POWER LEGEND AND SYMBOLS
<br />SYMBOL DESCRIPTION
<br />POWER LEGEND AND SYMBOLS
<br />SYMBOL DESCRIPTION
<br />NOTE TO CONTRACTOR
<br />CONTRACTOR SHALL VERIFY PLANS AND EXISTING DIMENSIONS AND CONDITIONS ON THE JOB SITE AND SHALL
<br />IMMEDIATELY NOTIFY THE ARCHITECT IN WRITING OF ANY DISCREPANCIES BEFORE PROCEEDING WITH THE WORK OR BE
<br />RESPONSIBLE FOR THE SAME.
<br />DO NOT SCALE DRAWINGS
<br />1.ALL MATERIALS AND WORKMANSHIP SHALL CONFORM TO THE LATEST CODE OF FEDERAL REGULATIONS (CFR), NATIONAL ELECTRICAL CODE EDITION AND ALL APPLICABLE LOCAL CODES AND
<br />REGULATIONS.
<br />2.ALL WORK IS NEW UNLESS NOTED OTHERWISE.
<br />3.ALL PANELS, SWITCHES, ETC. SHALL HAVE SUFFICIENT GUTTER SPACE AND LUGS IN COMPLIANCE TO UL REQUIREMENTS TO ACCOMMODATE CONDUCTORS SHOWN.
<br />4.WHERE WIRE SIZES ARE INDICATED ON PLANS, FOR INDIVIDUAL CIRCUITS, THE WIRE SIZE INDICATED SHALL APPLY TO THE COMPLETE CIRCUIT, UNLESS OTHERWISE NOTED.
<br />5.WHERE EXISTING CIRCUITS OR DEVICES ARE DEMOLISHED, MODIFIED, OR REUSED, ENSURE ALL EXISTING ELECTRICAL UTILIZATION DEVICES TO REMAIN ARE ENERGIZED UPON COMPLETION OF WORK.
<br />6.CONTRACTOR SHALL VERIFY THE EXACT LOCATION OF MECHANICAL, PLUMBING AND OTHER EQUIPMENT REQUIRING ELECTRICAL CONNECTION PRIOR TO ANY WORK.
<br />7.CONTRACTOR SHALL EXTEND WIRING FROM ALL JUNCTION BOXES, SWITCHES, ETC. AND MAKE FINAL CONNECTION AS REQUIRED TO ALL BUILDING EQUIPMENT REQUIRING ELECTRICAL CONNECTIONS.
<br />8.DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF SYSTEMS AND WORK INCLUDED. FOLLOW DRAWINGS IN LAYING OUT WORK AND CHECK DRAWINGS OR OTHER TRADES
<br />RELATING TO WORK TO VERIFY SPACE IN WHICH WORK WILL BE INSTALLED. MAINTAIN HEADROOM AND MINIMUM CODE REQUIRED WORKING CLEARANCES AT ALL TIMES.
<br />9.CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL WALL OUTLET BOXES FOR SWITCHES, BELL/STROBES, FIRE ALARM PULL STATIONS. RECEPTACLES ETC. WITH CABINETS, FURNITURE, EQUIPMENT
<br />ETC., TO AVOID CONFLICT.
<br />10.FURNISH PULL STRING IN EACH RACEWAY RUN OVER 10' IN LENGTH, IN WHICH PERMANENT WIRING IS NOT INSTALLED.
<br />11.NOT MORE THAN THREE LIGHTING OR CONVENIENCE OUTLET CIRCUITS ARE PERMITTED IN ONE CONDUIT, PROVIDE SEPARATE CONDUIT FOR EACH HOMERUN INDICATED ON THE DRAWING, UNLESS
<br />INDICATED OTHERWISE.
