ELECTRICAL SPECIFICATIONS <br />1.SCOPE OF WORK: <br />1.1.SCOPE OF WORK SHALL CONSIST OF PROVIDING LABOR, MATERIALS, EQUIPMENT, <br />SERVICES AND FEES NECESSARY FOR COMPLETE AND SAFE INSTALLATION IN <br />CONFORMITY WITH THE NATIONAL ELECTRICAL CODE , AND ALL OTHER APPLICABLE <br />INDUSTRY, NATIONAL AND LOCAL CODES AND AUTHORITIES HAVING JURISDICTION, AS <br />INDICATED ON DRAWINGS AND HEREIN SPECIFIED. <br />1.2.ALL DRAWINGS, PLANS, DETAILS, SPECIFICATIONS AND SPECIFICATION ADDENDA ARE <br />MADE PART OF THIS CONTRACT AND SHALL APPLY TO ALL WORK UNDER THE CONTRACT <br />UNLESS OTHERWISE AMENDED, MODIFIED, SUPPLEMENTED OR SPECIFIED HEREIN. <br />1.3.THE CONTRACTOR SHALL FURNISH A WRITTEN WARRANTY LETTER TO REPLACE OR <br />REPAIR PROMPTLY AND ASSUME RESPONSIBILITY FOR ALL EXPENSES INCURRED, FOR ANY <br />WORKMANSHIP AND EQUIPMENT IN WHICH DEFECTS DEVELOP WITHIN ONE YEAR FROM <br />THE DATE OF FINAL CERTIFICATE FOR PAYMENT AND/OR FROM DATE OR ACTUAL USE OF <br />EQUIPMENT OR OCCUPANCY OF SPACES BY OWNER, INCLUDED UNDER THE VARIOUS <br />PARTS OF THE WORK, WHICHEVER DATE IS EARLIER. THIS WORK SHALL BE DONE AS <br />DIRECTED BY THE OWNER. THIS WARRANTY SHALL ALSO PROVIDE THAT WHERE DEFECTS <br />OCCUR, THE CONTRACTOR WILL ASSUME RESPONSIBILITY FOR ALL EXPENSES INCURRED <br />IN REPAIRING AND REPLACING WORK OF OTHER TRADES AFFECTED BY DEFECTS, REPAIRS <br />OR REPLACEMENTS IN EQUIPMENT SUPPLIED BY THE CONTRACTOR. THE WARRANTY <br />LETTER IS TO BE COORDINATED WITH THE TERMS IN THE ELECTRADA MASTER SERVICE <br />AGREEMENT (MSA) BETWEEN ELECTRADA AND THE CONTRACTOR. <br />1.4.THE CONTRACTOR SHALL GIVE NECESSARY NOTICE, FILE DRAWINGS AND SPECIFICATIONS <br />WITH ALL DEPARTMENTS HAVING JURISDICTION, OBTAIN PERMITS OR LICENSES <br />NECESSARY TO CARRY OUT THIS WORK AND PAY ALL FEES THEREFORE. THE <br />CONTRACTOR SHALL ARRANGE FOR INSPECTION AND TESTS OF ANY OR ALL PARTS OF <br />THE WORK IF SO REQUIRED BY AUTHORITIES AND PAY ALL CHARGES FOR THE SAME. THE <br />CONTRACTOR SHALL PAY ALL COSTS FOR, AND FURNISH TO THE OWNER BEFORE FINAL <br />BILLING, ALL CERTIFICATES NECESSARY AS EVIDENCE THAT THE WORK INSTALLED <br />CONFORMS WITH ALL REGULATIONS WHERE THEY APPLY TO THIS WORK. <br />2.SHOP DRAWINGS <br />2.1.PRIOR TO THE INSTALLATION OF ANY WORK AND PROCUREMENT OF EQUIPMENT, <br />CONTRACTOR SHALL PROVIDE COMPLETE SETS OF COORDINATED SHOP DRAWINGS OF <br />ALL NEW AND EXISTING EQUIPMENT, INDICATING CAPACITY, DIMENSIONS AND SEQUENCE <br />OF OPERATION FOR WRITTEN APPROVAL BY THE ENGINEER. <br />2.2.INDICATE ON EACH SHOP DRAWINGS SUBMITTED: <br />2.2.1.PROJECT NAME AND LOCATION <br />2.2.2.NAME OF ENGINEER <br />2.2.3.ITEM IDENTIFICATION <br />2.2.4.APPROVAL STAMP OF PRIME CONTRACTOR <br />3.AS-BUILT DRAWINGS AND EQUIPMENT OPERATIONAL INSTRUCTIONS <br />3.1.UPON COMPLETION AND ACCEPTANCE OF WORK, CONTRACTOR SHALL FURNISH WRITTEN <br />INSTRUCTIONS AND EQUIPMENT MANUALS AND DEMONSTRATE TO THE OWNER THE <br />PROPER OPERATION AND MAINTENANCE OF