FN FOUNDATIONS
<br />FN-1)FOUNDATION DESIGN IS BASED ON THE GEOTECHNICAL REPORT BY
<br />LEIGHTON AND ASSOCIATES, INC. DATED SEPTEMBER 16, 2021. (LEIGHTON
<br />PROJECT No. 13227.001)
<br />FN-2)FOUNDATIONS HAVE BEEN DESIGNED BASED ON THE FOLLOWING DESIGN
<br />VALUES FROM THE GEOTECHNICAL REPORT:
<br />BEARING STRATUM: NATIVE QUATERNARY-AGED
<br />YOUNG ALLUVIAL FAN DEPOSITS
<br />NET ALLOWABLE BEARING CAPACITY: 4,000 PSF (AVERAGE)
<br /> 6,000 PSF (PEAK)
<br />ULTIMATE BEARING CAPACITY: 18,000 PSF
<br />ALLOWABLE BEARING CAPACITIES MAY BE INCREASED BY 1/3 FOR SHORT
<br />TERM LOADING SUCH AS WIND AND SEISMIC.
<br />ULTIMATE BEARING CAPACITY DOES NOT INCORPORATE A FACTOR OF
<br />SAFETY. A RESISTANCE FACTOR OF 0.45 SHOULD BE USED FOR BEARING
<br />CAPACITY EVALUATION WITH FACTORED LOADS.
<br />SEE GEOTECHNICAL REPORT FOR ADDITIONAL REQUIREMENTS AND
<br />INFORMATION. DESIGN VALUES SHALL BE FIELD VERIFIED BY QUALIFIED
<br />GEOTECHNICAL ENGINEER RETAINED BY THE OWNER.
<br />ADDITIONAL SOIL BORINGS SHALL BE DRILLED AT THE SITE AFTER DEMOLITION OF
<br />THE EXISTING BUILDING IS COMPLETE. AND FINAL GEOTECHNICAL REPORT SHALL
<br />BE PROVIDED TO THE SER.
<br />PRIOR TO COMMENCEMENT OF FOUNDATION WORK, CONTRACTOR MUST OBTAIN
<br />LETTER FROM SER DENOTING THAT DESIGNED FOUNDATION IS ADEQUATE BASED
<br />ON RESULTS OF ADDITIONAL BORINGS AND FINAL GEOTECHNICAL REPORT AND
<br />THAT NO REVISIONS ARE REQUIRED.
<br />FN-3)THE CONTRACTOR SHALL VERIFY FOUNDATION INSTALLATION AND
<br />CONSTRUCTION IS IN CONFORMANCE WITH THE RECOMMENDATIONS OUTLINED IN
<br />THE GEOTECHNICAL REPORT.
<br />FN-4)CONTRACTOR SHALL BE RESPONSIBLE TO ADEQUATELY PROTECT ALL
<br />EXCAVATION. WHERE NECESSARY, SHEET AND SHORE THE EXCAVATION WITH ALL
<br />REQUIRED TIEBACKS AND BRACING AS DETERMINED BY CONTRACTOR’S
<br />ENGINEER.
<br />FN-5)PROVIDE BRACING FOR ALL BASEMENT FOUNDATION WALLS PRIOR TO
<br />BACKFILLING. THIS BRACING SHALL REMAIN IN PLACE UNTIL ALL SLABS AND
<br />BEAMS FRAMING INTO WALL HAVE BEEN PLACED AND HAVE ATTAINED 100% OF
<br />THEIR DESIGN STRENGTH.
<br />FN-6)DO NOT BACKFILL AGAINST CANTILEVER RETAINING WALLS UNTIL THE
<br />CONCRETE HAS ATTAINED 100% OF ITS DESIGN STRENGTH
<br />GR GENERAL REQUIREMENTS
<br />GR-1)AS USED IN THESE GENERAL NOTES:
<br />"DRAWINGS" MEANS THE LATEST STRUCTURAL DESIGN DRAWINGS, UON.
<br />"SPECIFICATIONS" MEANS THE LATEST PROJECT SPECIFICATIONS, UON.
<br />“CONTRACT DOCUMENTS” IS DEFINED AS THE DESIGN DRAWINGS AND THE
<br />SPECIFICATIONS
<br />“SER” IS DEFINED AS THE STRUCTURAL ENGINEER OF RECORD FOR THE STRUCTURE
<br />IN ITS FINAL CONDITION.
<br />“DESIGN PROFESSIONALS” IS DEFINED AS THE OWNER’S ARCHITECT AND SER.
<br />“MEP” INCLUDES, BUT IS NOT LIMITED TO MECHANICAL, ELECTRICAL, PLUMBING, FIRE
<br />PROTECTION.
<br />“CONTRACTOR” IS DEFINED TO INCLUDE ANY OF THE FOLLOW ING: GENERAL
<br />CONTRACTOR AND THEIR SUBCONTRACTORS, CONSTRUCTION MANAGER AND THEIR
<br />SUBCONTRACTORS, STRUCTURAL STEEL FABRICATOR OR STRUCTURAL STEEL
<br />ERECTOR.
<br />“BASE BUILDING STRUCTURE” IS DEFINED AS THE STRUCTURAL FRAME DESIGNED BY
<br />THORNTON TOMASETTI.
<br />“STRUCTURE IN ITS FINAL CONDITION” MEANS ALL STRUCTURAL ELEMENTS SHOWN
<br />ON THE STRUCTURAL CONTRACT DOCUMENTS ARE INSTALLED AND COMPLETELY
<br />CONNECTED AND INSPECTED WITH NO OUTSTANDING NON-COMPLIANCE
<br />ISSUES.“DELEGATED DESIGN” MEANS A SCOPE OF WORK THAT MEETS
<br />PERFORMANCE CRITERIA ESTABLISHED IN THE CONTRACT DOCUMENTS AND IS TO
<br />BE COMPLETED BY THE CONTRACTOR’S LICENSED ENGINEER.
<br />GR-2)THE CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF THE STRUCTURAL
<br />WORK WITH THE ARCHITECTURAL, CIVIL, MEP CONTRACT DOCUMENTS, AS WELL AS
<br />ANY OTHER APPLICABLE TRADES.
<br />GR-3)THE CONTRACTOR IS RESPONSIBLE FOR THE STABILITY OF THE STRUCTURE
<br />UNTIL THE CONSTRUCTION OF THE STRUCTURE REACHES ITS FINAL CONDITION.
