ELECTRICAL ABBREVIATION KEY
<br />AFF ABOVE FINISHED FLOOR
<br />C CONDUIT
<br />CO CONDUIT AND BOX ROUGH-IN ONLY (ROUGH-IN ONLY)
<br />GFI GROUND FAULT INTERRUPTER
<br />ABBR:DESCRIPTION:
<br />TYP TYPICAL
<br />UON UNLESS OTHERWISE NOTED
<br />1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD
<br />SURVEYS, EXISTING BUILDING DOCUMENTS. CONTRACTOR SHALL REVIEW EXISTING
<br />CONDITIONS AND REPORT CONFLICTS.
<br />2. NOT ALL EXISTING EQUIPMENT, LUMINAIRES, AND CONDUIT ARE SHOWN. CONTRACTOR
<br />SHALL REVIEW EXISTING CONDITIONS AND REPORT CONFLICTS.
<br />3. ELECTRICAL CONTRACTOR SHALL REVIEW EXISTING CONDITIONS TO VERIFY ACCESSIBILITY
<br />TO THE AREAS OF THEIR WORK INCLUDING WALLS, FLOOR, AND CEILINGS. ELECTRICAL
<br />CONTRACTOR IS RESPONSIBLE TO PROVIDE CUTTING, REMOVAL, PATCHING, AND
<br />REINSTALLATION OF AFFECTED AREAS ASSOCIATED WITH THEIR WORK BY COORDINATING
<br />WITH THE GENERAL CONTRACTOR OR QUALIFIED CONTRACTOR.
<br />4. WHERE EXISTING ELECTRICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH NEW
<br />EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHER
<br />ARRANGE NEW EQUIPMENT, CONDUIT, OR DUCTWORK IN SUCH A FASHION THAT IT DOES
<br />NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING ELECTRICAL SYSTEMS TO
<br />ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.
<br />ELECTRICAL RENOVATION NOTES:
<br />THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
<br />TO LIGHTING AND POWER
<br />26 05 33 JUNCTION BOXJ
<br />ELECTRICAL SYMBOL LIST
<br />SYMBOL:TAG:SPEC
<br />SECTION:DESCRIPTION:
<br />PANEL '###'PANELBOARD -SURFACE MOUNT
<br />26 05 33 ELECTRICAL CONNECTIONE
<br />E
<br />SWITCH
<br />SUBSCRIPTS:
<br />3R= NEMA 3R WEATHERPROOF SWITCH
<br />##
<br />J
<br />BRANCH CIRCUITS: LIGHTING, RECEPTACLES,
<br />CONTROLS, ETC.
<br />CONDUIT INSTALLATION SCHEDULE
<br />THE FOLLOWING SCHEDULE SHALL BE ADHERED TO UNLESS THEY CONSTITUTE A VIOLATION OF
<br />APPLICABLE CODES OR ARE NOTED OTHERWISE ON THE DRAW INGS. THE INSTALLATION OF RMC
<br />CONDUIT WILL BE PERMITTED IN PLACE OF ALL CONDUIT SPECIFIED IN THIS SCHEDULE. REFER
<br />TO CONDUIT AND BOXES SPECIFICATION 26 05 33 FOR ADDITIONAL INFORMATION.
<br />INSTALLATION TYPE FMC
<br />X
<br />EMT
<br />X
<br />BRANCH CIRCUIT SCHEDULE
<br />SYMBOL:DESCRIPTION:
<br />CONDUIT HOMERUN TO PANELBOARD. LETTER AND NUMERALS
<br />INDICATE ELECTRICAL PANEL AND CIRCUIT NUMBER.