ALL EQUIPMENT AND APPARATUS FURNISHED <br />UNDER THIS CONTRACT. <br />3.2.THESE INSTRUCTIONS SHALL BE TYPED ON 8-1/2 IN. X 11 IN. PAPER AND BOUND IN THREE <br />RING BINDERS WITH CLEAR ACETATE COVERS. CONTRACTOR SHALL GIVE THREE COPIES <br />OF THE INSTRUCTIONS TO THE OWNER AND ONE COPY TO THE ENGINEER. PROVIDE PDF <br />ELECTRONIC COPY OF ALL PAPER INSTRUCTIONS. <br />3.3.THE INSTRUCTION BOOKLET SHALL BEAR THE NAME, ADDRESS AND TELEPHONE NUMBER <br />OF THE PROJECT AND ENGINEER. <br />3.4.REPRODUCIBLE "AS-BUILT" DRAWINGS SHALL BE PROVIDED IN FULL SIZE HARD COPY AND <br />ON ELECTRONIC COPY ON A PORTABLE DRIVE (AUTOCAD 2020 OR LATER) INDICATING THE <br />AS INSTALLED CONDITIONS OF THE WORK. "AS-BUILT" DRAWINGS SHALL BE PROVIDED TO <br />THE OWNER AFTER COMPLETION OF THE INSTALLATION. <br />4.GENERAL PROVISIONS FOR ELECTRICAL WORK: <br />4.1.SPECIFICATIONS ARE OF SIMPLIFIED FORM AND INCLUDE INCOMPLETE SENTENCES. <br />WORDS OR PHRASES SUCH AS "THE CONTRACTOR SHALL," "SHALL BE," "FURNISH," <br />"PROVIDE," "A," "THE," AND "ALL" HAVE BEEN OMITTED FOR BREVITY. <br />4.2.DEFINITIONS: <br />4.2.1."PROVIDE": TO SUPPLY, INSTALL AND CONNECT UP COMPLETE AND READY FOR SAFE <br />AND REGULAR OPERATION THE PARTICULAR WORK REFERRED TO UNLESS SPECIFICALLY <br />OTHERWISE NOTED. <br />4.3.GENERAL <br />4.3.1.THE DRAWINGS SHOW THE APPROXIMATE LOCATION OF ALL APPARATUS. THE EXACT <br />LOCATIONS OF WHICH ARE SUBJECT TO THE APPROVAL OF THE OWNER WHO RESERVES <br />THE RIGHT TO MAKE ANY REASONABLE CHANGES IN THE LOCATION WITHOUT EXTRA COST. <br />WHILE THE GENERAL RUN OF CONDUIT AND CABLES MAY BE INDICATED ON THE <br />DRAWINGS, IT IS NOT INTENDED THAT THE EXACT ROUTING OR LOCATIONS OF CONDUIT & <br />CABLES BE DETERMINED THEREFROM. <br />4.3.2.THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL REQUIRED BENDS, <br />OFFSETS, PULL BOXES AND CLEARING OBSTRUCTIONS IT SHALL BE RESPONSIBILITY OF <br />THE CONTRACTOR TO CONFORM TO THE STRUCTURE, MAINTAIN HEADROOM AND KEEP <br />OPENINGS AND PASSAGEWAYS CLEAR <br />4.3.3.THE CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATE WITH ALL TRADES <br />4.3.4.THE CONTRACTOR SHALL BE RESPONSIBLE FOR CLEAN-UP AND REMOVAL FROM THE <br />SITE OF RESULTING DEBRIS. <br />4.4.TEMPORARY LIGHT AND POWER: PROVIDE TEMPORARY LIGHT AND POWER SYSTEMS AT <br />EARLIEST POSSIBLE DATE WITHIN THE CONSTRUCTION AREAS FOR THE REQUIREMENTS OF <br />ALL TRADES AS HEREIN DESCRIBED. EXTEND SYSTEMS TO NEW CONSTRUCTION AS SOON <br />AS PHYSICALLY POSSIBLE. MAINTAIN SYSTEM DURING WORKING HOURS OF ALL TRADES. <br />PROVIDE ALL REQUIRED MAINTENANCE, INCLUDING LAMPS AND SOCKETS. <br />4.5.UL CERTIFICATION SHALL BE PROVIDED TO EQUIPMENT IN CASE OF FIELD MODIFICATIONS. <br />4.6.QUALITY ASSURANCE <br />4.6.1.QUALITY AND GAUGE OF MATERIALS: NEW, BEST OF THEIR RESPECTIVE KINDS, FREE <br />FROM DEFECTS AND LISTED BY UNDERWRITERS LABORATORIES, INC., OR OTHER <br />NATIONALLY APPROVED TESTING AGENCY AND BEARING THEIR LABEL. MATERIALS AND <br />EQUIPMENT OF SIMILAR APPLICATION SHALL BE OF SAME MANUFACTURER, EXCEPT AS <br />NOTED. <br />4.7.MATERIALS <br />4.7.1.NAMEPLATES: PROVIDE BLACK LAMICOID SHEET WITH 3/4 IN. WHITE LETTERING, <br />FASTENED WITH EPOXY CEMENT FOR EACH DISCONNECT SWITCH, CIRCUIT BREAKER, <br />PANEL, CABINET, ENCLOSURE, AND THE LIKE. NAMEPLATES SHALL DESCRIBE THE NAME <br />AND NUMBER OF EACH COMPONENT. <br />4.7.2.CABLE TAGS: TAG EACH CONDUCTOR PASSING THROUGH SPLICE OR PULLBOX WITH <br />A WHITE LINEN TAG, INDICATING POINT OF ORIGIN AND TERMINATION OF THE CIRCUIT. <br />5.GROUNDING <br />5.1.ELECTRICAL COMPONENTS, DEVICES, AND ACCESSORIES SHALL BE LISTED AND LABELED <br />UNDER UL 467 AS DEFINED IN NFPA 70, ARTICLE 100, BY A TESTING AGENCY ACCEPTABLE <br />TO AUTHORITIES HAVING JURISDICTION, AND MARKED FOR INTENDED USE. <br />5.2.GROUNDING CONDUCTORS <br />5.2.1.FOR INSULATED CONDUCTORS, COMPLY WITH PARAGRAPH "CONDUCTORS AND <br />CABLES." <br />5.2.2.MATERIAL: COPPER. <br />5.2.3.EQUIPMENT GROUNDING CONDUCTORS: INSULATED WITH GREEN-COLORED <br />INSULATION. <br />5.2.4.GROUNDING ELECTRODE CONDUCTORS: STRANDED CABLE. <br />5.3.GROUNDING CONNECTOR PRODUCTS <br />5.3.1.COMPLY WITH IEEE 837 AND UL 467; LISTED FOR USE FOR SPECIFIC TYPES, SIZES, <br />AND COMBINATIONS OF CONDUCTORS AND CONNECTED ITEMS. <br />5.3.2.CONNECTORS: BOLTED-PRESSURE-TYPE CONNECTORS SHALL BE PROVIDED FOR <br />ONLY CONDUCTORS #10 AND SMALLER. ALL OTHER CONNECTORS SHALL BE COMPRESSION <br />TYPE. <br />5.4.GROUNDING EXECUTION <br />5.4.1.IN ALL RACEWAYS, USE INSULATED EQUIPMENT GROUNDING CONDUCTORS. <br />5.4.2.EXOTHERMIC-WELDED CONNECTIONS: USE FOR CONNECTIONS TO STRUCTURAL <br />STEEL ONLY. ALL OTHER CONNECTIONS SHALL BE SWAGE HYDRAULIC COMPRESSION <br />FITTINGS. <br />5.4.3.BONDING STRAPS AND JUMPERS: INSTALL SO VIBRATION BY EQUIPMENT MOUNTED <br />ON VIBRATION ISOLATION HANGERS OR SUPPORTS IS NOT TRANSMITTED TO RIGIDLY <br />MOUNTED EQUIPMENT. BOND STRAPS DIRECTLY TO THE BASIC STRUCTURE TAKING CARE <br />NOT TO PENETRATE ANY ADJACENT PARTS. INSTALL STRAPS ONLY IN LOCATIONS <br />ACCESSIBLE FOR MAINTENANCE. <br />5.4.4.CONNECTIONS: MAKE CONNECTIONS SO GALVANIC ACTION OR ELECTROLYSIS <br />POSSIBILITY IS MINIMIZED. SELECT CONNECTORS, CONNECTION HARDWARE, <br />CONDUCTORS, AND CONNECTION METHODS SO METALS IN DIRECT CONTACT WILL BE <br />GALVANICALLY COMPATIBLE. <br />5.4.5.ALL CONDUIT TERMINATION SHALL BE BONDED TO THE EQUIPMENT GROUNDING <br />CONDUCTOR USING A GROUNDING BUSHING WITH LAY-IN LUG AND PROPERLY SIZED <br />GROUND WIRE. <br />6.SUPPORT, ANCHORAGE, AND ATTACHMENT <br />6.1.MODULE CLAMPS, NUTS, CAM BRACKET, BASE, MLPE BRACKETS, RAILS, BASES, WASHERS, <br />WIND DEFLECTORS, AND ALL OTHER RACKING COMPONENTS AS REQUIRED SHALL BE <br />SUPPLIED AND COORDINATED BY THE RACKING MANUFACTURER AND INSTALLED BY <br />ELECTRICAL CONTRACTOR. REFER TO RACKING DRAWINGS FOR INSTALLATION MEANS AND <br />METHODS AND SCOPE OF WORK. RACKING MANUFACTURER SHALL PERFORM DYNAMIC <br />WIND TESTS