SPECIFICATIONS TABLE OF CONTENTS
<br />SECTION 26 09 33 -LIGHTING CONTROL SYSTEMS
<br />PART 1 -GENERAL
<br />1.1 SECTION INCLUDES
<br />A. LINE AND LOW VOLTAGE STANDALONE LIGHTING CONTROLS
<br />B. AUTOMATIC LOAD CONTROL RELAY (ALCR20)
<br />C. DISTRIBUTED LIGHTING CONTROL
<br />1.2 RELATED SECTIONS
<br />A. THE LIGHTING SYSTEM DESIGN INCLUDES A COMBINATION OF LUMINAIRE SOURCES, LIGHTING
<br />CONTROL COMPONENTS, PROGRAMMING SEQUENCES, AND SUPPLEMENTARY COMPONENTS
<br />FOR BUILDING AND ENERGY CODE COMPLIANCE. THE DESIGN USES PERFORMANCE-BASED
<br />SPECIFICATIONS FOR PORTIONS OF THE LIGHTING SYSTEM TO ACCOUNT FOR THE LIMITATION
<br />OF COMPARABLE PRODUCT SOLUTIONS AVAILABLE BY COMPETITIVE MANUFACTURERS. THE
<br />CONTRACTOR SHALL REFERENCE RELATED SPECIFICATION SECTIONS, PLANS, SCHEDULES,
<br />AND DETAILS PRIOR TO SUBMITTING PRICING, SUBMITTALS, AND INSTALLATION. THE
<br />CONTRACTOR SHALL COORDINATE SYSTEM COMPONENT COMPATIBILITY AMONG VARIOUS
<br />MANUFACTURERS AND SUPPLIERS FOR A TURNKEY LIGHTING SYSTEM. REFERENCED
<br />SECTIONS INCLUDE, BUT ARE NOT LIMITED TO, THE FOLLOWING:
<br />1. 26 51 19 LED LIGHTING
<br />2. ELECTRICAL DRAWINGS: PLANS, LUMINAIRE SCHEDULES, AND DETAILS.
<br />1.3 QUALITY ASSURANCE
<br />A. MANUFACTURERS SHALL BE REGULARLY ENGAGED IN THE MANUFACTURE OF LIGHTING
<br />CONTROL EQUIPMENT AND ANCILLARY EQUIPMENT, OF TYPES AND CAPACITIES REQUIRED,
<br />WHOSE PRODUCTS HAVE BEEN IN SATISFACTORY USE IN SIMILAR SERVICE FOR NOT LESS
<br />THAN FIVE (5) YEARS.
<br />B. ALL COMPONENTS AND ASSEMBLIES ARE TO BE FACTORY PRE-TESTED PRIOR TO DELIVERY
<br />AND INSTALLATION.
<br />C. COMPLY WITH ELECTRICAL CODE AS APPLICABLE TO ELECTRICAL WIRING WORK.
<br />D. COMPLY WITH APPLICABLE PORTIONS OF NEMA STANDARDS PERTAINING TO TYPES OF
<br />ELECTRICAL EQUIPMENT AND ENCLOSURES.
<br />E. PANELS AND ACCESSORY DEVICES ARE TO BE UL LISTED UNDER UL 916 ENERGY MANAGEMENT
<br />EQUIPMENT. PANELS AND ACCESSORIES USED FOR CONTROL OF LIFE SAFETY AND CRITICAL
<br />BRANCH CIRCUITS SHALL BE LISTED UNDER UL 924 EMERGENCY LIGHTING AND POWER
<br />EQUIPMENT.
<br />F. ALL ASSEMBLIES ARE TO BE IN COMPLIANCE WITH FCC EMISSIONS STANDARDS SPECIFIED IN
<br />PART 15 SUBPART J FOR CLASS A APPLICATIONS.
<br />1.4 REFERENCES
<br />A. FCC RULES AND REGULATIONS, PART 15, SUBPART J -RADIO FREQUENCY INTERFERENCE
<br />B. FS W S 896 SWITCH, TOGGLE
<br />C. CALIFORNIA ENERGY CODE -BUILDING ENERGY EFFICIENCY STANDARDS TITLE 24
<br />D. NEMA WD 1 -GENERAL COLOR REQUIREMENTS FOR WIRING DEVICES
<br />E. NEMA WD 7 -OCCUPANCY MOTION SENSORS
<br />F. CEC CALIFORNIA ELECTRICAL CODE
<br />G. UL STANDARD 916 ENERGY MANAGEMENT EQUIPMENT
<br />H. UL 924 -EMERGENCY LIGHTING AND POWER EQUIPMENT
<br />I. UL 1472 -SOLID-STATE DIMMING CONTROLS
<br />1.5 SUBMITTALS
<br />A. SUBMIT PRODUCT DATA UNDER PROVISIONS OF SECTION 26 05 00.
<br />B. SUBMIT A COMPREHENSIVE PACKAGE INCLUDING DEVICES, HARDWARE, SOFTWARE, PRODUCT
<br />SPECIFICATION, FINISHES, DIMENSIONS, INSTALLATION INSTRUCTIONS, WARRANTY, SYSTEM
<br />SOFTWARE REQUIREMENTS[, AND ROLES AND RESPONSIBILITIES OF ALL PERSONS AND
<br />GROUPS INVOLVED IN INSTALLATION, EXECUTION, AND COMMISSIONING].
<br />C. PROVIDE FLOOR PLAN SHOWING LOCATION, ORIENTATION, AND COVERAGE AREA OF EACH
<br />CONTROL DEVICE, SENSOR, AND CONTROLLER/INTERFACE. FOR AREAS REQUIRING MULTIPLE
<br />SENSOR DEVICES FOR APPROPRIATE COVERAGE, SUBMIT SPECIFIC MANUFACTURER-
<br />APPROVED SENSOR LAYOUT AS AN OVERLAY DIRECTLY ON THE PROJECT DRAWINGS, EITHER
<br />IN PRINT OR APPROVED ELECTRONIC FORM.
<br />D. SUBMIT A LIST OF DEVICES AND EQUIPMENT THAT WILL BE INSTALLED FOR EACH SEQUENCE
<br />OF OPERATION.
<br />E. SUBMIT PROJECT SPECIFIC CONTROL WIRING DIAGRAMS SHOWING ALL EQUIPMENT, LINE
<br />VOLTAGE, AND CONTROL WIRING REQUIREMENTS FOR ALL COMPONENTS INCLUDING, BUT NOT
<br />LIMITED TO, DIMMERS, RELAYS, LOW VOLTAGE SWITCHES, OCCUPANCY SENSORS, CONTROL
<br />STATIONS, AND COMMUNICATION INTERFACES AND PROGRAMMING INSTRUCTIONS FOR EACH
<br />SEQUENCE OF OPERATION. INCLUDE NETWORK CABLE SPECIFICATION AND END-OF-LINE
<br />TERMINATION DETAILS, IF REQUIRED.