<br />GR-4)THE CONTRACTOR IS SOLELY RESPONSIBLE FOR THE DESIGN, INSTALLATION,
<br />AND REMOVAL OF TEMPORARY BRACING AND CONSTRUCTION SUPPORTS, FOR NEW
<br />AND EXISTING STRUCTURES, AS NECESSARY TO COMPLETE THE PROJECT. NO
<br />PORTION OF THE PROJECT WHILE UNDER CONSTRUCTION IS INTENDED TO BE
<br />STABLE IN THE ABSENCE OF THE CONTRACTOR’S TEMPORARY SUPPORTS AND
<br />BRACES. CONTRACTOR SHALL RETAIN A STRUCTURAL ENGINEER LICENSED IN THE
<br />STATE IN WHICH THE PROJECT IS LOCATED TO DESIGN TEMPORARY BRACING AND
<br />CONSTRUCTION SUPPORTS.
<br />GR-5)LATERAL LOAD RESISTANCE AND STABILITY OF THE STRUCTURE IN ITS FINAL
<br />CONDITION IS PROVIDED BY CORE WALLS, SHEAR WALLS, AND FLOOR SLABS.
<br />LATERAL STABILITY OF OTHER ELEMENTS IS PROVIDED THROUGH FLOOR SLABS;
<br />ROOF DECK; AND IN FLOOR BRACING.
<br />GR-6)THE SPECIFICATIONS ARE AN INTEGRAL PART OF THE CONTRACT DOCUMENTS
<br />AND SHALL BE USED IN CONJUNCTION WITH THE STRUCTURAL DRAWINGS.
<br />GR-7)THE CONTRACTOR SHALL VERIFY ALL EXISTING DIMENSIONS AND CONDITIONS
<br />AND COORDINATE WITH THE STRUCTURAL DRAWINGS, ARCHITECTURAL DRAWINGS,
<br />DRAWINGS FROM OTHER CONSULTANTS, PROJECT SHOP DRAWINGS AND FIELD
<br />CONDITIONS.
<br />GR-8)IN CASES OF CONFLICT BETWEEN DRAWINGS AND/OR SPECIFICATIONS AND
<br />OTHER DISCIPLINES OR EXISTING CONDITIONS, CONTRACTOR SHALL NOTIFY THE
<br />DESIGN PROFESSIONALS AND OBTAIN CLARIFICATION PRIOR TO BIDDING AND
<br />PROCEEDING WITH WORK.
<br />GR-9)APPLY DETAILS, SECTIONS, AND NOTES ON THE DRAWINGS WHERE
<br />CONDITIONS ARE SIMILAR TO THOSE INDICATED BY DETAIL, DETAIL TITLE OR NOTE.
<br />GR-10)ONLY USE DIMENSIONS INDICATED ON THE DRAWINGS. DO NOT SCALE
<br />DRAWINGS.
<br />GR-11)ASSUME EQUAL SPACING BETWEEN ESTABLISHED DIMENSIONS, IF NOT
<br />INDICATED ON DRAWINGS.
<br />GR-12)CENTERLINES OF COLUMNS AND FOUNDATIONS COINCIDE WITH GRID LINE
<br />INTERSECTIONS, UON.
<br />GR-13)CENTERLINES OF GRADE BEAMS AND WALLS COINCIDE WITH CENTERLINES
<br />OF FOUNDATIONS, UON.
<br />GR-14)CENTERLINES OF FRAMING MEMBERS COINCIDE WITH COLUMN CENTERLINES,
<br />UON.
<br />GR-15)THE CONTRACTOR SHALL PROTECT EXISTING FACILITIES, STRUCTURES AND
<br />UTILITIES FROM DAMAGE.
<br />GR-16)THE CONTRACTOR SHALL VERIFY THAT CONSTRUCTION LOADS DO NOT
<br />EXCEED THE CAPACITY OF THE STRUCTURE AT THE TIME THE LOAD IS APPLIED.
<br />GR-17)THE CONTRACTOR SHALL COORDINATE THE BOTTOM OF BASE PLATE
<br />ELEVATIONS WITH THE AS-BUILT TOP OF SUPPORT ELEVATIONS.
<br />GR-18)THE CONTRACTOR SHALL VERIFY ALL OPENING SIZES AND LOCATIONS WITH
<br />OTHER DISCIPLINES. THE DRAWINGS DO NOT SHOW ALL OPENINGS REQUIRED.
<br />ADDITIONAL OPENINGS, BLOCKOUTS AND SLEEVES MAY BE REQUIRED BY OTHER
<br />DISCIPLINES AND SHALL BE CONSTRUCTED USING THE TYPICAL DETAILS AND/OR
<br />THE CRITERIA INDICATED ON THE DRAWINGS. OPENINGS REQUIRED BUT NOT
<br />SHOWN ON THE STRUCTURAL DRAWINGS MUST BE APPROVED BY THE STRUCTURAL
<br />ENGINEER.
<br />GR-19)ELEVATIONS INDICATED ON STRUCTURAL DRAWINGS ARE BASED ON A
<br />PROJECT DATUM INDICATED ON THE ARCHITECTURAL / CIVIL DRAWINGS.
<br />GR-20) SEE ARCHITECTURAL, CIVIL, MEP, AND VERTICAL TRANSPORTATION,
<br />CONTRACT DOCUMENTS FOR ADDITIONAL INFORMATION RELATING TO THE
<br />COORDINATION OF STRUCTURAL COMPONENTS INCLUDING, BUT NOT LIMITED TO:
<br />CIVIL:
<br />PROJECT DATUM
<br />SITING OF BUILDING GRID LINES WITH RESPECT TO CITY BENCHMARKS
<br />SITE PREPARATION
<br />BACKFILLING MATERIALS AND REQUIREMENTS
<br />PAVING AND SITE ELEMENTS OUTSIDE OF BUILDING ENVELOPE
<br />NEW AND EXISTING SITE UTILITIES
<br />ARCHITECTURAL:
<br />PLAN DIMENSIONS AND PROJECT DATUM
<br />SLAB EDGE DIMENSIONS
<br />FINISH ELEVATIONS
<br />WATERPROOFING AND DAMP-PROOFING DETAILS
<br />RAMP GEOMETRY, PITS, SLAB SLOPES AND DEPRESSIONS
<br />EMBEDMENTS, INSERTS, BLOCKOUTS, ETC.
<br />EXACT OPENING SIZES FOR PIPES, DUCTS, ETC.