<br />12.PROVIDE PULL BOXES WHEREVER NECESSARY TO FACILITATE PULLING OF CONDUCTORS. COORDINATE LOCATIONS OF BOXES WITH OTHER TRADES TO AVOID CONFLICT. PULL BOXES SHALL BE
<br />ACCESSIBLE. THE SIZE OF PULL BOX SHALL COMPLY WITH N.E.C. REQUIREMENTS.
<br />13.ALL EXTERIOR ELECTRICAL DEVICES AND EQUIPMENT INCLUDING THOSE THAT ARE EXPOSED TO OUTSIDE ENVIRONMENT SHALL BE WEATHERPROOF TYPE, NEMA 3R AND ELECTRICAL DEVICES AND
<br />EQUIPMENT INCLUDING THOSE THAT ARE EXPOSED TO DIRECT WATER SPRAY OR IN CORROSIVE LOCATIONS SHALL BE NEMA 4X, REGARDLESS OF ALTERNATE NEMA RATING INDICATED IN NOTES OR
<br />SCHEDULES.
<br />14.NO CONDUIT RUNS SHALL BE ALLOWED IN CONCRETE SLABS. ALL CONDUITS WILL BE PLACED ABOVE ACCESSIBLE CEILING SPACES UNLESS SPECIFICALLY INDICATED TO BE UNDERGROUND.
<br />15.LIGHTING, POWER, TELEPHONE AND COMMUNICATIONS OUTLETS SHALL NOT BE PLACED BACK-TO-BACK.
<br />16.DISCONNECT SWITCHES SHALL BE MOUNTED ON INDIVIDUAL SUPPORTS, OR OTHERWISE DIRECTLY ON EQUIPMENT, PROVIDED NO MODIFICATION TO EQUIPMENT IS NECESSARY.
<br />17.ALL ELECTRICAL POWER, LIGHTING, TELEPHONE OR SIGNAL WIRING IN FIRE RATED WALL IS TO BE INSTALLED IN A METALLIC CONDUIT SYSTEM.
<br />18.ALL ELECTRIC MATERIAL SHALL BE LISTED BY "UL" FOR THE TYPE OF APPLICATION AND "UL" LABEL SHALL APPEAR ON ALL ELECTRICAL EQUIPMENT.
<br />19.ALL DISTRIBUTION AND CONTROL EQUIPMENT (SUCH AS CB's, SWITCHES, CONTACTORS, ETC.), TERMINATIONS SHALL BE FULLY RATED PER UL AS FOLLOWS:
<br />a. 100A OR LESS : 60°C OR MORE;
<br />b. MORE THAN 100A : 75°C OR MORE.
<br />20.ANY ERRORS, OMISSIONS, OR DESIGN DISCREPANCIES ON PLANS OR SPECIFICATIONS SHALL BE BROUGHT TO THE ATTENTION OF THE ELECTRICAL ENGINEER FOR CLARIFICATION OR CORRECTION PRIOR
<br />TO CONSTRUCTION AND PREPARATION OF SUBMITTAL PACKAGES.
<br />21.CONDUCTORS SHALL HAVE UNDERWRITER'S LABORATORIES, INC.(UL) LISTED, 600 VOLT INSULATION OF TYPE SPECIFIED BELOW OR ELSEWHERE IN THE SPECIFICATIONS. CONDUCTORS SHALL BE
<br />COPPER AND LISTED FOR 90 DEGREE APPLICATIONS.
<br />1. BRANCH CIRCUITS - LIGHTING AND POWER.
<br />a. #10 AWG AND SMALLER, SOLID WIRE TYPE THW OR THHN/THWN-2, THHW(THHN FOR DRY LOCATION ONLY).
<br />b. #8 AWG TO #2 AWG, STRANDED TYPE THW OR THHN/THHW.
<br />c. #1 AWG AND LARGER, STRANDED TYPE XHHW-2.
<br />2. FEEDERS : TYPE THW OR THHN/THWN-2, OR XHHW-2.
