SECTION 28 1000 ACCESS CONTROL AND ALARM MONITORING SYSTEM <br />PART 1 - GENERAL <br />1. SECTION INCLUDES <br />A. MATERIALS, EQUIPMENT, FABRICATION, INSTALLATION AND TESTS IN <br />CONFORMITY WITH APPLICABLE CODES AND AUTHORITIES HAVING <br />JURISDICTION FOR THE FOLLOWING: <br />1. A COMPLETE ACCESS CONTROL AND ALARM MONITORING SYSTEM <br />AS DESCRIBED IN THE SPECIFICATIONS AND AS SHOWN IN DETAIL <br />ON THE DRAWINGS. <br />2. COMPLETE SYSTEM IS DEFINED AS ALL LABOR AND MATERIALS <br />REQUIRED TO COMPLETE THE WORK DESCRIBED HEREIN AND ON <br />THE DRAWINGS INCLUDING BUT NOT LIMITED TO: CONDUIT, <br />RACEWAYS, CABLES, CABLING, CONNECTORS, RISERS, NETWORK <br />INTERFACES, BACK BOXES, CARD READERS, CARDS, REQUEST TO <br />EXIT SENSORS, MOTION DETECTORS, ALARM CONTACTS, <br />CONTROLLERS, SPECIFIC ALARM PANELS, ACCESS CONTROL <br />PANELS, POWER SUPPLIES, TRANSFORMERS, UPS’S, PRINTERS, <br />INTERCOMS, INTERCOM HEAD-END EQUIPMENT AND <br />PROGRAMMING, TELEPHONES, PROGRAMMING, LABOR, HARD <br />DRIVES, SOFTWARE UPGRADES, LICENSE UPGRADES, SOFTWARE <br />SUPPORT LICENSES AND ACCESS CONTROL HEAD END <br />SOFTWARE. ALSO PROVIDE AND INSTALL REQUIRED <br />COMMUNICATION EQUIPMENT AND GEAR, PHONE LINE <br />MONITORING, POWER FILTERING, ENCLOSURES, TAMPER <br />SWITCHES, LATCHES AND LOCKS, MOUNTS, HOUSINGS, STANDS, <br />INTERFACES TO NEW AND EXISTING ELECTRIFIED DOOR <br />HARDWARE, INTERFACES TO AUTOMATIC DOOR OPERATORS AND <br />INTERFACES TO EQUIPMENT FURNISHED BY OTHERS. <br />3. PRODUCTS, EQUIPMENT, MATERIALS, SYSTEMS, ASSEMBLIES, <br />SOFTWARE AND ACCESSORIES AS SPECIFIED HEREIN DEFINE THE <br />MINIMUM STANDARDS. SPECIFICATIONS AND DRAWINGS DO NOT <br />SHOW OR LIST EVERY ITEM, ACCESSORY, FASTENER, BRACKET, <br />SUB-ASSEMBLY AND APPURTENANCE TO BE PROVIDED. WHEN AN <br />ITEM NOT SHOWN OR LISTED IS CLEARLY NECESSARY FOR <br />PROPER INSTALLATION, OPERATION AND FUNCTIONING OF THE <br />EQUIPMENT AND SYSTEMS THE SECURITY CONTRACTOR SHALL <br />PROVIDE, INSTALL, TEST AND CERTIFY THE ITEM AT NO INCREASE <br />IN CONTRACT PRICE. <br />4. THE LENEL ACCESS CONTROL SERVER WILL COMMUNICATE TO <br />THE ACCESS CONTROL FIELD PANELS VIA A NETWORK <br />CONNECTION OVER THE OWNER’S LAN/WAN. SECURITY <br />CONTRACTOR SHALL COORDINATE IP ADDRESSES, LAN DROPS, <br />NETWORK CONNECTIVITY AND BANDWIDTH ALLOCATION AND <br />USAGE WITH THE OWNER’S IT DEPARTMENT. <br />5. PROVIDE ALL SOFTWARE, HARDWARE, AND PROGRAMMING FOR <br />INSTALLATION, CONNECTION AND OPERATION OF THE NEW <br />SECURITY SYSTEM EQUIPMENT. <br />6. SECURITY CONTRACTOR IS RESPONSIBLE FOR FULLY <br />IMPLEMENTING THE FUNCTIONS DESCRIBED IN THE <br />SPECIFICATIONS AND SHOWN ON THE DRAWINGS. <br />7. COORDINATE ALL TELEPHONE AND DATA NETWORK <br />CONNECTIONS, PROGRAMMING, AND REQUIREMENTS WITH <br />OWNER’S IT DEPARTMENT. <br />8.FURNISH AND INSTALL ANY INTERFACE RELAYS, MATERIALS, AND <br />CABLING REQUIRED FOR CONNECTION TO THE FIRE ALARM CONTROL <br />PANEL (FACP). <br />1. RELATED SECTIONS <br />A. CONDUIT, WIRE AND CABLE INSTALLATIONS PERFORMED UNDER THIS <br />DIVISION SHALL COMPLY WITH ALL APPLICABLE SECTIONS OF THE LOCAL <br />BUILDING CODES, CALIFORNIA ELECTRICAL CODE AND DIVISION 26 <br />REQUIREMENTS. <br />B.COORDINATE DOOR HARDWARE WITH THE DIVISION 8 HARDWARE <br />CONTRACTOR. <br />C.COORDINATE ALL ELECTRICAL POWER AND CONDUIT REQUIREMENTS WITH <br />THE DIVISION 26 ELECTRICAL CONTRACTOR AND THE OWNER. ALL SECURITY <br />SYSTEMS SHALL BE ON AN EMERGENCY POWER BRANCH CIRCUIT. <br />1. REFERENCES <br />A. PUBLISHED SPECIFICATIONS, STANDARDS, TESTS AND CODES AND <br />RECOMMENDED STANDARDS OF TRADE, INDUSTRY OR GOVERNMENTAL <br />ORGANIZATIONS APPLY TO WORK IN THIS SECTION INCLUDING: <br />1. ADA – TITLE 3 OF THE AMERICANS WITH DISABILITIES ACT <br />2. ASCII – AMERICAN STANDARD CODE FOR INFORMATION <br />INTERCHANGE <br />3. ASTM – AMERICAN SOCIETY FOR TESTING AND MATERIALS <br />4. CCR – TITLES 19 AND 24 OF THE CALIFORNIA CODE OF <br />REGULATIONS <br />5. EIA – ELECTRONIC INDUSTRY ASSOCIATION <br />6. NEMA – NATIONAL ELECTRICAL MANUFACTURERS' ASSOCIATION <br />7. NFPA – 2002 NATIONAL FIRE PROTECTION ASSOCIATION <br />STANDARDS <br />8. CEC – 2005 NATIONAL ELECTRICAL CODE WITH 2007 CA <br />AMENDMENTS <br />9. CBC – 2006 INTERNATIONAL BUILDING CODE WITH 2007 CA <br />AMENDMENTS <br />10. CFC – 2006 INTERNATIONAL FIRE CODE WITH 2007 CA <br />AMENDMENTS <br />11. CMC – 2006 INTERNATIONAL MECHANICAL CODE WITH 2007 CA <br />AMENDMENTS <br />12. UL – UNDERWRITERS LABORATORIES, INC. <br />B.ELECTRONIC DEVICES RADIATING "RF" ENERGY SHALL COMPLY WITH <br />FEDERAL COMMUNICATION COMMISSION REGULATIONS, PARTICULARLY PART <br />FIFTEEN, AND SHALL MEET MINIMUM CLASS "B" REQUIREMENTS. PROVIDE FCC <br />CERTIFICATE NUMBERS INDICATING THAT THE FCC HAS APPROVED THE PRODUCTS. <br />1. QUALITY ASSURANCE <br />A. SECURITY CONTRACTOR SHALL BE CAPABLE OF PERFORMING SERVICE OR <br />MAINTENANCE WORK ON THE SPECIFIED SYSTEMS. SECURITY <br />CONTRACTOR’S LEAD TECHNICIAN SHALL BE FACTORY-CERTIFIED BY THE <br />SECURITY SYSTEM MANUFACTURER. <br />B.SECURITY CONTRACTOR TO PROVIDE AS PART OF THEIR QUOTE <br />DOCUMENTATION OF NATIONAL SOURCING AGREEMENTS (NSA) DISCOUNTS FOR <br />LENEL EQUIPMENT. DOCUMENTATION SHALL INCLUDE LENEL MSRP PRICE, KAISER <br />NSA DISCOUNT PERCENTAGE AND REVISED PRICE. <br />C.SECURITY CONTRACTOR MUST BE A LENEL AUTHORIZED DEALER. THE <br />SECURITY CONTRACTOR SHALL POSSESS ALL REQUIRED CONTRACTOR'S LICENSES. <br />1. SUBMITTALS <br />A. SUBMIT THE FOLLOWING TO THE ARCHITECT FOR APPROVAL PRIOR TO <br />COMMENCEMENT OF WORK: <br />1. MANUFACTURER'S