<br /> <br /> Page 96 of 111 <br /> <br />Report No.: 2410B0143SHA-001 <br /> <br />TRF No. ANSI/CAN/UL 9540A_Unit <br /> <br />HF7 and HF8 were secured on the left surface of target unit 1, height is height is the same with upper <br />surface of relief valves. The detailed locations of heat flux are shown in below figure. <br /> Location of heat flux sensors <br /> <br />For non-residential use unit, heat flux was measured with the sensing element of 2 water-cooled Schmidt- <br />Boelter positioned at the mid height of the initiating unit and the point where the majority of off-gas venting is <br />expected from the initiating unit in the center of the accessible means of egress. <br /> <br />The same with upper surface of relief valves of the initiating unit in accessible means of egress was <br />confirmed to receive the majority of off-gas venting. <br /> <br />Due to the distance between initiating unit and instrumented wall C was 10cm, and hence max. heat flux <br />measured by HF5 and HF6 was used to represent the max. heat flux in in the center of the accessible <br />means of egress. <br /> Location of heat flux sensors <br />