<br />PANEL -CIRCUIT
<br />2022 CALIFORNIA BUILDING STANDARDS ADMINISTRATIVE CODE
<br />CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 24, PART 1
<br />2022 CALIFORNIA BUILDING CODE (CBC)
<br />CALIFORNIA CODE OF REGULATIONS TITLE 24, PART 2
<br />(2021 INTERNATIONAL BUILDING CODE (IBC) W/ 2022 CALIFORNIA AMENDMENTS)
<br />2022 CALIFORNIA ELECTRICAL CODE (CEC)
<br />CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 24, PART 3
<br />(2020 NATIONAL ELECTRICAL CODE (NEC) W/ 2022 CALIFORNIA AMENDMENTS)
<br />2022 CALIFORNIA MECHANICAL CODE (CMC)
<br />CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 24, PART 4
<br />(2021 UNIFORM MECHANICAL CODE (UMC) W/ 2022 CALIFORNIA AMENDMENTS)
<br />2022 CALIFORNIA PLUMBING CODE (CPC)
<br />CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 24, PART 5
<br />(2021 UNIFORM MECHANICAL CODE (UPC) W/ 2022 CALIFORNIA AMENDMENTS)
<br />2022 CALIFORNIA ENERGY CODE
<br />CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 24, PART 6
<br />2022 CALIFORNIA FIRE CODE (CFC)
<br />CALIFORNIA CODES OF REGULATIONS (CRR) TITLE 24, PART 9
<br />(2021 INTERNATIONAL FIRE CODE (IFC) W/ 2022 CALIFORNIA AMENDMENTS)
<br />2022 CALIFORNIA EXISTING BUILDING CODE
<br />CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 24, PART 10
<br />(2021 INTERNATIONAL EXISTING BUILDING CODE (IEBC))
<br />2022 CALIFORNIA GREEN BUILDING STANDARDS CODE (CALGREEN)
<br />CALIFORNIA CODES OF REGULATIONS (CCR) TITLE 24, PART 11
<br />2022 CALIFORNIA REFERENCED STANDARDS CODE
<br />CALIFORNIA DOE OF REGULATIONS (CCR) TITLE 24, PART 12
<br />APPLICABLE CODES AND STANDARDS:
<br />48
<br />"
<br />
<br />M
<br />A
<br />X
<br />.
<br />20" MAX.
<br />44
<br />"
<br />
<br />M
<br />A
<br />X
<br />.
<br />20"-25" MAX.
<br />48
<br />"
<br />
<br />M
<br />A
<br />X
<br />.
<br />15
<br />"
<br />
<br />M
<br />I
<br />N
<br />.
<br />48
<br />"
<br />
<br />M
<br />A
<br />X
<br />.
<br />46
<br />"
<br />
<br />M
<br />A
<br />X
<br />.
<br />10" MAX.10"-24" MAX.
<br />ADA STANDARDS -FRONT ACCESS
<br />ADA STANDARDS FOR ACCESSIBLE DESIGN
<br />INSTALL ABOVE COUNTER
<br />DEVICE AT 44" ABOVE
<br />FINISHED FLOOR.
<br />INSTALL ABOVE COUNTER
<br />DEVICE AT 40" ABOVE
<br />FINISHED FLOOR.
<br />INSTALL DEVICE AT 18"
<br />ABOVE FINISHED FLOOR.
<br />ADA STANDARDS -SIDE ACCESS
<br />INSTALL DEVICE AT 44"
<br />ABOVE FINISHED FLOOR.
<br />INSTALL DEVICE AT 42"
<br />ABOVE FINISHED FLOOR.
<br />ELECTRICAL CONTRACTORE.C.
<br />CONTRACTOR ABBREVIATION KEY
<br />ABBR:DESCRIPTION:
<br />VIEW KEY
<br />LINE TYPE AND TAG KEY:
<br />NEW WORK BY THIS CONTRACTOR (WIDE LINE)
<br />EXISTING TO REMAIN
<br />HALFTONING DOES NOT MODIFY SCOPE.
<br />'TAG'-(E)TAGS WITH DASH 'E' INDICATES THE REFERENCED OBJECT IS EXISTING
<br />'TAG'-(R)TAGS WITH DASH 'R' INDICATES THE REFERENCED OBJECT IS REMOVED
<br />TAG-1 UNDERLINED TAG INDICATES OBJECT IS IN-SCOPE. IF NEW, ADDITIONAL
<br />INFORMATION IS AVAILABLE IN A SCHEDULE, MATERIAL LIST, OR SYMBOL LIST
<br />INDICATES AN EXISTING SYSTEM'S POINT OF CONNECTION/REMOVAL
<br />PLAN OR DETAIL NUMBER
<br />PLAN OR DETAIL NAME
<br />PLAN OR DETAIL SCALE
<br />DETAIL REFERRED TO BY SECTION CUT
<br />SHEET DETAIL IS LOCATED ON
<br />NAME
<br />1 VIEW NAME
<br />1/8" = 1'-0"
<br />1
<br />M101
<br />1
<br />4
<br />3
<br />2
<br />SIMSIM
<br />INDICATES SIMILAR DETAIL REFERENCED
<br />IN MULTIPLE LOCATIONS
<br />LEVEL NAME
<br />10'-0"HEIGHT ABOVE
<br />PROJECT 0'-0"
<br />1 KEYNOTE: INDICATES NOTE USED TO
<br />DESCRIBE ADDITIONAL INFORMATION
<br />ABOUT WORK REQUIRED, SPECIFIC
<br />TO THE SHEET AND/OR DETAIL
<br />NO R HT
<br />INDICATES DIRECTION OF TRUE NORTH
<br />T101
<br />NEW
<br />EXISTING TO BE REMOVED (SHORT DASHED PATTERN)
<br />EXISTING (NARROW LINE PATTERN)
<br />SCOPE OF WORK NOTES:
<br />1. DEMOLITION OF EXISTING EXTERIOR SIGNAGE AND INSTALLATION OF NEW EXTERIOR
<br />ILLUMINATED SIGNAGE.