<br />CONCRETE FINISHES AND TOPPING SLABS
<br />CONCRETE CURBS AND HOUSEKEEPING PADS
<br />INTERIOR NON-STRUCTURAL MASONRY PARTITIONS
<br />FIRE RATINGS
<br />METAL PAN STAIRS AND SUPPORTS
<br />OPERABLE PARTITIONS
<br />MEP:
<br />PIPE AND DUCT SIZES FOR OPENING AND SLEEVE COORDINATION
<br />FLOOR DRAINS
<br />UNDERFLOOR AND PERIMETER DRAINAGE SYSTEMS
<br />EQUIPMENT CURBS
<br />CONDUITS AND EMBEDMENTS IN WALLS AND SLABS
<br />VERTICAL TRANSPORTATION:
<br />INSERTS, HANGERS, TRENCHES, PITS, CONDUITS IN WALLS AND SLABS
<br />EQUIPMENT SUPPORT, ELEVATOR DIVIDER BEAMS, EMBEDMENTS, AND ANCHOR
<br />RODS
<br />CD CODES AND DESIGN CRITERIA
<br />CD-1)PERFORM ALL CONSTRUCTION IN CONFORMANCE WITH THE BUILDING AND
<br />DESIGN CODES REFERENCED WITHIN THESE DOCUMENTS. THE PROJECT
<br />DOCUMENTS REFER TO THE FOLLOWING CODES AND STANDARDS, UON:
<br />CALIFORNIA BUILDING CODE, 2019 EDITION
<br />STRUCTURAL CONCRETE:
<br />"BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE"
<br />THE AMERICAN CONCRETE INSTITUTE (ACI 318-2014)
<br />CJ CONCRETE CONSTRUCTION JOINTS
<br />CJ-1)PROVIDE CONSTRUCTION JOINTS IN ACCORDANCE WITH ACI-318. SUBMIT
<br />SHOP DRAWINGS SHOWING PROPOSED CONSTRUCTION JOINT LOCATIONS,
<br />DETAILS AND THE PLACEMENT SEQUENCE FOR THE SER'S APPROVAL PRIOR TO
<br />PROCEEDING WITH WORK.
<br />CJ-2)UNLESS SPECIFICALLY SHOWN ON THE DRAWINGS, HORIZONTAL
<br />CONSTRUCTION JOINTS SHALL NOT BE PERMITTED IN FOOTINGS, PILE CAPS, MAT
<br />FOUNDATIONS, GRADE BEAMS, BEAMS, UPTURNED BEAMS, SLABS, AND WALLS
<br />WITHOUT PRIOR WRITTEN APPROVAL FROM THE SER BEFORE CONSTRUCTION.
<br />CJ-3)PLACE VERTICAL CONSTRUCTION JOINTS TO PROVIDE A 60 FT MAXIMUM
<br />LENGTH OF CONCRETE PLACEMENT AND LOCATE AS FOLLOWS:
<br />A. FOUNDATION WALLS: MINIMUM OF 8 FT FROM ANY WALL INTERSECTION,
<br />PILASTER, PIER, OR WALL OPENING
<br />B. BEAMS AND GRADE BEAMS: WITHIN THE MIDDLE THIRD OF THE CLEAR SPAN
<br />AVOIDING LAP SPLICES, SUBJECT TO SER APPROVAL.
<br />CJ-4)PROVIDE CONTINUOUS WATERSTOPS AT ALL CONSTRUCTION JOINTS
<br />EXPOSED TO SOIL OR WATER, AS DESCRIBED IN THE SPECIFICATIONS AND
<br />WHERE INDICATED IN THE ARCHITECTURAL DOCUMENTS.
<br />CONCRETE MASONRY:
<br />''BUILDING CODE REQUIREMENTS AND SPECIFICATION FOR MASONRY STRUCTURES''
<br />THE MASONRY SOCIETY (TMS 402-2016)
<br />STRUCTURAL STEEL:
<br />"SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS”, (AISC 360-16) CONFORMING TO
<br />THE PROVISIONS OF LOAD RESISTANCE FACTOR DESIGN,
<br />BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC-LRFD)
<br />DESIGN LOADS AND CRITERIA:
<br />"MINIMUM DESIGN LOADS AND CRITERIA FOR BUILDINGS AND OTHER STRUCTURES"
<br />AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE 7-16)
<br />CD-2)SEE DESIGN LOAD DIAGRAMS ON SHEET R1.S0.10 THRU R1.S0.16 FOR LOCATIONS
<br />AND EXTENT OF LIVE LOAD.
<br />CD-3)SUPERIMPOSED DEAD LOADS:
<br />SEE DESIGN LOAD DIAGRAMS ON SHEET R1.S0.10 THRU R1.S0.16 FOR LOCATIONS AND
<br />EXTENT OF SUPERIMPOSED DEAD LOADS.
<br />CD-4)RISK CATEGORY II
<br />CD-5)WIND LOAD DESIGN DATA:
<br />MAIN WIND FORCE RESISTING SYSTEM
<br />BASIC WIND SPEED, V 95 MPH
<br />EXPOSURE C
<br />WIND IMPORTANCE FACTOR (Iw) 1.0
<br />INTERNAL PRESSURE COEFFICIENT, GCpi +/- 0.18
<br />COMPONENTS & CLADDING EDGE DISTANCE, a 8.0 FT (TOWER)
<br /> 12.5FT (PODIUM)
<br />WIND DESIGN BASE SHEAR
<br />X-DIR: 575 KIPS
<br />Y-DIR: 1,345 KIPS
<br />CD-6)SEISMIC LOAD DESIGN DATA:
<br />SEISMIC IMPORTANCE FACTOR (Is) 1.0
<br />Ss (MAPPED) 1.292 g
<br />S1 (MAPPED) 0.641 g
<br />SDS (SITE-SPECIFIC) 1.177 g
<br />SD1 (SITE-SPECIFIC) 0.736 g
<br />SITE CLASS D
<br />SEISMIC DESIGN CATEGORY D
<br />LATERAL SYSTEM DESCRIPTION SPECIAL REINFORCED CONCRETE
<br /> SHEAR WALLS
<br />SEISMIC RESPONSE COEFFICIENT (Cs) 0.105
<br />RESPONSE MODIFICATION FACTOR (R) 5
<br />ANALYSIS PROCEDURE DESCRIPTION MODAL RESPONSE
<br />SPECTRUM ANALYSIS
<br />TORSION IRREGULARITY TYPE 1A
<br /> SEISMIC DESIGN BASE SHEAR
<br />X-DIR: 6,860 KIPS
<br />Y-DIR: 6,860 KIPS
<br />CD-7)IN CASES WHERE THE CONTRACTOR DETERMINES THAT SUSPENDED OR FLOOR
<br />MOUNTED MEP EQUIPMENT LOADS EXIST WHICH EXCEED DESIGN LOADS INDICATED ON
<br />CONTRACT DOCUMENTS, CONTRACTOR SHALL SUBMIT LOAD DATA TO DESIGN
<br />PROFESSIONALS FOR REVIEW PRIOR TO PROCEEDING WITH W ORK.
