SPECIFICATIONS TABLE OF CONTENTS <br />SECTION 26 09 33 -LIGHTING CONTROL SYSTEMS <br />PART 1 -GENERAL <br />1.1 SECTION INCLUDES <br />A. LINE AND LOW VOLTAGE STANDALONE LIGHTING CONTROLS <br />B. AUTOMATIC LOAD CONTROL RELAY (ALCR20) <br />C. DISTRIBUTED LIGHTING CONTROL <br />1.2 RELATED SECTIONS <br />A. THE LIGHTING SYSTEM DESIGN INCLUDES A COMBINATION OF LUMINAIRE SOURCES, LIGHTING <br />CONTROL COMPONENTS, PROGRAMMING SEQUENCES, AND SUPPLEMENTARY COMPONENTS <br />FOR BUILDING AND ENERGY CODE COMPLIANCE. THE DESIGN USES PERFORMANCE-BASED <br />SPECIFICATIONS FOR PORTIONS OF THE LIGHTING SYSTEM TO ACCOUNT FOR THE LIMITATION <br />OF COMPARABLE PRODUCT SOLUTIONS AVAILABLE BY COMPETITIVE MANUFACTURERS. THE <br />CONTRACTOR SHALL REFERENCE RELATED SPECIFICATION SECTIONS, PLANS, SCHEDULES, <br />AND DETAILS PRIOR TO SUBMITTING PRICING, SUBMITTALS, AND INSTALLATION. THE <br />CONTRACTOR SHALL COORDINATE SYSTEM COMPONENT COMPATIBILITY AMONG VARIOUS <br />MANUFACTURERS AND SUPPLIERS FOR A TURNKEY LIGHTING SYSTEM. REFERENCED <br />SECTIONS INCLUDE, BUT ARE NOT LIMITED TO, THE FOLLOWING: <br />1. 26 51 19 LED LIGHTING <br />2. ELECTRICAL DRAWINGS: PLANS, LUMINAIRE SCHEDULES, AND DETAILS. <br />1.3 QUALITY ASSURANCE <br />A. MANUFACTURERS SHALL BE REGULARLY ENGAGED IN THE MANUFACTURE OF LIGHTING <br />CONTROL EQUIPMENT AND ANCILLARY EQUIPMENT, OF TYPES AND CAPACITIES REQUIRED, <br />WHOSE PRODUCTS HAVE BEEN IN SATISFACTORY USE IN SIMILAR SERVICE FOR NOT LESS <br />THAN FIVE (5) YEARS. <br />B. ALL COMPONENTS AND ASSEMBLIES ARE TO BE FACTORY PRE-TESTED PRIOR TO DELIVERY <br />AND INSTALLATION. <br />C. COMPLY WITH ELECTRICAL CODE AS APPLICABLE TO ELECTRICAL WIRING WORK. <br />D. COMPLY WITH APPLICABLE PORTIONS OF NEMA STANDARDS PERTAINING TO TYPES OF <br />ELECTRICAL EQUIPMENT AND ENCLOSURES. <br />E. PANELS AND ACCESSORY DEVICES ARE TO BE UL LISTED UNDER UL 916 ENERGY MANAGEMENT <br />EQUIPMENT. PANELS AND ACCESSORIES USED FOR CONTROL OF LIFE SAFETY AND CRITICAL <br />BRANCH CIRCUITS SHALL BE LISTED UNDER UL 924 EMERGENCY LIGHTING AND POWER <br />EQUIPMENT. <br />F. ALL ASSEMBLIES ARE TO BE IN COMPLIANCE WITH FCC EMISSIONS STANDARDS SPECIFIED IN <br />PART 15 SUBPART J FOR CLASS A APPLICATIONS. <br />1.4 REFERENCES <br />A. FCC RULES AND REGULATIONS, PART 15, SUBPART J -RADIO FREQUENCY INTERFERENCE <br />B. FS W S 896 SWITCH, TOGGLE <br />C. CALIFORNIA ENERGY CODE -BUILDING ENERGY EFFICIENCY STANDARDS TITLE 24 <br />D. NEMA WD 1 -GENERAL COLOR REQUIREMENTS FOR WIRING DEVICES <br />E. NEMA WD 7 -OCCUPANCY MOTION SENSORS <br />F. CEC CALIFORNIA ELECTRICAL CODE <br />G. UL STANDARD 916 ENERGY MANAGEMENT EQUIPMENT <br />H. UL 924 -EMERGENCY LIGHTING AND POWER EQUIPMENT <br />I. UL 1472 -SOLID-STATE DIMMING CONTROLS <br />1.5 SUBMITTALS <br />A. SUBMIT PRODUCT DATA UNDER PROVISIONS OF SECTION 26 05 00. <br />B. SUBMIT A COMPREHENSIVE PACKAGE INCLUDING DEVICES, HARDWARE, SOFTWARE, PRODUCT <br />SPECIFICATION, FINISHES, DIMENSIONS, INSTALLATION INSTRUCTIONS, WARRANTY, SYSTEM <br />SOFTWARE REQUIREMENTS[, AND ROLES AND RESPONSIBILITIES OF ALL PERSONS AND <br />GROUPS INVOLVED IN INSTALLATION, EXECUTION, AND COMMISSIONING]. <br />C. PROVIDE FLOOR PLAN SHOWING LOCATION, ORIENTATION, AND COVERAGE AREA OF EACH <br />CONTROL DEVICE, SENSOR, AND CONTROLLER/INTERFACE. FOR AREAS REQUIRING MULTIPLE <br />SENSOR DEVICES FOR APPROPRIATE COVERAGE, SUBMIT SPECIFIC MANUFACTURER- <br />APPROVED SENSOR LAYOUT AS AN OVERLAY DIRECTLY ON THE PROJECT DRAWINGS, EITHER <br />IN PRINT OR APPROVED ELECTRONIC FORM. <br />D. SUBMIT A LIST OF DEVICES AND EQUIPMENT THAT WILL BE INSTALLED FOR EACH SEQUENCE <br />OF OPERATION. <br />E. SUBMIT PROJECT SPECIFIC CONTROL WIRING DIAGRAMS SHOWING ALL EQUIPMENT, LINE <br />VOLTAGE, AND CONTROL WIRING REQUIREMENTS FOR ALL COMPONENTS INCLUDING, BUT NOT <br />LIMITED TO, DIMMERS, RELAYS, LOW VOLTAGE SWITCHES, OCCUPANCY SENSORS, CONTROL <br />STATIONS, AND COMMUNICATION INTERFACES AND PROGRAMMING INSTRUCTIONS