NAME, BRAND NAME, EXACT PART NUMBER, <br />OPTIONS, ACCESSORIES AND CATALOG REFERENCES FOR ALL <br />EQUIPMENT SUPPLIED. INDICATE UL LISTINGS FOR ALL SYSTEM <br />COMPONENTS. <br />2. COMPLETE WIRING DIAGRAMS FOR ALL COMPONENTS, INCLUDING <br />CABLE TYPES AND QUANTITIES, ROUTINGS, FLOOR PLANS <br />INDICATING DEVICE LOCATIONS, CONDUIT SIZES, POINT- TO-POINT <br />TERMINATION AND RISER DIAGRAMS. <br />B.SUBMITTALS MUST BE COMPLETE. ALL SECURITY SYSTEM SUBMITTALS <br />SHALL BE IN A SIMILAR FORMAT FOR EASE OF REVIEW. THE ARCHITECT AND <br />SECURITY CONSULTANT RESERVE THE RIGHT TO REJECT ANY SUBMITTALS <br />DETERMINED TO BE INCOMPLETE. REJECTION OF SUBMITTALS FOR FAILURE TO <br />MEET THESE REQUIREMENTS SHALL NOT BE CONSIDERED GROUNDS FOR CLAIMS <br />OF DELAY. <br />PART 2 - PRODUCTS <br />2.1 ACCESS CONTROL AND ALARM MONITORING SYSTEM PRODUCTS <br />A. CARD READER DOORS <br />1. SECURITY CONTRACTOR TO PROVIDE AND INSTALL 12 INCH BY 12 <br />INCH SECURITY JUNCTION BOX IN THE ACCESSIBLE CEILING <br />SPACE ABOVE OR NEAR EACH CARD READER DOOR. INSTALL THE <br />JUNCTION BOX SO THAT IT IS ACCESSIBLE FROM THE SECURED <br />SIDE OF THE DOOR AND NOT BLOCKED BY EXIT LIGHTING, AIR <br />GRILLS, VENTS, SPRINKLERS OR SMOKE DETECTORS. <br />a. SECURITY CONTRACTOR TO INSTALL THE LNL-1300 OR <br />LNL-1320 READER INTERFACE MODULE IN THE SECURITY <br />JUNCTION BOX ASSOCIATED WITH EACH CARD READER <br />DOOR. <br />b. LABEL ALL WIRES AND CABLES WITH MACHINE- <br />GENERATED LABELS AS CLOSE AS POSSIBLE TO THEIR <br />TERMINATION POINT. ALL LABELS SHALL BE CLEARLY <br />VISIBLE WITHOUT THE NEED TO MOVE OTHER CABLES OR <br />REMOVE ANY CABLE MANAGEMENT DEVICES SUCH AS <br />TIE WRAPS. <br />c. INSTALL SUFFICIENT TERMINAL BLOCKS IN THE SECURITY <br />JUNCTION BOX TO MAKE UP ALL WIRE-TO-WIRE <br />CONNECTIONS. NO WIRE-NUT CONNECTIONS ARE <br />PERMITTED. <br />d. ALL WIRING WITHIN THE SECURITY JUNCTION BOX SHALL <br />BE DRESSED NEATLY AND PROFESSIONALLY. <br />e. PROVIDE SUFFICIENT SPARE CABLE LENGTH FOR EACH <br />CABLE TO FORM A SERVICE LOOP TO ENABLE IT TO <br />REACH ANY POINT WITHIN THE SECURITY JUNCTION BOX <br />WITHOUT THE NEED FOR SPLICING ADDITIONAL WIRE OR <br />PULLING ADDITIONAL CABLE IN FROM OUTSIDE THE <br />SECURITY JUNCTION BOX. <br />f. ALL SECURITY JUNCTION BOXES SHALL BE CLEARLY <br />MARKED ON THE OUTSIDE COVER SO THAT THEY CAN BE <br />IDENTIFIED FROM THE FLOOR BELOW WITHOUT THE USE <br />OF A LADDER WHEN THE ACCESSIBLE CEILING SPACE IS <br />OPEN. MARKINGS SHALL REFLECT THE DOOR NUMBER AS <br />WELL AS THE ACCESS CONTROL PANEL NUMBER AND <br />PORT ASSOCIATED WITH THAT CARD READER DOOR. <br />G.ALL INITIATING CIRCUITS SHALL BE WIRED NORMALLY <br />CLOSED WITH A 5-STATE SUPERVISION 1K/2K RESISTOR <br />INSTALLED AT THE END-OF-LINE DEVICE. <br />B.CARD READER DOOR DEVICES <br />1. SECURITY CONTRACTOR TO PROVIDE AND INSTALL HID CORPORATION <br />THINLINE II CLASSIC STYLE CARD READERS. NO SUBSTITUTIONS WILL <br />BE ACCEPTED. <br />a. THE CARD READER SHALL COMMUNICATE IN A WIEGAND <br />PROTOCOL INTERFACE AND BE COMPATIBLE WITH ALL <br />STANDARD ACCESS CONTROL SYSTEMS. <br />b. CARD READERS INSTALLED AT INTERIOR LOCATIONS SHALL <br />BE WHITE IN COLOR. <br />2. SECURITY CONTRACTOR TO PROVIDE AND INSTALL DETECTION <br />SYSTEMS DS160 REQUEST-TO- EXIT MOTION DETECTOR AND TP160 <br />MOUNTING PLATE AT ALL CARD READER DOOR LOCATIONS. NO <br />SUBSTITUTIONS WILL BE ACCEPTED. <br />a. REQUEST-TO-EXIT MOTION DETECTORS SHALL BE WIRED <br />NORMALLY CLOSED WITH A 5-STATE SUPERVISION 1K/2K <br />RESISTOR INSTALLED AT THE END-OF-LINE DEVICE. <br />3. SECURITY CONTRACTOR TO PROVIDE AND INSTALL GE SENTROL <br />1076(D) CONCEALED ALARM CONTACT IN DOOR FRAMES AND <br />CONCEALED MAGNETS IN DOOR LEAFS AT ALL CARD READER DOOR <br />LOCATIONS. <br />a. CONTACT SHALL CONSIST OF 2 SPDT CONTACTS IN ONE <br />SWITCH. <br />b. CONTACT SHALL HAVE AN ALARM GAP DISTANCE OF NO <br />MORE THAN 1/2 INCH. <br />c. DOOR CONTACTS SHALL BE WIRED NORMALLY CLOSED WITH <br />A 5-STATE SUPERVISION 1K/2K RESISTOR INSTALLED AT THE <br />END-OF-LINE DEVICE. <br />d. CONTACT COLOR SHALL BE PROVIDED TO BEST MATCH <br />DOOR FRAME FINISH. <br />e. CONTACT SHALL NOT BE LARGER THAN 3/4 INCH. <br />f. PAIRS OF DOORS SHALL HAVE ALARM CONTACTS ON EACH <br />DOOR LEAF AND THE ALARM CONTACTS WILL BE WIRED IN A <br />SERIES CIRCUIT. <br />4. SECURITY CONTRACTOR TO PROVIDE SWITCHED LOCK POWER TO <br />ELECTRIFIED LOCKS AND STRIKES. <br />a. LOCKS SHALL UNLOCK WHEN 24 VDC POWER IS APPLIED FOR <br />A “FAIL SECURE” OPERATION. <br />b. THE LNL-1300 OR LNL-1320 READER INTERFACE MODULE <br />SHALL BE USED TO SWITCH THE LOCK POWER TO THE <br />LOCKS. <br />5. THE SECURITY CONTRACTOR SHALL PROVIDE AND INSTALL A LABEL <br />AT EACH READER LOCATION. LABELS SHALL BE MACHINE GENERATED <br />AND BE ON THE BOTTOM OF THE READER INDICATING THE READER <br />NUMBER IN THE SYSTEM. <br />C.POWER SUPPLIES <br />1. SECURITY CONTRACTOR TO PROVIDE AND INSTALL ALTRONIX <br />AL1012ULX16CB AND AL1024ULX16CB POWER SUPPLIES WITH POWER <br />DISTRIBUTION MODULES TO POWER ALL ACCESS CONTROL PANELS, <br />INTRUSION ALARM PANELS, ELECTRICALLY CONTROLLED DOOR LOCKS <br />AND DOOR STRIKES, REQUEST TO EXITS AND PERIPHERAL DEVICES AT <br />LOCATIONS AS SHOWN ON THE DRAWINGS. NO SUBSTITUTIONS WILL <br />BE ACCEPTED. <br />a. POWER SUPPLY/CHARGER UNITS SHALL BE CLASS 2 RATED. <br />b. INSTALL EACH INDIVIDUAL LOCK, REQUEST TO EXIT AND <br />PERIPHERAL DEVICE ON A SEPARATE OUTPUT OF THE <br />POWER DISTRIBUTION MODULE. <br />c. PROVIDE SUFFICIENT QUANTITY OF POWER SUPPLIES WITH <br />FACTORY-INSTALLED POWER DISTRIBUTION MODULES TO <br />PERMIT SIMULTANEOUS CONTINUOUS-DUTY ACTIVATION OF <br />ALL DOOR LOCKS WITH AN ADDITIONAL MINIMUM 20 PERCENT <br />CAPACITY ON EACH SUPPLY. <br />d. CALCULATE VOLTAGE DROP TO LOCKS AND SIZE LOCK <br />CONTROL WIRING TO PROVIDE PROPER LOCK OPERATION. <br />e. PROVIDE BATTERY BACK-UP SUFFICIENT FOR FOUR HOURS <br />STANDBY PLUS TWENTY-FIVE ACTIVATIONS FOR ALL DC <br />LOCKS. BATTERIES SHALL BE 12V 7AHR. <br />f. MONITOR THE AC FAIL RELAY FOR POWER FAILURE AND THE <br />LOW BATTERY RELAY FOR LOW BATTERY. THESE ALARMS <br />SHALL HAVE INDIVIDUAL MONITOR POINTS ON THE ACCESS <br />CONTROL SYSTEM. <br />g. FURNISH AND INSTALL NOISE SUPPRESSION DIODES ON ALL <br />LOCKS AS CLOSE AS POSSIBLE TO THE LOCK AND AT THE <br />CONTROL RELAY COIL. <br />h. FURNISH AND INSTALL TAMPER SWITCHES ON EACH POWER <br />SUPPLY ENCLOSURE. TAMPER SWITCHES SHALL BE WIRED <br />TO MONITOR POINTS ON THE ACCESS CONTROL PANEL AND <br />SHALL BE CONFIGURED FOR TWENTY-FOUR HOUR ALARM <br />SUPERVISION. <br />i. PROVIDE AND INSTALL CABINET LOCKS ON EACH POWER <br />SUPPLY ENCLOSURE. SECURITY CONTRACTOR TO PROVIDE <br />LOCKS KEYED ALIKE FOR ALL POWER SUPPLY ENCLOSURES. <br />j. CONTRACTOR TO PROVIDE A MACHINE GENERATED LABEL <br />ON THE EXTERIOR OF ALL POWER SUPPLIES AND <br />TRANSFORMERS IDENTIFYING THE EQUIPMENT SERVED. <br />D.ELECTRIFIED LOCKS AND HARDWARE <br />1. ELECTRIFIED LOCKS, STRIKES, DOOR HARDWARE, “PANIC BAR” EXIT <br />DEVICES AND LOCAL ELECTRIFIED DOOR HARDWARE POWER <br />SUPPLIES TO BE USED IN CONJUNCTION WITH CARD READER ACCESS <br />DOORS SHALL BE FURNISHED AND INSTALLED BY THE DIVISION 8 <br />HARDWARE CONTRACTOR. THE SECURITY CONTRACTOR IS <br />RESPONSIBLE FOR ALL LOW VOLTAGE WIRING AND TERMINATIONS TO <br />ELECTRIFIED LOCKS, ELECTRIFIED DOOR HARDWARE AND ELECTRIC <br />TRANSFER HINGE HARDWARE. <br />a. SEQUENCING, SCHEDULING AND COORDINATING WITH THE <br />DIVISION 8 HARDWARE CONTRACTOR AND THE OWNER IS <br />THE RESPONSIBILITY OF THE SECURITY CONTRACTOR. <br />b. PROGRAMMING, INTERFACING AND TESTING OF SYSTEMS <br />INTEGRATION OF CONTROLLED HARDWARE IS THE <br />RESPONSIBILITY OF THE SECURITY CONTRACTOR. <br />c. PULLING, INSTALLING, DRESSING, TERMINATING AND <br />CONNECTING WIRING TO THE ELECTRIFIED LOCKS AND <br />HARDWARE IS THE RESPONSIBILITY OF THE SECURITY <br />CONTRACTOR. <br />D.SECURITY CONTRACTOR SHALL COORDINATE WITH DIVISION <br />16 ELECTRICAL CONTRACTOR FOR 120VAC POWER AND INTERFACE OF <br />CONTROLLED HARDWARE WITH THE FIRE ALARM CONTROL PANEL <br />(FACP). <br />E.ALL ELECTRIFIED LOCKS AND HARDWARE USED IN <br />CONJUNCTION WITH CARD READER ACCESS DOORS SHALL BE “FAIL <br />SECURE” UNLESS OTHERWISE NOTED OR REQUIRED BY LAW TO BE <br />“FAIL SAFE”. <br />E.ALARM CONTACTS <br />1. SECURITY CONTRACTOR TO PROVIDE AND INSTALL GE SENTROL <br />1076C(D) CONCEALED ALARM CONTACT IN DOOR FRAMES AND <br />CONCEALED MAGNETS IN DOOR LEAFS AT LOCATIONS SHOWN ON THE <br />DRAWINGS INCLUDING ALL DOORS WITH CARD READERS OR EXIT <br />ALARMS. <br />a. CONTACT SHALL CONSIST OF 2 SPDT CONTACTS IN ONE <br />SWITCH. <br />b. CONTACT SHALL HAVE AN ALARM GAP DISTANCE OF NO <br />MORE THAN 1/2 INCH. <br />c. DOOR CONTACTS SHALL BE WIRED NORMALLY CLOSED WITH <br />A 5-STATE SUPERVISION 1K/2K RESISTOR INSTALLED AT THE <br />END-OF-LINE DEVICE. <br />d. CONTACT COLOR SHALL BE PROVIDED TO BEST MATCH <br />DOOR FRAME FINISH. <br />e. CONTACT SHALL NOT BE LARGER THAN 3/4 INCH. <br />f. PAIRS OF DOORS SHALL HAVE ALARM CONTACTS ON EACH <br />DOOR LEAF AND THE ALARM CONTACTS WILL BE WIRED IN A <br />SERIES CIRCUIT. <br />2. SECURITY CONTRACTOR TO PROVIDE AND INSTALL GE SENTROL 2505A <br />SURFACE-MOUNTED ALARM CONTACT WITH 1092-A ROLL-UP DOOR <br />MOUNTING BRACKET FOR ROLL-UP DOORS AT LOCATIONS SHOWN ON <br />THE DRAWINGS. <br />a. THE CONTACT SHALL HAVE AN ALARM GAP DISTANCE OF NO <br />MORE THAN 2 INCHES. <br />b. DOOR CONTACTS SHALL BE WIRED NORMALLY CLOSED WITH <br />A 5-STATE SUPERVISION 1K/2K RESISTOR INSTALLED AT THE <br />END-OF-LINE DEVICE. <br />c. CONTACT AND MAGNETS SHALL BE IN BRUSHED ANODIZED <br />ALUMINUM TUBE HOUSING AND BE SEALED WITH <br />POLYURETHANE POTTING COMPOUND. <br />d. CONTACT SHALL HAVE 3 FEET OF PERMANENTLY ATTACHED <br />FLEX STAINLESS STEEL CONDUIT. <br />2.2 WIRE AND CABLE <br />A. WIRE AND CABLE SPECIFICATIONS <br />1. SECURITY CONTRACTOR SHALL FOLLOW THE MANUFACTURERS' <br />RECOMMENDATION FOR CABLING OR THE MINIMUM REQUIREMENTS <br />OF THE SPECIFICATIONS AND DRAWINGS, WHICHEVER PROVIDES <br />FOR THE MOST STRINGENT REQUIREMENTS. <br />2. WIRE AND CABLE SIZES, NUMBER OF CONDUCTORS, SHIELDING, OR <br />OTHER DATA LISTED IN THIS SPECIFICATION OR SHOWN ON <br />DRAWINGS ARE A GUIDE TO THE CORRECT PRODUCT REQUIRED TO <br />ACHIEVE A WORKING SYSTEM AND REPRESENT THE MINIMUM <br />ACCEPTABLE EQUIPMENT. <br />3. CABLES ARE TO BE SHIELDED AS NECESSARY TO PRECLUDE ANY <br />OUTSIDE NOISE OR INTERFERENCE FROM ENTERING THE CABLE AND <br />DEGRADING SYSTEM PERFORMANCE. ALL CABLES SHALL BE U.L. <br />LISTED, AND APPROPRIATE FOR THE APPLICATION. <br />4. USE PROPER GROUNDING PRACTICES TO ELIMINATE SHORTS, <br />GROUND FAULTS, GROUND LOOPS, RF INTERFERENCE, VOLTAGE <br />FLUCTUATIONS, FOREIGN VOLTAGES AND OPEN CIRCUITS. <br />5. COORDINATE WITH THE OWNER’S IT DEPARTMENT FOR TELEPHONE <br />LINE REQUIREMENTS AND LOCATION FOR OFF-SITE MONITORING. <br />PROVIDE RJ31X PHONE JACKS FOR TELEPHONE SYSTEM <br />CONNECTIONS. <br />6. CABLES RUN UNDERGROUND, UNDER SLAB, OR IN SLAB SHALL BE <br />INSTALLED IN CONDUIT AND RATED FOR DIRECT-BURIAL <br />APPLICATION. CABLES