<br />CD-8)DISTRIBUTE THE MAXIMUM LOAD HUNG FROM ANY STRUCTURAL MEMBER FOR
<br />MEP DUCTWORK, PIPING ETC OVER THE MEMBER’S TRIBUTARY AREA IN A WAY THAT
<br />THE DESIGN SUPERIMPOSED DEAD LOADS LISTED IN CONTRACT DOCUMENTS ARE NOT
<br />EXCEEDED. THE CONTRACTOR SHALL COORDINATE THE LOADS OF ALL TRADES AND
<br />PROVIDE ADDITIONAL SUPPORT OR DISTRIBUTION FRAMING AS REQUIRED TO ACHIEVE
<br />THE ALLOWABLE LOAD DISTRIBUTION.
<br />CD-9) ESCALATOR SUPPORTS AND PITS ARE BASED ON ESCALATOR TYPES INDICATED
<br />ON ARCHITECTURAL CONTRACT DOCUMENTS. CONTRACTOR SHALL SUBMIT FOR
<br />REVIEW ANY PLANNED CHANGE TO ESCALATORS TO DESIGN PROFESSIONALS PRIOR
<br />TO SUBMITTING CORRESPONDING STRUCTURAL SHOP DRAWINGS FOR ACTION.
<br />CD-10)ELEVATOR GUIDERAIL SUPPORTS, MACHINE ROOMS, PITS, AND PENTHOUSES
<br />ARE BASED ON ELEVATOR TYPES INDICATED ON ARCHITECTURAL CONTRACT
<br />DOCUMENTS. CONTRACTOR SHALL SUBMIT FOR REVIEW ANY PLANNED CHANGE TO
<br />ELEVATORS TO DESIGN PROFESSIONALS PRIOR TO SUBMITTING CORRESPONDING
<br />STRUCTURAL SHOP DRAWINGS FOR ACTION.
<br />CD-11)STRUCTURAL COMPONENTS ARE NOT DESIGNED FOR VIBRATING EQUIPMENT.
<br />MOUNT VIBRATING EQUIPMENT ON VIBRATION ISOLATORS.
<br />CD-12)SERVICEABILITY
<br />LIVE LOAD FLOOR DEFLECTION IS LESS THAN L/360 OR 1/4", WHICHEVER IS LESS.
<br />LONG-TERM FLOOR TOTAL DEFLECTION IS LESS THAN L/240 OR 3/4", WHICHEVER IS
<br />LESS.
<br />EXTERIOR EDGE BEAMS HAVE BEEN DESIGNED TO LIMIT LIVE LOAD MIDSPAN VERTICAL
<br />DEFLECTION TO 1/360 OF THE SPAN OR 1/4", WHICHEVER IS LESS.
<br />EXTERIOR EDGE BEAMS HAVE BEEN DESIGNED TO LIMIT DEAD PLUS SUPERIMPOSED
<br />DEAD LOAD MIDSPAN VERTICAL DEFLECTION TO 1/240 OF THE SPAN OR 3/4”,
<br />WHICHEVER IS LESS.
<br />LATERAL DRIFT DUE TO WIND LOADS IS LESS THAN OR EQUAL TO 1/400 OF THE
<br />BUILDING HEIGHT.
<br />LATERAL STORY DRIFT DUE TO SERVICE LEVEL SEISMIC OR WIND LOADS IS LESS THAN
<br />OR EQUAL TO THE LESSER OF 0.5% OF THE STORY HEIGHT, OR 3/4".
<br />LATERAL STORY DRIFT DUE TO DESIGN SEISMIC LOADS IS LESS THAN OR EQUAL TO 2%
<br />OF THE HEIGHT OF THE STORY.
<br />CD-13)CONNECTIONS OF SYSTEMS DESIGNED BY CONTRACTOR’S ENGINEER SUCH AS,
<br />BUT NOT LIMITED TO, CLADDING, STAIRS, ELEVATORS, ESCALATORS, PRECAST STADIA,
<br />AND MEP LOADS ARE ASSUMED TO IMPOSE VERTICAL AND/OR HORIZONTAL LOADS ON
<br />THE BASE BUILDING STRUCTURAL MEMBERS WITHOUT GENERATING TORSION IN THE
<br />SUPPORTING STRUCTURAL MEMBERS. CONTRACTOR IS RESPONSIBLE FOR
<br />FURNISHING AND INSTALLING ALL SUPPLEMENTARY BRACING MEMBERS AS REQUIRED
<br />TO PREVENT TORSION ON THE BASE BUILDING STRUCTURE.
<br />CD-14)FOR FIRE RATING AND FIREPROOFING ASSEMBLY EVALUATIONS, CONSIDER THE
<br />FOLLOWING ASSEMBLIES RESTRAINED: COMPOSITE WIDE-FLANGE STEEL FRAMING,
<br />INTERIOR BAYS OF CONTINUOUS CAST-IN-PLACE CONCRETE CONSTRUCTION.
<br />CONSIDER ALL OTHER ASSEMBLIES UNRESTRAINED.
<br />CD-15)THERE HAVE BEEN NO LOAD RESTRICTION FACTORS APPLIED TO THE
<br />STRUCTURAL DESIGN FOR THE PURPOSES OF SELECTING FIREPROOFING ASSEMBLIES.
<br />DE DEMOLITION
<br />DE-1)THE CONTRACTOR IS FULLY RESPONSIBLE FOR THE MEANS AND METHODS
<br />OF DEMOLITION AND THE INTEGRITY AND STABILITY OF THE EXISTING STRUCTURE
<br />DURING DEMOLITION UNTIL THE WORK IS COMPLETED. THE CONTRACTOR SHALL
<br />PROVIDE SHORING IN REQUIRED LOCATIONS WHERE EXISTING CONSTRUCTION TO
<br />REMAIN WILL BE AFFECTED BY DEMOLITION. CONTRACTOR SHALL RETAIN A
<br />PROFESSIONAL ENGINEER LICENSED IN THE STATE WHERE THE PROJECT IS
<br />LOCATED TO DESIGN SHORING.
