SPECIFICATIONS TABLE OF CONTENTS
<br />1. MANUFACTURERS:
<br />a. O-Z/GEDNEY CO.
<br />b. THOMAS & BETTS
<br />c. APPLETON ELECTRIC
<br />d. ELECTROLINE
<br />e. BRIDGEPORT
<br />f. MIDWEST
<br />g. REGAL
<br />h. ORBIT INDUSTRIES
<br />i. OR APPROVED EQUAL.
<br />2.4 LIQUIDTIGHT FLEXIBLE METALLIC CONDUIT (LFMC) AND FITTINGS
<br />A. MANUFACTURERS:
<br />1. ANACONDA TYPE UA
<br />2. ELECTRI-FLEX TYPE LA
<br />3. ALFLEX
<br />4. CARLON (LAMSON & SESSIONS)
<br />5. OR APPROVED EQUAL.
<br />B.CONSTRUCTION: FLEXIBLE STEEL, APPROVED FOR CONDUIT GROUND, ZINC COATED,
<br /> THREADLESS TYPE FORMED FROM A CONTINUOUS LENGTH OF SPIRALLY WOUND,
<br /> INTERLOCKED ZINC COATED STRIP STEEL AND AN EXTRUDED PVC COVER.
<br />C.FITTINGS AND CONDUIT BODIES:
<br />1. WATERTIGHT, COMPRESSION TYPE, GALVANIZED ZINC COATED CADMIUM PLATED
<br />MALLEABLE CAST IRON, UL LISTED.
<br />2. FITTINGS AND CONDUIT BODIES SHALL INCLUDE PLASTIC OR CAST METAL INSERTS
<br />SUPPLIED BY THE MANUFACTURER TO PROTECT CONDUCTORS FROM SHARP EDGES.
<br />3. MANUFACTURERS:
<br />a. APPLETON ELECTRIC
<br />b. O-Z/GEDNEY CO.
<br />c. ELECTROLINE
<br />d. BRIDGEPORT
<br />e. THOMAS & BETTS
<br />f. MIDWEST
<br />g. REGAL
<br />h. CARLON (LAMSON & SESSIONS)
<br />i. ORBIT INDUSTRIES
<br />j. OR APPROVED EQUAL.
<br />2.5 OUTLET BOXES
<br />A. SHEET METAL OUTLET BOXES: ANSI/NEMA OS 1; GALVANIZED STEEL, 16 GAUGE
<br />(APPROXIMATELY 0.0625 INCHES), WITH 1/2-INCH MALE FIXTURE STUDS WHERE REQUIRED.
<br />B. CAST BOXES: NEMA FB1, TYPE FD, ALUMINUM, CAST FERALLOY, OR STAINLESS STEEL DEEP
<br />TYPE, GASKETED COVER, THREADED HUBS.
<br />C. OUTLET BOXES FOR LUMINAIRES TO BE NOT LESS THAN 1-1/2" DEEP, DEEPER IF REQUIRED BY
<br />THE NUMBER OF WIRES OR CONSTRUCTION. THE BOX SHALL BE COORDINATED WITH SURFACE
<br />LUMINAIRES TO CONCEAL THE BOX FROM VIEW OR PROVIDE A FINISHED TRIM PLATE.
<br />D. SWITCH OUTLET BOXES FOR LOCAL LIGHT CONTROL SWITCHES, DIMMERS AND OCCUPANCY
<br />SENSORS SHALL BE 4 INCHES SQUARE BY 2-1/8 INCHES DEEP, WITH RAISED COVER TO FIT
<br />FLUSH WITH FINISH WALL LINE. MULTIPLE GANG SWITCH OUTLETS SHALL CONSIST OF THE
<br />REQUIRED NUMBER OF GANG BOXES APPROPRIATE TO THE QUANTITY OF SWITCHES
<br />COMPRISING THE GANG. WHERE WALLS ARE PLASTERED, PROVIDE A PLASTER RAISED COVER.
<br />WHERE SWITCH OUTLET BOXES OCCUR IN EXPOSED CONCRETE BLOCK WALLS, BOXES SHALL
<br />BE INSTALLED IN THE BLOCK CAVITY WITH A RAISED SQUARE EDGE TILE COVER OF SUFFICIENT
<br />DEPTH TO EXTEND OUT TO FACE OF BLOCK OR MASONRY BOXES.
<br />E. OUTLET BOXES FOR TECHNOLOGY ROUGH-INS IN WALLS AND COLUMNS SHALL BE 4-11/16
<br />INCHES SQUARE AND 2-1/8 INCHES DEEP WITH SINGLE GANG RAISED COVER TO FIT FLUSH
<br />WITH FINISHED WALL LINE EQUIPPED WITH FLUSH PLATE.
<br />F. WALL OR COLUMN RECEPTACLE OUTLET BOXES SHALL BE 4 INCHES SQUARE WITH RAISED
<br />COVER TO FIT FLUSH WITH FINISHED WALL LINE. BOXES IN CONCRETE BLOCK WALLS SHALL BE
<br />INSTALLED THE SAME AS FOR SWITCH BOXES IN BLOCK WALLS.
<br />2.6 ECONN; ELECTRICAL CONNECTION
<br />A. ELECTRICAL CONNECTION TO EQUIPMENT AND MOTORS, SIZED PER ELECTRICAL CODE.
<br />COORDINATE REQUIREMENTS WITH CONTRACTOR FURNISHING EQUIPMENT OR MOTOR. REFER
<br />TO SPECIFICATIONS AND GENERAL INSTALLATION NOTES FOR TERMINATIONS TO MOTORS.
<br />2.7 JB; PULL AND JUNCTION BOXES
<br />A. SHEET METAL BOXES: ANSI/NEMA OS 1; GALVANIZED STEEL.
<br />B. SHEET METAL BOXES LARGER THAN 12 INCHES IN ANY DIMENSION THAT CONTAIN
<br />TERMINATIONS OR COMPONENTS: CONTINUOUS HINGED ENCLOSURE WITH 1/4 TURN LATCH
<br />AND WHITE BACK PANEL FOR MOUNTING TERMINAL BLOCKS AND ELECTRICAL COMPONENTS.
<br />C. FLANGED TYPE BOXES SHALL BE USED WHERE INSTALLED FLUSH IN WALL.
<br />2.8 ROUGH-IN
<br />A. PROVIDE WITH ONE (1) FLUSH MOUNT DOUBLE GANG BOX WITH SINGLE GANG PLASTER RING
<br />AND APPROPRIATE COVER PLATE,
<br />B. CONDUIT STUBBED TO ABOVE THE LAY-IN CEILING.
<br />C. RI-TECH; TECHNOLOGY ROUGH-IN:
<br />1. ROUGH-IN SHALL HAVE ONE (1) 1" CONDUIT.
<br />D.RI-TECH-W; TECHNOLOGY ROUGH-IN -WALL PHONE:
<br />1. MOUNT ON WALL +54" OR AS NOTED IN PLANS. ROUGH-IN SHALL HAVE ONE (1) 1" CONDUIT.
<br />E.RI-TECH-C; TECHNOLOGY ROUGH-IN -CEILING FLUSH MOUNTED:
<br />1. MOUNT FLUSH IN FINISHED CEILING OR AS NOTED IN PLANS. ROUGH-IN SHALL HAVE ONE (1)
<br />1" CONDUIT.