ABOVE HARD CEILING OR INACCESSIBLE <br />AREAS SHALL BE INSTALLED IN CONDUIT. STUB UP CONDUITS FROM <br />WITHIN WALLS INTO ACCESSIBLE SPACES. <br />7. ALL CABLES RUN IN ENVIRONMENTAL AIR HANDLING SPACES SHALL <br />BE PLENUM RATED. PROVIDE PROPER J-HOOKS FOR CABLES NOT <br />RUN IN CONDUIT. CABLES NOT REQUIRED TO BE IN CONDUIT SHALL <br />BE RUN ALONG BUT NOT IN TEL/DATA CABLE TRAYS. <br />8. ALL CABLE SHALL BE RUN IN UNBROKEN LENGTHS OF 1000 FEET OR <br />LESS. NO COAXIAL OR POWER CABLES LESS THAN 1000 FEET SHALL <br />BE SPLICED. WHEN CABLE CANNOT BE RUN IN UNBROKEN LENGTHS <br />DUE TO CABLE SPOOL LIMITATIONS, SPLICES SHALL BE MADE IN <br />JUNCTION BOXES WITH TERMINAL BLOCKS OR TERMINAL STRIPS AND <br />FORK SPADE LUGS. ALL SPLICES AND JUNCTION BOXES SHALL BE <br />CLEARLY MARKED ON THE “AS-BUILT” RECORD DRAWINGS. <br />9. ALL WIRE TO WIRE SPLICES NOT UTILIZING TERMINAL BLOCKS OR <br />TERMINAL STRIPS SHALL BE DONE WITH ELECTRICAL TAPE. WIRES <br />SHALL BE INDIVIDUALLY TAPED, THEN NEATLY TAPED TOGETHER TO <br />FORM THE NARROWEST SPLICE POSSIBLE FOR EASE OF <br />INSTALLATION AND REMOVAL, AS WELL AS OVERALL PROTECTION OF <br />THE SPLICE. THE USE OF ALL CRIMP TYPE AND SCREW TYPE <br />CONNECTORS I.E. BEANS, TOP HATS, BUTT CONNECTORS, SNAP <br />CAPS, WIRE NUTS, AND THE “TWIST AND TAPE” METHOD ARE <br />PROHIBITED. <br />10. ALL END-OF-LINE SUPERVISION RESISTORS SHALL BE INSTALLED AT <br />THE INDIVIDUAL PROTECTION DEVICES, AND NOT IN THE CONTROL <br />PANELS. <br />11. ALL 24VAC POWER CABLING SHALL BE OF STRANDED <br />CONSTRUCTION. FOR CONNECTIONS REQUIRING PRESSURE CAPTIVE <br />CONNECTION, WIRE SHALL BE SOLDER TINNED PRIOR TO INSERTION <br />INTO PRESSURE CONNECTORS. <br />12. WIRING SHALL BE GROUPED AND HARNESSED TO FACILITATE <br />ACCESS TO ALL EQUIPMENT, AS WELL AS MAINTENANCE AND <br />REPLACEMENT OF EQUIPMENT. <br />13. ALL CABLE SHALL BE LABELED AT ORIGIN AND TERMINATION, <br />REFERENCING TO A MASTER LEGEND SCHEDULE AS SHOWN ON “AS- <br />BUILT” RECORD DRAWINGS. LABELING AND ANY SPLICE LOCATIONS <br />SHALL BE NOTED ON “AS-BUILT” RECORD DRAWINGS. ALL LABELS <br />SHALL BE DONE USING MACHINE GENERATED CABLE TAGS IN THE <br />“FLAGGED” POSITION. HAND WRITTEN LABELS ARE NOT ACCEPTABLE <br />14. CABLING SHALL BE SIZED AND INSTALLED ACCORDING TO <br />CALIFORNIA ELECTRIC CODE REQUIREMENTS. <br /> 15. ANY CABLING OR RACEWAY EXPOSED TO WEATHER SHALL BE <br />RATED F OR THAT USE. <br />16.STUB UP CONDUITS FROM OUTLETS INTO ACCESSIBLE SPACES. <br />CABLES SHALL BE RUN WITH BUT NOT IN THE TEL/DATA CABLE TRAY. MIXING <br />OF SECURITY LOW VOLTAGE CABLES WITH TEL/DATA CABLES WILL NOT BE <br />PERMITTED. UTILIZE APPROVED CLIPS OR MOUNTING TO SECURELY MOUNT <br />SECURITY CABLE TO THE RACK FRAMEWORK OR HANGERS. <br />17.CABLE NOT RUN WITH THE CABLE TRAY SHALL BE RUN ALONG THE <br />WALL USING J-HOOK HANGERS. HANGERS SHALL BE SUFFICIENT TO <br />PROPERLY SUPPORT CABLE. <br />18.CABLING SHALL BE WEST PENN, BELDEN, WINDY CITY WIRE OR <br />APPROVED EQUAL. <br />19.ALL FINAL LABELING SHALL BE WITH MACHINE-GENERATED PRINTED <br />LABELS, SPECIFICALLY MADE FOR CABLE LABELING. NO HANDWRITTEN LABELS <br />WILL BE ACCEPTED. ALL WIRING INCLUDING POWER CORDS AND FEEDS, <br />NETWORK CONNECTIONS, AND SYSTEM CABLING SHALL BE FITTED WITH A <br />MACHINE GENERATED LABEL IDENTIFYING THE DEVICE OR POINT SERVED. <br />THE ID MARKER FOR EACH LABEL SHALL HAVE THE DEVICE NUMBER AND <br />NAME. <br />20.EACH ENCLOSURE SHALL HAVE A SECURITY AS-BUILT DRAWING WITH <br />POINT LIST AND NAMING / NUMBERING TO MATCH THE MACHINE GENERATED <br />LABELING ON CABLES TERMINATED TO THE PANELS AND POWER SUPPLIES. <br />PART 3 - EXECUTION <br />3.1 REQUIREMENTS <br />A. SYSTEMS SHALL BE COMPLETE AND OPERATIONAL IN ALL RESPECTS. <br />B.SECURITY CONTRACTOR SHALL FURNISH AND INSTALL ALL EQUIPMENT FOR <br />ALL BUILDING SECURITY SYSTEMS. <br />C.WIRING AND CONDUIT SHOWN ON DRAWINGS REPRESENTS A MINIMUM <br />REQUIREMENT. SECURITY CONTRACTOR SHALL FURNISH AND INSTALL ALL WIRING <br />RECOMMENDED BY SUBMITTED SYSTEM MANUFACTURERS FOR OPTIMUM SYSTEM <br />PERFORMANCE AT NO INCREASE IN CONTRACT PRICE. <br />D.ALL WALL, FLOOR, AND CEILING PENETRATIONS, REGARDLESS OF THE FIRE <br />RATING OF THE PARTITION, MUST BE PROPERLY SLEEVED WITH CONDUIT AND <br />PROPERLY SEALED USING APPROVED FIRE STOPPING MATERIALS AND SEALANTS. <br />E.CONNECT POWER TO SECURITY SYSTEMS AS REQUIRED AND COORDINATE <br />WITH THE DIVISION 16 ELECTRICAL CONTRACTOR. <br />F.ALL SECURITY EQUIPMENT, JUNCTION BOXES, AND TERMINAL CANS INSTALLED <br />IN PUBLIC ACCESSIBLE AREAS SHALL BE INSTALLED UTILIZING TAMPER PROOF <br />MOUNTING HARDWARE. PROVIDE A MINIMUM OF TWO DRIVER BITS OR HAND TOOLS TO <br />THE OWNER’S REPRESENTATIVE FOR EACH TYPE AND SIZE OF SECURITY FASTENER <br />PROVIDED. <br />G.PROVIDE SEISMIC RESTRAINT FOR ALL EQUIPMENT, INCLUDING EQUIPMENT <br />RACKS AND CONSOLES. <br />H.SECURITY CONTRACTOR SHALL PROVIDE THE OWNER WITH A MINIMUM OF <br />FOUR COMPLETE SETS OF KEYS FOR ALL EQUIPMENT INSTALLED IN THIS PROJECT <br />PRIOR TO THE CLOSE OF THE PROJECT. ALL KEYS RELATING TO THE SECURITY <br />SYSTEMS SHALL BE KEPT SEPARATE FROM THE BUILDING SYSTEMS AND DELIVERED TO <br />THE OWNER’S REPRESENTATIVE. <br />3.2 RECORD DRAWINGS <br />A. MAINTAIN A COMPLETE SET OF “AS-BUILT” RECORD DRAWINGS UPDATED WITH <br />MARK-UPS INSERTED AS THE WORK IS PERFORMED. AS WORK IS INSTALLED <br />CAREFULLY MARK ON “AS-BUILT” RECORD DRAWINGS IN COLORED PENCIL THE <br />CORRECT LOCATION OF ALL WORK INCLUDING DEPTH OF UNDERGROUND <br />RUNS AND CONCEALED WORK WITH THEIR DIMENSIONS FROM CLEARLY <br />IDENTIFIED POINTS ON PERMANENT BUILDINGS, FIXTURES, WALLS, OR WALKS. <br />WIRING DIAGRAMS, RISERS AND DETAILS SHALL BE INCLUDED. <br />B.UPON COMPLETION OF THE PROJECT TRANSFER HAND-DRAWN INFORMATION <br />TO CAD DRAWINGS THEN COPY UPDATED CAD DRAWINGS ONTO COMPACT DISC AND <br />SUBMIT TO THE OWNER, ARCHITECT AND SECURITY CONSULTANT. NO HAND-DRAWN <br />“AS-BUILT” RECORD DRAWINGS WILL BE ACCEPTED. <br />C.