<br />DE-2)THE CONTRACTOR IS RESPONSIBLE FOR REPAIRS TO ANY STRUCTURAL
<br />ELEMENTS WHICH ARE TO REMAIN AND THAT HAVE BEEN DAMAGED DURING THE
<br />DEMOLITION PROCESS TO THE COMPLETE SATISFACTION OF THE OWNER. THE
<br />REPAIRS SHALL BE AT NO EXPENSE TO THE OWNER. ALL REPAIR WORK SHALL BE
<br />DESIGNED BY A PROFESSIONAL ENGINEER LICENSED IN THE STATE WHERE THE
<br />PROJECT IS LOCATED AND SUBMITTED TO THE SER FOR REVIEW AND APPROVAL
<br />PRIOR TO COMMENCING REPAIR WORK.
<br />DE-3)ALL EXISTING FRAMING IS INDICATED FOR REFERENCE ONLY AND IS TO BE
<br />FIELD VERIFIED BY THE CONTRACTOR. VERIFY THE EXACT EXTENT OF
<br />DEMOLITION AT THE SITE. DETERMINE THE NATURE AND EXTENT OF DEMOLITION
<br />THAT WILL BE NECESSARY BY COMPARING THE CONTRACT DOCUMENTS WITH THE
<br />EXISTING CONSTRUCTION. IMMEDIATELY NOTIFY THE DESIGN PROFESSIONALS OF
<br />ANY INCONSISTENCIES.
<br />DE-4)THE CONTRACTOR SHALL USE THE STRUCTURAL CONTRACT DOCUMENTS IN
<br />CONJUNCTION WITH THE ARCHITECTURAL AND MEP DEMOLITION CONTRACT
<br />DOCUMENTS. IN THE EVENT OF CONFLICTS, THE CONTRACTOR SHALL
<br />IMMEDIATELY NOTIFY THE DESIGN PROFESSIONALS.
<br />DE-5)THE CONTRACTOR SHALL USE QUALIFIED, EXPERIENCED PERSONNEL FOR
<br />DEMOLITION AND REMOVAL OPERATIONS. PERFORM DEMOLITION AND REMOVAL
<br />OPERATIONS IN A CAREFUL AND ORDERLY MANNER TO PREVENT HAZARDS TO
<br />PERSONS, DAMAGE TO PROPERTY, AND THE SPREADING OF DUST AND DEBRIS.
<br />DE-6)DO NOT PERMIT PORTIONS OF THE STRUCTURE TO FALL NOR DEBRIS TO
<br />DROP EXCEPT BY METHODS WHICH WILL INSURE INTEGRITY OF THE STRUCTURE.
<br />DE-7)PRIOR TO THE START OF WORK, VERIFY THAT THE SCOPE OF DEMOLITION
<br />INDICATED ON THE CONTRACT DOCUMENTS SHALL NOT DAMAGE, CUT OR
<br />DISRUPT SERVICE OF ANY MECHANICAL SYSTEM, ELECTRICAL SYSTEM OR UTILITY
<br />EMBEDDED IN THE EXISTING STRUCTURE.
<br />DE-8)DO NOT REMOVE MORE OF THE EXISTING STRUCTURE THAN INDICATED ON
<br />CONTRACT DOCUMENTS. DO NOT DAMAGE, MAR, CUT OR DEFACE THE REMAINING
<br />STRUCTURE OR MATERIALS TO BE REUSED.
<br />DE-9)THE CONTRACTOR SHALL INCLUDE IN HIS BID THE COST OF REMOVING
<br />DEMOLISHED MATERIALS FROM THE SITE IN ACCORDANCE WITH ALL APPLICABLE
<br />LAWS, CODES, AND REGULATIONS.
<br />DE-10) WHERE NEW OPENINGS IN EXISTING CONCRETE SLABS OR WALLS ARE TO
<br />BE CREATED, THE DEMOLITION CONTRACTOR SHALL CORE HOLES AT THE
<br />OUTSIDE CORNERS OF THE NEW OPENING PRIOR TO DEMOLITION. SAW-CUT AND
<br />DEMOLISH SLAB OR WALL ONLY AFTER THE INSTALLATION OF ALL REQUIRED NEW
<br />STRUCTURAL FRAMING AND/OR REINFORCEMENT IN PLAN OR SECTION, UON. SAW
<br />CUTTING SHALL BE STRAIGHT AND SHALL NOT EXTEND INTO EXISTING SLAB OR
<br />WALL TO REMAIN NOR BEYOND THE HOLES CORED AT THE CORNERS OF THE NEW
<br />OPENING.
<br />DI DELEGATED DESIGN ITEMS
<br />DI-1)THE CONTRACTOR SHALL EMPLOY OR RETAIN A PROFESSIONAL ENGINEER
<br />LICENSED IN THE STATE WHERE THIS PROJECT IS LOCATED TO DESIGN AND
<br />DETAIL DELEGATED DESIGN ITEMS TO MEET THE PERFORMANCE AND DESIGN
<br />CRITERIA ESTABLISHED AS PART OF THE BASE BUILDING STRUCTURE INDICATED
<br />IN THE CONTRACT DOCUMENTS INCLUDING BUT NOT LIMITED TO:
<br />POST-TENSIONING TENDON LAYOUT AND EFFECTIVE FORCE, FRICTION LOSS
<br />CALCULATIONS
<br />POST-TENSIONING SEQUENCE
<br />COLD-FORMED METAL FRAMING
<br />EXTERIOR CLADDING SYSTEMS
<br />STOREFRONT SYSTEM (INCLUDING INTEGRAL CANOPIES)
<br />METAL STAIRS
<br />ELEVATORS
<br />WINDOW WASHING TIEBACK OR DAVIT SYSTEMS
<br />CATWALKS
<br />MEP PLATFORMS, EQUIPMENT ANCHORAGE, AND BRACING
<br />POOL & SPA FIT-OUTS
<br />STORM WATER TANK
<br />CABLE RAIL RESTRAINT AT PARKING STALLS
<br />SHORING/RESHORING DESIGN AND CALCULATIONS
<br />CONTRATOR TO REFERENCE SHEET R1.G0.010 FOR FULL LIST OF DELEGATED
<br />DESIGN ITEMS
<br />SU SUBMITTALS
<br />SU-1)TWENTY WORKING DAYS PRIOR TO SUBMITTING SHOP DRAWINGS, THE
<br />CONTRACTOR SHALL SUBMIT FOR SER'S REVIEW A SCHEDULE WHICH DETAILS
<br />THE ESTIMATED QUANTITY OF SHOP DRAWINGS AND THE DATE THE SHOP
<br />DRAWINGS WILL BE RECEIVED BY THE SER. THE SER SHALL HAVE THE
<br />OPPORTUNITY TO REVIEW THE PROPOSED SCHEDULE AND SUBMIT COMMENTS TO
<br />THE CONTRACTOR. THE FINAL SHOP DRAWING SCHEDULE SHALL BE DEVELOPED
<br />AND SUBMITTED TO THE SER. IN ACCORDANCE WITH THE SHOP DRAWING
<br />SCHEDULE, THE SER WILL RETURN THE SHOP DRAWING ITEMS WITHIN TEN
<br />WORKING DAYS AFTER HAVING RECEIVED THE ELECTRONIC SHOP DRAWING.
