Laserfiche WebLink
<br /> <br /> Page 92 of 111 <br /> <br />Report No.: 2410B0143SHA-001 <br /> <br />TRF No. ANSI/CAN/UL 9540A_Unit <br /> <br />The measured surface temperatures of instrumented wall A during the test are shown in the below figure. <br /> <br /> <br />Temperatures of instrumented wall A <br /> <br />The detailed temperatures of the thermocouple arrays are shown in the figure below. <br /> <br />Thermocouple No. Maximum <br />temperature (°C) Thermocouple No. Maximum <br />temperature (°C) <br />TCA1 19.9 TCA13 17.5 <br />TCA2 19.2 TCA14 17.3 <br />TCA3 19.5 TCA15 17.3 <br />TCA4 20.1 TCA16 19.3 <br />TCA5 19.3 TCA17 14.8 <br />TCA6 19.2 TCA18 17.3 <br />TCA7 19.3 TCA19 18.3 <br />TCA8 21.2 TCA20 19.7 <br />TCA9 15.1 TCA21 18 <br />TCA10 19.4 TCA22 17.7 <br />TCA11 19.3 TCA23 15 <br />TCA12 21.6 TCA24 19.8 <br /> <br /> <br /> <br /> <br />