FOR EACH <br />SEQUENCE OF OPERATION. INCLUDE NETWORK CABLE SPECIFICATION AND END-OF-LINE <br />TERMINATION DETAILS, IF REQUIRED. <br />1.6 EXTRA STOCK <br />A. PROVIDE EXTRA STOCK UNDER PROVISIONS OF SECTION 26 05 00. <br />B. SENSORS, CONTROLS, POWER SUPPLIES, AND RELAYS: FIVE (5) PERCENT OF QUANTITY <br />INSTALLED. MINIMUM OF TWO (2) OF EACH CONFIGURATION AND TYPE. <br />1.7 PROJECT RECORD DOCUMENTS <br />A. SUBMIT PROJECT RECORD DOCUMENTS UNDER PROVISIONS OF SECTION 26 05 00. <br />B. ACCURATELY RECORD LOCATION OF ALL CONTROLS AND DEVICES. INCLUDE DESCRIPTION OF <br />SWITCHING SEQUENCES AND CIRCUITING ARRANGEMENTS. <br />1.8 OPERATION AND MAINTENANCE DATA <br />A. SUBMIT EMERGENCY, OPERATION, AND MAINTENANCE DATA UNDER PROVISIONS OF SECTION <br />26 05 00. DATA SHALL ALSO INCLUDE THE FOLLOWING: <br />1. SCHEDULE FOR ROUTINE MAINTENANCE, INSPECTION, AND CALIBRATION OF ALL LIGHTING <br />CONTROL DEVICES AND SYSTEM COMPONENTS. RECOMMENDED SCHEDULE FOR <br />INSPECTION AND RECALIBRATION OF SENSORS. <br />2. COMPLETE NARRATIVE DESCRIBING INTENDED OPERATION AND SEQUENCE FOR EACH <br />CONTROL SCENARIO AND SYSTEM COMPONENT, UPDATED TO REFLECT ALL CHANGES <br />RESULTING FROM COMMISSIONING OF SYSTEMS. NARRATIVE SHALL INDICATE <br />RECOMMENDED SETTINGS FOR DEVICES WHERE APPLICABLE. <br />3. REPLACEMENT PART NUMBERS FOR ALL SYSTEM COMPONENTS. <br />B.IDENTIFY INSTALLED LOCATION AND LABELING FOR EACH LUMINAIRE CONTROLLED BY <br /> AUTOMATED LIGHTING CONTROLS. <br />1.9 SYSTEM DESCRIPTION <br />A. PERFORMANCE STATEMENT: THIS SPECIFICATION SECTION AND THE ACCOMPANYING LIGHTING <br />DESIGN DOCUMENTS DESCRIBE THE MINIMUM MATERIAL QUALITY, REQUIRED FEATURES, AND <br />OPERATIONAL REQUIREMENTS OF THE LIGHTING CONTROL SYSTEM (LCS). THESE DOCUMENTS <br />DO NOT CONVEY EVERY WIRE THAT MUST BE INSTALLED AND EVERY EQUIPMENT CONNECTION <br />THAT MUST BE MADE. BASED ON THE PERFORMANCE REQUIRED OF THE SYSTEM, AS <br />PRESENTED IN THESE DOCUMENTS, THE CONTRACTOR AND SYSTEM MANUFACTURER/VENDOR <br />ARE SOLELY RESPONSIBLE FOR DETERMINING ALL EQUIPMENT, WIRING, AND PROGRAMMING <br />REQUIRED FOR A COMPLETE AND OPERATIONAL SYSTEM. <br />B. PROVIDE AN INTEGRATED LIGHTING CONTROLS SYSTEM CONSISTING OF PANELS, POWER <br />SUPPLIES, CONTROLLERS, SENSORS, RELAYS, SWITCHES, DEVICES, WIRING, ETC. NECESSARY <br />TO PERFORM THE LIGHTING CONTROL SEQUENCE OF OPERATION AS DEFINED ON THE PLANS <br />AND SPECIFICATIONS. CONTRACTOR IS RESPONSIBLE FOR CONFIRMING THAT ALL <br />COMPONENTS AND LUMINAIRES INTEROPERATE AS A SINGLE SYSTEM. <br />1. SEQUENCE OF OPERATION: DESCRIBES THE REQUIRED OPERATION AND PERFORMANCE <br />FOR LIGHTING CONTROL IN EACH SPACE. SEQUENCES OF OPERATION ARE INDICATED ON <br />THE DRAWINGS. <br />2. DRAWINGS: THE DRAWINGS INCLUDE SEQUENCES OF OPERATION, LOCATIONS OF <br />CONTROL INTERFACE DEVICES, SENSORS, AND CONTROL ZONES. WIRING AND ADDITIONAL <br />EQUIPMENT TO MAKE A COMPLETE AND FUNCTIONING SYSTEM HAS NOT BEEN SHOWN, BUT <br />SHALL BE SUBMITTED WITH THE SHOP DRAWINGS. <br />C.THE FOLLOWING CONTROL TYPES AND FEATURES ARE ACCEPTABLE. ACCEPTABLE CONTROL <br /> LOCATIONS ARE SHOWN ON THE DRAWINGS. <br />1. LINE VOLTAGE CONTROL: CONTROL EQUIPMENT CONSISTS OF TRADITIONAL LINE VOLTAGE <br />WIRING DEVICES AND EQUIPMENT SUCH AS SWITCHES, DIMMERS AND COMBINATION <br />OCCUPANCY/VACANCY SENSOR SWITCHES, ETC. <br />2. DISTRIBUTED CONTROL: CONTROL EQUIPMENT IS IN THE SPACE/ZONE BEING CONTROLLED; <br />NOT RELIANT ON CENTRALIZED CONTROLLERS. <br />1.10 WARRANTY <br />A. MANUFACTURER SHALL WARRANT PRODUCTS UNDER NORMAL USE AND SERVICE TO BE FREE <br />FROM DEFECTS IN MATERIALS AND WORKMANSHIP FOR A PERIOD OF TWO (2) YEARS FROM <br />DATE OF COMMISSIONING. <br />B. OCCUPANCY, VACANCY, DAYLIGHT SENSORS AND CONTROLS SHALL HAVE A FIVE (5) YEAR <br />WARRANTY FROM DATE OF SUBSTANTIAL COMPLETION. <br />PART 2 -PRODUCTS <br />2.1 LIGHTING CONTROLS <br />A. ALL ITEMS OF MATERIAL HAVING A SIMILAR FUNCTION (E.G., SWITCHES, DIMMERS, SENSORS, <br />CONTACTORS, RELAYS, ETC.) SHALL BE OF THE SAME MANUFACTURER, UNLESS SPECIFICALLY <br />STATED OTHERWISE ON DRAWINGS OR ELSEWHERE IN THE SPECIFICATIONS. LIGHTING <br />CONTROL SWITCHES, SYSTEMS, AND COMPONENTS SHALL BE LISTED. <br />B. COLOR OF LIGHTING CONTROLS AND SENSORS SHALL MATCH THE RECEPTACLE WIRING <br />DEVICES SPECIFIED IN THE SPACE. <br />C. THE FUNCTIONS DESCRIBED IN THE LIGHTING SEQUENCE OF OPERATION SHALL DICTATE THE <br />ACTUAL LIGHTING CONTROL DEVICE REQUIRED TO ACCOMPLISH THE FUNCTIONS DESCRIBED <br />FOR THE SPACE. <br />• SECTION 26 09 33 -LIGHTING CONTROL SYSTEMS <br />• SECTION 26 24 19 -MOTOR CONTROL <br />• SECTION 26 27 26 -WIRING DEVICES <br />2.2 DEVICE COLOR <br />A. ALL SWITCH, LIGHTING CONTROLS, AND COVER PLATE COLORS SHALL BE THE SAME AS WIRING <br />DEVICES, UNLESS INDICATED OTHERWISE. <br />2.3 COVERPLATES <br />A. ALL SWITCHES AND LIGHTING CONTROLS SHALL BE COMPLETE WITH COVER PLATES THAT <br />MATCH MATERIAL AND COLOR OF THE WIRING DEVICE COVER PLATES IN THE SPACE. <br />B. WHERE SEVERAL DEVICES ARE GANGED TOGETHER, THE COVER PLATE SHALL BE OF THE <br />GANGED STYLE FOR THE NUMBER OF DEVICES USED. <br />C. INSTALL NAMEPLATE IDENTIFICATION AS INDICATED IN SECTION 26 05 53. <br />D. PLATE-SECURING SCREWS SHALL BE METAL WITH HEAD COLOR MATCHING THE WALL PLATE <br />FINISH. <br />2.4 WALL SWITCHES <br />A. REFER TO ELECTRICAL SYMBOLS LIST FOR DEVICE TYPE. <br />B. SW-1P; SINGLE POLE SWITCH: <br />1. SINGLE THROW, 120/277-VOLT, 20-AMP MAINTAINED CONTACT. TOGGLE HANDLE, SIDE AND <br />BACK WIRED. <br />2. MANUFACTURERS: <br />a. HUBBELL HBL1221 <br />b. LEVITON 1221-2 <br />c. PASS & SEYMOUR PS20AC1 <br />d. COOPER AH1221 <br />C.SW-1P-EM; EMERGENCY SINGLE POLE SWITCH: <br />1. SINGLE THROW, 120/277-VOLT, 20-AMP MAINTAINED CONTACT. RED HANDLE, SIDE AND BACK <br />WIRED. <br />2. MANUFACTURERS: <br />a. HBL1221R <br />b. LEVITON 1221-2R <br />c. PASS & SEYMOUR PS20AC1-RED <br />d. COOPER AH1221RD <br />2.5 WALL DIMMERS <br />A. UL LISTED WITH INTEGRAL AIR-GAP SWITCH FOR ON/OFF CONTROL. <br />B. INTEGRAL EMI/RFI SUPPRESSION. <br />C. NON-VIEWABLE HEAT SINK. <br />D. DIMMER COMPATIBILITY AND WIRING WITH THE LOAD BEING CONTROLLED SHALL BE VERIFIED <br />BY CONTRACTOR PRIOR TO PURCHASE AND INSTALLATION. <br />E. DIMMER TO MATCH DEVICE COLOR. <br />F. SW-D-LED; LED ELECTRONIC DRIVER DIMMER: <br />1. 277-VOLT, DECORA STYLE LINEAR SLIDER OPERATOR WITH POSITIVE OFF. COLOR TO <br />MATCH ADJACENT DEVICES. LUMINAIRE MANUFACTURER SHALL LIST COMPATIBLE DIMMER <br />MANUFACTURERS AND MODELS. 0-10V DIMMERS SHALL COMPLY WITH IEC 60629 ANNEX E. <br />2. MANUFACTURERS: <br />a. COMPATIBLE WITH PROVIDED LED DRIVER. <br />2.6 INDOOR OCCUPANCY SENSORS <br />A. GENERAL DESCRIPTION: WALL-OR CEILING-MOUNTING, SOLID-STATE UNITS WITH A SEPARATE <br />POWER SUPPLY/RELAY UNIT. <br />1. OPERATION: UNLESS OTHERWISE INDICATED, TURN LIGHTS ON WHEN COVERED AREA IS <br />OCCUPIED AND OFF WHEN UNOCCUPIED, WITH A TIME DELAY FOR TURNING LIGHTS OFF, <br />ADJUSTABLE OVER A MINIMUM RANGE OF 1 TO 30 MINUTES. <br />2. SENSOR OUTPUT: CONTACTS RATED TO OPERATE THE CONNECTED RELAY, COMPLYING <br />WITH UL 773A. SENSOR SHALL BE POWERED FROM THE RELAY UNIT. <br />3. RELAY UNIT: DRY CONTACTS RATED FOR 20 A BALLAST LOAD AT 120 AND 277 VAC, FOR 13- <br />AMP TUNGSTEN AT 120 VAC, AND FOR 1 HP AT 120 VAC. POWER SUPPLY TO SENSOR SHALL <br />BE 24 V DC, 150-MA, CLASS 2 POWER SOURCE AS DEFINED BY ELECTRICAL CODE. <br />4. MOUNTING: <br />a. SENSOR: SUITABLE FOR MOUNTING IN ANY POSITION ON A STANDARD OUTLET BOX. <br />b. RELAY: EXTERNALLY MOUNTED THROUGH A 1/2-INCH KNOCKOUT IN A STANDARD <br />ELECTRICAL ENCLOSURE. MOUNT RELAY ABOVE ACCESSIBLE CEILING NEAR ENTRY <br />DOOR TO ROOM OR AREA. <br />c. TIME DELAY AND SENSITIVITY ADJUSTMENTS: RECESSED AND CONCEALED. <br />5.INDICATOR: LED TO SHOW WHEN MOTION IS BEING DETECTED DURING TESTING AND <br /> NORMAL OPERATION OF THE SENSOR. <br />6.BYPASS SWITCH: OVERRIDE THE ON