Laserfiche WebLink
<br /> <br /> Page 79 of 111 <br /> <br />Report No.: 2410B0143SHA-001 <br /> <br />TRF No. ANSI/CAN/UL 9540A_Unit <br /> <br />1 thermocouple (T14), Type K, was placed near the initiating unit to monitor the ambient temperature during <br />the test. <br /> <br />Additional 6 thermocouples (T15 to T20), Type K, were located on the surface of initiating module to monitor <br />the module enclosure temperatures during the test. <br /> <br />See below figure and table for detailed location of thermocouples. Module orientation as intended for final <br />installation. <br /> <br /> <br /> <br /> <br />Location of thermocouples on module enclosure and near the unit <br /> <br />Thermocouple No. Location <br />T14 Ambient temperature, near the unit <br />T15 Center of module front surface <br />T16 Center of module rear surface <br />T17 Center of module left surface <br />T18 Center of module right surface <br />T19 Center of module top surface <br />T20 Center of module bottom surface <br />