<br />1. THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE WITH THE ADA STANDARDS FOR
<br />ACCESSIBLE DESIGN. REFER TO THE ADA GUIDELINES FOR ALL CONFIGURATION DETAILS ON
<br />THIS PAGE FOR ADDITIONAL INFORMATION.
<br />2. CIRCUIT NUMBERS ARE SHOWN FOR CIRCUIT IDENTIFICATION. CIRCUITING SHALL AGREE
<br />WITH NUMBERING ON THE PANEL PROVIDED. COMMON NEUTRALS MAY NOT BE USED FOR
<br />BRANCH CIRCUITS.
<br />3. FLUSH MOUNT ALL LIGHTING CONTROL DEVICES AT +42" FROM FLOOR (CENTERLINE
<br />DIMENSION), EXCEPT WHERE OTHERWISE NOTED.
<br />4. FLUSH MOUNT ALL DUPLEX RECEPTACLES OUTLETS AT +18" FROM FLOOR (CENTERLINE
<br />DIMENSION), EXCEPT WHERE OTHERWISE NOTED.
<br />5. CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL CEILING MOUNTED DEVICES AND
<br />EQUIPMENT WITH LUMINAIRES, SPRINKLER, AND CEILING DIFFUSERS. CENTER ALL DEVICES
<br />IN CEILING TILE PATTERN. OCCUPANCY/VACANCY SENSORS SHALL BE LOCATED NO CLOSER
<br />THAN 3 FEET TO AN AIR SUPPLY DIFFUSER OR RETURN GRILLE.
<br />6. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL OPENINGS REQUIRED IN WALLS. ALL
<br />OPENINGS SHALL BE REPAIRED TO MATCH EXISTING BY A QUALIFIED CONTRACTOR AT THE
<br />EXPENSE OF THIS CONTRACTOR. ALL CONDUITS THROUGH W ALLS SHALL BE GROUTED OR
<br />SEALED INTO OPENINGS.
<br />7. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO THE
<br />WALLS, FLOORS, AND CEILINGS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE IS
<br />RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND
<br />FINISH.
<br />8. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN, ELECTRICAL AND OTHER
<br />ELECTRICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING MOUNTED DEVICES, OTHER
<br />THAN SPRINKLERS.
<br />9. ELECTRICAL IDENTIFICATION. REFER TO SPECIFICATION SECTION 26 05 53 FOR COLOR/LABEL
<br />REQUIREMENTS FOR CONDUIT, BOX, CABLE/WIRE, AND EQUIPMENT.
<br />ELECTRICAL INSTALLATION NOTES:
<br />TE OLIRFFOAC
<br />LANRP
<br />E 23191
<br />STA
<br />ER
<br />REGIST
<br />ED
<br />INA
<br />N
<br />REENIGE
<br />FO OISSE
<br />E AICLCERTL
<br />Exp. 06/30/26
<br />MIRASOPHOCLISGEORGY
<br />IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO
<br />THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAW ING
<br />AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
<br />BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE
<br />EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
<br />©2024 IMEG CONSULTANTS CORP.