WITH THE SELECTED MODULE AND SHALL INDICATE COMPATIBILITY OF <br />MODULE, COORDINATED BY CONTRACTOR. REQUIRED TORQUE VALUES SHALL BE <br />DOCUMENTED AND COORDINATED. <br />6.2.PROVIDE SUPPORTS FOR ALL RACEWAYS AS REQUIRED PER NEC, PROVIDE MATERIALS, <br />SIZES AND TYPES OF ANCHORS, AND FASTENERS TO CARRY THE LOADS OF EQUIPMENT <br />AND CONDUIT. HANGERS OR SUPPORTS SHALL BE INSTALLED AT THE HORIZONTAL OR <br />VERTICAL POINT OF CHANGE IN DIRECTION OF ALL CONDUIT RUNS. <br />6.3.THE FOLLOWING SUPPORT ITEMS SHALL BE HOT DIPPED GALVANIZED FINISH: STRUT, <br />CONDUIT STRAPS, BOLT ROD, THREADED BEAM CLAMPS, RISER CLAMPS, WALL PLATES, <br />SHALL BE HOT DIPPED GALVANIZED FINISH. <br />6.4.THE FOLLOWING HARDWARE SHALL BE 316, 312, 308 OR 18-8 STAINLESS STEEL: BOLTS, <br />U-BOLTS, NUTS, WASHERS, SPRING WASHERS, CHANNEL NUT WITH SPRING, FENDER <br />WASHER, FLAT WASHER, PV MODULE CLIPS, AND OTHER ASSOCIATED HARDWARE. <br />6.5.SPRING STEEL, ELECTRO GALVANIZED, AND ZINC PLATED HARDWARE OR SUPPORTS <br />SHALL NOT BE ACCEPTABLE ALTERNATIVE TO THE ABOVE. <br />6.6.STRUT SHALL BE 12-GAUGE STEEL CHANNELS 1-5/8"X1-5/8", WITH HOLES ON TOP SURFACE, <br />2 INCHES ON CENTER. <br />6.7.STRUT FITTINGS AND ACCESSORIES SHALL MATE AND MATCH WITH STRUT. PROVIDE <br />ANGLES AND OTHER STANDARD STRUCTURAL SHAPES. CONNECT WITH MACHINE BOLTS <br />TO FORM RIGID, BONDED SUPPORT STRUCTURES. <br />6.8.APPLY CORROSION-RESISTANT FINISH TO FIELD-CONNECTIONS, AFTER CUTTING AND <br />THREADING, AND BURIED METALLIC GROUNDING AND BONDING PRODUCTS, AND PLACES <br />WHERE FACTORY APPLIED PROTECTIVE COATINGS HAVE BEEN DESTROYED, WHICH ARE <br />SUBJECTED TO CORROSIVE ACTION. APPLY CORROSION INHIBITOR TO RACKING AS <br />RECOMMENDED BY RACKING MANUFACTURER. <br />6.9.RATED STRENGTH: ADEQUATE IN TENSION, SHEAR, AND PULLOUT FORCE TO RESIST <br />MAXIMUM LOADS CALCULATED OR IMPOSED UNDER THIS PROJECT, WITH A MINIMUM <br />STRUCTURAL SAFETY FACTOR OF FIVE TIMES THE APPLIED FORCE. <br />6.10.STEEL SLOTTED SUPPORT SYSTEMS: COMPLY WITH MFMA-3, FACTORY-FABRICATED <br />COMPONENTS FOR FIELD ASSEMBLY, AND PROVIDE FINISH SUITABLE FOR THE <br />ENVIRONMENT IN WHICH INSTALLED. SELECT CHANNEL DIMENSIONS FOR STRUCTURAL <br />LOADING. <br />6.11.RACEWAY AND CABLE SUPPORTS: AS DESCRIBED IN NECA 1. <br />6.12.CONDUIT AND CABLE SUPPORT DEVICES: STAINLESS STEEL HANGERS, CLAMPS, AND <br />ASSOCIATED FITTINGS, DESIGNED FOR TYPES AND SIZES OF RACEWAY OR CABLE TO BE <br />SUPPORTED. <br />6.13.STRUCTURAL STEEL FOR FABRICATED SUPPORTS AND RESTRAINTS: ASTM A 36/A 36M, <br />STEEL PLATES, SHAPES, AND BARS; GALVANIZED. <br />6.14.FURNISH AND INSTALL POSITIVE LOCKING OF ALL SYSTEM NUTS AND FASTENERS. PROVIDE <br />DOUBLE NUTS, LOCK WASHERS OR LOCKNUTS ON ALL SUSPENDED LOADS SUPPORTS. <br />FINISH TO MATCH APPLICATION. <br />6.15.TORQUE ALL CONNECTIONS MEETING MANUFACTURER RECOMMENDATIONS AND APPLY <br />TORQUE MARKING ON ALL CONNECTIONS. <br />6.16.CABLE TIES SHALL BE SUNLIGHT RESISTANT AND RATED