<br />22.PROVIDE GREEN INSULATED GROUNDING CONDUCTOR IN EACH RACEWAY INCLUDING CONDUITS, PLUG STRIPS, WIREMOLD. SIZE OF GROUNDING SHALL BE IN ACCORDANCE WITH NATIONAL ELECTRIC
<br />CODE ARTICLE 250.
<br />23.WIRING METHOD SHALL BE EMT ABOVE GROUND AND MOUNTED IN CONCEALED SPACES AND SCHEDULE-40 PVC FOR UNDERGROUND INSTALLATION. USE RIGID WHEN ENCASED IN CONCRETE OR
<br />SUSCEPTIBLE TO DAMAGE.
<br />24.UNLESS OTHERWISE INDICATED, SHARING OF NEUTRAL/GROUNDED CONDUCTORS AMONG SINGLE PHASE BRANCH CIRCUITS OF DIFFERENT PHASES INSTALLED IN THE SAME RACEWAY IS NOT PERMITTED.
<br />PROVIDE DEDICATED NEUTRAL/GROUNDED CONDUCTOR FOR EACH INDIVIDUAL BRANCH CIRCUIT.
<br />25.UNLESS OTHERWISE INDICATED, PROVIDE A SEPARATE SWITCHED AND UNSWITCHED PHASE CONDUCTOR TO ALL CONTROLLED RECEPTACLES REGARDLESS OF RECEPTACLE CONFIGURATION.
<br />26.BASIS OF ELECTRICAL DESIGN LIMITS VOLTAGE DROP TO 2% FOR FEEDERS AND 3% FOR BRANCH CIRCUITS. ANY CHANGES MADE IN THE FIELD SHALL LIMIT VOLTAGE DROP TO THESE PERCENTAGES.
<br />27.BRANCH CIRCUIT CONDUITS SHALL BE CONCEALED IN WALL OR CEILING SPACES. EXPOSED CONDUITS ARE NOT ALLOWED WHERE CONCEALED METHODS ARE AVAILABLE.
<br />28.CONTRACTOR SHALL PROVIDE CONDUCTORS AND CONDUITS REQUIRED FOR ALL BRANCH CIRCUITS AND FEEDERS. FOR CIRCUIT SIZES NOT SHOWN, REFER TO PANEL SCHEDULES FOR CONDUCTOR AND
<br />CONDUIT SIZES.
<br />29.THE CONTRACTOR SHALL COORDINATE THE WORK WITH OTHER TRADES. ANY COSTS TO INSTALL WORK TO ACCOMPLISH SAID COORDINATION, WHICH DIFFERS FROM THE WORK AS SHOWN ON THE
<br />CONTRACT DOCUMENTS, SHALL BE INCURRED BY THE CONTRACTOR. ANY DISCREPANCIES, AMBIGUITIES OR CONFLICTS SHALL BE BROUGHT TO THE ATTENTION OF THE OWNER'S REPRESENTATIVE
<br />DURING BID TIME FOR CLARIFICATION. ANY SUCH CONFLICTS NOT CLARIFIED PRIOR TO BID SHALL BE SUBJECT TO THE INTERRUPTION OF THE OWNER'S REPRESENTATIVE AT NO ADDITIONAL COST TO THE
<br />OWNER.
<br />30.ALL 125 AND 250-VOLT, 15- AND 20-AMPERE NONLOCKING TYPE RECEPTACLES SHALL BE LISTED TAMPER RESISTANT RECEPTACLES IN AREAS SPECIFIED IN NEC 406.12.
<br />31.ALL 125-VOLT THROUGH 250-VOLT RECEPTACLES SUPPLIED BY SINGLE-PHASE BRANCH CIRCUITS RATED 150 VOLTS OR LESS TO GROUND, 50 AMPERES OR LESS, AND ALL RECEPTACLES SUPPLIED BY
<br />THREE-PHASE BRANCH CIRCUITS RATED 150 VOLTS OR LESS TO GROUND, 100 AMPERES OR LESS, INSTALLED IN THE LOCATIONS SPECIFIED BELOW SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER
<br />PROTECTION FOR PERSONNEL AND ANY OTHER AREAS SPECIFIED IN NEC 210.8
<br />a.OUTDOORS
<br />APPLICABLE CODES
<br />ABBREVIATIONSGENERAL NOTES
<br />1.2022 BUILDING STANDARDS ADMINISTRATIVE CODE, PART 1, TITLE 24 C.C.R.