“AS-BUILT” RECORD DRAWINGS SHALL BE PROVIDED IN FOUR PLOTTED SETS <br />AS WELL AS ONE SET OF CAD DRAWINGS ON COMPACT DISC TO THE OWNER, <br />ARCHITECT AND SECURITY CONSULTANT. ONE ADDITIONAL COMPLETE HALF-SIZE <br />PLOTTED SET SHALL REMAIN ON THE PROJECT SITE IN FOLDERS SECURED INSIDE THE <br />ELECTRONIC RACKS. <br />3.3 TESTS AND REPORTS <br />A. PERFORM SYSTEMS TESTS USING PERSONNEL WHO HAVE ATTENDED A <br />MANUFACTURER'S TRAINING SCHOOL FOR INSTALLATION AND TESTING OF THE <br />SYSTEMS AS DESCRIBED ABOVE. PERFORM TESTING WITH THE TEST <br />INSTRUMENTS AS REQUIRED BY THE MANUFACTURER; TESTING BY MEANS <br />OTHER THAN THE MANUFACTURER'S PROCEDURES WILL NOT BE ACCEPTABLE <br />UNLESS AGREED TO BY THE OWNER, ARCHITECT, SECURITY CONSULTANT AND <br />MANUFACTURER. <br />B.THE SECURITY CONTRACTOR SHALL TEST THE FOLLOWING SYSTEM AND <br />DOCUMENT THESE TESTS FOR THE OWNER, ARCHITECT AND SECURITY CONSULTANT <br />PRIOR TO FINAL COMMISSIONING; <br />1. CARD READERS <br />a. THE CARD READER LED IS RED WHEN THE DOOR IS SECURE. <br />b. THE CARD READER LED IS SOLID GREEN WHEN THE DOOR IS <br />PLACED IN AN UNLOCKED MODE. <br />c. THE CARD READER BEEPS AND THE LED FLASHES GREEN <br />AND WHEN A VALID CARD IS PRESENTED. <br />d. THE CARD READER WILL READ THE ACCESS CARDS AS <br />SPECIFIED FOR THIS PROJECT WHEN PRESENTED TO THE <br />READER AT THE RANGE AS SPECIFIED BY THE <br />MANUFACTURER. <br />e. THE CARD READER PRODUCES AN OFFLINE SIGNAL ON THE <br />SYSTEM WHEN POWER OR COMMUNICATION TO THE <br />READER IS LOST. <br />f. THE CARD READER WILL PRODUCE ALARMS FROM DENIED <br />ACCESS AND EXPIRED CARDS ON THE SYSTEM. <br />2. DOOR ALARM CONTACT <br />a. THE CONTACT IS FREE FROM FAULTS AND TROUBLE <br />CONDITIONS. <br />b. THE CONTACT PRODUCES A DOOR FORCED OPEN ALARM ON <br />THE SYSTEM WHEN THE DOOR IS OPENED WITHOUT A VALID <br />CARD READ OR WITH A KEY. <br />c. THE CONTACT PRODUCES A DOOR HELD OPEN ALARM ON <br />THE SYSTEM 15 SECONDS FOR PERIMETER DOORS AND 30 <br />SECONDS FOR INTERIOR DOORS AFTER THE DOOR IS <br />OPENED. <br />3. REQUEST-TO-EXIT <br />a. THE REQUEST-TO-EXIT IS FREE FROM FAULTS AND TROUBLE <br />CONDITIONS. <br />b. THE REQUEST-TO-EXIT SHUNTS THE DOOR ALARM CONTACT <br />UPON ACTIVATION FROM A USER EXITING THE ROOM. <br />c. THE REQUEST-TO-EXIT BEEPS WHEN A HELD OR FORCED <br />OPEN ALARM IS CREATED ON THE CORRESPONDING DOOR. <br />4. ELECTRIFIED HARDWARE <br />a. THE ELECTRIFIED HARDWARE UNLOCKS WHEN A VALID CARD <br />IS PRESENTED TO THE CORRESPONDING READER. <br />b. THE ELECTRIFIED HARDWARE UNLOCKS WHEN AN UNLOCK <br />COMMAND IS SENT FROM THE SYSTEM. <br />c. THE ELECTRIFIED HARDWARE STAYS UNLOCKED FOR A <br />MAXIMUM OF 10 SECONDS ON PERIMETER DOORS AND 20 <br />SECONDS ON INTERIOR DOORS AFTER A VALID CARD IS <br />PRESENTED. FAILURE TO OPEN THE DOOR WITHIN THE <br />STATED TIME WILL RESULT IN RELOCKING OF THE DOOR. <br />d. THE ELECTRIFIED HARDWARE RE-LOCKS AFTER A VALID <br />CARD IS PRESENTED AND THE DOOR IS OPENED. <br />5. ALARM CONTACTS <br />a. THE ALARM CONTACT IS FREE FROM FAULTS AND TROUBLE <br />CONDITIONS. <br />B.THE ALARM CONTACT GENERATES AND ALARM ON THE <br />SYSTEM WHEN THE ASSOCIATED DOOR IS OPENED WITHIN THE <br />SPECIFIED GAP DISTANCE. <br />C.THE ALARM CONTACT GENERATES A RESET OR CLEAR <br />ALARM ON THE SYSTEM WHEN THE DOOR IS CLOSED AND LATCHED. <br />D.THE ALARM CONTACT DOES NOT PRODUCE ALARMS ON THE <br />SYSTEM WHEN THE DOOR IS SHUT AND MOVED BACK AND FORTH <br />INSIDE THE FRAME. <br />C.UPON COMPLETION OF THE INSTALLATION OF THE SECURITY SYSTEMS <br />SECURITY CONTRACTOR SHALL SUBMIT WRITTEN REPORTS INCLUDING BUT NOT <br />LIMITED TO THE FOLLOWING INFORMATION: <br />1. A COMPLETE LIST OF ALL EQUIPMENT INSTALLED INCLUDING SERIAL <br />NUMBERS OF MAJOR COMPONENTS. <br />2. CERTIFICATION THAT ALL EQUIPMENT IS PROPERLY INSTALLED, <br />PROGRAMMED, FUNCTIONAL, 100 PERCENT OPERATIONAL AND <br />CONFORMS TO SPECIFICATIONS AND DRAWINGS. <br />3. TEST REPORTS OF ALL ZONES, DEVICES, AND EQUIPMENT. <br />4. TEST TECHNICIAN'S NAME, COMPANY AND DATE OF TEST. <br />END OF SECTION <br />SECTION 10 2600 - WALL PROTECTION <br />PART 1 - GENERAL <br />1.1 SUMMARY: <br />A. WORK OF THIS SECTION INCLUDES: <br />1. CORNER GUARDS <br />B. RELATED WORK SPECIFIED ELSEWHERE: GYPSUM BOARD. <br />1.2 REFERENCES: <br />A. ASTM INTERNATIONAL (ASTM) <br />B. INTERNATIONAL BUILDING CODE (IBC) <br />C. NATIONAL FIRE PROTECTION ASSOCIATION (NFPA); LIFE SAFETY CODE. <br />D. UNDERWRITERS LABORATORIES (UL). <br />1.3 ACTION SUBMITTALS: <br />A. PRODUCT DATA: SUBMIT PRODUCT DATA AND DETAILED SPECIFICATIONS FOR EACH <br />SYSTEM COMPONENT AND INSTALLATION ACCESSORY REQUIRED, INCLUDING <br />INSTALLATION METHODS FOR EACH TYPE OF SUBSTRATE. <br />B. SHOP DRAWINGS: SUBMIT SHOP DRAWINGS SHOWING LOCATIONS, EXTENT AND <br />INSTALLATION DETAILS OF WALL PROTECTION. SHOW METHODS OF ATTACHMENT TO <br />ADJOINING CONSTRUCTION. <br />C. SAMPLES: SAMPLES FOR VERIFICATION PURPOSES: SUBMIT 6" LONG SAMPLE OF EACH <br />MODEL SPECIFIED AND AS PROPOSED FOR THIS WORK, FOR VERIFICATION OF GUARD. <br />1.4 INFORMATIONAL SUBMITTALS: <br />A. SUBMIT PRODUCT TEST REPORTS FROM A QUALIFIED INDEPENDENT