Laserfiche WebLink
<br /> <br /> Page 91 of 111 <br /> <br />Report No.: 2410B0143SHA-001 <br /> <br />TRF No. ANSI/CAN/UL 9540A_Unit <br /> <br />To monitor the surface temperatures of instrumented walls, vertical array at 152 mm intervals for the full <br />height of the instrumented wall sections using Type K, 24 AWG thermocouples, were used. <br /> <br />Thermocouples were secured to gypsum surfaces by the use of staples placed over the insulated portion of <br />the wires. The first thermocouple starts from 152 mm from the ground. <br /> <br />The thermocouple array A was on instrument ed wall A, collinear with vertical center line of initiating unit rear <br />surface. The thermocouples were numbered from low to high as TCA1 to TCA24 for thermocouple array A. <br /> <br />The thermocouple array B was on instrumented wall B, collinear with vertical center line of initiating unit left <br />surface. The thermocouples were numbered from low to high as TCB1 to TCB24 for thermocouple array B. <br /> <br />The thermocouple array C was on instrumented wall C, collinear with vertical center line of initiating unit front <br />surface. The thermocouples were numbered from low to high as TCC1 to TCC24 for thermocouple array C. <br /> <br /> <br /> Thermocouple array location (view side: side view) <br /> <br /> <br /> <br /> <br /> <br />