<br />1.6 EXTRA STOCK
<br />A. PROVIDE EXTRA STOCK UNDER PROVISIONS OF SECTION 26 05 00.
<br />B. SENSORS, CONTROLS, POWER SUPPLIES, AND RELAYS: FIVE (5) PERCENT OF QUANTITY
<br />INSTALLED. MINIMUM OF TWO (2) OF EACH CONFIGURATION AND TYPE.
<br />1.7 PROJECT RECORD DOCUMENTS
<br />A. SUBMIT PROJECT RECORD DOCUMENTS UNDER PROVISIONS OF SECTION 26 05 00.
<br />B. ACCURATELY RECORD LOCATION OF ALL CONTROLS AND DEVICES. INCLUDE DESCRIPTION OF
<br />SWITCHING SEQUENCES AND CIRCUITING ARRANGEMENTS.
<br />1.8 OPERATION AND MAINTENANCE DATA
<br />A. SUBMIT EMERGENCY, OPERATION, AND MAINTENANCE DATA UNDER PROVISIONS OF SECTION
<br />26 05 00. DATA SHALL ALSO INCLUDE THE FOLLOWING:
<br />1. SCHEDULE FOR ROUTINE MAINTENANCE, INSPECTION, AND CALIBRATION OF ALL LIGHTING
<br />CONTROL DEVICES AND SYSTEM COMPONENTS. RECOMMENDED SCHEDULE FOR
<br />INSPECTION AND RECALIBRATION OF SENSORS.
<br />2. COMPLETE NARRATIVE DESCRIBING INTENDED OPERATION AND SEQUENCE FOR EACH
<br />CONTROL SCENARIO AND SYSTEM COMPONENT, UPDATED TO REFLECT ALL CHANGES
<br />RESULTING FROM COMMISSIONING OF SYSTEMS. NARRATIVE SHALL INDICATE
<br />RECOMMENDED SETTINGS FOR DEVICES WHERE APPLICABLE.
<br />3. REPLACEMENT PART NUMBERS FOR ALL SYSTEM COMPONENTS.
<br />B.IDENTIFY INSTALLED LOCATION AND LABELING FOR EACH LUMINAIRE CONTROLLED BY
<br /> AUTOMATED LIGHTING CONTROLS.
<br />1.9 SYSTEM DESCRIPTION
<br />A. PERFORMANCE STATEMENT: THIS SPECIFICATION SECTION AND THE ACCOMPANYING LIGHTING
<br />DESIGN DOCUMENTS DESCRIBE THE MINIMUM MATERIAL QUALITY, REQUIRED FEATURES, AND
<br />OPERATIONAL REQUIREMENTS OF THE LIGHTING CONTROL SYSTEM (LCS). THESE DOCUMENTS
<br />DO NOT CONVEY EVERY WIRE THAT MUST BE INSTALLED AND EVERY EQUIPMENT CONNECTION
<br />THAT MUST BE MADE. BASED ON THE PERFORMANCE REQUIRED OF THE SYSTEM, AS
<br />PRESENTED IN THESE DOCUMENTS, THE CONTRACTOR AND SYSTEM MANUFACTURER/VENDOR
<br />ARE SOLELY RESPONSIBLE FOR DETERMINING ALL EQUIPMENT, WIRING, AND PROGRAMMING
<br />REQUIRED FOR A COMPLETE AND OPERATIONAL SYSTEM.
<br />B. PROVIDE AN INTEGRATED LIGHTING CONTROLS SYSTEM CONSISTING OF PANELS, POWER
<br />SUPPLIES, CONTROLLERS, SENSORS, RELAYS, SWITCHES, DEVICES, WIRING, ETC. NECESSARY
<br />TO PERFORM THE LIGHTING CONTROL SEQUENCE OF OPERATION AS DEFINED ON THE PLANS
<br />AND SPECIFICATIONS. CONTRACTOR IS RESPONSIBLE FOR CONFIRMING THAT ALL
<br />COMPONENTS AND LUMINAIRES INTEROPERATE AS A SINGLE SYSTEM.
<br />1. SEQUENCE OF OPERATION: DESCRIBES THE REQUIRED OPERATION AND PERFORMANCE
<br />FOR LIGHTING CONTROL IN EACH SPACE. SEQUENCES OF OPERATION ARE INDICATED ON
<br />THE DRAWINGS.
<br />2. DRAWINGS: THE DRAWINGS INCLUDE SEQUENCES OF OPERATION, LOCATIONS OF
<br />CONTROL INTERFACE DEVICES, SENSORS, AND CONTROL ZONES. WIRING AND ADDITIONAL
<br />EQUIPMENT TO MAKE A COMPLETE AND FUNCTIONING SYSTEM HAS NOT BEEN SHOWN, BUT
<br />SHALL BE SUBMITTED WITH THE SHOP DRAWINGS.
<br />C.THE FOLLOWING CONTROL TYPES AND FEATURES ARE ACCEPTABLE. ACCEPTABLE CONTROL
<br /> LOCATIONS ARE SHOWN ON THE DRAWINGS.
<br />1. LINE VOLTAGE CONTROL: CONTROL EQUIPMENT CONSISTS OF TRADITIONAL LINE VOLTAGE
<br />WIRING DEVICES AND EQUIPMENT SUCH AS SWITCHES, DIMMERS AND COMBINATION
<br />OCCUPANCY/VACANCY SENSOR SWITCHES, ETC.
<br />2. DISTRIBUTED CONTROL: CONTROL EQUIPMENT IS IN THE SPACE/ZONE BEING CONTROLLED;
<br />NOT RELIANT ON CENTRALIZED CONTROLLERS.
<br />1.10 WARRANTY
<br />A. MANUFACTURER SHALL WARRANT PRODUCTS UNDER NORMAL USE AND SERVICE TO BE FREE
<br />FROM DEFECTS IN MATERIALS AND WORKMANSHIP FOR A PERIOD OF TWO (2) YEARS FROM
<br />DATE OF COMMISSIONING.
<br />B. OCCUPANCY, VACANCY, DAYLIGHT SENSORS AND CONTROLS SHALL HAVE A FIVE (5) YEAR
<br />WARRANTY FROM DATE OF SUBSTANTIAL COMPLETION.