FOR OUTDOOR USE. <br />7.CONDUCTORS AND CABLES <br />7.1.MATERIALS <br />7.1.1.CONDUCTOR MATERIAL: COPPER COMPLYING WITH NEMA WC 7; ALL CONDUCTORS <br />SHALL BE SINGLE STRANDED. <br />7.1.2.CONDUCTOR INSULATION TYPES: CONDUCTORS SHALL HAVE 600V INSULATION TYPE <br />XHHW-2 AND SHALL BE 90C RATED. <br />7.1.3.MINIMUM SIZE #12 AWG UNLESS OTHERWISE NOTED. <br />7.1.4.DC CONDUCTOR STRING CABLING SHALL BE 7-STRAND (CLASS B) #10AWG MINIMUM: <br />COPPER, STRANDED UL4703 AS XLP/USE-2 OR RHH/RHW-2 90C, 2000V. UV RATED. <br />7.1.5.DC CONDUCTOR ABOVE #10: COPPER OR ALUMINUM AS INDICATED, CLASS B <br />STRANDED UL4703 AS XLP/USE-2 OR RHH/RHW-2 90C, 2000V. UV RATED. <br />7.2.CONDUCTOR CONNECTORS AND SPLICES <br />7.2.1.DESCRIPTION: FACTORY-FABRICATED CONNECTORS AND SPLICES OF SIZE, <br />AMPACITY RATING, MATERIAL, TYPE, AND CLASS FOR APPLICATION AND SERVICE <br />INDICATED. <br />7.3.CONDUCTOR INSTALLATION <br />7.3.1.USE MANUFACTURER-APPROVED PULLING COMPOUND OR LUBRICANT WHERE <br />NECESSARY; COMPOUND USED MUST NOT DETERIORATE CONDUCTOR OR INSULATION. <br />DO NOT EXCEED MANUFACTURER'S RECOMMENDED MAXIMUM PULLING TENSIONS AND <br />SIDEWALL PRESSURE VALUES. <br />7.3.2.USE PULLING MEANS INCLUDING FISH TAPE, CABLE, ROPE, AND BASKET-WEAVE <br />WIRE/CABLE GRIPS THAT WILL NOT DAMAGE CABLES OR RACEWAY. <br />7.3.3.MAKE SPLICES AND TAPS THAT ARE COMPATIBLE WITH CONDUCTOR MATERIAL AND <br />THAT POSSESS EQUIVALENT OR BETTER MECHANICAL STRENGTH AND INSULATION <br />RATINGS THAN UNSPLICED CONDUCTORS. <br />7.3.4.WIRE SIZES SHOWN ON PLANS MAY BE OVERSIZED TO ACCOMMODATE VOLTAGE <br />DROP. CONTRACTOR MAY ELECT TO REDUCE WIRE SIZE WIRE AT SOURCE AND/OR <br />APPLIANCE IN A LISTED MANNER COMPLIANT WITH THE CODE THAT MAY INCLUDE BUT NOT <br />BE LIMITED TO THE INSTALLATION OF JUNCTION BOXES WHICH MAY NOT BE SHOWN ON <br />THE PLAN. <br />7.3.5.INCREASED CONDUCTOR SIZES SHALL BE COORDINATED WITH TERMINAL SIZES OF <br />EQUIPMENT. CONTRACTOR SHALL PROVIDE LISTED MEANS TO INCREASE CONDUCTOR SIZE <br />WITHIN THE TERMINALS SUCH AS A FERRULE, COMPRESSION SLEEVE, OR OTHER MEANS <br />TO REDUCE CONDUCTOR SIZE COMPATIBLE WITH MECHANICAL TERMINALS. <br />7.3.6.ALL GROUNDING CONDUCTORS SHALL BE SOFT DRAWN. <br />8.RACEWAYS AND BOXES <br />8.1.MATERIALS <br />8.1.1.EMT: ANSI C80.3. <br />8.1.2.FLEXIBLE METAL CONDUIT,EMT, FMC: GALVANIZED STEEL TUBING COVERED WITH A <br />LIQUID TIGHT POLYVINYL JACKET. <br />8.1.3.EMT, POLYVINYL CHLORIDE, PVC SCHEDULE 40: UL 651 <br />8.1.4.FITTINGS FOR CONDUIT (INCLUDING ALL TYPES AND FLEXIBLE AND LIQUIDTIGHT), <br />RGS, AND CABLE: NEMA FB 1; LISTED FOR TYPE AND SIZE RACEWAY WITH WHICH USED, <br />AND FOR APPLICATION AND ENVIRONMENT IN WHICH INSTALLED. <br />8.2.RACEWAY APPLICATION <br />8.2.1.RACEWAY FITTINGS: COMPATIBLE WITH RACEWAYS AND SUITABLE FOR USE AND <br />LOCATION. <br />8.2.2.BELOW GRADE: PVC SCHEDULE 40 CONDUIT NEMA TC2 UL 651, WITH NEMA TC 3 AND <br />UL 51413 FITTINGS. <br />8.2.3.ABOVE GRADE: EMT <br />8.2.4.JOIN