<br />REF. SCALE IN INCHES
<br />0 1 2 3
<br />222 S. HARBOR BOULEVARD
<br />SUITE 800
<br />ANAHEIM, CA 92805
<br />P: 714.490.5555 F: 714.490.5560
<br />The FUTURE. Built Smarter www.imegcorp.com
<br />PROJECT #24007312.00
<br />0 5'
<br />GRAPHIC SCALES:
<br />Issue Date
<br />1/16" = 1'-0"
<br />50'
<br />1/8" = 1'-0"1/4" = 1'-0"1/2" = 1'-0"3/4" = 1'-0"1" = 1'-0"1-1/2" = 1'-0"3" = 1'-0"
<br />0 5'25' 0 1'12' 0 1'6' 0 4' 0 3'1'0 2' 0 1'
<br />Chckd By
<br />Drwn By
<br />Scale
<br />Building ID:
<br />KP Proj. No.
<br />Permit No.
<br />Sheet
<br />SheetsOf
<br />Sheet Title
<br />Project
<br />Facility
<br />This document is the property of the Owner and is
<br />Project Architect Approval:
<br />Architect/Engineer Of Record:
<br />IF THIS SHEET IS NOT 30"x42" , IT IS
<br />A REDUCED PRINT - SCALE ACCORDINGLY
<br />National Facilities Services
<br />Post Office Box 12916
<br />Oakland California 94604
<br />not to be used without owner's written permission.
<br />Floor Lev:Section:
<br />HGW Proj. No.
<br />©
<br />A
<br />R
<br />C
<br />H
<br />I
<br />T
<br />E
<br />C
<br />T
<br />S
<br />
<br />h
<br />a
<br />n
<br />n
<br />a
<br />
<br />g
<br />a
<br />b
<br />r
<br />i
<br />e
<br />l
<br />
<br />w
<br />e
<br />l
<br />l
<br />s
<br />,
<br />
<br />a
<br />l
<br />l
<br />
<br />r
<br />i
<br />g
<br />h
<br />t
<br />s
<br />
<br />r
<br />e
<br />s
<br />e
<br />r
<br />v
<br />ed
<br />.
<br />
<br />
<br />A
<br />n
<br />y
<br />
<br />u
<br />s
<br />e
<br />
<br />w
<br />i
<br />t
<br />h
<br />o
<br />u
<br />t
<br />
<br />p
<br />e
<br />r
<br />m
<br />i
<br />s
<br />s
<br />i
<br />o
<br />n
<br />
<br />i
<br />s
<br />
<br />e
<br />x
<br />p
<br />r
<br />e
<br />s
<br />s
<br />l
<br />y
<br />
<br />p
<br />r
<br />o
<br />h
<br />i
<br />b
<br />i
<br />t
<br />ed
<br />.
<br />
<br />
<br />P
<br />l
<br />o
<br />t
<br />t
<br />e
<br />d
<br />CAP029271
<br />1955 Bacon Street. San Diego, CA 92107
<br />Office 619 523 8487
<br />www.hgwarchitecture.com
<br />PROJECT #24007312.00
<br />Revisions
<br />By Appr.
<br />KAISER HARBOR MACARTHUR MOB
<br />EXTERIOR SIGNAGE
<br />KAISER PERMANENTE
<br />HARBOR MACARTHUR MOB
<br />As indicated
<br />1/
<br />2
<br />3
<br />/
<br />2
<br />0
<br />2
<br />6
<br />
<br />1
<br />2
<br />:
<br />4
<br />5
<br />:
<br />5
<br />2
<br />
<br />P
<br />M
<br />01/23/2026
<br />MG
<br />CL
<br />ES001
<br />ELECTRICAL COVERSHEET
<br />3401 South Harbor Boulevard,
<br />Santa Ana, CA 92704
<br />10
<br />0
<br />%
<br />
<br />C
<br />D
<br />
<br />S
<br />E
<br />T
<br />2441
<br />ELECTRICAL SHEET INDEX
<br />ES001 ELECTRICAL COVERSHEET
<br />ES002 ELECTRICAL SPECIFICATIONS
<br />ES003 ELECTRICAL SPECIFICATIONS
<br />ES004 ELECTRICAL SPECIFICATIONS
<br />ES102 LEVEL 02 - ELECTRICAL PLAN - OVERALL
<br />ES103 LEVEL 03 - ELECTRICAL PLAN - OVERALL
<br />ES122 LEVEL 02 - ENLARGED POWER PLAN
<br />ES123 LEVEL 03 - ENLARGED POWER PLAN
<br />ES400 PARTIAL SINGLE LINE DIAGRAM, PANEL SCHEDULES, LOAD CALCULATIONS, &
<br />DETAILS
<br />GRAND TOTAL: 9