<br />PART 2 -PRODUCTS
<br />2.1 LIGHTING CONTROLS
<br />A. ALL ITEMS OF MATERIAL HAVING A SIMILAR FUNCTION (E.G., SWITCHES, DIMMERS, SENSORS,
<br />CONTACTORS, RELAYS, ETC.) SHALL BE OF THE SAME MANUFACTURER, UNLESS SPECIFICALLY
<br />STATED OTHERWISE ON DRAWINGS OR ELSEWHERE IN THE SPECIFICATIONS. LIGHTING
<br />CONTROL SWITCHES, SYSTEMS, AND COMPONENTS SHALL BE LISTED.
<br />B. COLOR OF LIGHTING CONTROLS AND SENSORS SHALL MATCH THE RECEPTACLE WIRING
<br />DEVICES SPECIFIED IN THE SPACE.
<br />C. THE FUNCTIONS DESCRIBED IN THE LIGHTING SEQUENCE OF OPERATION SHALL DICTATE THE
<br />ACTUAL LIGHTING CONTROL DEVICE REQUIRED TO ACCOMPLISH THE FUNCTIONS DESCRIBED
<br />FOR THE SPACE.
<br />• SECTION 26 09 33 -LIGHTING CONTROL SYSTEMS
<br />• SECTION 26 24 19 -MOTOR CONTROL
<br />• SECTION 26 27 26 -WIRING DEVICES
<br />2.2 DEVICE COLOR
<br />A. ALL SWITCH, LIGHTING CONTROLS, AND COVER PLATE COLORS SHALL BE THE SAME AS WIRING
<br />DEVICES, UNLESS INDICATED OTHERWISE.
<br />2.3 COVERPLATES
<br />A. ALL SWITCHES AND LIGHTING CONTROLS SHALL BE COMPLETE WITH COVER PLATES THAT
<br />MATCH MATERIAL AND COLOR OF THE WIRING DEVICE COVER PLATES IN THE SPACE.
<br />B. WHERE SEVERAL DEVICES ARE GANGED TOGETHER, THE COVER PLATE SHALL BE OF THE
<br />GANGED STYLE FOR THE NUMBER OF DEVICES USED.
<br />C. INSTALL NAMEPLATE IDENTIFICATION AS INDICATED IN SECTION 26 05 53.
<br />D. PLATE-SECURING SCREWS SHALL BE METAL WITH HEAD COLOR MATCHING THE WALL PLATE
<br />FINISH.
<br />2.4 WALL SWITCHES
<br />A. REFER TO ELECTRICAL SYMBOLS LIST FOR DEVICE TYPE.
<br />B. SW-1P; SINGLE POLE SWITCH:
<br />1. SINGLE THROW, 120/277-VOLT, 20-AMP MAINTAINED CONTACT. TOGGLE HANDLE, SIDE AND
<br />BACK WIRED.
<br />2. MANUFACTURERS:
<br />a. HUBBELL HBL1221
<br />b. LEVITON 1221-2
<br />c. PASS & SEYMOUR PS20AC1
<br />d. COOPER AH1221
<br />C.SW-1P-EM; EMERGENCY SINGLE POLE SWITCH:
<br />1. SINGLE THROW, 120/277-VOLT, 20-AMP MAINTAINED CONTACT. RED HANDLE, SIDE AND BACK
<br />WIRED.
<br />2. MANUFACTURERS:
<br />a. HBL1221R
<br />b. LEVITON 1221-2R
<br />c. PASS & SEYMOUR PS20AC1-RED
<br />d. COOPER AH1221RD
<br />2.5 WALL DIMMERS
<br />A. UL LISTED WITH INTEGRAL AIR-GAP SWITCH FOR ON/OFF CONTROL.
<br />B. INTEGRAL EMI/RFI SUPPRESSION.
<br />C. NON-VIEWABLE HEAT SINK.
<br />D. DIMMER COMPATIBILITY AND WIRING WITH THE LOAD BEING CONTROLLED SHALL BE VERIFIED
<br />BY CONTRACTOR PRIOR TO PURCHASE AND INSTALLATION.
<br />E. DIMMER TO MATCH DEVICE COLOR.
<br />F. SW-D-LED; LED ELECTRONIC DRIVER DIMMER:
<br />1. 277-VOLT, DECORA STYLE LINEAR SLIDER OPERATOR WITH POSITIVE OFF. COLOR TO
<br />MATCH ADJACENT DEVICES. LUMINAIRE MANUFACTURER SHALL LIST COMPATIBLE DIMMER
<br />MANUFACTURERS AND MODELS. 0-10V DIMMERS SHALL COMPLY WITH IEC 60629 ANNEX E.
<br />2. MANUFACTURERS:
<br />a. COMPATIBLE WITH PROVIDED LED DRIVER.
<br />2.6 INDOOR OCCUPANCY SENSORS
<br />A. GENERAL DESCRIPTION: WALL-OR CEILING-MOUNTING, SOLID-STATE UNITS WITH A SEPARATE
<br />POWER SUPPLY/RELAY UNIT.
<br />1. OPERATION: UNLESS OTHERWISE INDICATED, TURN LIGHTS ON WHEN COVERED AREA IS
<br />OCCUPIED AND OFF WHEN UNOCCUPIED, WITH A TIME DELAY FOR TURNING LIGHTS OFF,
<br />ADJUSTABLE OVER A MINIMUM RANGE OF 1 TO 30 MINUTES.
<br />2. SENSOR OUTPUT: CONTACTS RATED TO OPERATE THE CONNECTED RELAY, COMPLYING
<br />WITH UL 773A. SENSOR SHALL BE POWERED FROM THE RELAY UNIT.
<br />3. RELAY UNIT: DRY CONTACTS RATED FOR 20 A BALLAST LOAD AT 120 AND 277 VAC, FOR 13-
<br />AMP TUNGSTEN AT 120 VAC, AND FOR 1 HP AT 120 VAC. POWER SUPPLY TO SENSOR SHALL
<br />BE 24 V DC, 150-MA, CLASS 2 POWER SOURCE AS DEFINED BY ELECTRICAL CODE.
<br />4. MOUNTING:
<br />a. SENSOR: SUITABLE FOR MOUNTING IN ANY POSITION ON A STANDARD OUTLET BOX.
<br />b. RELAY: EXTERNALLY MOUNTED THROUGH A 1/2-INCH KNOCKOUT IN A STANDARD
<br />ELECTRICAL ENCLOSURE. MOUNT RELAY ABOVE ACCESSIBLE CEILING NEAR ENTRY
<br />DOOR TO ROOM OR AREA.
<br />c. TIME DELAY AND SENSITIVITY ADJUSTMENTS: RECESSED AND CONCEALED.
<br />5.INDICATOR: LED TO SHOW WHEN MOTION IS BEING DETECTED DURING TESTING AND
<br /> NORMAL OPERATION OF THE SENSOR.