<br />2.9 ACCESSORIES
<br />A. FIRE RATED MOLDABLE PADS: UL #9700, MOLDABLE SHEET PUTTY AT REQUIRED THICKNESS ON
<br />ALL FIVE SIDES OF BACK BOXES. KINETICS NOISE CONTROL -ISOBACKER PAD, SPECSEAL -SSP
<br />PUTTY AND PADS, 3M #MPP-4S OR EQUAL.
<br />PART 3 -EXECUTION
<br />3.1 CONDUIT INSTALLATION SCHEDULE AND SIZING
<br />A. IN THE EVENT THE LOCATION OF CONDUIT INSTALLATION REPRESENTS CONFLICTING
<br />INSTALLATION REQUIREMENTS AS SPECIFIED IN THE FOLLOWING SCHEDULE, A CLARIFICATION
<br />SHALL BE OBTAINED FROM THE ARCHITECT/ENGINEER. IF THIS CONTRACTOR IS UNABLE TO
<br />OBTAIN A CLARIFICATION AS OUTLINED ABOVE, CONCEALED RIGID GALVANIZED STEEL
<br />CONDUIT INSTALLED PER THESE SPECIFICATIONS AND THE ELECTRICAL CODE SHALL BE
<br />REQUIRED.
<br />B. INSTALLATION SCHEDULE: REFER TO DRAWINGS.
<br />C. SIZE CONDUIT AS SHOWN ON THE DRAWINGS AND SPECIFICATIONS. WHERE NOT INDICATED IN
<br />THE CONTRACT DOCUMENTS, CONDUIT SIZE SHALL BE ACCORDING TO THE ELECTRICAL CODE.
<br />CONDUIT AND CONDUCTOR SIZING SHALL BE COORDINATED TO LIMIT CONDUCTOR FILL TO
<br />LESS THAN 40%, MAINTAIN CONDUCTOR AMPERE CAPACITY AS REQUIRED BY THE ELECTRICAL
<br />CODE (TO INCLUDE ENLARGED CONDUCTORS DUE TO TEMPERATURE AND QUANTITY
<br />DERATING VALUES) AND TO PREVENT EXCESSIVE VOLTAGE DROP AND PULLING TENSION DUE
<br />TO LONG CONDUIT/CONDUCTOR LENGTHS.
<br />D. MINIMUM CONDUIT SIZE (UNLESS NOTED OTHERWISE):
<br />1. ABOVE GRADE: 3/4 INCH. (THE USE OF 1/2 INCH WOULD BE ALLOWED FOR INSTALLATION
<br />CONDUIT TO INDIVIDUAL FIXTURE WHIPS FROM JUNCTION BOX.)
<br />2. TELECOMMUNICATION CONDUIT: 1 INCH.
<br />3. CONTROLS CONDUIT: 3/4 INCH.
<br />4. MAXIMUM SIZE 1-1/4 INCH FOR CONDUITS CROSSING EACH OTHER.
<br />E.CONDUIT SIZES SHALL CHANGE ONLY AT THE ENTRANCE OR EXIT TO A JUNCTION BOX, UNLESS
<br /> SPECIFICALLY NOTED ON THE DRAWINGS.
<br />3.2 CONDUIT ARRANGEMENT
<br />A. IN GENERAL, CONDUIT SHALL BE INSTALLED CONCEALED IN WALLS, IN FINISHED SPACES AND
<br />WHERE POSSIBLE OR PRACTICAL, OR AS NOTED OTHERWISE. CONDUIT SHALL BE INSTALLED
<br />PARALLEL OR PERPENDICULAR TO WALLS, CEILINGS, AND EXPOSED STRUCTURAL MEMBERS.
<br />IN UNFINISHED SPACES, MECHANICAL AND UTILITY AREAS, CONDUIT MAY RUN EITHER
<br />CONCEALED OR EXPOSED AS CONDITIONS DICTATE AND AS PRACTICAL UNLESS NOTED
<br />OTHERWISE ON DRAWINGS. INSTALLATION SHALL MAINTAIN HEADROOM IN EXPOSED VICINITIES
<br />OF PEDESTRIAN OR VEHICULAR TRAFFIC.
<br />B. CONDUIT RUNS SHALL BE ROUTED AS SHOWN ON LARGE SCALE DRAWINGS. CONDUIT
<br />ROUTING ON DRAWINGS SCALED 1/4"=1'-0" OR LESS SHALL BE CONSIDERED DIAGRAMMATIC,
<br />UNLESS NOTED OTHERWISE. THE CORRECT ROUTING, WHEN SHOWN DIAGRAMMATICALLY
<br />SHALL BE CHOSEN BY THE CONTRACTOR BASED ON INFORMATION IN THE CONTRACT
<br />DOCUMENTS, IN ACCORDANCE WITH MANUFACTURER'S WRITTEN INSTRUCTIONS, APPLICABLE
<br />CODES, THE NECA'S "STANDARD OF INSTALLATION", IN ACCORDANCE WITH RECOGNIZED
<br />INDUSTRY STANDARDS, AND COORDINATED WITH OTHER CONTRACTORS.
<br />C. CONTRACTOR SHALL ADAPT CONTRACTOR'S WORK TO THE JOB CONDITIONS AND MAKE SUCH
<br />CHANGES AS REQUIRED AND PERMITTED BY THE ARCHITECT/ENGINEER, SUCH AS MOVING TO
<br />CLEAR BEAMS AND JOISTS, ADJUSTING AT COLUMNS, AVOIDING INTERFERENCE WITH
<br />WINDOWS, ETC., TO PERMIT THE PROPER INSTALLATION OF OTHER MECHANICAL AND/OR
<br />ELECTRICAL EQUIPMENT.
<br />D. CONTRACTOR SHALL COOPERATE WITH ALL CONTRACTORS ON THE PROJECT. CONTRACTOR
<br />SHALL OBTAIN DETAILS OF OTHER CONTRACTOR'S WORK TO ENSURE FIT AND AVOID
<br />CONFLICT. ANY EXPENSE DUE TO THE FAILURE OF THIS CONTRACTOR TO DO SO SHALL BE PAID
<br />FOR IN FULL BY CONTRACTOR. THE OTHER TRADES INVOLVED AS DIRECTED BY THE
<br />ARCHITECT/ENGINEER SHALL PERFORM THE REPAIR OF WORK DAMAGED AS A RESULT OF
<br />NEGLECT OR ERROR BY THIS CONTRACTOR. THE RESULTANT COSTS SHALL BE BORNE BY THIS
<br />CONTRACTOR.
<br />3.3 CONDUIT SUPPORT
<br />A. CONDUIT RUNS INSTALLED ABOVE A SUSPENDED CEILING SHALL BE PROPERLY SUPPORTED. IN
<br />NO CASE SHALL CONDUIT REST ON THE SUSPENDED CEILING CONSTRUCTION, NOR UTILIZE
<br />CEILING SUPPORT SYSTEM FOR CONDUIT SUPPORT.