<br />SU-2)THE CONTRACTOR IS TO REVIEW EACH SUBMITTAL PRIOR TO FORWARDING
<br />TO DESIGN PROFESSIONALS. THE CONTRACTOR IS TO STAMP EACH SUBMITTAL
<br />VERIFYING THAT THE FOLLOWING IS ADDRESSED:
<br />1. THE SHOP DRAWING IS REQUESTED.
<br />2. THE SHOP DRAWING IS BASED ON THE LATEST DESIGN.
<br />3. THE DESIGN PROFESSIONALS’ COMMENTS FROM ANY PREVIOUS SUBMITTALS
<br />ARE ADDRESSED.
<br />4. THE WORK IS COORDINATED AMONG ALL CONSTRUCTION TRADES.
<br />5. REVISIONS FROM PREVIOUS SUBMITTALS ARE CLEARLY MARKED BY CIRCLING
<br />OR CLOUDS.
<br />6. SUBMITTAL IS COMPLETE.
<br />7. SUBMITTAL DOES NOT INCLUDE SUBSTITUTION REQUEST
<br />8. SUBMITTAL SHALL INCLUDE A STAMP INDICATING PROJECT NAME AND
<br />LOCATION, SUBMITTAL NUMBER, SPECIFICATION SECTION NUMBER.
<br />THE SER SHALL RETURN, WITHOUT COMMENT, SUBMITTALS W HICH THE
<br />CONTRACTOR HAS NOT STAMPED OR WHICH DO NOT MEET THE ABOVE
<br />REQUIREMENTS. THE SER’S REVIEW OF SUBMITTALS SHALL BE FOR GENERAL
<br />CONFORMANCE WITH THE DESIGN INTENT. NO WORK SHALL BE STARTED
<br />WITHOUT SUCH REVIEW.
<br />SU-3)FOR COMPONENTS THAT REQUIRE ENGINEERING BY THE CONTRACTOR,
<br />PROVIDE A NOTE ON EACH SHOP DRAWING, WRITTEN AND SIGNED BY THE
<br />SUPPLIER'S ENGINEER, INDICATING THAT THE SHOP DRAWING IS IN
<br />CONFORMANCE WITH THE CALCULATIONS OF THE CONTRACTOR'S ENGINEER.
<br />SU-4)THE FOLLOWING ITEMS REQUIRE SUBMITTALS FOR STRUCTURAL REVIEW AS
<br />OUTLINED IN THE SPECIFICATIONS:
<br />031000 S CALC CONCRETE FORMWORK
<br />032000 S CONCRETE REINFORCING LAYOUT
<br />033000 CALC CONCRETE MIX DESIGNS
<br />033000 S CONCRETE CONSTRUCTION JOINT LAYOUT
<br />033800 S POST-TENSIONING TENDON LAYOUT
<br />033800 CALC POST-TENSIONING FRICTION LOSSES
<br />034120 S CALC STRUCTURAL PRECAST CONCRETE
<br />034120 S CALC STRUCTURAL PRECAST CONCRETE CONNECTIONS
<br />041000 S MASONRY REINFORCEMENT LAYOUT
<br />051000 S STRUCTURAL STEEL
<br />051000 S CALC STRUCTURAL STEEL CONNECTIONS
<br />051000 S SHEAR STUD LAYOUT
<br />053000 S CALC STEEL COMPOSITE DECK
<br />053000 S CALC STEEL FORM DECK
<br />053000 S CALC STEEL ROOF DECK
<br />S = SHOP DRAWINGS REQUIRED
<br />CALC = SUPPORTING CALCULATIONS REQUIRED, SEALED AND SIGNED BY A
<br />PROFESSIONAL ENGINEER LICENSED IN THE STATE WHERE THE PROJECT IS
<br />LOCATED.
<br />SU-5)THE ITEMS IN THIS SECTION REFER TO LOADS IMPOSED BY CONTRACTOR
<br />DESIGNED SYSTEMS, SPECIFICALLY:
<br />ARCHITECTURAL PRECAST CONCRETE AND CONNECTIONS
<br />COLD-FORMED METAL FRAMING
<br />EXTERIOR CLADDING SYSTEMS
<br />METAL STAIRS
<br />ARCHITECTURAL ORNAMENTATION (FLAGPOLES, BANNERS, MASTS, ETC.)
<br />ELEVATOR REACTIONS
<br />SKYLIGHTS
<br />WINDOW WASHING TIEBACK OR DAVIT SYSTEMS
<br />CATWALKS
<br />MEP PLATFORMS, EQUIPMENT ANCHORAGE AND BRACING
<br />WHERE CONTRACTOR LOADS IMPOSED DO NOT EXCEED AND/OR CONNECTION
<br />CONDITIONS DO NOT DIFFER FROM WHAT IS INDICATED IN THE STRUCTURAL
<br />DRAWINGS, SUBMIT FOR RECORD A LETTER SEALED AND SIGNED BY A
<br />PROFESSIONAL ENGINEER LICENSED IN THE STATE WHERE THE PROJECT IS
<br />LOCATED STATING THE FOLLOWING:
<br />“THE CONTRACTOR DESIGNED SYSTEM HAS BEEN DESIGNED TO IMPOSE LOADS
<br />ON THE BASE BUILDING STRUCTURE THAT ARE WITHIN THE LOAD LIMITS AND AT
<br />THE LOCATIONS INDICATED ON THE STRUCTURAL DRAWINGS.”