RACEWAYS WITH FITTINGS DESIGNED AND APPROVED FOR THE PURPOSE AND <br />MAKE JOINTS AND TERMINATIONS TIGHT. WHERE JOINTS CANNOT BE MADE TIGHT, USE <br />BONDING JUMPERS TO PROVIDE ELECTRICAL CONTINUITY OF THE METALLIC RACEWAY <br />SYSTEM. <br />8.2.5.USE GASKETED LOCKNUTS OR HUBS TO FASTEN CONDUIT TO BOXES IN DAMP AND <br />WET LOCATIONS WHICH ALLOW THE EQUIPMENT TO MAINTAIN ITS NEMA WEATHERPROOF <br />RATING. <br />8.2.6.PVC CONDUIT TRANSITIONS BETWEEN TWO FIXED POINTS (INCLUDING FROM BELOW <br />GRADE) SHALL INCLUDE CONDUIT EXPANSION FITTING. <br />8.2.7.EXPANSION FITTINGS SHALL BE PROVIDED ACROSS EXPANSION JOINTS. EXPANSION <br />FITTINGS SHALL HAVE INTEGRAL BONDING JUMPER. <br />8.2.8.ALL FITTINGS ON EQUIPMENT SHALL BE LISTED TO UL514B AND SHALL BE RATED TO <br />MAINTAIN THE EQUIPMENT NEMA RATING. <br />8.2.9.PROVIDE NYLON INSULATION BUSHINGS TO PROTECT CONDUCTORS. <br />8.2.10.CUT CONDUIT SQUARE USING SAW OR PIPE CUTTER AND DE-BURR CUT ENDS. <br />8.3.BOXES <br />8.3.1.ALL JUNCTION BOXES FURNISHED BY CONTRACTOR IN NON-CLASSIFIED AREAS <br />SHALL BE NEMA 4X OUTDOORS. <br />9.IDENTIFICATION OF EQUIPMENT/SIGNAGE <br />9.1.LABELS SHALL BE EITHER ENGRAVED, PRINTED OR PLATED AND BE OF METALLIC OR <br />PLASTIC VINYL CONSTRUCTION SUCH THAT IT IS WEATHERPROOF, CORROSION PROOF, <br />UV-STABILIZED AND FADE RESISTANT. <br />9.2.LABEL ATTACHMENT, ADHESIVE, STOCK, AND LAMINATION SHALL BE LISTED TO UL 969. <br />9.3.ALL LABELS SHALL BE DESIGNED AND USE COLORS, SYMBOLS, AND WORDING AS DEFINED <br />IN ANSI Z535. <br />9.4.TEXT SHALL BE AS SHOWN BUT TEXT HEIGHT SHALL BE A MINIMUM OF 3/8" FOR TITLES (I.E. <br />"WARNING") AND 3/16" HIGH FOR DATA. <br />9.5.LABELS SHALL BE INSTALLED AT THE LOCATIONS INDICATED AND AS REQUIRED BY THE <br />NEC. <br />9.6.ALL MAJOR EQUIPMENT SHALL BE FIELD LABELED USING NAMES INDICATED ON DRAWINGS. <br />9.7.AT ALL TERMINAL BLOCKS AND HOME RUN LOCATIONS, DC CONDUCTORS SHALL BE <br />LABELED WITH MARKING TAPE IDENTIFYING '+' AND '-' FOR THE POSITIVE AND NEGATIVE <br />CIRCUIT NUMBERS. <br />9.8.ALL LABELING SHALL COMPLY WITH REQUIREMENTS OF NEC 690, UL, NFPA 70E, ANSI, <br />OSHA, AND IEEE REQUIREMENTS. <br />10.LOW VOLTAGE DISTRIBUTION EQUIPMENT <br />10.1.DISCONNECT SWITCHES SHALL BE FUSED OR NONFUSED, AS NOTED. VOLTAGE SHALL BE <br />AS REQUIRED. SWITCHES SHALL BE HEAVY DUTY AND HORSEPOWER RATED FOR MOTOR <br />LOADS. <br />10.1.1.KNIFE-BLADE TYPE SWITCHES SHALL BE LOAD BREAK, <br />QUICK-MAKE-QUICK-BREAK WITH ARC QUENCHERS, UL CLASS R UP TO 600A. SWITCHES <br />SHALL BE SIMILAR TO EATON DH36, UNLESS OTHERWISE NOTED. <br />10.2.SWITCHBOARDS <br />10.2.1.PROVIDE BY SIEMENS, SQUARE-D, EATON, GE, OR SIMILAR. <br />10.2.2.THIS CRITERIA APPLIES TO ALL DISTRIBUTION EQUIPMENT WITH AN AMPERE <br />RATING EQUAL TO AND GREATER THAN 800A. PROVIDE AMPERE RATING AS NOTED WITH A <br />SHORT CIRCUIT WITHSTAND RATING OF 200,000A. <br />10.2.3.BUS BARS: PROVIDE HARD DRAWN COPPER, MINIMUM 98% CONDUCTIVITY, <br />SILVER OR TIN PLATED