<br />• SECTION 26 05 33 -CONDUIT AND BOXES
<br />• SECTION 26 05 53 -ELECTRICAL IDENTIFICATION
<br />B. CONDUIT SHALL NOT BE SUPPORTED FROM DUCTWORK, WATER, SPRINKLER PIPING, OR
<br />OTHER NON-STRUCTURAL MEMBERS, UNLESS APPROVED BY THE ARCHITECT/ENGINEER. ALL
<br />SUPPORTS SHALL BE FROM STRUCTURAL SLABS, WALLS, STRUCTURAL MEMBERS, AND BAR
<br />JOISTS, AND COORDINATED WITH ALL OTHER APPLICABLE CONTRACTORS, UNLESS NOTED
<br />OTHERWISE.
<br />C. CONDUIT SHALL BE HELD IN PLACE BY THE CORRECT SIZE OF GALVANIZED ONE-HOLE CONDUIT
<br />CLAMPS, TWO-HOLE CONDUIT STRAPS, PATENTED SUPPORT DEVICES, CLAMP BACK CONDUIT
<br />HANGERS, OR BY OTHER MEANS IF CALLED FOR ON THE DRAWINGS.
<br />D. SUPPORT INDIVIDUAL HORIZONTAL RACEWAYS WITH SEPARATE, MALLEABLE-IRON PIPE
<br />HANGERS OR CLAMPS.
<br />E. SPRING-STEEL CONDUIT CLIPS SPECIFICALLY DESIGNED FOR SUPPORTING SINGLE CONDUITS
<br />OR TUBING MAY BE USED IN LIEU OF MALLEABLE-IRON HANGERS FOR 1" AND SMALLER
<br />RACEWAYS SERVING LIGHTING AND RECEPTACLE BRANCH CIRCUITS ABOVE ACCESSIBLE
<br />CEILINGS AND FOR SECURING RACEWAYS TO SLOTTED CHANNEL AND ANGLE SUPPORTS.
<br />F. GROUP CONDUITS IN PARALLEL RUNS WHERE PRACTICAL AND USE CONDUIT RACKS OR
<br />TRAPEZE HANGERS CONSTRUCTED OF STEEL CHANNEL, SUSPENDED WITH THREADED SOLID
<br />RODS OR WALL MOUNTED FROM METAL CHANNELS WITH CONDUIT STRAPS OR CLAMPS.
<br />PROVIDE SPACE IN EACH RACK OR TRAPEZE FOR 25% ADDITIONAL CONDUITS.
<br />G. DO NOT EXCEED 25 LBS. PER HANGER AND A MINIMUM SPACING OF 2'-0" ON CENTER WHEN
<br />ATTACHING TO METAL ROOF DECKING (EXCLUDES CONCRETE ON METAL DECK). THIS 25 LBS.
<br />LOAD AND 2'-0" SPACING INCLUDE ADJACENT ELECTRICAL AND MECHANICAL ITEMS HANGING
<br />FROM DECK. IF THE HANGER RESTRICTIONS CANNOT BE ACHIEVED, SUPPLEMENTAL FRAMING
<br />OFF STEEL FRAMING WILL NEED TO BE ADDED.
<br />H. ARRANGE SUPPORTS IN VERTICAL RUNS SO THE WEIGHT OF RACEWAYS AND ENCLOSED
<br />CONDUCTORS IS CARRIED ENTIRELY BY RACEWAY SUPPORTS, WITH NO WEIGHT LOAD ON
<br />RACEWAY TERMINALS.
<br />I. SUPPORTS FOR METALLIC CONDUIT SHALL BE NO GREATER THAN 10 FEET. A SMALLER
<br />INTERVAL MAY BE USED IF NECESSITATED BY BUILDING CONSTRUCTION, BUT IN NO EVENT
<br />SHALL SUPPORT SPANS EXCEED THE ELECTRICAL CODE REQUIREMENTS. CONDUIT SHALL BE
<br />SECURELY FASTENED WITHIN 3 FEET OF EACH OUTLET BOX, JUNCTION BOX, DEVICE BOX,
<br />CABINET, OR FITTING.
<br />J. SUPPORTS OF FLEXIBLE CONDUIT SHALL BE WITHIN 12 INCHES OF EACH OUTLET BOX,
<br />JUNCTION BOX, DEVICE BOX, CABINET, OR FITTING AND AT INTERVALS NOT TO EXCEED 4.5
<br />FEET.
<br />K. FINISH:
<br />1. PRIME COAT EXPOSED STEEL HANGERS AND SUPPORTS. HANGERS AND SUPPORTS IN
<br />CRAWL SPACES, PIPE SHAFTS, AND ABOVE SUSPENDED CEILING SPACES ARE NOT
<br />CONSIDERED EXPOSED.
<br />2. TRIM ALL ENDS OF EXPOSED FIELD FABRICATED STEEL HANGERS, SLOTTED CHANNEL AND
<br />THREADED ROD TO WITHIN 1" OF SUPPORT OR FASTENER TO ELIMINATE POTENTIAL INJURY
<br />TO PERSONNEL UNLESS SHOWN OTHERWISE ON THE DRAWINGS. SMOOTH ENDS AND
<br />INSTALL ELASTOMERIC INSULATION WITH TWO COATS OF LATEX PAINT IF EXPOSED STEEL
<br />IS WITHIN 6'-6" OF FINISH FLOOR AND PRESENTS POTENTIAL INJURY TO PERSONNEL.
<br />3.4 CONDUIT INSTALLATION
<br />A. CONDUIT CONNECTIONS:
<br />1. SHORTER THAN STANDARD CONDUIT LENGTHS SHALL BE CUT SQUARE USING INDUSTRY
<br />STANDARDS. THE ENDS OF ALL CONDUITS CUT SHALL BE REAMED OR OTHERWISE
<br />FINISHED TO REMOVE ALL ROUGH EDGES.
<br />2. METALLIC CONDUIT CONNECTIONS IN SLAB ON GRADE INSTALLATION SHALL BE SEALED
<br />AND ONE COAT OF RUST INHIBITOR PRIMER APPLIED AFTER THE CONNECTION IS MADE.
<br />3. WHERE CONDUITS WITH TAPERED THREADS CANNOT BE COUPLED WITH STANDARD
<br />COUPLINGS, THEN APPROVED SPLIT OR ERICKSON COUPLINGS SHALL BE USED. RUNNING
<br />THREADS WILL NOT BE PERMITTED.
<br />4. INSTALL EXPANSION/DEFLECTION JOINTS WHERE CONDUIT CROSSES STRUCTURE
<br />EXPANSION/SEISMIC JOINTS.
<br />B.CONDUIT TERMINATIONS FOR ALL LOW VOLTAGE WIRING SHALL HAVE NYLON BUSHINGS
<br /> INSTALLED ON EACH END OF EVERY CONDUIT RUN.
<br />C.CONDUIT BENDS:
<br />1. USE A HYDRAULIC ONE-SHOT CONDUIT BENDER OR FACTORY ELBOWS FOR BENDS IN
<br />CONDUIT 2" IN SIZE OR LARGER. ALL STEEL CONDUIT BENDING SHALL BE DONE COLD; NO
<br />HEATING OF STEEL CONDUIT SHALL BE PERMITTED.
<br />2. A RUN OF CONDUIT SHALL NOT CONTAIN MORE THAN THE EQUIVALENT OF FOUR (4)
<br />QUARTER BENDS (360°), INCLUDING THOSE BENDS LOCATED IMMEDIATELY AT THE OUTLET
<br />OR BODY.