FUNCTION IN CASE OF SENSOR FAILURE. <br />7.POWER SUPPLY AND CHILD PACKS: PROVIDE AS REQUIRED FOR SENSOR QUANTITY AND <br /> SWITCHING SCHEME. MOUNT TO STANDARD 1/2" KNOCKOUT ON ELECTRICAL BOX ABOVE <br /> ACCESSIBLE CEILING NEAR ENTRY DOOR TO ROOM OR AREA. SENSOR POWER SHALL BE <br /> FROM EMERGENCY CIRCUIT IF EMERGENCY LIGHTING IS IN THE AREA. <br />8.DETECTION COVERAGE (ROOM): DETECT OCCUPANCY ANYWHERE IN AN AREA BASED ON <br /> HAND MOTION. <br />9.WARRANTY: FIVE (5) YEAR WARRANTY. <br />B.DUAL-TECHNOLOGY TYPE: DETECT OCCUPANCY BY USING A COMBINATION OF PIR AND <br /> ULTRASONIC [OR ACOUSTIC] DETECTION METHODS IN AREA OF COVERAGE. PARTICULAR <br /> TECHNOLOGY OR COMBINATION OF TECHNOLOGIES THAT CONTROLS ON AND OFF FUNCTIONS <br /> SHALL BE SELECTABLE IN THE FIELD BY OPERATING CONTROLS ON UNIT. <br />1. SW-VS-D OR SW-OC-D; 360 DEGREE COVERAGE PATTERN: <br />a. FREQUENCY GREATER THAN 40 KHZ. DUAL SENSING VERIFICATIONS (REQUIRES BOTH <br />TECHNOLOGIES TO ACTIVATE), EITHER TECHNOLOGY MAINTAINS ON STATUS. <br />INTEGRATED AMBIENT LIGHT LEVEL SENSOR (2 TO 200 FC RANGE), ADJUSTABLE <br />SENSITIVITY AND TIME DELAY[, INTEGRATED ISOLATED RELAY CONTACT]. SENSOR <br />SHALL CONTROL ALL CIRCUITS IN AREA, UNLESS NOTED OTHERWISE. INITIAL SETTINGS: <br />AMBIENT SENSOR 40 FC. <br />b. MANUFACTURERS: <br />1. WATT STOPPER DT 300 SERIES <br />2. LEVITON OSC##-MOW <br />2.SW-O; WALL SWITCH: <br />a. WALL SWITCH WITH MANUAL ON/AUTO OFF. 120/277 VAC LOAD RATING OF 0-800 W FOR <br />BALLAST, LED OR TUNGSTEN. 5-, 15-, 30-MINUTE ADJUSTABLE OFF DELAY. COVERAGE <br />OF MINOR MOTION IN 12' X 15' PATTERN. <br />b. MANUFACTURERS: <br />1. WATT STOPPER DW-100 SERIES <br />2.7 DISTRIBUTED LIGHTING CONTROL <br />A. MANUFACTURERS: AS LISTED BELOW MEET THE QUALIFICATIONS AS OUTLINED IN THIS <br />SPECIFICATION. CONTRACTOR IS RESPONSIBLE FOR VERIFYING THAT SELECTED <br />MANUFACTURER IS CAPABLE OF FURNISHING THE COMPLETE SYSTEM AS SPECIFIED HEREIN. <br />1. ACUITY CONTROLS NLIGHT SERIES <br />2. LEGRAND WATT STOPPER DLM SERIES <br />3. APPROVED EQUAL <br />B.SYSTEM DESCRIPTION: THE LIGHTING CONTROL SYSTEM SHALL BE A NETWORK OF REMOTE <br /> MODULES SYSTEM INCLUDES ALL ASSOCIATED WIRING, RELAY MODULES, PHOTOCELLS, <br /> SWITCHES, DIMMERS, TIME CLOCK, OCCUPANCY SENSORS. SYSTEM SHALL UTILIZE <br /> DISTRIBUTED RELAYS MODULES, ALLOWING THESE RELAY MODULES TO BE LOCATED ABOVE <br /> ACCESSIBLE CEILINGS IN OR ADJACENT TO ROOMS THEY ARE CONTROLLING. <br />C.CONTROL DEVICES: ALL OCCUPANCY SENSORS SHALL BE DUAL TECHNOLOGY TYPE. <br /> OCCUPANCY SENSORSSHALL BE PROVIDED WITH SYSTEM AND DESIGNED TO OPERATE ON <br /> SYSTEM NETWORK. SUPPLEMENTAL POWER PACKS SHALL BE PROVIDED AS REQUIRED FOR <br /> MULTIPLE CONTROL DEVICES. THIS EQUIPMENT SHALL BE IDENTIFIED IN SHOP DRAWING <br /> SUBMISSION. <br />D.RELAY MODULES: MOUNTED IN NEMA ENCLOSURE WITH PHYSICALLY SEPARATE 120/277-VOLT <br /> WIRING COMPARTMENT FROM LOW VOLTAGE CONTROL WIRING. PROVIDE LOW VOLTAGE <br /> DIGITAL COMMUNICATION TO CONTROL DEVICES AS SHOWN ON DRAWINGS AND SCHEDULES. <br /> SUPPLEMENTAL POWER PACKS SHALL BE PROVIDED AS REQUIRED FOR MULTIPLE CONTROL <br /> DEVICES. THIS EQUIPMENT SHALL BE IDENTIFIED IN SHOP DRAWING SUBMISSION. DIMMABLE <br /> RELAY MODULES SHALL BE PROVIDED WHERE INDICATED. RELAY MODULES SHALL CONTAIN UP <br /> TO FOUR (4) RELAYS. RELAY MODULES SHALL BE LABELED WITH ROOM NUMBER THAT RELAYS <br /> CONTROL LIGHTING WITHIN. <br />2.8 CONDUCTORS AND CABLES <br />A. CONTROL WIRING: <br />1. NETWORK CABLING AS REQUIRED BY MANUFACTURER. <br />PART 3 -EXECUTION <br />3.1 EXAMINATION <br />A. VERIFY THAT SURFACES ARE READY TO RECEIVE WORK. <br />B. VERIFY FIELD DIMENSIONS AND COORDINATE PHYSICAL SIZE OF ALL EQUIPMENT WITH THE <br />ARCHITECTURAL REQUIREMENTS OF THE SPACES INTO WHICH THEY ARE TO BE INSTALLED. <br />ALLOW SPACE FOR ADEQUATE VENTILATION AND CIRCULATION OF AIR. <br />C. VERIFY THAT REQUIRED UTILITIES ARE AVAILABLE, IN PROPER LOCATION, AND READY FOR USE. <br />D. BEGINNING OF INSTALLATION MEANS INSTALLER ACCEPTS EXISTING CONDITIONS. <br />3.2 INSTALLATION <br />A. INSTALL IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND APPROVED SHOP <br />DRAWINGS. <br />B. ALL WIRING SHALL BE INSTALLED IN CONDUIT. CLASS II LOW VOLTAGE CONTROL WIRING MAY <br />BE OPEN WIRING AND SHALL MAINTAIN 150 MM (6 INCH) SPACING FROM ELECTRONIC BALLAST <br />AND OTHER RFI/EMI SOURCES. <br />C. ALL BRANCH LOAD CIRCUITS SHALL BE LIVE TESTED BEFORE CONNECTING THE LOADS TO THE <br />LIGHTING CONTROL PANEL. <br />3.3 AUTOMATIC LOAD CONTROL RELAYS (ALCR20) AND BRANCH CIRCUIT EMERGENCY LIGHTING <br />TRANSFER SWITCH (BCELTS) <br />3.4 SUPPORT SERVICES <br />A. SYSTEM STARTUP: <br />1. MANUFACTURER SHALL PROVIDE FACTORY AUTHORIZED TECHNICIAN TO CONFIRM <br />PROPER INSTALLATION AND OPERATION OF ALL SYSTEM COMPONENTS. <br />B.TESTING: <br />1. SYSTEM SHALL BE COMPLETELY FUNCTIONAL TESTED BY A FACTORY-AUTHORIZED <br />TECHNICIAN. ALL LOADS SHALL BE TESTED LIVE FOR CONTINUITY AND FREEDOM FROM <br />DEFECTS, AND ALL CONTROL WIRING SHALL BE TESTED FOR CONTINUITY AND <br />CONNECTIONS PRIOR TO ENERGIZING THE SYSTEM COMPONENTS. <br />2. PROGRAMMING OF INITIAL ZONES, SCHEDULES, LIGHTING LEVELS, CONTROL STATION <br />GROUPS, AND SENSOR SETTINGS SHALL BE PERFORMED BY A FACTORY-AUTHORIZED <br />TECHNICIAN. LIGHTING CONTROL SEQUENCE OF OPERATION SHALL SERVE AS A BASIS FOR <br />PROGRAMMING, HOWEVER, ALL FINAL DECISIONS REGARDING GROUPS AND SCHEDULES <br />SHALL BE AT THE DIRECTION OF THE OWNER. THE FOLLOWING PROCEDURES SHALL BE <br />PERFORMED AT A MINIMUM: <br />a. CONFIRM OCCUPANCY SENSOR PLACEMENT, SENSITIVITY, AND TIME DELAY SETTINGS <br />TO MEET SPECIFIED PERFORMANCE CRITERIA. <br />b. CONFIRM DAYLIGHT SENSOR PLACEMENT, SENSITIVITY, DEADBAND, AND DELAY <br />SETTINGS TO MEET SPECIFIED PERFORMANCE CRITERIA. <br />c. CONFIRM THAT SCHEDULES AND TIME CONTROLS ARE CONFIGURED TO MEET <br />SPECIFIED PERFORMANCE CRITERIA AND OWNER'S OPERATING REQUIREMENTS. <br />3.VERIFY OCCUPANCY SENSOR OPERATION IS CORRECT AFTER FURNITURE AND EQUIPMENT <br /> IS INSTALLED IN EACH AREA. MAKE ADJUSTMENTS TO SENSOR SETTINGS AND TIME DELAYS <br /> TO ALLOW PROPER OPERATION. <br />4.VERIFY OCCUPANCY/VACANCY SENSORS ARE LOCATED TO PROVIDE COMPLETE <br /> COVERAGE FOR THE AREA SERVED WITH NO NUISANCE SWITCHING. <br />a. RELOCATE SENSORS OR PROVIDE ADDITIONAL SENSORS AS NECESSARY TO PROVIDE <br />ADEQUATE COVERAGE. <br />b. MASK OCCUPANCY SENSORS WHERE NECESSARY TO PREVENT NUISANCE SWITCHING <br />FROM ADJACENT AREAS. <br />C.TRAINING: <br />1. MANUFACTURER SHALL PROVIDE COMPETENT FACTORY-AUTHORIZED TECHNICIAN TO <br />TRAIN OWNER PERSONNEL IN THE OPERATION, MAINTENANCE AND PROGRAMMING OF THE <br />LIGHTING CONTROL SYSTEM. SUBMIT TRAINING PLAN WITH NOTIFICATION SEVEN (7) DAYS <br />PRIOR TO PROPOSED TRAINING DATES. <br />2. TRAINING DURATION SHALL BE NO LESS THAN THREE (3) DAYS, WITH ONE (1) DAY BEING <br />SCHEDULED AT LEAST TWO (2) WEEKS AFTER INITIAL TRAINING. <br />D.DOCUMENTATION: <br />1. MANUFACTURER SHALL PROVIDE SYSTEM DOCUMENTATION INCLUDING: <br />a. SYSTEM ONE-LINE SHOWING ALL PANELS, NUMBER AND TYPE OF CONTROL STATIONS <br />AND SENSORS, COMMUNICATION LINE, AND NETWORK OR BMS/BAS INTERFACE UNIT. <br />b. DRAWINGS FOR EACH PANEL SHOWING HARDWARE CONFIGURATION AND NUMBERING. <br />c. PANEL WIRING SCHEDULES. <br />d. TYPICAL DIAGRAMS FOR EACH COMPONENT. <br />END OF SECTION <br />SECTION 26 24 19 -MOTOR CONTROL <br />PART 1 -GENERAL <br />1.1 SECTION INCLUDES <br />A. MANUAL MOTOR STARTERS <br />B. ENCLOSED CIRCUIT BREAKERS <br />1.2 RELATED SECTIONS AND WORK <br />A. REFER TO THE ONE-LINE DIAGRAM FOR RATING AND CONFIGURATION. <br />1.3 REFERENCES <br />A. ANSI/UL STANDARD 508. STANDARD FOR INDUSTRIAL CONTROL EQUIPMENT <br />B. FS W -C-375 -CIRCUIT BREAKERS, MOLDED CASE; BRANCH CIRCUIT AND SERVICE <br />C. FS W -S-865 -SWITCH, BOX, (ENCLOSED), SURFACE-MOUNTED <br />D. NEMA AB 1 -MOLDED CASE CIRCUIT BREAKERS <br />E. NEMA KS 1 -ENCLOSED SWITCHES <br />F. NEMA PB 1.1 -INSTRUCTIONS FOR SAFE INSTALLATION, OPERATION AND MAINTENANCE OF <br />PANELBOARDS RATED 600 VOLTS OR LESS <br />1.4 SUBMITTALS <br />A. SUBMIT SHOP DRAWINGS AND PRODUCT DATA UNDER PROVISIONS OF SECTION 26 05 00. <br />B. INDICATE ON SHOP DRAWINGS, FRONT AND SIDE VIEWS OF ENCLOSED CIRCUIT BREAKER WITH <br />OVERALL DIMENSIONS. INCLUDE CONDUIT ENTRANCE LOCATIONS AND REQUIREMENTS; <br />WIRING DIAGRAMS THAT DIFFERENTIATE BETWEEN MANUFACTURER-INSTALLED AND FIELD- <br />INSTALLED WIRING; NAMEPLATE LEGENDS; SIZE AND NUMBER OF BUS BARS PER PHASE, <br />[ NEUTRAL,] AND GROUND; ELECTRICAL CHARACTERISTICS INCLUDING VOLTAGE, FRAME SIZE <br />AND TRIP RATINGS, WITHSTAND RATINGS, AND TIME-CURRENT CURVES OF ALL EQUIPMENT <br />AND COMPONENTS. INDICATE CIRCUIT BREAKER DESIGNATION ON SHOP DRAWINGS. <br />C. PROVIDE PRODUCT DATA ON MOTOR STARTERS AND COMBINATION MOTOR STARTERS, <br />RELAYS, PILOT DEVICES, AND SWITCHING AND OVER-CURRENT PROTECTIVE DEVICES. <br />1.5 DELIVERY, STORAGE, AND HANDLING <br />A. DELIVER PRODUCTS TO SITE UNDER PROVISIONS OF SECTION 26 05 00. <br />B. STORE AND PROTECT PRODUCTS UNDER PROVISIONS OF SECTION 26 05 00. <br />C. STORE IN A CLEAN, DRY SPACE. MAINTAIN FACTORY WRAPPING OR PROVIDE AN ADDITIONAL <br />HEAVY CANVAS OR HEAVY PLASTIC COVER TO PROTECT UNITS FROM FUMES, DIRT, WATER, <br />CONSTRUCTION DEBRIS, TRAFFIC, AND PHYSICAL DAMAGE. <br />D. HANDLE IN ACCORDANCE WITH MANUFACTURER'S WRITTEN INSTRUCTIONS. LIFT ONLY WITH <br />LUGS PROVIDED FOR THE PURPOSE. HANDLE CAREFULLY TO AVOID DAMAGE TO MOTOR <br />CONTROL CENTER COMPONENTS, ENCLOSURE, AND FINISH. <br />1.6 OPERATION AND MAINTENANCE DATA <br />A. SUBMIT OPERATION AND MAINTENANCE DATA UNDER PROVISIONS OF SECTION 26 05 00. <br />B. INCLUDE SPARE PARTS DATA LISTING; SOURCE AND CURRENT PRICES OF REPLACEMENT <br />PARTS AND SUPPLIES; AND RECOMMENDED MAINTENANCE PROCEDURES AND INTERVALS. <br />PART 2 -PRODUCTS <br />2.1 MANUAL MOTOR STARTERS <br />A. ACCEPTABLE MANUFACTURERS: <br />1. SQUARE D 2500 SERIES <br />2. EATON MS SERIES <br />3. ABB <br />4. SIEMENS SMF / MMS SERIES <br />B.MANUAL MOTOR STARTER: NEMA ICS 2; AC GENERAL-PURPOSE CLASS A MANUALLY OPERATED <br /> NON-REVERSING FULL-VOLTAGE CONTROLLER FOR INDUCTION MOTORS RATED IN <br /> HORSEPOWER, WITH OVERLOAD RELAY, AND TOGGLE OPERATOR. <br />C.FRACTIONAL HORSEPOWER MANUAL STARTER: NEMA ICS 2; AC GENERAL-PURPOSE CLASS A <br /> MANUALLY OPERATED, FULL-VOLTAGE CONTROLLER FOR FRACTIONAL HORSEPOWER <br /> INDUCTION MOTORS, WITH THERMAL OVERLOAD UNIT, AND TOGGLE OPERATOR. <br />D.ENCLOSURE: NEMA ICS 6; TYPE 1. <br />2.2 ENCLOSEDOVER-CURRENT PROTECTION AND DISCONNECTING MEANS <br />1. STARTER MANUFACTURER <br />B.MOLDED CASE THERMAL-MAGNETIC CIRCUIT BREAKERS: CIRCUIT BREAKERS WITH INTEGRAL <br /> THERMAL AND ADJUSTABLE INSTANTANEOUS MAGNETIC TRIP IN EACH POLE. <br />C.NON-FUSIBLE SWITCH ASSEMBLIES: QUICK-MAKE, QUICK-BREAK, LOAD INTERRUPTER <br />ENCLOSED <br /> KNIFE SWITCH WITH EXTERNALLY OPERABLE HANDLE. PROVIDE INTERLOCK TO PREVENT <br /> OPENING FRONT COVER WITH SWITCH IN ON POSITION. HANDLE LOCKABLE IN OFF POSITION. <br />PART 3 -EXECUTION <br />3.1 INSTALLATION <br />A. SELECT AND INSTALL HEATER ELEMENTS IN MOTOR STARTERS TO MATCH INSTALLED MOTOR <br />CHARACTERISTICS. <br />B. SET FIELD-ADJUSTABLE SWITCHES AND CIRCUIT-BREAKER TRIP RANGES. <br />END OF SECTION <br />SECTION 26 27 26 -WIRING DEVICES <br />PART 1 -GENERAL <br />1.1 SECTION INCLUDES <br />A. DEVICE PLATES AND BOX COVERS <br />B. RECEPTACLES (REC-#) <br />1.2 QUALITY ASSURANCE <br />A. PROVIDE SIMILAR DEVICES FROM A SINGLE MANUFACTURER. <br />B. ELECTRICAL COMPONENTS, DEVICES, AND ACCESSORIES: LISTED AND LABELED AS DEFINED IN <br />THE ELECTRICAL CODE, BY A TESTING AGENCY TO AUTHORITIES HAVING JURISDICTION AND <br />MARKED FOR INTENDED USE. <br />C. CEC CALIFORNIA ELECTRICAL CODE <br />D. UL 498 -STANDARD FOR ATTACHMENT PLUGS AND RECEPTACLES <br />E. UL 943 -STANDARD