILES, AND APPLY PROFILES
<br />TO SELECTED SENSORS.
<br />5.TEMPORARILY ADJUST LIGHT LEVEL OF ANY LOAD(S) ON THE LOCAL NETWORK, AND
<br />INCORPORATE THOSE LEVELS IN SCENE SETTING. SET ROOM MODE FOR TESTING OF
<br />NORMAL-HOURS (NH) AND AFTER-HOURS (AH) PARAMETER SETTINGS.
<br />6.ADJUST OR FINE-TUNE DAYLIGHTING SETTINGS ESTABLISHED DURING
<br />AUTO-CONFIGURATION, AND INPUT LIGHT LEVEL DATA TO COMPLETE
<br />CONFIGURATION OF OPEN LOOP DAYLIGHTING CONTROLS.
<br />7.SET ROOM MODE FOR TESTING OF NORMAL-HOURS (NH) AND AFTER-HOURS (AH)
<br />PARAMETER SETTINGS.
<br />8.VERIFY STATUS OF BUILDING LEVEL NETWORK DEVICES.
<br />2.10 EMERGENCY LIGHTING CONTROL DEVICES
<br />A.EMERGENCY LIGHTING CONTROL UNIT - A UL 924 LISTED DEVICE THAT MONITORS A
<br />SWITCHED CIRCUIT PROVIDING NORMAL LIGHTING TO AN AREA. THE UNIT PROVIDES
<br />NORMAL ON/OFF CONTROL OF EMERGENCY LIGHTING ALONG WITH THE NORMAL
<br />LIGHTING. UPON NORMAL POWER FAILURE THE EMERGENCY LIGHTING CIRCUIT WILL
<br />CLOSE, FORCING THE EMERGENCY LIGHTING ON UNTIL NORMAL POWER IS RESTORED.
<br />FEATURES INCLUDE:
<br />1.120/277 VOLTS, 50/60 HZ, 20 AMP BALLAST RATING
<br />2.PUSH TO TEST BUTTON AUXILIARY CONTACT FOR REMOTE TEST OR FIRE ALARM
<br />SYSTEM INTERFACE
<br />PART 3 - EXECUTION
<br />3.01 CONTRACTOR INSTALLATION AND SERVICES
<br />A.INSTALL DEVICES AND WIRING IN A PROFESSIONAL MANNER. LINE VOLTAGE
<br />CONNECTIONS TO BE TAGGED TO INDICATE CIRCUIT AND SWITCHED LEGS.
<br />B.INSTALL ROOM/AREA DEVICES USING MANUFACTURER'S FACTORY-TESTED CAT 5E
<br />CABLE WITH PRE-TERMINATED RJ-45 CONNECTORS. IF PRE-TERMINATED CABLE IS NOT
<br />USED FOR ROOM/AREA WIRING, THE CONTRACTOR IS RESPONSIBLE FOR TESTING EACH
<br />FIELD-TERMINATED CABLE FOLLOWING INSTALLATION, AND SHALL SUPPLY THE LIGHTING
<br />CONTROLS MANUFACTURER WITH TEST RESULTS.
<br />C.INSTALL THE WORK IN ACCORDANCE WITH MANUFACTURER'S PRINTED INSTRUCTIONS
<br />UNLESS OTHERWISE INDICATED. BEFORE START UP, TEST EACH DEVICE TO ENSURE
<br />PROPER COMMUNICATION.
<br />D.CALIBRATE SENSOR TIME DELAYS AND SENSITIVITY TO GUARANTEE PROPER DETECTION
<br />OF OCCUPANTS AND ENERGY SAVINGS.
<br />E.ADJUST TIME DELAY SO THAT CONTROLLED AREA REMAINS LIGHTED WHILE OCCUPIED.
<br />F.PROVIDE WRITTEN OR COMPUTER-GENERATED DOCUMENTATION ON THE
<br />CONFIGURATION OF THE SYSTEM INCLUDING ROOM BY ROOM DESCRIPTION INCLUDING:
<br />G.SENSOR PARAMETERS, TIME DELAYS, SENSITIVITIES, AND DAYLIGHTING SETPOINTS.
<br />H.SEQUENCE OF OPERATION, (E.G. MANUAL ON, AUTO OFF. ETC.)
<br />I.LOAD PARAMETERS (E.G. BLINK WARNING, ETC.)
<br />J.POST START-UP TUNING - AFTER 30 DAYS FROM OCCUPANCY CONTRACTOR SHALL
<br />ADJUST SENSOR TIME DELAYS AND SENSITIVITIES TO MEET THE INDUSTRY
<br />REQUIREMENTS. PROVIDE A DETAILED REPORT TO THE OWNER'S REPRESENTATIVE OF
<br />POST START-UP ACTIVITY.
<br />3.02 FACTORY SERVICES (OPTIONAL)
<br />A.UPON COMPLETION OF THE INSTALLATION, THE MANUFACTURER'S FACTORY
<br />AUTHORIZED REPRESENTATIVE SHALL START UP AND VERIFY A COMPLETE FULLY
<br />FUNCTIONAL SYSTEM.