<br />3. TELECOMMUNICATIONS CONDUITS SHALL HAVE NO MORE THAN TWO (2) 90-DEGREE BENDS
<br />BETWEEN PULL POINTS AND CONTAIN NO CONTINUOUS SECTIONS LONGER THAN 100 FEET.
<br />INSERT PULL POINTS OR PULL BOXES FOR CONDUITS EXCEEDING 100 FEET IN LENGTH.
<br />a. A THIRD BEND IS ACCEPTABLE IF:
<br />1. THE TOTAL RUN IS NOT LONGER THAN (33) FEET.
<br />2. THE CONDUIT SIZE IS INCREASED TO THE NEXT TRADE SIZE.
<br />4.TELECOMMUNICATIONS PULL BOXES SHALL NOT BE USED IN LIEU OF A BEND. ALIGN
<br /> CONDUITS THAT ENTER THE PULL BOX FROM OPPOSITE ENDS WITH EACH OTHER. PULL
<br /> BOX SIZE SHALL BE TWELVE (12) TIMES THE DIAMETER OF THE LARGEST CONDUIT. SLIP
<br /> SLEEVES OR GUTTERS CAN BE USED IN PLACE OF A PULL BOX.
<br />5.TELECOMMUNICATIONS CONDUIT(S): MAINTAIN APPROPRIATE CONDUIT BEND RADIUS AT
<br /> ALL TIMES. FOR CONDUITS WITH AN INTERNAL DIAMETER OF LESS THAN 2", MAINTAIN A
<br /> BEND RADIUS OF AT LEAST 6 TIMES THE INTERNAL DIAMETER. FOR CONDUITS WITH AN
<br /> INTERNAL DIAMETER 2" OR GREATER, MAINTAIN A BEND RADIUS OF AT LEAST 10 TIMES THE
<br /> INTERNAL DIAMETER.
<br />6.USE CONDUIT BODIES TO MAKE SHARP CHANGES IN DIRECTION (I.E. AROUND BEAMS).
<br />D.CONDUIT PLACEMENT:
<br />1. CONDUIT SHALL BE MECHANICALLY CONTINUOUS FROM SOURCE OF CURRENT TO ALL
<br />OUTLETS. CONDUIT SHALL BE ELECTRICALLY CONTINUOUS FROM SOURCE OF CURRENT TO
<br />ALL OUTLETS, UNLESS A PROPERLY SIZED GROUNDING CONDUCTOR IS ROUTED WITHIN
<br />THE CONDUIT. ALL METALLIC CONDUITS SHALL BE BONDED PER THE ELECTRICAL CODE.
<br />2. ROUTE EXPOSED CONDUIT AND CONDUIT ABOVE SUSPENDED CEILINGS (ACCESSIBLE OR
<br />NOT) PARALLEL/PERPENDICULAR TO THE BUILDING STRUCTURAL LINES, AND AS CLOSE TO
<br />BUILDING STRUCTURE AS POSSIBLE. WHEREVER POSSIBLE, ROUTE HORIZONTAL CONDUIT
<br />RUNS ABOVE WATER AND STEAM PIPING.
<br />3. AVOID MOISTURE TRAPS WHERE POSSIBLE. WHERE UNAVOIDABLE, PROVIDE A JUNCTION
<br />BOX WITH DRAIN FITTING AT CONDUIT LOW POINT.
<br />4. ALL CONDUITS THROUGH WALLS SHALL BE GROUTED OR SEALED INTO OPENINGS. WHERE
<br />CONDUIT PENETRATES FIREWALLS AND FLOORS, SEAL WITH A UL LISTED SEALANT. ; REFER
<br />TO SECTION 26 05 03 FOR THROUGH PENETRATION FIRESTOPPING REQUIREMENTS.
<br />5. CONTRACTOR SHALL PROVIDE SUITABLE MECHANICAL PROTECTION AROUND ALL
<br />CONDUITS STUBBED OUT FROM FLOORS, WALLS OR CEILINGS DURING CONSTRUCTION TO
<br />PREVENT BENDING OR DAMAGING OF STUBS DUE TO CARELESSNESS WITH
<br />CONSTRUCTION EQUIPMENT.
<br />6. CONTRACTOR SHALL PROVIDE A POLYPROPYLENE PULL CORD WITH 2000 LBS. TENSILE
<br />STRENGTH IN EACH EMPTY CONDUIT (INDOOR AND OUTDOOR), EXCEPT IN SLEEVES AND
<br />NIPPLES.
<br />3.5 CONDUIT TERMINATIONS
<br />A. WHERE CONDUIT BONDING IS INDICATED OR REQUIRED IN THE CONTRACT DOCUMENTS, THE
<br />BUSHINGS SHALL BE A GROUNDING TYPE SIZED FOR THE CONDUIT AND GROUND BONDING
<br />CONDUCTOR AS MANUFACTURED BY O-Z/GEDNEY, APPLETON, THOMAS & BETTS, BURNDY,
<br />REGAL, ORBIT INDUSTRIES OR APPROVED EQUAL.
<br />B. CONDUITS WITH TERMINATION FITTINGS SHALL BE THREADED FOR ONE (1) LOCK NUT ON THE
<br />OUTSIDE AND ONE (1) LOCK NUT AND BUSHING ON THE INSIDE OF EACH BOX.
<br />C. WHERE CONDUITS TERMINATE IN BOXES WITH KNOCKOUTS, THEY SHALL BE SECURED TO THE
<br />BOXES WITH LOCK NUTS AND PROVIDED WITH APPROVED SCREW TYPE TINNED IRON
<br />BUSHINGS OR FITTINGS WITH PLASTIC INSERTS.
<br />D. WHERE CONDUITS TERMINATE IN BOXES, FITTINGS, OR BODIES WITH THREADED OPENINGS,
<br />THEY SHALL BE TIGHTLY SCREWED AGAINST THE SHOULDER PORTION OF THE THREADED
<br />OPENINGS.
<br />E. CONDUIT TERMINATIONS TO ALL MOTORS SHALL BE MADE WITH FLEXIBLE METALLIC CONDUIT
<br />(FMC), UNLESS NOTED OTHERWISE. FINAL CONNECTIONS TO ROOF EXHAUST FANS, OR OTHER
<br />EXTERIOR MOTORS AND MOTORS IN DAMP OR WET LOCATIONS SHALL BE MADE WITH
<br />LIQUIDTIGHT FLEXIBLE METALLIC CONDUIT (LFMC). MOTORS IN HAZARDOUS AREAS, AS
<br />DEFINED IN THE ELECTRICAL CODE, SHALL BE CONNECTED USING FLEXIBLE CONDUIT RATED
<br />FOR THE ENVIRONMENT. FLEXIBLE CONDUIT SHALL NOT EXCEED 6' IN LENGTH. ROUTE
<br />EQUIPMENT GROUND CONDUCTORS FROM CIRCUIT GROUND TO MOTOR GROUND TERMINAL
<br />THROUGH FLEXIBLE CONDUIT.
<br />F. ALL CONDUIT ENDS SHALL BE SEALED WITH PLASTIC IMMEDIATELY AFTER INSTALLATION TO
<br />PREVENT THE ENTRANCE OF ANY FOREIGN MATTER DURING CONSTRUCTION. THE SEALS
<br />SHALL BE REMOVED AND THE CONDUITS BLOWN CLEAR OF ALL FOREIGN MATTER PRIOR TO
<br />ANY WIRES OR PULL CORDS BEING INSTALLED.