<br />2.2022 CALIFORNIA BUILDING CODE (CBC),PART 2, TITLE 24 C.C.R. (IBC WITH AMENDMENTS)
<br />3.2022 CALIFORNIA ELECTRICAL CODE (CEC), PART 3, TITLE 24 C.C.R. (NEC WITH AMENDMENTS)
<br />4.2022 CALIFORNIA MECHANICAL CODE (CMC), PART 4, TITLE 24 C.C.R. (UMC WITH AMENDMENTS)
<br />5.2022 CALIFORNIA PLUMBING CODE (CPC), PART 5, TITLE 24 C.C.R. (UPC WITH AMENDMENTS)
<br />6.2022 CALIFORNIA FIRE CODE, PART 9, TITLE 24 C.C.R. (IFC WITH AMENDMENTS)
<br />7.2022 CALIFORNIA REFERENCED STANDARDS, PART 12, TITLE 24 C.C.R.
<br />8.TITLE 19 C.C.R., PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS.
<br />9.2022 CALIFORNIA ENERGY CODE (PART 6, TITLE 24 C.C.R.)
<br />10.2022 CALIFORNIA GREEN BUILDING STANDARDS CODE (CGBSG), PART 11, TITLE 24 C.C.R.
<br />+96" OR 7'-6" AFF
<br />MOUNTING HEIGHT FROM FINISHED FLOOR TO BOTTOM LINE OF OUTLET OR EQUIPMENT. FOR
<br />LIGHT FIXTURES, IT IS TO BOTTOM OF FIXTURE.
<br />MAIN SWITCHBOARD, POWER OR LIGHT, FLOOR STANDING ENCLOSURE, (SEE SINGLE LINE
<br />DIAGRAM AND LOAD SUMMARY)
<br />BRANCH PANELBOARD, WALL MOUNTED, SEE PLANS AND SCHEDULE. (RECESSED MOUNTED)
<br />BRANCH PANELBOARD, WALL MOUNTED, SEE PLANS AND SCHEDULE. (SURFACE MOUNTED)
<br />CONDUIT STUBBED AND CAPPED, SIZE AND QUANTITIES PER PLANS.
<br />CONDUIT CONCEALED IN OR UNDER FLOOR, 3/4" UON, COORDINATE WITH G.C.: OR, BURIAL
<br />CONDUIT UNDERGROUND. REFER TO PLANS, DETAILS AND SPECIFICATIONS.
<br />SPECIALTY OUTLET. VERIFY NEMA CONFIGURATION AS NOTED ON PLANS.L5-30R
<br />HEAVY DUTY SAFETY SWITCH H.P. AND 600 VOLTS RATED. "F" INDICATES FUSE TYPE. FUSES
<br />PER APPROVED EQUIPMENT MANUFACTURERS SHOP DRAWINGS. SUBSCRIPT INDICATES
<br />SWITCH AMPERE RATING. # OF POLES TO MATCH SUPPLY CIRCUIT.
<br />MAGNETIC MOTOR STARTER H.P. RATED (NUMBER INDICATES NEMA SIZE)#2
<br />OR
<br />200-Y CONDUIT WIRING DESCRIPTION PER FEEDER SCHEDULE ON OTHER PLAN
<br />ELECTRICAL UTILITY PRIMARY
<br />ELECTRICAL UTILITY SECONDARY
<br />CONCRETE ELECTRICAL PULL BOX WITH LID APPROPRIATE FOR INSTALLATION LOCATION. LID
<br />SHALL BE LABELED "ELECTRICAL" OR "COMM" ACCORDING TO USE.