<br />B.THE ELECTRICAL CONTRACTOR SHALL PROVIDE BOTH THE MANUFACTURER AND THE
<br />ELECTRICAL ENGINEER WITH THREE WEEKS WRITTEN NOTICE OF THE SYSTEM START UP
<br />AND ADJUSTMENT DATE.
<br />C.UPON COMPLETION OF THE SYSTEM START UP, THE FACTORY-AUTHORIZED TECHNICIAN
<br />SHALL PROVIDE THE PROPER TRAINING TO THE OWNER'S PERSONNEL ON THE
<br />ADJUSTMENT AND MAINTENANCE OF THE SYSTEM.
<br />3.03 ACCEPTANCE TESTING SUPPORT SERVICES
<br />A.A CERTIFIED LIGHTING CONTROLS ACCEPTANCE TEST TECHNICIAN (CLCATT) MUST
<br />VERIFY THE INSTALLATION OF THE LIGHTING CONTROL SYSTEM. MANUFACTURER
<br />SHOULD INCLUDE AN EXTRA DAY OF FACTORY TECHNICIAN'S TIME TO ASSIST THE
<br />CLCATT REVIEW THE FUNCTIONALITY AND SETTINGS OF THE LIGHTING CONTROL
<br />HARDWARE PER THE REQUIREMENTS IN THE CALIFORNIA STATE FORMS. IT WILL BE THE
<br />CLCATT'S RESPONSIBILITY TO CREATE AND COMPLETE ANY FORMS REQUIRED FOR THE
<br />COMMISSIONING PROCESS, ALTHOUGH THE MANUFACTURER OR CONTRACTOR MAY
<br />OFFER SPREADSHEETS AND/OR PRINTOUTS TO ASSIST THE CLCATT WITH THIS TASK.
<br />3.04 INSTALLATION
<br />A.COMPLY WITH NECA 1.
<br />B.WIRING METHOD: INSTALL CABLES IN RACEWAYS, EXCEPT IN ACCESSIBLE CEILING
<br />SPACES AND IN GYPSUM BOARD PARTITIONS WHERE UNENCLOSED WIRING METHOD
<br />MAY BE USED. CONCEAL RACEWAY AND CABLES EXCEPT IN UNFINISHED SPACES.
<br />C.SPLICES, TAPS, AND TERMINATIONS: MAKE CONNECTIONS ONLY ON NUMBERED
<br />TERMINAL STRIPS IN JUNCTION, PULL, AND OUTLET BOXES; TERMINAL CABINETS; AND
<br />EQUIPMENT ENCLOSURES.
<br />LABEL EACH SCENE-CONTROL BUTTON WITH APPROVED SCENE DESCRIPTION.
<br />TYPE DESCRIPTION
<br />DP 208/120V DISTRIBUTION PANELBOARD
<br />LP 208/120V PANELBOARD - RECEPTACLES & LIGHTING
<br />HDP 480/277V DISTRIBUTION PANELBOARD
<br />HLP 480/277 V PANELBOARD - LIGHTING
<br />ATS AUTOMATIC TRANSFER SWITCH
<br />CB CIRCUIT BREAKER
<br />DS DISCONNECT SWITCH
<br />EDP EMERGENCY 208/120V DISTRIBUTION PANELBOARD
<br />ELP EMERGENCY 208/120V PANELBOARD
<br />EHDP EMERGENCY 480/277V DISTRIBUTION PANELBOARD
<br />EMCC EMERGENCY MOTOR CONTROL CENTER
<br />MSB MAIN SWITCHBOARD
<br />MCC MOTOR CONTROL CENTER
<br />T TRANSFORMER
<br />US UNIT SUBSTATION
<br />Sheet No.
<br />Project
<br />Agency Plan Check / Permit No.
<br />Petersen Design Project No.
<br />Consultant
<br />5082.1
<br />652 East Dyer Drive
<br />Santa Ana, CA 92705
<br />DYER WAREHOUSE
<br />Staging & Set-Up Space
<br />Tenant Improvements
<br />Sheet Title
<br />Revision / Submittal History
<br />Scale
<br />Status
<br />.
<br />architecture + planning
<br />Agency Approval
<br />Petersen Design Architects, Inc.
<br />17582 Fiesta Way, Tustin, CA 92780
<br />M: 714.904.6720 E: mike@mpdarch.com
<br />www.mpdarch.com
<br />Architect's Stamp
<br />.
<br />255 E. Rincon St., Suite 301
<br />Corona, CA 92879
<br />P 951.340.1977 | F 951.340.1090
<br />www.gossengineering.com
<br />CALOFI
<br />GI
<br />RE
<br />NG
<br />A
<br />E
<br />S
<br />No. E17083
<br />T
<br />E
<br />ET
<br />SAT L CE A
<br />F
<br />RIC L
<br />ORNI
<br />EPR
<br />RAET
<br />RED D.D
<br />OF ONABR
<br />L
<br />SSI
<br />NE
<br />RE
<br />IWD
<br />UT
<br />HCE
<br />Project Number: 125-09-07
<br />Date Signed 01-09-2026
<br />1 01/09/2026 PLAN CHECK RESUBMITTAL
<br />ELECTRICAL
<br />SPECIFICATIONS
<br />E7.2
|