FOR GROUND FAULT CIRCUIT INTERRUPTERS <br />1.3 SUBMITTALS <br />A. SUBMIT PRODUCT DATA UNDER PROVISIONS OF SECTION 26 05 00. <br />B. PROVIDE PRODUCT DATA SHOWING CONFIGURATIONS, FINISHES, DIMENSIONS, AND <br />MANUFACTURER'S INSTRUCTIONS. <br />1.4 COORDINATION <br />A. RECEPTACLES FOR OWNER FURNISHED EQUIPMENT: MATCH PLUG CONFIGURATIONS. <br />B. CORD AND PLUG SETS: MATCH EQUIPMENT REQUIREMENTS <br />PART 2 -PRODUCTS <br />2.1 DEVICE COLOR <br />A. ALL SWITCH, RECEPTACLE, AND OUTLET COLORS SHALL BE WHITE FOR NORMAL POWER AND <br />RED FOR EMERGENCY POWER. <br />2.2 COVERPLATES <br />A. ALL SWITCHES, RECEPTACLES, AND OUTLETS SHALL BE COMPLETE WITH THE FOLLOWING: <br />1. DECORATOR GRADE -DECORATOR THERMOPLASTIC AND MATCH DEVICE COLOR <br />WALLPLATES IN FINISHED SPACES WHERE WALLS ARE FINISHED. <br />a. MANUFACTURER: <br />1. LEVITON DECORA <br />2. HUBBELL DECORATOR <br />3. COOPER DECORATOR <br />4. OR APPROVED EQUAL <br />B.WHERE SEVERAL DEVICES ARE GANGED TOGETHER, THE COVERPLATE SHALL BE OF THE <br /> GANGED STYLE FOR THE NUMBER OF DEVICES USED. <br />C.INSTALL NAMEPLATE IDENTIFICATION AS INDICATED IN SECTION 26 05 53. <br />D.PLATE SECURING SCREWS SHALL BE METAL WITH HEAD COLOR MATCHING THE WALL PLATE <br />FINISH. <br />2.3 RECEPTACLES <br />A. REFER TO ELECTRICAL SYMBOLS LIST FOR DEVICE TYPE. <br />B. DEVICES THAT ARE SHADED ON THE DRAWINGS SHALL BE RED. <br />C. REC-DUP: NEMA 5-20R DUPLEX RECEPTACLE: <br />1. HOSPITAL GRADE: 125-VOLT, 20 AMP, 3-WIRE GROUNDING TYPE HOSPITAL GRADE WITH <br />IMPACT RESISTANT THERMOPLASTIC FACE AND ONE-PIECE NICKEL-PLATED BRASS BACK <br />STRAP WITH INTEGRAL GROUND CONTACTS. <br />a. MANUFACTURERS: <br />1. HUBBELL HBL8300 <br />2. LEVITON 8300 <br />3. PASS & SEYMOUR 8300 <br />4. COOPER AH8300 <br />D.REC-DUP-GFI: NEMA 5-20R GROUND FAULT DUPLEX RECEPTACLE: <br />1. HOSPITAL GRADE: 125-VOLT, 20 AMP, 3-WIRE GROUNDING TYPE HOSPITAL GRADE WITH <br />TEST AND RESET BUTTONS IN IMPACT RESISTANT THERMOPLASTIC FACE. <br />a. DEVICE SHALL PERFORM SELF-TEST OF GFCI CIRCUITRY IN ACCORDANCE WITH UL 943. <br />b. MANUFACTURERS: <br />1. HUBBELL GFRST83 <br />2. LEVITON GFNT2-HG <br />3. PASS & SEYMOUR 2097HG <br />4. COOPER SGFH20 <br />E.REC-QUAD: NEMA 5-20R DOUBLE DUPLEX RECEPTACLE: <br />1. CONSISTS OF TWO DUPLEX RECEPTACLES, DOUBLE GANG BOX, PLASTER RING AND <br />FACEPLATE. <br />a. MANUFACTURERS: <br />1. REFER TO DUPLEX RECEPTACLE ABOVE. <br />F.REC-QUAD-GFI: NEMA 5-20R DOUBLE DUPLEX GFI RECEPTACLE: <br />1. CONSISTS OF TWO DUPLEX GFI RECEPTACLES, DOUBLE GANG BOX, PLASTER RING AND <br />FACEPLATE. <br />a. MANUFACTURERS: <br />1. REFER TO DUPLEX GFI RECEPTACLE ABOVE. <br />G.BACK WIRED DEVICES SHALL BE COMPLETE WITH EIGHT HOLES THAT ARE SCREW ACTIVATED <br /> WITH METAL CLAMPS FOR CONNECTION TO #12 OR #10 COPPER CONDUCTORS. <br />H.SIDE WIRED DEVICES SHALL HAVE FOUR BINDING SCREWS THAT ARE UNDERCUT FOR POSITIVE <br /> WIRE RETENTION. <br />I.GROUND FAULT CIRCUIT INTERRUPTER (GFCI) RECEPTACLES SHALL COMPLY WITH UL 943 <br /> REQUIRING INCREASED SURGE IMMUNITY, IMPROVED CORROSION RESISTANCE, IMPROVED <br /> RESISTANCE TO FALSE TRIPPING AND DIAGNOSTIC INDICATION FOR MISWIRING IF THE LINE <br /> AND LOAD CONDUCTORS ARE REVERSED DURING INSTALLATION. <br />PART 3 -EXECUTION <br />3.1 INSTALLATION <br />A. INSTALL CONVENIENCE RECEPTACLES AT ELEVATIONS INDICATED IN THE GENERAL <br />INSTALLATION NOTES ON THE CONTRACT DRAWINGS. <br />B. INSTALL SPECIFIC-USE RECEPTACLES AT HEIGHTS SHOWN ON THE CONTRACT DRAWINGS. <br />INSTALL DEVICES LEVEL, PLUMB, AND SQUARE WITH BUILDING LINES. COORDINATE <br />INSTALLATION OF ADJACENT DEVICES OF SEPARATE SYSTEMS WITH COMMON MOUNTING <br />HEIGHTS, INCLUDING LIGHTING, POWER, SYSTEMS, TECHNOLOGY, AND TEMPERATURE <br />CONTROL DEVICE ROUGH-INS. <br />C. GROUND FAULT PROTECTION: PROVIDE GROUND FAULT PROTECTION FOR ALL BRANCH <br />CIRCUIT BREAKERS SERVING 120/208 RECEPTACLE OUTLETS RATED 21 -50 AMPS SINGLE <br />PHASE AND 21-100 AMPS THREE PHASE