<br />EQUIPMENT
<br />ID. No.
<br />SHEET No.
<br />DETAIL No.
<br />EQUIPMENT REFERENCE
<br />DETAIL REFERENCE
<br />ABOVE CEILING, CONCEALED, JUNCTION BOX, WITH COVER, PER NATIONAL ELECTRICAL CODE
<br />(NEC) TABLE 314.16(A)/(B), 4" SQUARE DEEP, WITH PLASTER RING.
<br />RECESSED WALL MOUNTED JUNCTION BOX, WITH COVER, PER NATIONAL ELECTRICAL CODE
<br />(NEC) TABLE 314.16(A)/(B), 4" SQUARE DEEP, WITH PLASTER RING.
<br />DUPLEX RECEPTACLE OUTLET, CONVENIENCE. (20 AMPS, 125 VOLTS, GFCI TYPE) WITH
<br />MOUNTING HEIGHT HORIZONTALLY ABOVE COUNTER TOP PER ARCHITECTURAL PLANS OR
<br />APPROVAL.
<br />DOUBLE DUPLEX RECEPTACLE OUTLET, CONVENIENCE. (20 AMPS, 125 VOLTS) MOUNTED +15"
<br />A.F.F. TO BOTTOM OF DEVICE U.O.N.
<br />DUPLEX RECEPTACLE OUTLET, CONVENIENCE. (20 AMPS, 125 VOLTS, GFCI TYPE) MOUNTED +15"
<br />A.F.F. TO BOTTOM OF DEVICE U.O.N.
<br />DUPLEX RECEPTACLE OUTLET, CONVENIENCE. (20 AMPS, 125 VOLTS) MOUNTED +15" A.F.F. TO
<br />BOTTOM OF DEVICE U.O.N.
<br />WEATHERPROOF DUPLEX RECEPTACLE OUTLET, CONVENIENCE. (20 AMPS, 125 VOLTS)
<br />MOUNTED +15" A.F.F. TO BOTTOM OF DEVICE U.O.N.
<br />MOLDED CASE CIRCUIT BREAKER
<br />SWITCH AND FUSE ASSEMBLY
<br />GROUNDING CONNECTION AT SWITCHGEAR/DISTRIBUTION BOARD WITH NEUTRAL BONDING.
<br />UTILITY COMPANY PULL SECTION LUGS
<br />G
<br />N
<br />GROUNDING CONNECTION TO MAIN BUILDING GROUND SYSTEM U.O.N.
<br />EXISTING (DASH INDICATES) ELECTRICAL EQUIPMENT
<br />TELEPHONE BACKBOARD 2'X4'X3/4" PLYWOOD. PROVIDE 2" CONDUIT TO TELEPHONE POC.
<br />HOMERUN TO CIRCUITS #1 AND #3 IN PANEL "A". REFER TO PANEL SCHEDULE
<br />FOR CONDUIT AND CONDUCTOR SIZES. QTY AS REQUIRED.