AT JOINTS. CAPACITY SHALL BE AS NOTED. RATINGS FOR MAINS: <br />MINIMUM SHALL BE EQUAL TO SIZE OF MAIN DISCONNECT OR SUPPLY FEEDER PROTECTIVE <br />DEVICE AND CONTINUOUS FULL CAPACITY THROUGHOUT SWITCHBOARD. <br />10.2.4.SECTIONS: PROVIDE FULL BUS DISTRIBUTION RATING FOR INDICATED <br />AMPACITY. <br />10.2.5.GROUND BUS: GROUND SHALL BE 25% OF MAINS BUT NOT LESS THAN 1/2 SQ. <br />IN. EXTEND LENGTH OF SWITCHBOARD AND BOLT TO EACH SECTION. LOCATE TO PERMIT <br />DRILLING FOR FUTURE EXTENSION. IN SERVICE SWITCHBOARDS, CONNECT TO NEUTRAL <br />BUS WITH DISCONNECTING LINK. <br />10.2.6.ENCLOSURE: PROVIDE FRONT ACCESSIBLE GROUP MOUNTED DEVICES. <br />PROVIDE SWITCHING UNITS: AS INDICATED. METAL-ENCLOSED STRUCTURE SHALL BE <br />BOLTED OR WELDED STEEL FRAMING OF SUFFICIENT STRENGTH TO MAINTAIN ALIGNMENT <br />AND WITHSTAND RATED A.I.C. PANELS: PROVIDE PAN TYPE CONSTRUCTION, LOUVERED, <br />MINIMUM NO. 12 USSG STEEL WITH HINGED ACCESS COVERS. PULL BOX (CROWN BOX): <br />ENCLOSURE CONSTRUCTION SHALL BE THE SAME AS SWITCHBOARD WITH REMOVABLE <br />COVERS. BOTTOM SHALL HAVE A MINIMUM 1 IN. APPROVED INSULATING MATERIAL WITH <br />INDIVIDUAL CABLE OPENINGS AND SHALL BE FULLY ACCESSIBLE. CABLE SUPPORTS SHALL <br />BE INSULATED. <br />10.2.7.FINISH SHALL BE RUST-RESISTIVE BAKED-ON PRIMER AND FINISH COAT OF <br />MANUFACTURER'S SWITCHBOARD GRAY LACQUER, EXCEPT AS NOTED. PROVIDE <br />NAMEPLATES FOR SWITCHBOARD, SWITCHING UNITS AND DEVICES. <br />10.2.8.CURRENT TRANSFORMER CABINETS: PROVIDE IN ACCORDANCE WITH RULES <br />OF UTILITY COMPANY AND SUBJECT TO ITS APPROVAL. METER PANS: PROVIDE <br />TRANSFORMER TYPE WITH 10-POINT TEST BLOCK COMPLYING WITH UTILITY STANDARDS. <br />10.2.9.PROVIDE SWITCHBOARD WITH HEATER PACKAGE CONTROLLED VIA HUMIDISTAT <br />AND THERMOSTAT. <br />10.2.10.SWITCHBOARD SHALL BE SERVICE ENTRANCE RATED. <br />10.3.PANELBOARDS <br />10.3.1.BUS BARS SHALL BE HARD DRAWN COPPER, MINIMUM 98 PERCENT <br />CONDUCTIVITY. FOR BLANK (SPACE) COMPARTMENTS, PROVIDE FULL RATED BUS. MINIMUM <br />GUTTER SPACES SHALL BE 5-3/4 I. SIDES, TOP AND BOTTOM, INCREASE FOR THROUGH <br />FEEDERS. GROUND, PHASE, AND NEUTRAL BUS SHALL BE COPPER DIRECTORY HOLDER <br />SHALL BE METAL FRAME WITH CLEAR PLASTIC, TRANSPARENT COVER. PROVIDE A <br />TYPEWRITTEN PANEL SCHEDULE INDICATING FEEDER SIZE, FEEDER MATERIAL, CONDUIT <br />SIZE, CIRCUIT NUMBERS, LOADS SERVED AND THEIR LOCATIONS. <br />10.3.2.ALL PANELBOARDS SHALL HAVE INTEGRAL SURGE PROTECTION DEVICE (SPD) <br />OF A NOMINAL DISCHARGE RATING OF 100kA OR AS IDENTIFIED LISTED TO UL1449. WHERE <br />'HYBRID SPD' IS IDENTIFIED ON PLAN, PROVIDE A SPD LISTED TO UL1283, MIL-STD-220A <br />WITH 100kHz ATTENUATION OF OVER 40dB, AND IEEE 62.41 CATEGORY B3 RINGWAVE <br />SHOULD BE <200V L-N. <br />10.3.3.ALL BUS RATINGS SHALL BE 400A OR GREATER AS IDENTIFIED. <br />10.3.4.PANELBOARDS SHALL BE NEMA 3R WHERE LOCATED OUTDOORS. PROVIDE <br />SURFACE MOUNTED. <br />10.3.5.MAINS SHALL BE COMPRESSION LUG TYPE. <br />10.3.6.ALL