TESTING <br />LABORATORY SHOWING COMPLIANCE OF EACH COMPONENT WITH REQUIREMENTS <br />INDICATED. <br />1.5 CLOSEOUT SUBMITTALS: <br />A. SUBMIT MAINTENANCE DATA FOR WALL PROTECTION SYSTEM COMPONENTS FOR <br />INCLUSION IN OPERATING AND MAINTENANCE MANUALS SPECIFIED IN DIVISION 01. <br />1.6 QUALITY ASSURANCE: <br />A. INSTALLER QUALIFICATIONS: ENGAGE AN INSTALLER WHO HAS NO LESS THAN 3 YEARS <br />EXPERIENCE IN INSTALLATION OF SYSTEMS SIMILAR IN COMPLEXITY TO THOSE <br />REQUIRED FOR THIS PROJECT. <br />B. MANUFACTURER'S QUALIFICATIONS: NOT LESS THAN 5 YEARS EXPERIENCE IN THE <br />PRODUCTION OF SPECIFIED PRODUCTS AND A RECORD OF SUCCESSFUL IN-SERVICE <br />PREFORMANCE. <br />C. CODE COMPLIANCE: ASSEMBLIES SHALL CONFORM TO APPLICABLE CODES INCLUDING <br />IBC, AND LIFE SAFETY. <br />D. FIRE PERFORMANCE CHARACTERISTICS: PROVIDE WALL PROTECTION SYSTEM <br />COMPONENTS WITH UL LABEL INDICATING THAT THEY ARE IDENTICAL TO THOSE TESTED <br />IN ACCORD WITH ASTM E84-12A FOR CLASS 1 CHARACTERISTICS LISTED BELOW" <br />1. FLAME SPREAD: 25 OR LESS <br />2. SMOKE DEVELOPED: 450 OR LESS. <br />E. IMPACT STRENGTH: PROVIDE ASSEMBLED WALL PROTECTION UNITS THAT HAVE BEEN <br />TESTED IN ACCORD WITH THE APPLICABLE PROVISIONS OF ASTM F476-84(2002) <br />F. CHEMICAL AND STAIN RESISTANCE: PROVIDE WALL PROTECTION SYSTEM COMPONENTS <br />WITH CHEMICAL AND STAIN RESISTANCE IN ACCORDANCE WITH ASTM D1308-02(2007). <br />G. COLOR MATCH: PROVIDE WALL PROTECTION COMPONENTS THAT ARE COLOR MATCHED <br />IN ACCORDANCE WITH THE FOLLOWING: <br />1. DELTA ECMC OF NO GREATER THAN 1.0 USING CIELAB COLOR SPACE. <br />H. SINGLE SOURCE RESPONSIBILITY: PROVIDE ALL COMPONENTS OF THE WALL <br />PROTECTION SYSTEM MANUFACTURED BY THE SAME COMPANY TO ENSURE <br />COMPATIBILITY OF COLOR, TEXTURE AND PHYSICAL PROPERTIES. <br />1.7 DELIVERY, STORAGE AND HANDLING: <br />A. DELIVER MATERIALS TO THE PROJECT SITE IN UNOPENED ORIGINAL FACTORY <br />PACKAGING CLEARLY LABELED TO SHOW MANUFACTURER. <br />B. STORE MATERIALS IN ORIGINAL, UNDAMAGED PACKAGING IN A COOL, DRY PLACE OUT <br />OF DIRECT SUNLIGHT AND EXPOSURE TO THE ELEMENTS. MAINTAIN A MINIMUM ROOM <br />TEMPERATURE OF 40 DEGREES F. AND A MAXIMUM TEMPERATURE OF 100 DEGREES F. <br />C. STORE MATERIAL FLAT. <br />1.8 PROJECT CONDITIONS: <br />A. ACCLIMATE MATERIALS IN AN ENVIRONMENT OF 65 DEGREES TO 75 DEGREES FOR AT <br />LEAST 24 HOURS PRIOR TO BEGINNING INSTALLATION. <br />B. INSTALLATION AREAS SHALL BE ENCLOSED AND WEATHERPROOFED BEFORE <br />INSTALLATION COMMENCES. <br />PART 2 - PRODUCTS <br />2.2 CORNER GUARD: <br />A. SURFACE-MOUNTED, STAINLESS STEEL CORNER GUARDS : <br />MANUFACTURER'S STANDARD TYPE 304. NO. 4 FINISH, SMOOTH, STAINLESS STEEL <br />FINISH, ADHESIVE ATTACHED, WITH 90- DEGREE TURN TO MATCH WALL <br />CONDITION. <br />1. ACCEPTABLE MANUFACTURERS: <br />A. SEE FINISH LIST FOR SPECIFIED PRODUCT <br />2.3 MATERIALS: <br />A. STAINLESS STEEL: CORNER GUARDS SHALL BE MANUFACTURED FROM TYPE 304 <br />(MEETS NSF STANDARD 51), 16 GAUGE. <br />B. ADHESIVE: AS RECOMMENDED BY PROTECTION PRODUCT MANUFACTURER. <br />PART 3 - EXECUTION <br />3.1 EXAMINATION: <br />A. EXAMINE SUBSTRATES AND WALL AREAS, WITH INSTALLER PRESENT, FOR <br />COMPLIANCE WITH REQUIREMENTS FOR INSTALLATION TOLERANCES AND OTHER <br />CONDITIONS AFFECTING PERFORMANCE OF WORK. <br />B. PROCEED WITH INSTALLATION ONLY AFTER UNSATISFACTORY CONDITIONS HAVE BEEN <br />CORRECTED. <br />3.2 PREPARATION: <br />A. COMPLETE FINISHING OPERATIONS, INCLUDING PAINTING , BEFORE INSTALLING <br />IMPACT-RESISTANT WALL PROTECTION SYSTEM COMPONENTS. <br />B. BEFORE INSTALLATION, CLEAN SUBSTRATE TO REMOVE DUST, DEBRIS, AND LOOSE <br />PARTICLES. <br />3.3 INSTALLATION: <br />A. GENERAL: INSTALL IMPACT-RESISTANCE HANDRAILS UNITS LEVEL, PLUMB, AND TRUE <br />TO LINE WITHOUT DISTORTIONS. DO NOT USE MATERIALS WITH CHIPS, CRACKS, VOIDS, <br />STAINS, OR OTHER DEFECTS THAT MIGHT BE VISIBLE IN THE FINISHED WORK. <br />3.4 CLEANING: <br />A. IMMEDIATELY AFTER COMPLETION OF INSTALLATION, CLEAN PLSTIC COVERS AND <br />ACCESSORIES USING A STANDARD, AMMONIA-BASED, HOUSEHOLD CLEANING AGENT. <br />B. REMOVE EXCESS ADHESIVE USING METHODS AND MATERIALS RECOMMENDED IN <br />MANUFACTURER'S PRODUCT DATA. <br />END OF SECTION <br />SECTION 10 2310 - GLAZED INTERIOR WALL AND DOOR ASSEMBLIES <br />PART 1 - GENERAL <br />1. SECTION INCLUDES <br />A. FRAMED GLAZED INTERIOR WALL AND DOOR ASSEMBLIES. <br />2. REFERENCE STANDARDS <br />A. AAMA 611 - VOLUNTARY SPECIFICATION FOR ANODIZED ARCHITECTURAL <br />ALUMINUM; 2012. <br />B. ASTM B221 - STANDARD SPECIFICATION FOR ALUMINUM AND ALUMINUM- <br />ALLOY EXTRUDED BARS, RODS, WIRE, PROFILES, AND TUBES; 2013. <br />C. ASTM B221M - STANDARD SPECIFICATION FOR ALUMINUM AND ALUMINUM- <br />ALLOY EXTRUDED BARS, RODS, WIRE, PROFILES, AND TUBES [METRIC]; 2013. <br />D. ASTM C920 - STANDARD SPECIFICATION FOR ELASTOMERIC JOINT SEALANTS; <br />2014. <br />E. ASTM C1036 - STANDARD SPECIFICATION FOR FLAT GLASS; 2011E1. <br />F. ASTM C1048 - STANDARD SPECIFICATION FOR HEAT-STRENGTHENED AND <br />FULLY TEMPERED FLAT GLASS; 2012. <br />G. WDMA I.S.1-A - ARCHITECTURAL WOOD FLUSH DOORS; WINDOW AND DOOR <br />MANUFACTURERS ASSOCIATION; 2011. <br />3. ADMINISTRATIVE REQUIREMENTS <br />A. PRE-INSTALLATION MEETING: CONVENE AT PROJECT SITE SEVEN CALENDAR <br />DAYS PRIOR TO SCHEDULED BEGINNING OF CONSTRUCTION ACTIVITIES OF <br />THIS SECTION TO REVIEW SECTION REQUIREMENTS. <br />1. REQUIRE ATTENDANCE BY REPRESENTATIVES OF INSTALLER, <br />OTHER ENTITIES DIRECTLY AFFECTING, OR AFFECTED BY, <br />CONSTRUCTION ACTIVITIES OF THIS SECTION. <br />2. NOTIFY ARCHITECT FOUR CALENDAR DAYS IN ADVANCE OF <br />SCHEDULED MEETING DATE. <br />4. SUBMITTALS <br />A. PRODUCT DATA: MANUFACTURER'S DESCRIPTIVE LITERATURE FOR EACH <br />COMPONENT IN PARTITION ASSEMBLY. <br />B. SHOP DRAWINGS: DRAWINGS SHOWING LAYOUT, DIMENSIONS, <br />IDENTIFICATION OF COMPONENTS, AND INTERFACE WITH ADJACENT <br />CONSTRUCTION. <br />1. INCLUDE FIELD MEASUREMENTS OF OPENINGS. <br />2. INCLUDE ELEVATIONS SHOWING: <br />a. LOCATIONS AND IDENTIFICATION OF MANUFACTURER- <br />SUPPLIED DOOR HARDWARE AND FITTINGS. <br />b. LOCATIONS AND SIZES OF CUT-OUTS AND DRILLED HOLES <br />FOR OTHER DOOR HARDWARE. <br />3. INCLUDE DETAILS SHOWING: <br />a. REQUIREMENTS FOR SUPPORT AND BRACING OF <br />OVERHEAD TRACK. <br />b. INSTALLATION DETAILS. <br />c. APPEARANCE OF MANUFACTURER-SUPPLIED DOOR <br />HARDWARE AND FITTINGS. <br />C. CERTIFICATES: CONTRACTOR TO CERTIFY THAT INSTALLER OF PARTITION <br />ASSEMBLIES MEETS SPECIFIED QUALIFICATIONS. <br />D. OPERATION AND MAINTENANCE DATA: FOR MANUFACTURER-SUPPLIED <br />OPERATING HARDWARE. <br />E.WARRANTY DOCUMENTATION: SUBMIT MANUFACTURER WARRANTY AND <br />ENSURE THAT FORMS HAVE BEEN COMPLETED IN OWNER'S NAME AND REGISTERED <br />WITH MANUFACTURER. <br />F.SPECIMEN WARRANTY. <br />G.MANUFACTURER'S INSTALLATION INSTRUCTIONS: INCLUDE COMPLETE <br />PREPARATION, INSTALLATION, AND CLEANING REQUIREMENTS. <br />1. QUALITY ASSURANCE <br />A. FABRICATOR QUALIFICATIONS: MINIMUM THREE YEARS OF EXPERIENCE <br />DESIGNING, ASSEMBLING, AND INSTALLING PARTITION ASSEMBLIES SIMILAR <br />TO THOSE SPECIFIED IN THIS SECTION. <br />2. DELIVERY, STORAGE, AND HANDLING <br />A. STORE PRODUCTS IN MANUFACTURER'S UNOPENED PACKAGING UNTIL <br />INSTALLATION. <br />3. WARRANTY <br />A. CORRECT DEFECTIVE WORK WITHIN A ONE YEAR PERIOD AFTER DATE OF <br />SUBSTANTIAL COMPLETION. <br />B. PROVIDE FIVE YEAR MANUFACTURER WARRANTY AGAINST EXCESSIVE <br />DEGRADATION OF METAL FINISHES. INCLUDE PROVISION FOR REPLACEMENT <br />OF UNITS WITH EXCESSIVE FADING, CHALKING, OR FLAKING. <br />PART 2 PRODUCTS <br />2.1 MANUFACTURERS <br />A. FRAMED GLAZED INTERIOR WALL AND DOOR ASSEMBLIES: <br />1. C.R. LAURENCE CO., INC; CRL 487 SERIES FRAMED GLASS WALL <br />OFFICE SYSTEM: WWW.CRL-ARCH.COM. <br />2. APPROVED EQUAL <br />1. FRAMED GLAZED INTERIOR WALL AND DOOR ASSEMBLIES <br />A. FRAMED GLAZED INTERIOR WALL ASSEMBLY: FACTORY FABRICATED <br />ASSEMBLIES CONSISTING OF CENTER -GLAZED RECTILINEAR ALUMINUM <br />FRAMING WITH SCREW SPLINE OR CLIP JOINERY. <br />1. CONFIGURATION: AS INDICATED ON DRAWINGS. <br />2. PROFILE WIDTH: 1-1/2 INCH (38 MM). <br />3. PROFILE DEPTH: 5-11/16 INCH (144 MM) OVERALL. <br />4. PROFILE FACE TRIM: 1-1/2 INCH (38 MM) WIDE BY 3/8 INCH (9.5 MM) <br />DEEP, SNAP IN PLACE. <br />5. WALL CONSTRUCTION WIDTH, THROAT SIZE: 4-7/8 INCH (124 MM) <br />MAXIMUM WALL, CONSISTING OF METAL STUDS. <br />6. FRAME FINISH: CLASS I NATURAL ANODIZED. <br />7. PROVIDE WOOD BLOCKING AT SILL OF GLAZING FRAME TO MATCH <br />HEIGHT OF FLOOR FINISH. <br />8. EXPOSED FASTENERS: ALUMINUM. <br />9. PERIMETER ANCHORS: STEEL, PROPERLY SEPARATED FROM <br />ALUMINUM FRAMING. <br />10. COORDINATE WALL AND DOOR ASSEMBLY PREPARATION AND <br />PROVIDE HARDWARE AS NECESSARY FOR FULLY OPERABLE <br />INSTALLATION. <br />11. DESIGN SYSTEM TO WITHSTAND NORMAL OPERATION WITHOUT <br />DAMAGE, RACKING, SAGGING, OR DEFLECTION. <br />12. FACTORY ASSEMBLED TO GREATEST EXTENT PRACTICAL; MAY BE <br />DISASSEMBLED TO ACCOMMODATE SHIPPING CONSTRAINTS. <br />B. PIVOTING GLASS DOORS: DRY GLAZED PATCH FITTINGS. <br />1. DOOR CONFIGURATION: AS INDICATED ON DRAWINGS. <br />2. HEIGHT: 2 INCH (51 MM). <br />3. LENGTH: 6-7/16 INCH (164 MM). <br />1. CLADDING FINISH: SATIN ANODIZED. <br />2. GLASS THICKNESS: 1/2 INCH (12.7 MM), TEMPERED. <br />3. DOOR HARDWARE: LOCKING LADDER PULLS, BRUSHED STAINLESS STEEL TUBING. <br />4. PROVIDE ACCESSORIES AS REQUIRED FOR COMPLETE INSTALLATION. <br />5. BASIS OF DESIGN: C.R. LAURENCE CO., INC; CRL COMMERCIAL PATCH HARDWARE, <br />CATALOG NO. PH20AA (TOP), PH10CA (BOTTOM): WWW.CRL-ARCH.COM. <br />C.PIVOTING GLASS DOORS: FULL LENGTH DRY GLAZED RAIL FITTINGS. <br />1. DOOR CONFIGURATION: AS INDICATED ON DRAWINGS. <br />2.FULL LENGTH TOP AND BOTTOM RAILS: 2-5/16 INCH (59 MM) HIGH BY <br />1-1/2 INCH (38 MM) DEEP WITH END CAPS. <br />3.GLASS THICKNESS: 1/2 INCH (12.7 MM), TEMPERED. <br />4.SIDELITE RAILS: MATCH DOOR RAIL SIGHTLINES AND FINISH. <br />5.ALUMINUM FINISH: SATIN ANODIZED. <br />6.DOOR HARDWARE: REFER TO SECTION 08 7100. <br />7.PROVIDE ACCESSORIES AS REQUIRED FOR COMPLETE <br />INSTALLATION. <br />8.BASIS OF DESIGN: C.R. LAURENCE CO., INC; CRL WEDGE-LOCK LOW <br />PROFILE DOOR RAIL SYSTEM: WWW.CRL-ARCH.COM. <br />D.OTHER MANUFACTURERS: PROVIDE EITHER THE PRODUCT IDENTIFIED AS <br />"BASIS OF DESIGN" OR AN EQUIVALENT PRODUCT OF ANOTHER MANUFACTURER. <br />2.03 FITTINGS AND HARDWARE <br />A. OPERABLE PANEL HARDWARE: COORDINATE WITH ADDITIONAL REQUIREMENTS AS SPECIFIED IN <br />SECTION 08 7100. <br />2.04 MATERIALS <br />A.GLASS: FLAT GLASS MEETING REQUIREMENTS OF ASTM C1036, TYPE I - TRANSPARENT FLAT <br />GLASS, QUALITY Q3, FULLY TEMPERED IN ACCORDANCE WITH ASTM C1048, KIND FT, AND AS FOLLOWS: <br />1.THICKNESS: AS INDICATED. <br />2.COLOR: AS INDICATED ON DRAWINGS. <br />3.GLAZING STOPS: SQUARE EDGE, WITH RUBBER GLAZING GASKETS. <br />4.GLAZING GASKETS: PROVIDE FLEXIBLE VINYL FOR NON-FIRE RATED AND <br />ELASTOMERIC SILICONE FOR FIRE RATED FRAMES. <br />5.PREPARE GLAZING PANELS FOR INDICATED FITTINGS AND HARDWARE BEFORE <br />TEMPERING. <br />6.POLISH EDGES THAT WILL BE EXPOSED IN FINISHED