<br />1. APPROVED EQUAL
<br />3.6 BOX INSTALLATION SCHEDULE
<br />A. GALVANIZED STEEL BOXES MAY BE USED IN:
<br />1. CONCEALED INTERIOR LOCATIONS ABOVE CEILINGS AND IN HOLLOW STUDDED PARTITIONS.
<br />2. EXPOSED INTERIOR LOCATIONS IN MECHANICAL ROOMS AND IN ROOMS WITHOUT
<br />CEILINGS; HIGHER THAN 8' ABOVE THE HIGHEST PLATFORM LEVEL.
<br />B.CAST BOXES SHALL BE USED IN:
<br />1. EXPOSED INTERIOR LOCATIONS WITHIN 8' OF THE HIGHEST PLATFORM LEVEL.
<br />2. WET LOCATIONS.
<br />3.7 COORDINATION OF BOX LOCATIONS
<br />A. PROVIDE ELECTRICAL BOXES AS SHOWN ON THE DRAWINGS, AND AS REQUIRED FOR SPLICES,
<br />TAPS, WIRE PULLING, EQUIPMENT CONNECTIONS, AND CODE COMPLIANCE.
<br />B. ELECTRICAL BOX LOCATIONS SHOWN ON THE CONTRACT DRAWINGS ARE APPROXIMATE,
<br />UNLESS DIMENSIONED. VERIFY LOCATION OF FLOOR BOXES AND OUTLETS IN OFFICES AND
<br />WORK AREAS PRIOR TO ROUGH-IN.
<br />C. LOCATE AND INSTALL BOXES TO ALLOW ACCESS. AVOID INTERFERENCES WITH DUCTWORK,
<br />PIPING, STRUCTURE, EQUIPMENT, ETC. RECESSED LUMINAIRES SHALL NOT BE USED AS
<br />ACCESS TO OUTLET, PULL, AND JUNCTION BOXES. WHERE INSTALLATION IS INACCESSIBLE,
<br />PROVIDE ACCESS DOORS. COORDINATE LOCATIONS AND SIZES OF REQUIRED ACCESS DOORS
<br />WITH THE ARCHITECT/ENGINEER AND GENERAL CONTRACTOR.
<br />D. LOCATE AND INSTALL TO MAINTAIN HEADROOM AND TO PRESENT A NEAT APPEARANCE.
<br />3.8 OUTLET BOX INSTALLATION
<br />A. DO NOT INSTALL BOXES BACK-TO-BACK IN WALLS.
<br />1. PROVIDE A MINIMUM HORIZONTAL SEPARATION OF 6 INCHES BETWEEN BOXES INSTALLED
<br />ON OPPOSITE SIDES OF NON-RATED STUD WALLS.
<br />2. PROVIDE A MINIMUM HORIZONTAL SEPARATION OF 24 INCHES BETWEEN BOXES INSTALLED
<br />ON OPPOSITE SIDES OF FIRE-RATED WALLS. WHEN THE MINIMUM SEPARATION CANNOT BE
<br />MAINTAINED, THE BOX IS GREATER THAN 16 SQUARE INCHES OR THE TOTAL BOX AREA (ALL
<br />TRADES) PER 100 SQUARE FEET IS GREATER THAN OR EQUAL TO 100 SQUARE INCHES,
<br />INSTALL FIRE-RATED MOLDABLE PADS TO ALL FIVE SIDES OF THE BACK BOX TO MAINTAIN
<br />THE FIRE RATING OF THE WALL. INSTALL MOLDABLE PADS IN ACCORDANCE WITH UL
<br />LISTING FOR THE SPECIFIC PRODUCT. SOUND INSULATION PADS ARE NOT ACCEPTABLE
<br />FOR USE IN FIRE-RATED WALL APPLICATIONS UNLESS THE PRODUCT CARRIES THE
<br />NECESSARY FIRE RATING.
<br />B.THE CONTRACTOR SHALL ANCHOR SWITCH AND OUTLET BOX TO WALL CONSTRUCTION SO
<br /> THAT IT IS FLUSH WITH THE FINISHED MASONRY, PANELING, DRYWALL, PLASTER, ETC. THE
<br /> CONTRACTOR SHALL CHECK THE BOXES AS THE FINISH WALL SURFACE IS BEING INSTALLED TO
<br /> ASSURE THAT THE BOX IS FLUSH. (PROVIDE PLASTER RINGS AS NECESSARY.)
<br />C.MOUNT AT HEIGHTS SHOWN OR NOTED ON THE DRAWINGS.
<br />D.PROVIDE KNOCKOUT CLOSURES FOR UNUSED OPENINGS.
<br />E.SUPPORT BOXES INDEPENDENTLY OF CONDUIT.
<br />F.USE MULTIPLE-GANG BOXES WHERE MORE THAN ONE DEVICE IS MOUNTED TOGETHER; DO
<br /> NOT USE SECTIONAL BOXES. PROVIDE BARRIERS TO SEPARATE WIRING OF DIFFERENT
<br /> VOLTAGE SYSTEMS.
<br />G.INSTALL BOXES IN WALLS WITHOUT DAMAGING WALL INSULATION.
<br />H.COORDINATE MOUNTING HEIGHTS AND LOCATIONS OF OUTLETS MOUNTED ABOVE COUNTERS,
<br /> BENCHES, AND BACKSPLASHES.
<br />I.POSITION OUTLETS TO LOCATE LUMINAIRES AS SHOWN ON REFLECTED CEILING DRAWINGS.
<br />J.PROVIDE RECESSED OUTLET BOXES IN FINISHED AREAS; SECURE BOXES TO INTERIOR WALL
<br /> AND PARTITION STUDS, ACCURATELY POSITIONED TO ALLOW FOR SURFACE FINISH
<br /> THICKNESS. USE STAMPED STEEL STUD BRIDGES FOR FLUSH OUTLETS IN HOLLOW STUD WALL,
<br /> AND ADJUSTABLE STEEL CHANNEL FASTENERS FOR FLUSH CEILING OUTLET BOXES.
<br />K.ALIGN WALL-MOUNTED OUTLET BOXES FOR SWITCHES, THERMOSTATS, AND SIMILAR DEVICES.
<br />3.9 PULL AND JUNCTION BOX INSTALLATION
<br />A. LOCATE PULL BOXES AND JUNCTION BOXES ABOVE ACCESSIBLE CEILINGS OR IN UNFINISHED
<br />AREAS.
<br />B. SUPPORT PULL AND JUNCTION BOXES INDEPENDENT OF CONDUIT.
<br />C. DO NOT INSTALL BOXES BACK-TO-BACK IN WALLS.
<br />1. PROVIDE A MINIMUM HORIZONTAL SEPARATION OF 6 INCHES BETWEEN BOXES INSTALLED
<br />ON OPPOSITE SIDES OF NON-RATED STUD WALLS.