MAINS SHALL BE UL489 LISTED AND BE PROVIDED WITH AN LSIG TRIP UNIT. <br />10.3.7.PANELBOARDS SHALL BE NEMA PB 1 DISTRIBUTION TYPE, WITH ALL BRANCH <br />CIRCUIT BREAKERS AS THE BOLT-ON TYPE. ALL PANELBOARDS SHALL BE PROVIDED WITH <br />DOOR-IN-DOOR CONSTRUCTION. <br />10.4 TRANSFORMERS <br />10.4.1 TRANSFORMERS SHALL BE OPEN VENTILATED, DRY TYPE, CLASS 220 INSULATION, <br /> 115 DEGREE TEMPERATURE RISE. <br />10.4.2 TRANSFORMER SHALL BE COMPLETELY ENCLOSED EXCEPT FOR VENTILATING <br /> OPENINGS. <br />10.4.3 WINDINGS SHALL BE COPPER. <br />10.4.4 PRIMARY AND SECONDARY WINDING SHALL BE DELTA AND WYE, UON. <br />10.4.5 PROVIDE PRIMARY TAPS: 6-1/2% TAPS, 2 ABOVE AND 4 BELOW RATED VOLTAGE. <br />10.4.6 HARMONIC CAPABILITY SHALL BE 'K9'. <br />10.4.7 TRANSFORMER TO COMPLY WITH ANSI C57.96-01.250. <br />11.TESTING <br />11.1.ALL DC CONDUCTORS SHALL BE TESTED PER NETA 100.1 INSULATION RESISTANCE TEST <br />AND SHALL READ GREATER THAN 100MOHM. <br />11.2.PROVIDE FALL OF POTENTIAL 3-POINT TEST INDICATING GROUND RESISTANCE OF LESS <br />THAN 10 OHMS. <br />11.3.GROUNDING SHALL BE INSTALLED AS INDICATED AND REFLECTED ON STEP AND TOUCH <br />POTENTIAL RISE STUDY PER IEEE 80. <br />J: <br />\ <br />2 <br />0 <br />2 <br />4 <br />b <br />\ <br />2 <br />0 <br />2 <br />4 <br />- <br />0 <br />0 <br />6 <br />7 <br />. <br />1 <br />1 <br />- <br />r <br />e <br />d <br />_ <br />b <br />u <br />l <br />l <br />_ <br />e <br />l <br />e <br />c <br />t <br />r <br />a <br />d <br />a <br />_ <br />s <br />a <br />n <br />t <br />a <br />_ <br />a <br />n <br />a <br />\ <br />1 <br />0 <br />- <br />d <br />e <br />s <br />i <br />g <br />n <br />\ <br />D <br />r <br />a <br />w <br />i <br />n <br />g <br />s <br />\ <br />w <br />o <br />r <br />k <br />i <br />n <br />g <br />d <br />o <br />c <br />u <br />m <br />e <br />n <br />t <br />s <br />\ <br />S <br />H <br />E <br />E <br />T <br />S <br />\ <br />L <br />A <br /> <br />M <br />I <br />R <br />A <br />D <br />A <br />\ <br />E <br />L <br />E <br />C <br />T <br />R <br />I <br />C <br />A <br />L <br />\ <br />E <br />V <br />- <br />0 <br />7 <br />. <br />d <br />w <br />g <br /> <br /> <br />2 <br />0 <br />2 <br />6 <br />- <br />0 <br />1 <br />- <br />1 <br />4 <br />Project Title: <br />Drawing Title: <br />RevisionDateNo. <br />Date: <br />Drawn: <br />Checked: <br />Job No: <br />Scale: <br />Drawing No: <br />SHT:OF <br />BURNS ENGINEERING, INC. | 310-439-5643 <br />300 NORTH CONTINENTAL BLVD SUITE 540 <br />EL SEGUNDO, CA 90245 <br />10 <br />RED BULL <br />ELECTRADA <br />EV CHARGING <br />SANTA ANA <br />1900 EAST DEERE AVE, SANTA ANA, CA92705 <br />ADDRESS: <br />1 06/24/2025 CD30 <br />2 07/02/2025 CD90 <br />3 07/15/2025 ISSUE FOR PERMIT <br />4 01/14/2026 PLAN CHECK COMMENTS <br />ELECTRICAL <br />SPECIFICATIONS <br />1/14/2026 <br />AS NOTED <br />CS <br />IB <br />2024.0067.11 <br />EV-07 <br />EV <br />- <br />0 <br />7 <br />. <br />D <br />W <br />G <br />7