<br />WHERE CONTRACTOR LOADS IMPOSED FOR THE FOLLOWING ITEMS EXCEED
<br />AND/OR CONNECTION CONDITIONS DIFFER FROM WHAT IS SHOWN IN THE
<br />STRUCTURAL DRAWINGS, SUBMIT FOR APPROVAL TO SER LOADS IMPOSED ON
<br />THE PRIMARY STRUCTURAL FRAME DUE TO THE DEAD, LIVE, AND WIND/SEISMIC
<br />LOADS INDICATED ON THE CONTRACT DOCUMENTS.
<br />SUBMITTAL SHALL LIST THE DESIGN LOADS USED AND BE SEALED AND SIGNED BY
<br />A PROFESSIONAL ENGINEER LICENSED IN THE STATE WHERE THE PROJECT IS
<br />LOCATED. SUBMITTAL SHALL INCLUDE LOCATION, MAGNITUDE AND DIRECTION OF
<br />UNFACTORED IMPOSED LOADS, GRAPHICALLY REPRESENTED IN THEIR
<br />APPROPRIATE LOCATIONS ON A COPY OF THE CONTRACT DOCUMENT
<br />STRUCTURAL FRAMING PLANS OR ELEVATIONS AS APPROPRIATE. DETAIL
<br />REFERENCES IN THE CONNECTIONS APPLICABLE AT EACH LOCATION SHALL BE
<br />NOTED ON THE SUBMITTAL DRAWINGS.
<br />FOR EXTERIOR WALL ASSEMBLIES, THE LOADS IMPOSED SUBMITTAL SHALL BE
<br />COMPREHENSIVE INDICATING THE LOADS IMPOSED ON THE BASE BUILDING
<br />STRUCTURE AND SHALL INCLUDE THE REACTIONS BASED ON THE ACTUAL LOADS
<br />OF THE ENTIRE ASSEMBLY, INCLUDING BUT NOT LIMITED TO GLAZING, CLADDING,
<br />METAL STUD BACKUP, AND MULLIONS.
<br />FOR MEP SYSTEMS, THE LOADS IMPOSED SUBMITTAL SHALL BE COMPREHENSIVE
<br />INDICATING THE LOADS IMPOSED ON THE BASE BUILDING STRUCTURE AND SHALL
<br />INCLUDE THE REACTIONS BASED ON THE ACTUAL LOADS OF THE ENTIRE
<br />MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE PROTECTION SYSTEM,
<br />INCLUDING BUT NOT LIMITED TO PIPING, DUCTS, ELECTRICAL RACEWAYS, AND
<br />EQUIPMENT WEIGHTS.
<br />A SUBSTITUTION REQUEST MAY BE REQUIRED WHERE CONTRACTOR LOADS
<br />IMPOSED EXCEED AND/OR CONNECTION CONDITIONS DIFFER FROM THE BASIS OF
<br />DESIGN.
<br />RE CONCRETE REINFORCEMENT
<br />RE-1)ALL CONCRETE SHALL INCLUDE REINFORCEMENT. IF REINFORCEMENT IS NOT
<br />SPECIFICALLY INDICATED ON THE DRAWINGS VERIFY WITH THE SER.
<br />RE-2)REINFORCEMENT SHALL CONFORM TO THE FOLLOWING STANDARDS AND MATERIAL
<br />PROPERTIES UON:
<br />DEFORMED BARS: ASTM A615
<br />GRADE 60/75 OR 80 (AS INDICATED)
<br />WELDABLE DEFORMED BARS: ASTM A706
<br />EPOXY COATED DEFORMED BARS: ASTM A615 / A775
<br />WELDED WIRE REINFORCEMENT ASTM A1064
<br />EPOXY COATED WELDED WIRE REINFORCEMENT ASTM A1064 / A884
<br />SHEAR/CORE WALL VERTICAL REINFORCEMENT ASTM A706
<br />AND COUPLING BEAM LONGITUDINAL/DIAGONAL
<br />REINFORCEMENT
<br />RE-3)DETAIL REINFORCEMENT BASED ON THE PROJECT REQUIREMENTS, ACI-318 AND ACI-315,
<br />UON.
<br />RE-4)WHERE A 90-DEG, 135 –DEG OR 180-DEG HOOK IS GRAPHICALLY INDICATED, PROVIDE
<br />CORRESPONDING ACI STANDARD HOOKS UON.
<br />RE-5)DOWELS SHALL MATCH SIZE AND SPACING OF MAIN REINFORCEMENT UON.
<br />RE-6)REINFORCEMENT SHALL HAVE CONCRETE PROTECTION (CLEAR COVER) PER ACI 318
<br />UNLESS OTHERWISE INDICATED ON THE DRAWINGS.
<br />RE-7)LAP REINFORCEMENT ONLY AT LOCATIONS AS SPECIFICALLY DETAILED ON THE
<br />DRAWINGS EXCEPT REINFORCEMENT MARKED AS CONTINUOUS CAN BE SPLICED AT
<br />LOCATIONS DETERMINED BY CONTRACTOR USING TENSION LAP SPLICES (LTS). SEE LAP
<br />SPLICE AND EMBEDMENT SCHEDULE.
<br />RE-8)UNLESS OTHERWISE NOTED ALL LAP SPLICES ARE TO BE TENSION LAP SPLICES PER LAP
<br />SPLICE AND EMBEDMENT SCHEDULE.
<br />RE-9)PROVIDE MECHANICAL SPLICES FOR BARS LARGER THAN #11 OR WHERE INDICATED.
<br />PROVIDE TENSILE, PRE-QUALIFIED, WELDED OR THREADED MECHANICAL SPLICES UON.
<br />RE-10)LAP WELDED WIRE REINFORCEMENT TWO PANEL SPACINGS, UON.
<br />RE-11)PROVIDE LAP SPLICE LOCATIONS AS FOLLOWS, UON:
<br />A. GRADE BEAM / WALL (TOP HORIZONTAL REINFORCEMENT): AT CENTER OF
<br />SPAN
<br />B. GRADE BEAM / WALL (BOTTOM HORIZONTAL REINFORCEMENT): AT
<br />SUPPORTS
<br />C. WALL INSIDE FACE (VERTICAL REINFORCEMENT): AT SUPPORT
<br />D. WALL OUTSIDE FACE (VERTICAL REINFORCEMENT): AT STORY MIDHEIGHT
<br />OF WALL FOR BELOW GRADE FOUNDATION WALLS, AT SUPPORT FOR
<br />OTHER WALLS
<br />E. UNLESS OTHERWISE NOTED TERMINATE BARS AT DISCONTINUOUS ENDS
<br />WITH STANDARD HOOKS.