<br />2. PROVIDE A MINIMUM HORIZONTAL SEPARATION OF 24 INCHES BETWEEN BOXES INSTALLED
<br />ON OPPOSITE SIDES OF FIRE-RATED WALLS. WHEN THE MINIMUM SEPARATION CANNOT BE
<br />MAINTAINED, THE BOX IS GREATER THAN 16 SQUARE INCHES OR THE TOTAL BOX AREA (ALL
<br />TRADES) PER 100 SQUARE FEET IS GREATER THAN OR EQUAL TO 100 SQUARE INCHES,
<br />INSTALL FIRE-RATED MOLDABLE PADS TO ALL FIVE SIDES OF THE BACK BOX TO MAINTAIN
<br />THE FIRE RATING OF THE WALL. INSTALL MOLDABLE PADS IN ACCORDANCE WITH UL
<br />LISTING FOR THE SPECIFIC PRODUCT. SOUND INSULATION PADS ARE NOT ACCEPTABLE
<br />FOR USE IN FIRE-RATED WALL APPLICATIONS UNLESS THE PRODUCT CARRIES THE
<br />NECESSARY FIRE RATING.
<br />END OF SECTION
<br />SECTION 26 05 53 -ELECTRICAL IDENTIFICATION
<br />PART 1 -GENERAL
<br />1.1 SECTION INCLUDES
<br />A. ADHESIVE MARKINGS AND FIELD LABELS
<br />B. NAMEPLATES AND SIGNS
<br />C. PRODUCT COLORS
<br />1.2 REFERENCES
<br />A. NFPA 70E -NATIONAL ELECTRICAL SAFETY CODE
<br />B. CEC CALIFORNIA ELECTRICAL CODE
<br />PART 2 -PRODUCTS
<br />2.1 ADHESIVE MARKINGS AND FIELD LABELS
<br />A. COLORED ADHESIVE MARKING TAPE FOR BANDING RACEWAYS, WIRES, AND CABLES: SELF-
<br />ADHESIVE VINYL TAPE NOT LESS THAN 3 MILS THICK BY 1 INCH TO 2 INCHES IN WIDTH.
<br />B. PRETENSIONED FLEXIBLE WRAPAROUND COLORED PLASTIC SLEEVES FOR CABLE
<br />IDENTIFICATION: FLEXIBLE ACRYLIC BANDS SIZED TO SUIT THE CABLE DIAMETER AND
<br />ARRANGED TO STAY IN PLACE BY PRE-TENSIONED GRIPPING ACTION WHEN COILED AROUND
<br />THE CABLE.
<br />C. WIRE/CABLE DESIGNATION TAPE MARKERS: VINYL OR VINYL-CLOTH, SELF-ADHESIVE,
<br />WRAPAROUND, CABLE/CONDUCTOR MARKERS WITH PREPRINTED NUMBERS AND LETTER.
<br />D. CABLE TIES: FUNGUS-INERT, SELF-EXTINGUISHING, ONE-PIECE, SELF-LOCKING NYLON CABLE
<br />TIES, 0.18-INCH MINIMUM WIDTH, 50-LB MINIMUM TENSILE STRENGTH, AND SUITABLE FOR A
<br />TEMPERATURE RANGE FROM -40°F TO 185°F (-40°C TO 85°C), TYPE 2/2S OR TYPE 21/21S BASED
<br />ON APPLICATION. PROVIDE TIES IN SPECIFIED COLORS WHEN USED FOR COLOR CODING.
<br />CABLE TIES SHALL BE LISTED AND IDENTIFIED FOR THE APPLICATION, SECUREMENT, AND
<br />SUPPORT.
<br />2.2 NAMEPLATES AND SIGNS
<br />A. ENGRAVED, PLASTIC-LAMINATED LABELS, SIGNS AND INSTRUCTION PLATES: ENGRAVING
<br />STOCK MELAMINE PLASTIC LAMINATE, 1/16-INCH MINIMUM THICK FOR SIGNS UP TO 20 SQUARE
<br />INCHES, OR 8 INCHES IN LENGTH; 1/8 INCH THICK FOR LARGER SIZES. LABELS SHALL BE
<br />PUNCHED FOR MECHANICAL FASTENERS.
<br />2.3 PRODUCT COLORS
<br />1. NORMAL POWER AND GENERAL LABELS: BLACK LETTERS ON WHITE FACE
<br />2. EMERGENCY: RED LETTERS ON WHITE FACE
<br />B.NAMEPLATES AND SIGNS:
<br />1. NORMAL POWER: BLACK LETTERS ON WHITE FACE
<br />2. EMERGENCY: WHITE LETTERS ON RED FACE
<br />3. PROVIDE COLOR CODED CONDUIT AS INDICATED BELOW. CONDUIT SHALL BE COLORED BY
<br />THE MANUFACTURER:
<br />a. NORMAL POWER AND GENERAL DISTRIBUTION: SILVER
<br />b. EMERGENCY POWER DISTRIBUTION SYSTEM: RED
<br />PART 3 -EXECUTION
<br />3.1 INSTALLATION
<br />A. LETTERING AND GRAPHICS: COORDINATE NAMES, ABBREVIATIONS, COLORS, AND OTHER
<br />DESIGNATIONS USED IN ELECTRICAL IDENTIFICATION WORK WITH CORRESPONDING
<br />DESIGNATIONS SPECIFIED OR INDICATED. INSTALL NUMBERS, LETTERING, AND COLORS AS
<br />INDICATED ON DRAWINGS OR AS REQUIRED BY CODE.
<br />B. INSTALL IDENTIFICATION DEVICES IN ACCORDANCE WITH MANUFACTURER'S WRITTEN
<br />INSTRUCTION AND REQUIREMENTS OF ELECTRICAL CODE.
<br />C. SEQUENCE OF WORK: WHERE IDENTIFICATION IS TO BE APPLIED TO SURFACES THAT REQUIRE
<br />FINISH, INSTALL IDENTIFICATION AFTER COMPLETION OF FINISH WORK. ALL MOUNTING
<br />SURFACES SHALL BE CLEANED AND DEGREASED PRIOR TO IDENTIFICATION INSTALLATION.
<br />D. CIRCUIT IDENTIFICATION: TAG OR LABEL CONDUCTORS AS FOLLOWS:
<br />1. MULTIPLE POWER OR LIGHTING CIRCUITS IN SAME ENCLOSURE: WHERE MULTIPLE BRANCH
<br />CIRCUITS ARE TERMINATED OR SPLICED IN A BOX OR ENCLOSURE, LABEL EACH
<br />CONDUCTOR WITH SOURCE AND CIRCUIT NUMBER.
<br />2. MULTIPLE CONTROL WIRING AND COMMUNICATION/SIGNAL CIRCUITS IN SAME ENCLOSURE:
<br />FOR CONTROL AND COMMUNICATIONS/SIGNAL WIRING, USE W IRE/CABLE MARKING TAPE AT
<br />TERMINATIONS IN WIRING BOXES, TROUGHS, AND CONTROL CABINETS. USE CONSISTENT
<br />LETTER/NUMBER CONDUCTOR DESIGNATIONS THROUGHOUT ON WIRE/CABLE MARKING
<br />TAPE.
<br />3. MATCH IDENTIFICATION MARKINGS WITH DESIGNATIONS USED IN PANELBOARDS SHOP
<br />DRAWINGS, CONTRACT DOCUMENTS, AND SIMILAR PREVIOUSLY ESTABLISHED
<br />IDENTIFICATION SCHEMES FOR THE FACILITY'S ELECTRICAL INSTALLATIONS.