<br />A-1,3
<br />SMOKE FIRE DAMPER
<br />IN-LINE UTILITY COMPANY METER
<br />UTILITY METER WITH CIRCUIT TRANSFORMERS (CT'S) METER
<br />WP
<br />GROUND WELL
<br />A AMPERE
<br />AF AMPERE FRAME RATING (CIRCUIT BREAKER)
<br />AFC AVAILABLE FAULT CURRENT
<br />AFF ABOVE FINISHED FLOOR
<br />AFG ABOVE FINISHED GRADE
<br />AFU AMPERE FUSE RATING (FUSE)
<br />AIC AMPERE INTERRUPTING CAPACITY
<br />AS AMPERE SWITCH RATING (FUSE)
<br />AT AMPERE TRIP RATING (CIRCUIT BREAKER)
<br />AWG AMERICAN WIRE GAUGE
<br />BCG BARE COPPER GROUND
<br />BKBD BACKBOARD
<br />BLDG BUILDING
<br />BKR BREAKER
<br />C CONDUIT
<br />CB CIRCUIT BREAKER
<br />CKT CIRCUIT
<br />CFSD COMBINATION FIRE SMOKE DAMPER
<br />CO CONDUIT ONLY
<br />CT CURRENT TRANSFORMER
<br />CU COPPER
<br />CL CENTERLINE
<br />DISC DISCONNECT
<br />DSBN DISTRIBUTION SECTION
<br />DN DOWN
<br />DWG DRAWING
<br />EA EACH
<br />EC ELECTRICAL CONTRACTOR
<br />EGC EQUIPMENT GROUNDING CONDUCTOR
<br />EM EMERGENCY
<br />EMT ELECTRICAL METALLIC TUBING
<br />EPO EMERGENCY POWER OFF
<br />EXIST, (E)EXISTING
<br />EXO EXTERNAL OPERABLE DISCONNECT
<br />F FUSE
<br />FA FIRE ALARM
<br />FACP FIRE ALARM CONTROL PANEL
<br />FF FINISHED FLOOR
<br />FG FINISHED GRADE
<br />FLA FULL LOAD CURRENT
<br />GEC GROUNDING ELECTRODE CONDUCTOR
<br />GEN GENERATOR
<br />GFCI GROUND FAULT CIRCUIT INTERRUPTER
<br />GFP GROUND FAULT PROTECTION
<br />GND GROUND
<br />GRC GALVANIZED RIGID CONDUIT
<br />HD HEAVY DUTY
<br />HOA HAND-OFF-AUTOMATIC
<br />HP HORSE POWER
<br />HV HIGH VOLTAGE
<br />IDF INTERMEDIATE DISTRIBUTION FRAME
<br />IG ISOLATED/INSULATED GROUND
<br />ISC SHORT CIRCUIT CURRENT AVAILABLE IN RMS
<br />SYMMETRICAL AMPERES
<br />J-BOX JUNCTION BOX
<br />KCMIL THOUSAND CIRCULAR MILS
<br />KW KILOWATT
<br />KV KILO VOLT
<br />KVA KILO VOLT-AMPERE
<br />LDC LOCAL DISTRIBUTION CABINET
<br />LDF LOCAL DISTRIBUTION FRAME
<br />LCL LONG CONTINUOUS LOAD
<br />LFMC LIQUID TIGHT FLEXIBLE METAL CONDUIT
<br />LSIG LONG, SHORT, INSTANTANEOUS, GROUND
<br />LTG LIGHTING
<br />LV LOW VOLTAGE
<br />MFR MANUFACTURER
<br />MAX MAXIMUM
<br />MCC MOTOR CONTROL CENTER
<br />MIN MINIMUM
<br />MH MANHOLE / METAL HALIDE
<br />MLO MAIN LUGS ONLY
<br />M/M METER AND MAIN SECTION
<br />MV MEDIUM VOLTAGE
<br />NC NORMALLY CLOSED
<br />NEC NATIONAL ELECTRICAL CODE
<br />NEMA NATIONAL ELECTRICAL MANUFACTURER'S
<br />ASSOCIATION
<br />NEW (N)NEW, TO BE FURNISHED AND INSTALLED BY
<br />CONTRACTOR
<br />NF NON-FUSED
<br />NIC NOT IN CONTRACT
<br />N/L NIGHT LIGHT
<br />NO NUMBER, NORMALLY OPEN
<br />NTS NOT TO SCALE
<br />OC ON CENTER
<br />OD OUTSIDE DIAMETER
<br />P POLE
<br />PB PULL BOX
<br />PF POWER FACTOR
<br />PH PHASE
<br />PNL PANEL
<br />POC POINT OF CONNECTION