<br />6.BYPASS SWITCH: OVERRIDE THE ON FUNCTION IN CASE OF SENSOR FAILURE.
<br />7.POWER SUPPLY AND CHILD PACKS: PROVIDE AS REQUIRED FOR SENSOR QUANTITY AND
<br /> SWITCHING SCHEME. MOUNT TO STANDARD 1/2" KNOCKOUT ON ELECTRICAL BOX ABOVE
<br /> ACCESSIBLE CEILING NEAR ENTRY DOOR TO ROOM OR AREA. SENSOR POWER SHALL BE
<br /> FROM EMERGENCY CIRCUIT IF EMERGENCY LIGHTING IS IN THE AREA.
<br />8.DETECTION COVERAGE (ROOM): DETECT OCCUPANCY ANYWHERE IN AN AREA BASED ON
<br /> HAND MOTION.
<br />9.WARRANTY: FIVE (5) YEAR WARRANTY.
<br />B.DUAL-TECHNOLOGY TYPE: DETECT OCCUPANCY BY USING A COMBINATION OF PIR AND
<br /> ULTRASONIC [OR ACOUSTIC] DETECTION METHODS IN AREA OF COVERAGE. PARTICULAR
<br /> TECHNOLOGY OR COMBINATION OF TECHNOLOGIES THAT CONTROLS ON AND OFF FUNCTIONS
<br /> SHALL BE SELECTABLE IN THE FIELD BY OPERATING CONTROLS ON UNIT.
<br />1. SW-VS-D OR SW-OC-D; 360 DEGREE COVERAGE PATTERN:
<br />a. FREQUENCY GREATER THAN 40 KHZ. DUAL SENSING VERIFICATIONS (REQUIRES BOTH
<br />TECHNOLOGIES TO ACTIVATE), EITHER TECHNOLOGY MAINTAINS ON STATUS.
<br />INTEGRATED AMBIENT LIGHT LEVEL SENSOR (2 TO 200 FC RANGE), ADJUSTABLE
<br />SENSITIVITY AND TIME DELAY[, INTEGRATED ISOLATED RELAY CONTACT]. SENSOR
<br />SHALL CONTROL ALL CIRCUITS IN AREA, UNLESS NOTED OTHERWISE. INITIAL SETTINGS:
<br />AMBIENT SENSOR 40 FC.
<br />b. MANUFACTURERS:
<br />1. WATT STOPPER DT 300 SERIES
<br />2. LEVITON OSC##-MOW
<br />2.SW-O; WALL SWITCH:
<br />a. WALL SWITCH WITH MANUAL ON/AUTO OFF. 120/277 VAC LOAD RATING OF 0-800 W FOR
<br />BALLAST, LED OR TUNGSTEN. 5-, 15-, 30-MINUTE ADJUSTABLE OFF DELAY. COVERAGE
<br />OF MINOR MOTION IN 12' X 15' PATTERN.
<br />b. MANUFACTURERS:
<br />1. WATT STOPPER DW-100 SERIES
<br />2.7 DISTRIBUTED LIGHTING CONTROL
<br />A. MANUFACTURERS: AS LISTED BELOW MEET THE QUALIFICATIONS AS OUTLINED IN THIS
<br />SPECIFICATION. CONTRACTOR IS RESPONSIBLE FOR VERIFYING THAT SELECTED
<br />MANUFACTURER IS CAPABLE OF FURNISHING THE COMPLETE SYSTEM AS SPECIFIED HEREIN.
<br />1. ACUITY CONTROLS NLIGHT SERIES
<br />2. LEGRAND WATT STOPPER DLM SERIES
<br />3. APPROVED EQUAL
<br />B.SYSTEM DESCRIPTION: THE LIGHTING CONTROL SYSTEM SHALL BE A NETWORK OF REMOTE
<br /> MODULES SYSTEM INCLUDES ALL ASSOCIATED WIRING, RELAY MODULES, PHOTOCELLS,
<br /> SWITCHES, DIMMERS, TIME CLOCK, OCCUPANCY SENSORS. SYSTEM SHALL UTILIZE
<br /> DISTRIBUTED RELAYS MODULES, ALLOWING THESE RELAY MODULES TO BE LOCATED ABOVE
<br /> ACCESSIBLE CEILINGS IN OR ADJACENT TO ROOMS THEY ARE CONTROLLING.
<br />C.CONTROL DEVICES: ALL OCCUPANCY SENSORS SHALL BE DUAL TECHNOLOGY TYPE.
<br /> OCCUPANCY SENSORSSHALL BE PROVIDED WITH SYSTEM AND DESIGNED TO OPERATE ON
<br /> SYSTEM NETWORK. SUPPLEMENTAL POWER PACKS SHALL BE PROVIDED AS REQUIRED FOR
<br /> MULTIPLE CONTROL DEVICES. THIS EQUIPMENT SHALL BE IDENTIFIED IN SHOP DRAWING
<br /> SUBMISSION.
<br />D.RELAY MODULES: MOUNTED IN NEMA ENCLOSURE WITH PHYSICALLY SEPARATE 120/277-VOLT
<br /> WIRING COMPARTMENT FROM LOW VOLTAGE CONTROL WIRING. PROVIDE LOW VOLTAGE
<br /> DIGITAL COMMUNICATION TO CONTROL DEVICES AS SHOWN ON DRAWINGS AND SCHEDULES.
<br /> SUPPLEMENTAL POWER PACKS SHALL BE PROVIDED AS REQUIRED FOR MULTIPLE CONTROL
<br /> DEVICES. THIS EQUIPMENT SHALL BE IDENTIFIED IN SHOP DRAWING SUBMISSION. DIMMABLE
<br /> RELAY MODULES SHALL BE PROVIDED WHERE INDICATED. RELAY MODULES SHALL CONTAIN UP
<br /> TO FOUR (4) RELAYS. RELAY MODULES SHALL BE LABELED WITH ROOM NUMBER THAT RELAYS
<br /> CONTROL LIGHTING WITHIN.
<br />2.8 CONDUCTORS AND CABLES
<br />A. CONTROL WIRING:
<br />1. NETWORK CABLING AS REQUIRED BY MANUFACTURER.
<br />PART 3 -EXECUTION
<br />3.1 EXAMINATION
<br />A. VERIFY THAT SURFACES ARE READY TO RECEIVE WORK.
<br />B. VERIFY FIELD DIMENSIONS AND COORDINATE PHYSICAL SIZE OF ALL EQUIPMENT WITH THE
<br />ARCHITECTURAL REQUIREMENTS OF THE SPACES INTO WHICH THEY ARE TO BE INSTALLED.