<br />4. EMERGENCY OPERATING SIGNS: INSTALL, WHERE REQUIRED BY ELECTRICAL CODE,
<br />WHERE INDICATED, OR WHERE REASONABLY REQUIRED TO ASSURE SAFE OPERATION AND
<br />MAINTENANCE OF ELECTRICAL SYSTEMS AND OF THE ITEMS TO WHICH THEY CONNECT,
<br />ENGRAVED LAMINATE SIGNS WITH WHITE LEGEND ON RED BACKGROUND WITH MINIMUM
<br />3/8-INCH HIGH LETTERING FOR EMERGENCY INSTRUCTIONS ON EMERGENCY POWER OFF,
<br />POWER TRANSFER, OR OTHER EMERGENCY OPERATIONS.
<br />E.APPLY CIRCUIT/CONTROL/ITEM DESIGNATION LABELS OF ENGRAVED PLASTIC LAMINATE FOR
<br /> PUSHBUTTONS, PILOT LIGHTS, ALARM/SIGNAL COMPONENTS, AND SIMILAR ITEMS, EXCEPT
<br /> WHERE LABELING IS SPECIFIED ELSEWHERE.
<br />F.INSTALL LABELS PARALLEL TO EQUIPMENT LINES AT LOCATIONS AS REQUIRED AND AT
<br /> LOCATIONS FOR BEST CONVENIENCE OF VIEWING WITHOUT INTERFERENCE WITH OPERATION
<br /> AND MAINTENANCE OF EQUIPMENT.
<br />G.SELECTIVE COORDINATION LABEL: INSTALL CAUTION SIGNS ON ALL SWITCHBOARDS,
<br /> DISTRIBUTION PANELS, PANELBOARDS, DISCONNECTS, AND OTHER EQUIPMENT WITH
<br /> SELECTIVELY COORDINATED OVERCURRENT PROTECTION DEVICES. SIGN AT A MINIMUM SHALL
<br /> CONTAIN:
<br />1. CAUTION: OVERCURRENT DEVICES IN THIS ENCLOSURE ARE SELECTIVELY COORDINATED.
<br />EQUIVALENT REPLACEMENTS AND TRIP SETTINGS ARE REQUIRED.
<br />3.2 LIGHTING CONTROL AND RECEPTACLE COVER PLATES
<br />A. PRODUCT:
<br />1. ADHESIVE LABELS AND FIELD MARKINGS
<br />B.IDENTIFICATION MATERIAL TO BE ENGRAVED PLASTIC-LAMINATED LABELS, 1/16-INCH MINIMUM
<br /> THICKNESS WITH WHITE LETTERS ON A RED FACE. LETTER AND NUMBER SIZE TO 1/8-INCH
<br /> HIGH.
<br />C.PROVIDE IDENTIFICATION ON ALL SWITCH AND RECEPTACLE COVER PLATES. IDENTIFICATION
<br /> SHALL INDICATE SOURCE AND CIRCUIT NUMBER SERVING THE DEVICE (E.G. "C1A #24").
<br />3.3 CONDUIT AND EXPOSED CABLE LABELING
<br />A. PRODUCT:
<br />1. ADHESIVE LABELS AND FIELD MARKINGS
<br />B.CONDUIT IDENTIFICATION: PRE-PRINTED, FLEXIBLE, SELF-ADHESIVE VINYL LABELS WITH
<br /> LEGEND AT 20 FOOT (6 METER) INTERVALS TO IDENTIFY ALL CONDUITS RUN EXPOSED OR
<br /> LOCATED ABOVE ACCESSIBLE CEILINGS. CONDUITS LOCATED ABOVE NON-ACCESSIBLE
<br /> CEILING OR IN FLOORS AND WALLS SHALL BE LABELED WITHIN 3 FEET OF BECOMING
<br /> ACCESSIBLE, OR SEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS, AND FLOORS.
<br /> LABELS FOR MULTIPLE CONDUITS SHALL BE ALIGNED. REFER TO COLOR REQUIREMENTS IN
<br /> PART 2 WHEN APPLICABLE IN ADDITION TO THE FOLLOWING:
<br />1. 1000 VOLT OR LESS NORMAL/EMERGENCY POWER: INDICATE FEEDER IDENTIFICATION AND
<br />VOLTAGE.
<br />2. ESSENTIAL ELECTRICAL SYSTEM EES: WHEN APPLICABLE THE LABEL SHALL INCLUDE
<br />"ESSENTIAL ELECTRICAL SYSTEM EES". MAXIMUM INTERVAL BETWEEN LABEL INTERVALS
<br />SHALL BE 25 FEET OR AS REQUIRED BY CODE.
<br />3.4 BOX LABELING
<br />A. PRODUCTS:
<br />1. ADHESIVE LABELS AND FIELD MARKINGS
<br />B.IDENTIFY JUNCTION, PULL AND CONNECTION BOXES: LABELING SHALL BE 3/8-INCH KROY TAPE
<br /> OR BROTHER SELF-LAMINATING VINYL LABEL, LETTERS/NUMBERS COLOR CODED SAME AS
<br /> CONDUITS. IN ROOMS THAT ARE PAINTED OUT, PROVIDE LABELING ON INSIDE OF COVER.
<br />C.ALL JUNCTION, PULL, AND CONNECTION BOXES SHALL BE IDENTIFIED AS FOLLOWS:
<br />1. FOR POWER AND LIGHTING CIRCUITS, INDICATE SYSTEM VOLTAGE AND IDENTITY OF
<br />CONTAINED CIRCUITS ("120V, 1LA1-3,5,7").
<br />2. ESSENTIAL ELECTRICAL SYSTEM EES: WHEN APPLICABLE THE LABEL SHALL INCLUDE
<br />"ESSENTIAL ELECTRICAL SYSTEM EES". MAXIMUM INTERVAL BETWEEN LABEL INTERVALS
<br />SHALL BE 25 FEET OR AS REQUIRED BY CODE.
<br />3.5 CONDUCTOR COLOR CODING
<br />A. PRODUCTS:
<br />1. ALL WIRE AND CABLES SHALL BE COLOR CODED BY THE MANUFACTURER.
<br />B.COLOR CODING SHALL BE APPLIED AT ALL PANELS, SWITCHES, JUNCTION BOXES, PULL BOXES,
<br /> VAULTS, MANHOLES ETC., WHERE THE WIRES AND CABLES ARE VISIBLE AND TERMINATIONS
<br /> ARE MADE. THE SAME COLOR CODING SHALL BE USED THROUGHOUT THE ENTIRE ELECTRICAL
<br /> SYSTEM, THEREFORE MAINTAINING PROPER PHASING THROUGHOUT THE ENTIRE PROJECT.
<br />C.COLORED CABLE TIES SHALL BE APPLIED IN GROUPS OF THREE TIES OF SPECIFIED COLOR TO
<br /> EACH CONDUCTOR AT EACH TERMINAL OR SPLICE POINT STARTING 3 INCHES FROM THE
<br /> TERMINATION AND SPACED AT 3-INCHES CENTERS. TIGHTEN TO A SNUG FIT, AND CUT OFF
<br /> EXCESS LENGTH.
<br />D.WHERE MORE THAN ONE NOMINAL VOLTAGE SYSTEM EXISTS IN A BUILDING OR FACILITY, EACH
<br /> UNGROUNDED CONDUCTOR OF A MULTI-WIRE BRANCH CIRCUIT, WHERE ACCESSIBLE, SHALL
<br /> BE IDENTIFIED BY PHASE AND SYSTEM.