<br />PP POWER POLE
<br />PWR POWER
<br />PVC POLYVINYL CHLORIDE
<br />QUAD QUADRUPLEX
<br />QTY QUANTITY
<br />RGS RIGID GALVANIZED STEEL
<br />RMC RIGID METALLIC CONDUIT
<br />RM ROOM
<br />RNC RIGID NONMETALLIC CONDUIT
<br />SHT SHEET
<br />SN SOLID NEUTRAL
<br />SPEC SPECIFICATIONS
<br />SW SWITCH
<br />SWBD SWITCHBOARD
<br />TC TIME CLOCK
<br />TEL TELEPHONE
<br />TERM TERMINAL
<br />TP TEMPORARY POLE
<br />TYP TYPICAL
<br />UGPS UNDERGROUND PULL SECTION
<br />UL UNDERWRITERS LABORATORY
<br />UPS UNINTERRUPTIBLE POWER SUPPLY
<br />UON UNLESS OTHERWISE NOTED
<br />V VOLT, VOLTAGE
<br />VA VOLT-AMPERE
<br />VD VOLTAGE DROP
<br />VFC VARIABLE FREQUENCY CONTROLLER
<br />VFD VARIABLE FREQUENCY DRIVE
<br />W WATT
<br />WH WATT-HOUR
<br />WP WEATHERPROOF
<br />WW WIREWAY
<br />XP EXPLOSION PROOF
<br />Z IMPEDANCE
<br />4W FOUR-WIRE
<br />3W THREE-WIRE
<br />5S JUNCTION BOX
<br />(4 11/16" SQUARED X2 1/8" DEEP)
<br />Ø DIAMETER, PHASE
<br />#NUMBER
<br />°C DEGREE CELSIUS
<br />(E)EXISTING DEVICE TO REMAIN
<br />(R)REMOVE EXISTING DEVICE AND ASSOCIATED
<br />CONDUIT AND WIRE
<br />(RL)REMOVE EXISTING DEVICE AND RELOCATE AS
<br />SHOWN ON PLAN
<br />(NL)NEW LOCATION OF RELOCATED DEVICE
<br />SUBSCRIPT "A-1" REFERS TO PANEL DESIGNATION WITH CIRCUIT NUMBER. TYPICAL OF ALL
<br />RECEPTACLE OUTLETS.A-1
<br />100AS
<br />NUMBER DATE INITIALS DESCRIPTION
<br />PREPARED UNDER THE
<br />SUPERVISION OF:
<br />CITY OF SANTA ANA
<br />FILE NO.:
<br />INSTALLEDAPPROVED
<br />CONSTRUCTION COMPLETED:
<br />BENCHMARK NO.: SA-253-70
<br />RECOMMENDED FOR
<br />CONSTRUCTION:
<br />REFERENCES
<br />PUBLIC WORKS AGENCY
<br />RCE NO.:
<br />ELEV.: 176.00 (2010)
<br />REVISIONS
<br />SHEET OF
<br />BENCHMARK DESCRIPTION:
<br />OCS BM SA-253-70
<br />FD 3 3/4" OCS ALUMINUM BENCH MARK DISK STAMPED "SA-253-70", SET IN NW'LY CORNER OF A 3.5FT X 16FT
<br />CONCRETE CATCH BASIN. MONUMENT IS LOCATED IN THE NE'LY CORNER OF THE INTERSECTION OF GRAND AVE
<br />AND SANTA CLARA AVE, 87FT N'LY OF THE CENTERLINE OF SANTA CLARA AVE AND 39FT E'LY OF THE CENTERLINE
<br />OF GRAND AVE. MONUMENT IS SET LEVEL WITH THE SIDEWALK
<br />PORTOLA PARK
<br />SPLASH PADREVIEWED FOR
<br />CONSTRUCTABLITY:
<br />PRINCIPAL CIVIL ENGINEER
<br />DESIGNED:
<br />PRINCIPAL CIVIL ENGINEER RCE NO.:
<br />LM MR BK
<br />ELECTRICAL ENGINEER
<br />DRAWN:CHECKED:
<br />PS-
<br />2
<br />5
<br />-
<br />2
<br />4
<br />0
<br />1
<br />BRADEN KEMPTON
<br />1700 E. SANTA CLARA AVENUE, SANTA ANA, CA 92705
<br />811
<br />UNDERGROUND SERVICE ALERT. DIAL 811
<br />LOCATION OF UNDERGROUND UTILITIES BY CONTRACTING
<br />BEFORE EXCAVATING, THE CONTRACTOR SHALL VERIFY THE
<br />DAMAGE SUCH FACILITIES OR INTERFERE WITH THEIR SERVICE.