<br />ALLOW SPACE FOR ADEQUATE VENTILATION AND CIRCULATION OF AIR.
<br />C. VERIFY THAT REQUIRED UTILITIES ARE AVAILABLE, IN PROPER LOCATION, AND READY FOR USE.
<br />D. BEGINNING OF INSTALLATION MEANS INSTALLER ACCEPTS EXISTING CONDITIONS.
<br />3.2 INSTALLATION
<br />A. INSTALL IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND APPROVED SHOP
<br />DRAWINGS.
<br />B. ALL WIRING SHALL BE INSTALLED IN CONDUIT. CLASS II LOW VOLTAGE CONTROL WIRING MAY
<br />BE OPEN WIRING AND SHALL MAINTAIN 150 MM (6 INCH) SPACING FROM ELECTRONIC BALLAST
<br />AND OTHER RFI/EMI SOURCES.
<br />C. ALL BRANCH LOAD CIRCUITS SHALL BE LIVE TESTED BEFORE CONNECTING THE LOADS TO THE
<br />LIGHTING CONTROL PANEL.
<br />3.3 AUTOMATIC LOAD CONTROL RELAYS (ALCR20) AND BRANCH CIRCUIT EMERGENCY LIGHTING
<br />TRANSFER SWITCH (BCELTS)
<br />3.4 SUPPORT SERVICES
<br />A. SYSTEM STARTUP:
<br />1. MANUFACTURER SHALL PROVIDE FACTORY AUTHORIZED TECHNICIAN TO CONFIRM
<br />PROPER INSTALLATION AND OPERATION OF ALL SYSTEM COMPONENTS.
<br />B.TESTING:
<br />1. SYSTEM SHALL BE COMPLETELY FUNCTIONAL TESTED BY A FACTORY-AUTHORIZED
<br />TECHNICIAN. ALL LOADS SHALL BE TESTED LIVE FOR CONTINUITY AND FREEDOM FROM
<br />DEFECTS, AND ALL CONTROL WIRING SHALL BE TESTED FOR CONTINUITY AND
<br />CONNECTIONS PRIOR TO ENERGIZING THE SYSTEM COMPONENTS.
<br />2. PROGRAMMING OF INITIAL ZONES, SCHEDULES, LIGHTING LEVELS, CONTROL STATION
<br />GROUPS, AND SENSOR SETTINGS SHALL BE PERFORMED BY A FACTORY-AUTHORIZED
<br />TECHNICIAN. LIGHTING CONTROL SEQUENCE OF OPERATION SHALL SERVE AS A BASIS FOR
<br />PROGRAMMING, HOWEVER, ALL FINAL DECISIONS REGARDING GROUPS AND SCHEDULES
<br />SHALL BE AT THE DIRECTION OF THE OWNER. THE FOLLOWING PROCEDURES SHALL BE
<br />PERFORMED AT A MINIMUM:
<br />a. CONFIRM OCCUPANCY SENSOR PLACEMENT, SENSITIVITY, AND TIME DELAY SETTINGS
<br />TO MEET SPECIFIED PERFORMANCE CRITERIA.
<br />b. CONFIRM DAYLIGHT SENSOR PLACEMENT, SENSITIVITY, DEADBAND, AND DELAY
<br />SETTINGS TO MEET SPECIFIED PERFORMANCE CRITERIA.
<br />c. CONFIRM THAT SCHEDULES AND TIME CONTROLS ARE CONFIGURED TO MEET
<br />SPECIFIED PERFORMANCE CRITERIA AND OWNER'S OPERATING REQUIREMENTS.
<br />3.VERIFY OCCUPANCY SENSOR OPERATION IS CORRECT AFTER FURNITURE AND EQUIPMENT
<br /> IS INSTALLED IN EACH AREA. MAKE ADJUSTMENTS TO SENSOR SETTINGS AND TIME DELAYS
<br /> TO ALLOW PROPER OPERATION.
<br />4.VERIFY OCCUPANCY/VACANCY SENSORS ARE LOCATED TO PROVIDE COMPLETE
<br /> COVERAGE FOR THE AREA SERVED WITH NO NUISANCE SWITCHING.
<br />a. RELOCATE SENSORS OR PROVIDE ADDITIONAL SENSORS AS NECESSARY TO PROVIDE
<br />ADEQUATE COVERAGE.
<br />b. MASK OCCUPANCY SENSORS WHERE NECESSARY TO PREVENT NUISANCE SWITCHING
<br />FROM ADJACENT AREAS.
<br />C.TRAINING:
<br />1. MANUFACTURER SHALL PROVIDE COMPETENT FACTORY-AUTHORIZED TECHNICIAN TO
<br />TRAIN OWNER PERSONNEL IN THE OPERATION, MAINTENANCE AND PROGRAMMING OF THE
<br />LIGHTING CONTROL SYSTEM. SUBMIT TRAINING PLAN WITH NOTIFICATION SEVEN (7) DAYS
<br />PRIOR TO PROPOSED TRAINING DATES.
<br />2. TRAINING DURATION SHALL BE NO LESS THAN THREE (3) DAYS, WITH ONE (1) DAY BEING
<br />SCHEDULED AT LEAST TWO (2) WEEKS AFTER INITIAL TRAINING.
<br />D.DOCUMENTATION:
<br />1. MANUFACTURER SHALL PROVIDE SYSTEM DOCUMENTATION INCLUDING:
<br />a. SYSTEM ONE-LINE SHOWING ALL PANELS, NUMBER AND TYPE OF CONTROL STATIONS
<br />AND SENSORS, COMMUNICATION LINE, AND NETWORK OR BMS/BAS INTERFACE UNIT.
<br />b. DRAWINGS FOR EACH PANEL SHOWING HARDWARE CONFIGURATION AND NUMBERING.
<br />c. PANEL WIRING SCHEDULES.
<br />d. TYPICAL DIAGRAMS FOR EACH COMPONENT.
<br />END OF SECTION
<br />SECTION 26 24 19 -MOTOR CONTROL
<br />PART 1 -GENERAL
<br />1.1 SECTION INCLUDES
<br />A. MANUAL MOTOR STARTERS
<br />B. ENCLOSED CIRCUIT BREAKERS
<br />1.2 RELATED SECTIONS AND WORK
<br />A. REFER TO THE ONE-LINE DIAGRAM FOR RATING AND CONFIGURATION.