<br />1. 208Y/120 VOLT, 4-WIRE:
<br />a. A-PHASE -BLACK
<br />b. B-PHASE -RED
<br />c. C-PHASE -BLUE
<br />d. NEUTRAL -WHITE
<br />e. GROUND BOND -GREEN
<br />2.480Y/277 VOLT, 4-WIRE:
<br />a. A-PHASE -BROWN
<br />b. B-PHASE -ORANGE
<br />c. C-PHASE -YELLOW
<br />d. NEUTRAL -GRAY
<br />e. GROUND BOND -GREEN
<br />3.GROUNDING CONDUCTORS:
<br />a. EQUIPMENT GROUNDING CONDUCTORS, MAIN/SYSTEM/SUPPLY-SIDE BONDING
<br />JUMPERS: GREEN.
<br />3.6 CONTROL EQUIPMENT IDENTIFICATION
<br />A. PRODUCTS:
<br />1. NAMEPLATES AND SIGNS
<br />B.PROVIDE IDENTIFICATION ON THE FRONT OF ALL CONTROL EQUIPMENT SUCH AS ENCLOSED
<br /> CIRCUIT BREAKERS, COMBINATION STARTERS, STARTERS, VFDS, CONTACTORS, ETC.
<br />C.IDENTIFICATION SHALL BE PROVIDED FOR ALL CONNECTIONS TO EQUIPMENT FURNISHED BY
<br /> THIS CONTRACTOR, OTHER CONTRACTORS, OR THE OWNER.
<br />D.LABELING SHALL INCLUDE:
<br />1. EQUIPMENT TYPE AND CONTRACT DOCUMENTS DESIGNATION OF EQUIPMENT BEING
<br />SERVED.
<br />2. LOCATION OF EQUIPMENT BEING SERVED IF IT IS NOT LOCATED WITHIN SIGHT.
<br />3. VOLTAGE AND PHASE OF CIRCUIT(S).
<br />4. PANEL AND CIRCUIT NUMBER(S) SERVING THE EQUIPMENT.
<br />5. SAMPLE LABEL:
<br />EXHAUST FAN EF-1 ("LOCATED ON ROOF")
<br />480V, 3-PHASE
<br />FED FROM "1HA1-1"
<br />3.7 EQUIPMENT CONNECTION IDENTIFICATION
<br />A. PRODUCTS:
<br />1. NAMEPLATES AND SIGNS
<br />B.PROVIDE IDENTIFICATION FOR HARD WIRED ELECTRICAL CONNECTIONS TO EQUIPMENT SUCH
<br /> AS DISCONNECTS SWITCHES, STARTERS, ETC. PLUG AND CORD TYPE CONNECTIONS DO NOT
<br /> REQUIRE THIS SPECIFIC LABEL.
<br />END OF SECTION
<br />TE OLIRFFOAC
<br />LANRP
<br />E 23191
<br />STA
<br />ER
<br />REGIST
<br />ED
<br />INA
<br />N
<br />REENIGE
<br />FO OISSE
<br />E AICLCERTL
<br />Exp. 06/30/26
<br />MIRASOPHOCLISGEORGY
<br />IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,
<br />TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
<br />AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND SHALL
<br />NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE
<br />EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP.
<br />©2022 IMEG CORP.
<br />REF. SCALE IN INCHES
<br />0 1 2 3
<br />The FUTURE. Built Smarter www.imegcorp.com
<br />R
<br />SHEET TITLE
<br />PROJECT
<br />FACILITY
<br />FAC NO: BLDG NO: FLOOR LEV: SECTION:
<br />KP PROJ. NO.
<br />PERMIT NO.
<br />555 W. 5th St Suite 2950 | Los Angeles, CA 90013 USA
<br />Phone 310.820.4600 | Fax 310.207.4215
<br />www.huitt-zollars.com
<br />ARCHITECT
<br />CONSULTANT
<br />ARCHITECT SEAL CONSULTANT SEAL
<br />KAISER FOUNDATION
<br />HOSPITALS NATIONAL
<br />FACILITIES SERVICES 1800
<br />HARRISON STREET OAKLAND,
<br />CALIFORNIA 94612
<br />ISSUE / REVISION LOG
<br />NO. ISSUED DATE
<br />0
<br />5'
<br />
<br />5
<br />0
<br />'
<br />GR
<br />A
<br />P
<br />H
<br />I
<br />C
<br />
<br />S
<br />C
<br />A
<br />L
<br />E
<br />S
<br />:
<br />
<br />1
<br />/
<br />1
<br />6
<br />"
<br />
<br />=
<br />
<br />1
<br />'
<br />-
<br />0
<br />"
<br />0
<br />25
<br />'
<br />1/
<br />8
<br />"
<br />
<br />=
<br />
<br />1
<br />'
<br />-
<br />0
<br />"
<br />5'
<br />0
<br />12
<br />'
<br />1/
<br />4
<br />"
<br />
<br />=
<br />
<br />1
<br />'
<br />-
<br />0
<br />"
<br />1'
<br />0
<br />6'
<br />1/
<br />2
<br />"
<br />
<br />=
<br />
<br />1
<br />'
<br />-
<br />0
<br />"
<br />1'
<br />0
<br />2'
<br />1-
<br />1
<br />/
<br />2
<br />"
<br />
<br />=
<br />
<br />1
<br />'
<br />-
<br />0
<br />"
<br />0
<br />1'
<br />3"
<br />
<br />=
<br />
<br />1
<br />'
<br />-
<br />0
<br />"
<br />IF
<br />
<br />T
<br />H
<br />I
<br />S
<br />
<br />S
<br />H
<br />E
<br />E
<br />T
<br />
<br />I
<br />S
<br />
<br />N
<br />O
<br />T
<br />
<br />30
<br />"
<br />x
<br />4
<br />2
<br />"
<br />,
<br />
<br />I
<br />T
<br />
<br />I
<br />S
<br />
<br />A
<br />
<br />R
<br />E
<br />D
<br />U
<br />C
<br />E
<br />D
<br />
<br />PR
<br />I
<br />N
<br />T
<br />
<br />-
<br />
<br />S
<br />C
<br />A
<br />L
<br />E
<br />
<br />AC
<br />C
<br />O
<br />R
<br />D
<br />I
<br />N
<br />G
<br />L
<br />Y
<br />AGENCY APPLICATION NUMBER
<br />AGENCY APPROVAL STAMP
<br />THIS DOCUMENT IS THE PROPERTY OF THE OWNER AND IS
<br />NOT TO BE USED WITHOUT OWNER'S WRITTEN PERMISSION.
<br />HZ PROJ. NO.
<br />222 S. HARBOR BOULEVARD, SUITE 800 I ANAHEIM, CA 92805
<br />PH: 714.490.5555 I FAX: 714.490.5560
<br />IMEG PROJ. NO.: 22008618.00
<br />PROJECT #22008618.00
<br />SOCC 2022 R HBM 1st Fl KPOJ
<br />REMODEL
<br />E0-04
<br />ELECTRICAL SPECIFICATION
<br />CA394-1
<br />CAP0227721R314412.35
<br />HARBOR/MacARTHUR MEDICAL OFF
<br />3401 S. HARBOR BLVD.
<br />SANTA ANA, CALIFORNIA 92704
<br />CITY SUBMITTAL 11/03/2025
<br />101125520, 20187249, 40140902
|