<br />UNDERGROUND FACILITIES PRIOR TO DOING WORK THAT MAY
<br />STEPS TO ASCERTAIN THE EXACT LOCATION OF ALL
<br />THE SPECIAL PROVISIONS. THE CONTRACTOR SHALL TAKE
<br />DIFFERENT FROM THAT WHICH IS SHOWN ON THE PLANS OR IN
<br />UNDERGROUND FACILITIES NOT KNOWN OR IN A LOCATION
<br />ATTENTION IS DIRECTED TO THE POSSIBLE EXISTENCE OF
<br />UNDERGROUND SERVICE ALERT OF SOUTHERN CALIFORNIA
<br />\\
<br />E
<br />G
<br />N
<br />Y
<br />T
<br />E
<br />D
<br />R
<br />I
<br />V
<br />E
<br />\
<br />D
<br />W
<br />E
<br />\
<br />_
<br />P
<br />R
<br />O
<br />J
<br />E
<br />C
<br />T
<br />\
<br />2
<br />0
<br />2
<br />4
<br />\
<br />2
<br />4
<br />-
<br />3
<br />0
<br />5
<br />
<br />P
<br />O
<br />R
<br />T
<br />O
<br />L
<br />A
<br />
<br />P
<br />A
<br />R
<br />K
<br />\
<br />_
<br />C
<br />A
<br />D
<br />\
<br />2
<br />4
<br />-
<br />3
<br />0
<br />5
<br />
<br />E
<br />-
<br />F
<br />R
<br />O
<br />N
<br />T
<br /> -
<br />
<br />20
<br />2
<br />5
<br />-
<br />1
<br />1
<br />-
<br />2
<br />4
<br /> -
<br />
<br />LU
<br />I
<br />S
<br />
<br />M
<br />U
<br />N
<br />G
<br />U
<br />I
<br />A
<br />24-305
<br />DESIGN WEST ENGINEERING
<br />MECHANICAL ELECTRICAL ENERGY CONSULTANTS
<br />San Bernardino, CA 92408
<br />412 E. Vanderbilt Way
<br />Phone: 909.890.3700
<br />Fax: 909.890.3770
<br />Email: cadd@designwesteng.com
<br />PO
<br />R
<br />T
<br />O
<br />L
<br />A
<br />
<br />P
<br />A
<br />R
<br />K
<br />
<br />S
<br />P
<br />L
<br />A
<br />S
<br />H
<br />
<br />P
<br />A
<br />D
<br />
<br />PR
<br />O
<br />J
<br />E
<br />C
<br />T
<br />
<br />N
<br />O
<br />.
<br />
<br />2
<br />5
<br />-
<br />2
<br />4
<br />0
<br />1
<br />E-0.1
<br />SHEET INDEX
<br />Sheet Number Sheet Title
<br />E-0.1 ELECTRICAL LEGEND & NOTES
<br />E-0.3 SINGLE LINE DIAGRAM
<br />E-1.1 ELECTRICAL SITE PLAN
<br />E-2.1 ELECTRICAL DETAILS
<br />E-0.1ELECTRICAL LEGEND & NOTES
<br />24 57
<br />SIGNED:11/24/2025
<br />24 57
|