<br />1.3 REFERENCES
<br />A. ANSI/UL STANDARD 508. STANDARD FOR INDUSTRIAL CONTROL EQUIPMENT
<br />B. FS W -C-375 -CIRCUIT BREAKERS, MOLDED CASE; BRANCH CIRCUIT AND SERVICE
<br />C. FS W -S-865 -SWITCH, BOX, (ENCLOSED), SURFACE-MOUNTED
<br />D. NEMA AB 1 -MOLDED CASE CIRCUIT BREAKERS
<br />E. NEMA KS 1 -ENCLOSED SWITCHES
<br />F. NEMA PB 1.1 -INSTRUCTIONS FOR SAFE INSTALLATION, OPERATION AND MAINTENANCE OF
<br />PANELBOARDS RATED 600 VOLTS OR LESS
<br />1.4 SUBMITTALS
<br />A. SUBMIT SHOP DRAWINGS AND PRODUCT DATA UNDER PROVISIONS OF SECTION 26 05 00.
<br />B. INDICATE ON SHOP DRAWINGS, FRONT AND SIDE VIEWS OF ENCLOSED CIRCUIT BREAKER WITH
<br />OVERALL DIMENSIONS. INCLUDE CONDUIT ENTRANCE LOCATIONS AND REQUIREMENTS;
<br />WIRING DIAGRAMS THAT DIFFERENTIATE BETWEEN MANUFACTURER-INSTALLED AND FIELD-
<br />INSTALLED WIRING; NAMEPLATE LEGENDS; SIZE AND NUMBER OF BUS BARS PER PHASE,
<br />[ NEUTRAL,] AND GROUND; ELECTRICAL CHARACTERISTICS INCLUDING VOLTAGE, FRAME SIZE
<br />AND TRIP RATINGS, WITHSTAND RATINGS, AND TIME-CURRENT CURVES OF ALL EQUIPMENT
<br />AND COMPONENTS. INDICATE CIRCUIT BREAKER DESIGNATION ON SHOP DRAWINGS.
<br />C. PROVIDE PRODUCT DATA ON MOTOR STARTERS AND COMBINATION MOTOR STARTERS,
<br />RELAYS, PILOT DEVICES, AND SWITCHING AND OVER-CURRENT PROTECTIVE DEVICES.
<br />1.5 DELIVERY, STORAGE, AND HANDLING
<br />A. DELIVER PRODUCTS TO SITE UNDER PROVISIONS OF SECTION 26 05 00.
<br />B. STORE AND PROTECT PRODUCTS UNDER PROVISIONS OF SECTION 26 05 00.
<br />C. STORE IN A CLEAN, DRY SPACE. MAINTAIN FACTORY WRAPPING OR PROVIDE AN ADDITIONAL
<br />HEAVY CANVAS OR HEAVY PLASTIC COVER TO PROTECT UNITS FROM FUMES, DIRT, WATER,
<br />CONSTRUCTION DEBRIS, TRAFFIC, AND PHYSICAL DAMAGE.
<br />D. HANDLE IN ACCORDANCE WITH MANUFACTURER'S WRITTEN INSTRUCTIONS. LIFT ONLY WITH
<br />LUGS PROVIDED FOR THE PURPOSE. HANDLE CAREFULLY TO AVOID DAMAGE TO MOTOR
<br />CONTROL CENTER COMPONENTS, ENCLOSURE, AND FINISH.
<br />1.6 OPERATION AND MAINTENANCE DATA
<br />A. SUBMIT OPERATION AND MAINTENANCE DATA UNDER PROVISIONS OF SECTION 26 05 00.
<br />B. INCLUDE SPARE PARTS DATA LISTING; SOURCE AND CURRENT PRICES OF REPLACEMENT
<br />PARTS AND SUPPLIES; AND RECOMMENDED MAINTENANCE PROCEDURES AND INTERVALS.
<br />PART 2 -PRODUCTS
<br />2.1 MANUAL MOTOR STARTERS
<br />A. ACCEPTABLE MANUFACTURERS:
<br />1. SQUARE D 2500 SERIES
<br />2. EATON MS SERIES
<br />3. ABB
<br />4. SIEMENS SMF / MMS SERIES
<br />B.MANUAL MOTOR STARTER: NEMA ICS 2; AC GENERAL-PURPOSE CLASS A MANUALLY OPERATED
<br /> NON-REVERSING FULL-VOLTAGE CONTROLLER FOR INDUCTION MOTORS RATED IN
<br /> HORSEPOWER, WITH OVERLOAD RELAY, AND TOGGLE OPERATOR.
<br />C.FRACTIONAL HORSEPOWER MANUAL STARTER: NEMA ICS 2; AC GENERAL-PURPOSE CLASS A
<br /> MANUALLY OPERATED, FULL-VOLTAGE CONTROLLER FOR FRACTIONAL HORSEPOWER
<br /> INDUCTION MOTORS, WITH THERMAL OVERLOAD UNIT, AND TOGGLE OPERATOR.
<br />D.ENCLOSURE: NEMA ICS 6; TYPE 1.
<br />2.2 ENCLOSEDOVER-CURRENT PROTECTION AND DISCONNECTING MEANS
<br />1. STARTER MANUFACTURER
<br />B.MOLDED CASE THERMAL-MAGNETIC CIRCUIT BREAKERS: CIRCUIT BREAKERS WITH INTEGRAL
<br /> THERMAL AND ADJUSTABLE INSTANTANEOUS MAGNETIC TRIP IN EACH POLE.
<br />C.NON-FUSIBLE SWITCH ASSEMBLIES: QUICK-MAKE, QUICK-BREAK, LOAD INTERRUPTER
<br />ENCLOSED
<br /> KNIFE SWITCH WITH EXTERNALLY OPERABLE HANDLE. PROVIDE INTERLOCK TO PREVENT
<br /> OPENING FRONT COVER WITH SWITCH IN ON POSITION. HANDLE LOCKABLE IN OFF POSITION.
<br />PART 3 -EXECUTION
<br />3.1 INSTALLATION
<br />A. SELECT AND INSTALL HEATER ELEMENTS IN MOTOR STARTERS TO MATCH INSTALLED MOTOR
<br />CHARACTERISTICS.
<br />B. SET FIELD-ADJUSTABLE SWITCHES AND CIRCUIT-BREAKER TRIP RANGES.
<br />END OF SECTION
<br />SECTION 26 27 26 -WIRING DEVICES
<br />PART 1 -GENERAL
<br />1.1 SECTION INCLUDES
<br />A. DEVICE PLATES AND BOX COVERS
<br />B. RECEPTACLES (REC-#)
<br />1.2 QUALITY ASSURANCE
<br />A. PROVIDE SIMILAR DEVICES FROM A SINGLE MANUFACTURER.
<br />B. ELECTRICAL COMPONENTS, DEVICES, AND ACCESSORIES: LISTED AND LABELED AS DEFINED IN
<br />THE ELECTRICAL CODE, BY A TESTING AGENCY TO AUTHORITIES HAVING JURISDICTION AND
<br />MARKED FOR INTENDED USE.