IN THE FOLLOWING LOCATIONS, AS SHOWN ON <br />DRAWINGS, OR REQUIRED BY ADOPTED CODE: <br />1. INTERIOR/EXTERIOR LOCATIONS SUBJECT TO DAMP/WET CONDITIONS <br />2. WHEN LOCATED WITHIN 6 FEET OF SINKS, BATHTUBS, AND SHOWER STALLS <br />D.INSTALL RECEPTACLES VERTICALLY WITH GROUND SLOT UP OR WHERE INDICATED ON THE <br /> DRAWINGS, HORIZONTALLY WITH GROUND SLOT TO THE LEFT. <br />E.INSTALL DECORATIVE PLATES ON SWITCH, RECEPTACLE, AND BLANK OUTLETS IN FINISHED <br /> AREAS, USING JUMBO SIZE PLATES FOR OUTLETS INSTALLED IN MASONRY WALLS. <br />F.INSTALL DEVICES AND WALL PLATES FLUSH AND LEVEL. <br />G.INSTALL NAMEPLATE IDENTIFICATION TO RECEPTACLE COVER PLATES INDICATED. <br /> IDENTIFICATION SHALL IDENTIFY PANEL NAME AND CIRCUIT NUMBER. REFER TO SPECIFICATION <br /> SECTION 26 05 53 -ELECTRICAL IDENTIFICATION. <br />H.TEST RECEPTACLES FOR PROPER POLARITY, GROUND CONTINUITY AND COMPLIANCE WITH <br /> REQUIREMENTS. <br />END OF SECTION <br />TE OLIRFFOAC <br />LANRP <br />E 23191 <br />STA <br />ER <br />REGIST <br />ED <br />INA <br />N <br />REENIGE <br />FO OISSE <br />E AICLCERTL <br />Exp. 06/30/26 <br />MIRASOPHOCLISGEORGY <br />IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, <br />TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING <br />AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND SHALL <br />NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE <br />EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. <br />©2022 IMEG CORP. <br />REF. SCALE IN INCHES <br />0 1 2 3 <br />The FUTURE. Built Smarter www.imegcorp.com <br />R <br />SHEET TITLE <br />PROJECT <br />FACILITY <br />FAC NO: BLDG NO: FLOOR LEV: SECTION: <br />KP PROJ. NO. <br />PERMIT NO. <br />555 W. 5th St Suite 2950 | Los Angeles, CA 90013 USA <br />Phone 310.820.4600 | Fax 310.207.4215 <br />www.huitt-zollars.com <br />ARCHITECT <br />CONSULTANT <br />ARCHITECT SEAL CONSULTANT SEAL <br />KAISER FOUNDATION <br />HOSPITALS NATIONAL <br />FACILITIES SERVICES 1800 <br />HARRISON STREET OAKLAND, <br />CALIFORNIA 94612 <br />ISSUE / REVISION LOG <br />NO. ISSUED DATE <br />0 <br />5' <br /> <br />5 <br />0 <br />' <br />GR <br />A <br />P <br />H <br />I <br />C <br /> <br />S <br />C <br />A <br />L <br />E <br />S <br />: <br /> <br />1 <br />/ <br />1 <br />6 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />0 <br />25 <br />' <br />1/ <br />8 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />5' <br />0 <br />12 <br />' <br />1/ <br />4 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />1' <br />0 <br />6' <br />1/ <br />2 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />1' <br />0 <br />2' <br />1- <br />1 <br />/ <br />2 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />0 <br />1' <br />3" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />IF <br /> <br />T <br />H <br />I <br />S <br /> <br />S <br />H <br />E <br />E <br />T <br /> <br />I <br />S <br /> <br />N <br />O <br />T <br /> <br />30 <br />" <br />x <br />4 <br />2 <br />" <br />, <br /> <br />I <br />T <br /> <br />I <br />S <br /> <br />A <br /> <br />R <br />E <br />D <br />U <br />C <br />E <br />D <br /> <br />PR <br />I <br />N <br />T <br /> <br />- <br /> <br />S <br />C <br />A <br />L <br />E <br /> <br />AC <br />C <br />O <br />R <br />D <br />I <br />N <br />G <br />L <br />Y <br />AGENCY APPLICATION NUMBER <br />AGENCY APPROVAL STAMP <br />THIS DOCUMENT IS THE PROPERTY OF THE OWNER AND IS <br />NOT TO BE USED WITHOUT OWNER'S WRITTEN PERMISSION. <br />HZ PROJ. NO. <br />222 S. HARBOR BOULEVARD, SUITE 800 I ANAHEIM, CA 92805 <br />PH: 714.490.5555 I FAX: 714.490.5560 <br />IMEG PROJ. NO.: 22008618.00 <br />PROJECT #22008618.00 <br />SOCC 2022 R HBM 1st Fl KPOJ <br />REMODEL <br />E0-05 <br />ELECTRICAL SPECIFICATION <br />CA394-1 <br />CAP0227721R314412.35 <br />HARBOR/MacARTHUR MEDICAL OFF <br />3401 S. HARBOR BLVD. <br />SANTA ANA, CALIFORNIA 92704 <br />CITY SUBMITTAL 11/03/2025 <br />101125520, 20187249, 40140902