Laserfiche WebLink
<br /> <br /> Page 94 of 111 <br /> <br />Report No.: 2410B0143SHA-001 <br /> <br />TRF No. ANSI/CAN/UL 9540A_Unit <br /> <br />The measured surface temperatures of instrumented wall C during the test are shown in the below figure. <br /> <br /> <br />Temperatures of instrumented wall C <br /> <br />The detailed temperatures of the thermocouple arrays are shown in the figure below. <br /> <br />Thermocouple No. Maximum <br />temperature (°C) Thermocouple No. Maximum <br />temperature (°C) <br />TCC1 15 TCC13 17.3 <br />TCC2 16.9 TCC14 17.5 <br />TCC3 19.2 TCC15 17 <br />TCC4 19.7 TCC16 17.1 <br />TCC5 17.2 TCC17 18 <br />TCC6 18.1 TCC18 17.8 <br />TCC7 18.7 TCC19 17.9 <br />TCC8 18.8 TCC20 17.6 <br />TCC9 14 TCC21 17.7 <br />TCC10 18.7 TCC22 17.3 <br />TCC11 19.6 TCC23 18 <br />TCC12 20.8 TCC24 18.3 <br /> <br /> <br />Temperatures of instrumented wall C