<br />C. CEC CALIFORNIA ELECTRICAL CODE
<br />D. UL 498 -STANDARD FOR ATTACHMENT PLUGS AND RECEPTACLES
<br />E. UL 943 -STANDARD FOR GROUND FAULT CIRCUIT INTERRUPTERS
<br />1.3 SUBMITTALS
<br />A. SUBMIT PRODUCT DATA UNDER PROVISIONS OF SECTION 26 05 00.
<br />B. PROVIDE PRODUCT DATA SHOWING CONFIGURATIONS, FINISHES, DIMENSIONS, AND
<br />MANUFACTURER'S INSTRUCTIONS.
<br />1.4 COORDINATION
<br />A. RECEPTACLES FOR OWNER FURNISHED EQUIPMENT: MATCH PLUG CONFIGURATIONS.
<br />B. CORD AND PLUG SETS: MATCH EQUIPMENT REQUIREMENTS
<br />PART 2 -PRODUCTS
<br />2.1 DEVICE COLOR
<br />A. ALL SWITCH, RECEPTACLE, AND OUTLET COLORS SHALL BE WHITE FOR NORMAL POWER AND
<br />RED FOR EMERGENCY POWER.
<br />2.2 COVERPLATES
<br />A. ALL SWITCHES, RECEPTACLES, AND OUTLETS SHALL BE COMPLETE WITH THE FOLLOWING:
<br />1. DECORATOR GRADE -DECORATOR THERMOPLASTIC AND MATCH DEVICE COLOR
<br />WALLPLATES IN FINISHED SPACES WHERE WALLS ARE FINISHED.
<br />a. MANUFACTURER:
<br />1. LEVITON DECORA
<br />2. HUBBELL DECORATOR
<br />3. COOPER DECORATOR
<br />4. OR APPROVED EQUAL
<br />B.WHERE SEVERAL DEVICES ARE GANGED TOGETHER, THE COVERPLATE SHALL BE OF THE
<br /> GANGED STYLE FOR THE NUMBER OF DEVICES USED.
<br />C.INSTALL NAMEPLATE IDENTIFICATION AS INDICATED IN SECTION 26 05 53.
<br />D.PLATE SECURING SCREWS SHALL BE METAL WITH HEAD COLOR MATCHING THE WALL PLATE
<br />FINISH.
<br />2.3 RECEPTACLES
<br />A. REFER TO ELECTRICAL SYMBOLS LIST FOR DEVICE TYPE.
<br />B. DEVICES THAT ARE SHADED ON THE DRAWINGS SHALL BE RED.
<br />C. REC-DUP: NEMA 5-20R DUPLEX RECEPTACLE:
<br />1. HOSPITAL GRADE: 125-VOLT, 20 AMP, 3-WIRE GROUNDING TYPE HOSPITAL GRADE WITH
<br />IMPACT RESISTANT THERMOPLASTIC FACE AND ONE-PIECE NICKEL-PLATED BRASS BACK
<br />STRAP WITH INTEGRAL GROUND CONTACTS.
<br />a. MANUFACTURERS:
<br />1. HUBBELL HBL8300
<br />2. LEVITON 8300
<br />3. PASS & SEYMOUR 8300
<br />4. COOPER AH8300
<br />D.REC-DUP-GFI: NEMA 5-20R GROUND FAULT DUPLEX RECEPTACLE:
<br />1. HOSPITAL GRADE: 125-VOLT, 20 AMP, 3-WIRE GROUNDING TYPE HOSPITAL GRADE WITH
<br />TEST AND RESET BUTTONS IN IMPACT RESISTANT THERMOPLASTIC FACE.
<br />a. DEVICE SHALL PERFORM SELF-TEST OF GFCI CIRCUITRY IN ACCORDANCE WITH UL 943.
<br />b. MANUFACTURERS:
<br />1. HUBBELL GFRST83
<br />2. LEVITON GFNT2-HG
<br />3. PASS & SEYMOUR 2097HG
<br />4. COOPER SGFH20
<br />E.REC-QUAD: NEMA 5-20R DOUBLE DUPLEX RECEPTACLE:
<br />1. CONSISTS OF TWO DUPLEX RECEPTACLES, DOUBLE GANG BOX, PLASTER RING AND
<br />FACEPLATE.
<br />a. MANUFACTURERS:
<br />1. REFER TO DUPLEX RECEPTACLE ABOVE.
<br />F.REC-QUAD-GFI: NEMA 5-20R DOUBLE DUPLEX GFI RECEPTACLE:
<br />1. CONSISTS OF TWO DUPLEX GFI RECEPTACLES, DOUBLE GANG BOX, PLASTER RING AND
<br />FACEPLATE.
<br />a. MANUFACTURERS:
<br />1. REFER TO DUPLEX GFI RECEPTACLE ABOVE.
<br />G.BACK WIRED DEVICES SHALL BE COMPLETE WITH EIGHT HOLES THAT ARE SCREW ACTIVATED
<br /> WITH METAL CLAMPS FOR CONNECTION TO #12 OR #10 COPPER CONDUCTORS.
<br />H.SIDE WIRED DEVICES SHALL HAVE FOUR BINDING SCREWS THAT ARE UNDERCUT FOR POSITIVE
<br /> WIRE RETENTION.
<br />I.GROUND FAULT CIRCUIT INTERRUPTER (GFCI) RECEPTACLES SHALL COMPLY WITH UL 943
<br /> REQUIRING INCREASED SURGE IMMUNITY, IMPROVED CORROSION RESISTANCE, IMPROVED
<br /> RESISTANCE TO FALSE TRIPPING AND DIAGNOSTIC INDICATION FOR MISWIRING IF THE LINE
<br /> AND LOAD CONDUCTORS ARE REVERSED DURING INSTALLATION.
<br />PART 3 -EXECUTION
<br />3.1 INSTALLATION
<br />A. INSTALL CONVENIENCE RECEPTACLES AT ELEVATIONS INDICATED IN THE GENERAL
<br />INSTALLATION NOTES ON THE CONTRACT DRAWINGS.
<br />B. INSTALL SPECIFIC-USE RECEPTACLES AT HEIGHTS SHOWN ON THE CONTRACT DRAWINGS.
<br />INSTALL DEVICES LEVEL, PLUMB, AND SQUARE WITH BUILDING LINES. COORDINATE
<br />INSTALLATION OF ADJACENT DEVICES OF SEPARATE SYSTEMS WITH COMMON MOUNTING
<br />HEIGHTS, INCLUDING LIGHTING, POWER, SYSTEMS, TECHNOLOGY, AND TEMPERATURE
<br />CONTROL DEVICE ROUGH-INS.