<br />RE-12)PROVIDE EPOXY COATED REINFORCEMENT AND ACCESSORIES IN AREAS
<br />OF DIRECT EXPOSURE TO THE ENVIRONMENT, CHEMICALS, OR DE-ICING FOR
<br />THE AREAS INDICATED ON THE DRAWINGS.
<br />CM CONCRETE MATERIALS
<br />CM-1)CONCRETE STRENGTH SHALL MEET THE FOLLOWING 28-DAY COMPRESSIVE
<br />STRENGTHS (f' c), UON:
<br />SITE RETAINING WALLS 4,000 PSI
<br />FOOTINGS 5,000 PSI
<br />MAT FOUNDATIONS 5,000 PSI
<br />GRADE BEAMS 5,000 PSI
<br />FOUNDATION WALLS, PILASTERS, BUTTRESSES 5,000 PSI
<br />NON-SHRINK GROUT 8,000 PSI
<br />SLAB ON GRADE, CONCRETE CURBS 4,000 PSI
<br />CONCRETE ON STEEL DECK 4,000 PSI
<br />FORMED CONCRETE SLABS AND BEAMS* 5,750 PSI
<br />CONCRETE HOUSEKEEPING PADS, AND FILL SLABS 4,000 PSI (LIGHTWEIGHT)
<br />COLUMNS 6,000-8,000 PSI **
<br />CONCRETE SHEAR WALLS 8,000 PSI
<br />SEE QUALITY CONTROL FOR HIGH STRENGTH CONCRETE NOTES FOR ADDITIONAL
<br />INFORMATION.
<br />* USE OF SILICEOUS AGGREGATE IN ELEVATED SLABS AND BEAMS IS PROHIBITED.
<br />** SEE COLUMN SCHEDULE.
<br />*** SEE CORE AND SHEAR WALL SCHEDULE.
<br />CM-2)PROVIDE NORMALWEIGHT CONCRETE WITH CURED DENSITY OF 145 +/- 5
<br />PCF, AND AGGREGATE CONFORMING TO ASTM C33, UON. WHERE INDICATED,
<br />PROVIDE LIGHTWEIGHT CONCRETE WITH CURED DENSITY OF 112+/-3 PCF AND
<br />AGGREGATE CONFORMING TO ASTM C330.
<br />CM-3)THE USE OF CALCIUM CHLORIDE AND OTHER CHLORIDE CONTAINING
<br />AGENTS IS PROHIBITED. THE USE OF RECYCLED CONCRETE IS PROHIBITED.
<br />PLACEMENT WITHIN AND CONTACT BETWEEN ALUMINUM ITEMS, INCLUDING
<br />ALUMINUM CONDUIT, AND CONCRETE IS PROHIBITED.
<br />CM-4)ALL CAST-IN-PLACE CONCRETE WILL EXPERIENCE DIFFERING VARIATIONS
<br />OF CRACKING. ANY ELEMENT EXPOSED TO DIRECT WEATHER AND/OR
<br />TEMPERATURE VARIATIONS DURING CONSTRUCTION OR IN THE FINAL CONDITION
<br />IS TO BE TREATED AND REGULARLY MAINTAINED TO PREVENT PROPAGATION OF
<br />CRACKS AND WATER PENETRATION. THE CONTRACTOR SHALL DEVELOP A
<br />REGULAR MAINTENANCE PROGRAM AND SUBMIT IT TO THE OW NER.
<br />MAXIMUM INELASTIC LATERAL DISPLACEMENT DUE TO SEISMIC LOADS ARE
<br />AS FOLLOWS:
<br />NORTH-SOUTH
<br />16.0"ROOF LEVEL
<br />LEVEL 10"
<br />EAST-WEST
<br />16.4" ROOF LEVEL
<br />LEVEL 10"
<br />8.7"LEVEL 09 8.2"LEVEL 09
<br />CONCRETE CAST AGAINST AND
<br />PERMANENTLY EXPOSED TO EARTH
<br />CONCRETE EXPOSED TO EARTH OR WEATHER:
<br />NO 5 BARS OR SMALLER...........................................................
<br />NO 6 BARS AND LARGER...........................................................
<br />CONCRETE NOT EXPOSED TO WEATHER OR IN
<br />CONTACT WITH GROUND
<br />SLABS, WALLS, JOISTS:
<br />NO 11 BARS OR SMALLER.........................................................
<br />NO 14 BARS AND LARGER.........................................................
<br />BEAMS, COLUMNS:
<br />PRIMARY REINFORCEMENT, TIES,
<br />STIRRUPS, SPIRALS..................................................................
<br />SHELLS, FOLDED PLATE MEMBERS:
<br />NO 11 BARS OR SMALLER.........................................................
<br />NO 14 BARS AND LARGER.........................................................
<br />COVERLOCATION
<br />3"
<br />1 1/2"
<br />2"
<br />3/4"
<br />1 1/2"
<br />1 1/2"
<br />1/2"
<br />3/4"
<br />T: F:
<br />© Gensler
<br />Date Description
<br />Project Name
<br />Project Number
<br />Description
<br />Scale
<br />Seal / Signature
<br />2021
<br />Tel 949.863.9434
<br />Fax 949-553-1676
<br />4675 MacArthur Court
<br />Suite 100
<br />Newport Beach, CA
<br />92600
<br />USA
<br />301 N. Broadway, Santa Ana, CA
<br />707 Wilshire Blvd, Suite 4450
<br />Los Angeles, CA 90017-3618
<br />Thornton Tomasetti, Inc.
<br />213.330.7700 213.330.7001
<br />3RD & BROADWAY -
<br />RESIDENTIAL
<br />12" = 1'-0"
<br />11/19/2024 3:19:57 PM
<br />R1.S0.02
<br />GENERAL NOTES
<br />S21043.00
<br />1 12.10.2021 REISSUE FOR PLAN CHECK
<br />A 06.10.2022 REISSUE FOR PLAN CHECK
<br />B 06.17.2024 REVISION TO PERMIT
<br />1/7/25
|