WORK TO BRIGHT FLAT POLISH. <br />7.TEMPER GLASS MATERIALS HORIZONTALLY; VISIBLE TONG MARKS OR TONG MARK <br />DISTORTIONS ARE NOT PERMITTED. <br />B.ALUMINUM COMPONENTS: CONFORMING TO ASTM B221 (ASTM B221M), ALLOY 6063, T5 TEMPER. <br />C.SEALANT: ONE-PART SILICONE SEALANT, CONFORMING TO ASTM C920, CLEAR. <br />2.05 FINISHES <br />A.CLASS I NATURAL ANODIZED FINISH: AAMA 611 AA-M12C22A41 CLEAR ANODIC COATING NOT <br />LESS THAN 0.7 MILS (0.018 MM) THICK. <br />PART 3 EXECUTION <br />3.1 EXAMINATION <br />A. VERIFY THAT FIELD MEASUREMENTS ARE AS INDICATED. <br />B. VERIFY THAT TRACK SUPPORTS ARE PROPERLY BRACED, LEVEL WITHIN 1/4 <br />INCH (6 MM) OF REQUIRED POSITION AND PARALLEL TO THE FLOOR <br />SURFACE. <br />C. VERIFY FLOOR FLATNESS OF 1/8 INCH IN 10 FEET (3 MM IN 3 M), NON- <br />CUMULATIVE. <br />D. DO NOT BEGIN INSTALLATION UNTIL SUPPORTS AND ADJACENT SUBSTRATES <br />HAVE BEEN PROPERLY PREPARED. <br />E. IF SUBSTRATE PREPARATION IS THE RESPONSIBILITY OF ANOTHER <br />INSTALLER, NOTIFY ARCHITECT OF UNSATISFACTORY PREPARATION BEFORE <br />PROCEEDING. <br />1. PREPARATION <br />A. CLEAN SUBSTRATES THOROUGHLY PRIOR TO INSTALLATION. <br />B. PREPARE SUBSTRATES USING THE METHODS RECOMMENDED BY THE <br />MANUFACTURER FOR ACHIEVING ACCEPTABLE RESULT FOR THE SUBSTRATE <br />UNDER THE PROJECT CONDITIONS. <br />2. INSTALLATION <br />A. INSTALL IN ACCORDANCE WITH GLAZED INTERIOR WALL AND DOOR <br />ASSEMBLY MANUFACTURER'S INSTRUCTIONS. <br />B. FIT AND ALIGN GLAZED INTERIOR WALL AND DOOR ASSEMBLY LEVEL AND <br />PLUMB. <br />3. ADJUSTING <br />A. ADJUST GLAZED INTERIOR WALL AND DOOR ASSEMBLY TO OPERATE <br />SMOOTHLY FROM SLIDING OR PIVOTING POSITIONS. <br />B. ADJUST SWING DOOR HARDWARE FOR SMOOTH OPERATION. <br />4. CLEANING <br />A. CLEAN INSTALLED WORK TO LIKE-NEW CONDITION. <br />5. CLOSEOUT ACTIVITIES <br />A. DEMONSTRATE OPERATION OF GLAZED INTERIOR WALL AND DOOR <br />ASSEMBLY AND IDENTIFY POTENTIAL OPERATIONAL PROBLEMS. <br />6. PROTECTION <br />A. PROTECT INSTALLED PRODUCTS UNTIL COMPLETION OF PROJECT. <br />B. TOUCH-UP, REPAIR OR REPLACE DAMAGED PRODUCTS BEFORE DATE OF <br />SUBSTANTIAL COMPLETION. <br />END OF SECTION <br />R <br />No. <br />F <br />LICENSE <br />STATE <br />D <br />O <br />A RCHITECT <br />C AL IFORNIA <br />STEPHE WHITE <br />RENEWAL <br />DATE <br />C-34829 <br />N <br />08/31/27 <br />SHEET TITLE <br />PROJECT <br />FACILITY <br />FAC NO: BLDG NO: FLOOR LEV: SECTION: <br />KP PROJ. NO. <br />PERMIT NO. <br />555 W. Fifth Street Suite 2950 | Los Angeles, CA 90013 USA <br />ARCHITECT <br />CONSULTANT <br />ARCHITECT SEAL CONSULTANT SEAL <br />KAISER FOUNDATION HOSPITALS <br />NATIONAL FACILITIES SERVICES <br />1800 HARRISON STREET OAKLAND, <br />CALIFORNIA 94612 <br />ISSUE / REVISION LOG <br />NO. ISSUED DATE <br />0 <br />5' <br /> <br />5 <br />0 <br />' <br />GR <br />A <br />P <br />H <br />I <br />C <br /> <br />S <br />C <br />A <br />L <br />E <br />S <br />: <br /> <br />1 <br />/ <br />1 <br />6 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />0 <br />25 <br />' <br />1/ <br />8 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />5' <br />0 <br />12 <br />' <br />1/ <br />4 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />1' <br />0 <br />6' <br />1/ <br />2 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />1' <br />0 <br />2' <br />1- <br />1 <br />/ <br />2 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />0 <br />1' <br />3" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />IF <br /> <br />T <br />H <br />I <br />S <br /> <br />S <br />H <br />E <br />E <br />T <br /> <br />I <br />S <br /> <br />N <br />O <br />T <br /> <br />30 <br />" <br />x <br />4 <br />2 <br />" <br />, <br /> <br />I <br />T <br /> <br />I <br />S <br /> <br />A <br /> <br />R <br />E <br />D <br />U <br />C <br />E <br />D <br /> <br />PR <br />I <br />N <br />T <br /> <br />- <br /> <br />S <br />C <br />A <br />L <br />E <br /> <br />AC <br />C <br />O <br />R <br />D <br />I <br />N <br />G <br />L <br />Y <br />AGENCY APPLICATION NUMBER <br />AGENCY APPROVAL STAMP <br />THIS DOCUMENT IS THE PROPERTY OF THE OWNER AND IS <br />NOT TO BE USED WITHOUT OWNER'S WRITTEN PERMISSION. <br />HZ PROJ. NO. <br />www.huitt-zollars.com <br />Phone 310.820.4600 | Fax 310.207.4215 <br />C: <br />\ <br />U <br />s <br />e <br />r <br />s <br />\ <br />l <br />r <br />o <br />b <br />i <br />n <br />s <br />o <br />n <br />\ <br />O <br />n <br />e <br />D <br />r <br />i <br />v <br />e <br /> <br />- <br /> <br />H <br />u <br />i <br />t <br />t <br />- <br />Z <br />o <br />l <br />l <br />a <br />r <br />s <br />, <br /> <br />I <br />n <br />c <br />\ <br />D <br />o <br />cu <br />m <br />e <br />n <br />t <br />s <br />\ <br />R <br />3 <br />1 <br />4 <br />4 <br />1 <br />2 <br />. <br />3 <br />5 <br /> <br />K <br />P <br /> <br />H <br />B <br />M <br /> <br />K <br />P <br />O <br />J <br />_ <br />A <br />2 <br />4 <br />_ <br />l <br />r <br />o <br />b <br />i <br />n <br />s <br />o <br />n <br />L <br />2 <br />M <br />D <br />X <br />. <br />r <br />vt <br />1 <br />1 <br />/ <br />3 <br />/ <br />2 <br />0 <br />2 <br />5 <br /> <br />3 <br />: <br />4 <br />4 <br />: <br />0 <br />4 <br /> <br />P <br />M <br />SOCC 2022 R HBM 1st Fl KPOJ <br />REMODEL <br />G0-05 <br />SPECIFICATIONS <br />CA394-1 - <br />CAP027721R314412.35 <br />HARBOR/MacARTHUR MEDICAL OFF <br />3401 S. HARBOR BLVD. <br />SANTA ANA, CALIFORNIA 92704 <br />N/ASPECIFICATIONS - DIVISION 28 28N/ASPECIFICATIONS - DIVISION 10 10 <br />CITY SUBMITTAL 11/03/2025 <br />101125520, 20187249, 40140902