<br />C. GROUND FAULT PROTECTION: PROVIDE GROUND FAULT PROTECTION FOR ALL BRANCH
<br />CIRCUIT BREAKERS SERVING 120/208 RECEPTACLE OUTLETS RATED 21 -50 AMPS SINGLE
<br />PHASE AND 21-100 AMPS THREE PHASE IN THE FOLLOWING LOCATIONS, AS SHOWN ON
<br />DRAWINGS, OR REQUIRED BY ADOPTED CODE:
<br />1. INTERIOR/EXTERIOR LOCATIONS SUBJECT TO DAMP/WET CONDITIONS
<br />2. WHEN LOCATED WITHIN 6 FEET OF SINKS, BATHTUBS, AND SHOWER STALLS
<br />D.INSTALL RECEPTACLES VERTICALLY WITH GROUND SLOT UP OR WHERE INDICATED ON THE
<br /> DRAWINGS, HORIZONTALLY WITH GROUND SLOT TO THE LEFT.
<br />E.INSTALL DECORATIVE PLATES ON SWITCH, RECEPTACLE, AND BLANK OUTLETS IN FINISHED
<br /> AREAS, USING JUMBO SIZE PLATES FOR OUTLETS INSTALLED IN MASONRY WALLS.
<br />F.INSTALL DEVICES AND WALL PLATES FLUSH AND LEVEL.
<br />G.INSTALL NAMEPLATE IDENTIFICATION TO RECEPTACLE COVER PLATES INDICATED.
<br /> IDENTIFICATION SHALL IDENTIFY PANEL NAME AND CIRCUIT NUMBER. REFER TO SPECIFICATION
<br /> SECTION 26 05 53 -ELECTRICAL IDENTIFICATION.
<br />H.TEST RECEPTACLES FOR PROPER POLARITY, GROUND CONTINUITY AND COMPLIANCE WITH
<br /> REQUIREMENTS.
<br />END OF SECTION
<br />TE OLIRFFOAC
<br />LANRP
<br />E 23191
<br />STA
<br />ER
<br />REGIST
<br />ED
<br />INA
<br />N
<br />REENIGE
<br />FO OISSE
<br />E AICLCERTL
<br />Exp. 06/30/26
<br />MIRASOPHOCLISGEORGY
<br />IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,
<br />TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
<br />AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND SHALL
<br />NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE
<br />EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP.
<br />©2022 IMEG CORP.
<br />REF. SCALE IN INCHES
<br />0 1 2 3
<br />The FUTURE. Built Smarter www.imegcorp.com
<br />R
<br />SHEET TITLE
<br />PROJECT
<br />FACILITY
<br />FAC NO: BLDG NO: FLOOR LEV: SECTION:
<br />KP PROJ. NO.
<br />PERMIT NO.
<br />555 W. 5th St Suite 2950 | Los Angeles, CA 90013 USA
<br />Phone 310.820.4600 | Fax 310.207.4215
<br />www.huitt-zollars.com
<br />ARCHITECT
<br />CONSULTANT
<br />ARCHITECT SEAL CONSULTANT SEAL
<br />KAISER FOUNDATION
<br />HOSPITALS NATIONAL
<br />FACILITIES SERVICES 1800
<br />HARRISON STREET OAKLAND,
<br />CALIFORNIA 94612
<br />ISSUE / REVISION LOG
<br />NO. ISSUED DATE
<br />0
<br />5'
<br />
<br />5
<br />0
<br />'
<br />GR
<br />A
<br />P
<br />H
<br />I
<br />C
<br />
<br />S
<br />C
<br />A
<br />L
<br />E
<br />S
<br />:
<br />
<br />1
<br />/
<br />1
<br />6
<br />"
<br />
<br />=
<br />
<br />1
<br />'
<br />-
<br />0
<br />"
<br />0
<br />25
<br />'
<br />1/
<br />8
<br />"
<br />
<br />=
<br />
<br />1
<br />'
<br />-
<br />0
<br />"
<br />5'
<br />0
<br />12
<br />'
<br />1/
<br />4
<br />"
<br />
<br />=
<br />
<br />1
<br />'
<br />-
<br />0
<br />"
<br />1'
<br />0
<br />6'
<br />1/
<br />2
<br />"
<br />
<br />=
<br />
<br />1
<br />'
<br />-
<br />0
<br />"
<br />1'
<br />0
<br />2'
<br />1-
<br />1
<br />/
<br />2
<br />"
<br />
<br />=
<br />
<br />1
<br />'
<br />-
<br />0
<br />"
<br />0
<br />1'
<br />3"
<br />
<br />=
<br />
<br />1
<br />'
<br />-
<br />0
<br />"
<br />IF
<br />
<br />T
<br />H
<br />I
<br />S
<br />
<br />S
<br />H
<br />E
<br />E
<br />T
<br />
<br />I
<br />S
<br />
<br />N
<br />O
<br />T
<br />
<br />30
<br />"
<br />x
<br />4
<br />2
<br />"
<br />,
<br />
<br />I
<br />T
<br />
<br />I
<br />S
<br />
<br />A
<br />
<br />R
<br />E
<br />D
<br />U
<br />C
<br />E
<br />D
<br />
<br />PR
<br />I
<br />N
<br />T
<br />
<br />-
<br />
<br />S
<br />C
<br />A
<br />L
<br />E
<br />
<br />AC
<br />C
<br />O
<br />R
<br />D
<br />I
<br />N
<br />G
<br />L
<br />Y
<br />AGENCY APPLICATION NUMBER
<br />AGENCY APPROVAL STAMP
<br />THIS DOCUMENT IS THE PROPERTY OF THE OWNER AND IS
<br />NOT TO BE USED WITHOUT OWNER'S WRITTEN PERMISSION.
<br />HZ PROJ. NO.
<br />222 S. HARBOR BOULEVARD, SUITE 800 I ANAHEIM, CA 92805
<br />PH: 714.490.5555 I FAX: 714.490.5560
<br />IMEG PROJ. NO.: 22008618.00
<br />PROJECT #22008618.00
<br />SOCC 2022 R HBM 1st Fl KPOJ
<br />REMODEL
<br />E0-05
<br />ELECTRICAL SPECIFICATION
<br />CA394-1
<br />CAP0227721R314412.35
<br />HARBOR/MacARTHUR MEDICAL OFF
<br />3401 S. HARBOR BLVD.
<br />SANTA ANA, CALIFORNIA 92704
<br />CITY SUBMITTAL 11/03/2025
<br />101125520, 20187249, 40140902
|