PART 1 GENERAL <br />1.01 SCOPE OF WORK <br />A.WORK COVERED BY THIS SECTION CONSISTS OF FURNISHING ALL LABOR, EQUIPMENT, SUPPLIES, AND MATERIALS, <br />UNLESS OTHERWISE SPECIFIED, AND IN PERFORMING ALL OPERATIONS NECESSARY FOR THE INSTALLATION OF A <br />COMPLETE AND OPERABLE ELECTRICAL SYSTEM AS REQUIRED BY THESE SPECIFICATIONS AND AS INDICATED ON THE <br />DRAWINGS. <br />B.THE CONTRACTOR SHALL EXAMINE ALL DRAWINGS AND SPECIFICATIONS IN A MANNER TO BE FULLY COGNIZANT OF <br />ALL WORK REQUIRED UNDER THIS SECTION. <br />C.THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL REQUIRED PERMITS UNLESS OTHERWISE ARRANGED AND <br />SCHEDULE ALL REQUIRED INSPECTIONS FOR THE EXECUTION OF THE WORK UNDER THIS CONTRACT. <br />1.02 GENERAL REQUIREMENTS <br />A.WORK DONE UNDER THIS SECTION SHALL COMPLY WITH THE LATEST EDITION OF THE CALIFORNIA ELECTRICAL CODE, <br />NEC (NATIONAL ELECTRICAL CODE), THE STATE OF CALIFORNIA TITLE 24, THE STATE BUILDING STANDARDS, (OSHA) <br />OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION, AND TO ANY APPLICABLE LOCAL JURISDICTIONAL <br />REQUIREMENTS. IN CASE OF CONFLICT BETWEEN REQUIREMENT, THE MOST RESTRICTIVE SHALL APPLY. <br />1.03 ELECTRICAL CONTRACTOR'S RESPONSIBILITY <br />A.IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO OBTAIN A COMPLETE SET OF DRAWINGS AND SPECIFICATIONS. <br />CONTRACTOR SHALL CHECK THE DRAWINGS OF THE OTHER TRADES AND SHALL CAREFULLY READ THE ENTIRE <br />SPECIFICATIONS AND DETERMINE HIS RESPONSIBILITIES. <br />B.BEFORE SUBMITTING THE BID, THE ELECTRICAL CONTRACTOR SHALL VISIT THE JOB SITE AND FULLY ACQUAINT <br />HIMSELF WITH EXISTING CONDITIONS. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO INSTALL THE EQUIPMENT <br />AND ASSOCIATED WIRING IN SUCH A MANNER AS TO CONFORM WITH THE EXISTING STRUCTURE OF THE BUILDING, <br />AVOID OBSTRUCTIONS, AND MEET APPLICABLE CODE REQUIREMENTS. <br />C.THE INTENT OF THESE DRAWINGS IS TO DESCRIBE A COMPLETE AND OPERABLE SYSTEM. WHERE EXISTING <br />CONDITIONS DIFFER FROM DRAWINGS, ADJUSTMENT SHALL BE MADE AND ALLOWANCES INCLUDED FOR ALL <br />NECESSARY EQUIPMENT TO COMPLETE ALL PARTS OF THE DRAWINGS AND SPECIFICATIONS. BRING ANY QUESTIONS <br />TO THE ARCHITECT OR ENGINEER'S ATTENTION PRIOR TO BIDDING. <br />D.WHEREVER A DISCREPANCY IN QUANTITY OR SIZE OF CONDUIT, WIRE, EQUIPMENT, DEVICES, CIRCUIT BREAKERS, <br />ETC., ARISES ON THE DRAWING AND/OR SPECIFICATION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING <br />AND INSTALLING ALL MATERIAL AND SERVICES REQUIRED BY THE STRICTEST CONDITION NOTED ON DRAWINGS <br />AND/OR IN SPECIFICATIONS TO ENSURE COMPLETE AND OPERABLE SYSTEMS AS REQUIRED BY THE OWNER AND <br />ENGINEER. <br />1.04 WORK NOT INCLUDED <br />A.CERTAIN LABOR, MATERIALS, OR EQUIPMENT MAY BE FURNISHED UNDER OTHER CONTRACTS BY THE OWNER. WHEN <br />SUCH IS THE CASE, THE EXTENT, SOURCE, AND DESCRIPTION OF THESE ITEMS WILL BE INDICATED ON THE DRAWINGS <br />OR DESCRIBED IN THE SPECIFICATIONS. UNLESS OTHERWISE NOTED, ALL LABOR, MATERIALS AND EQUIPMENT FOR <br />THE COMPLETE INSTALLATION OF THE ELECTRICAL WORK SHALL BE PROVIDED UNDER THIS SECTION OF THESE <br />SPECIFICATIONS. <br />1.05 SPECIAL REQUIREMENTS <br />A.THE DRAWINGS INDICATE GENERAL ARRANGEMENT OF CIRCUITS, OUTLETS, LOCATIONS OF MOTOR CONTROLLERS <br />WITH DISCONNECTS, PANELBOARDS, CONDUIT ROUTING, AND OTHER WORK. INFORMATION SHOWN ON THE <br />DRAWINGS IS ESSENTIALLY DIAGRAMMATIC; HOWEVER, RECIRCUITING OR RELOCATING ELECTRICAL EQUIPMENT WILL <br />NOT BE PERMITTED WITHOUT SPECIFIC WRITTEN APPROVAL OF THE ENGINEER. <br />1.06 SUBMITTALS <br />A.AFTER AWARD OF THE CONTRACT AND BEFORE ANY MATERIALS ARE DELIVERED TO THE JOB SITE, A COMPLETE LIST <br />OF ALL MATERIALS PROPOSED TO BE FURNISHED AND INSTALLED UNDER THIS SECTION MUST BE PROVIDED. <br />B.SUBMIT TO THE ENGINEER FOR APPROVAL ONE PRINT AND ONE REPRODUCIBLE OF ALL LIGHTING FIXTURES, <br />SWITCHGEAR, PANELBOARDS, MOTOR CONTROL CENTERS, TRANSFORMERS, AND MOTOR STARTERS. SHOP <br />DRAWINGS SHALL INCLUDE MANUFACTURER'S PRINTED INFORMATION FOR EACH OF THESE ITEMS IDENTIFIED ON THE <br />DRAWINGS. THE INFORMATION SHALL INCLUDE, AS MINIMUM, OVERALL DIMENSIONS, WEIGHT, PHASE, VOLTAGE <br />RATINGS, WIRING DIAGRAMS, AND NAMEPLATE DATA. <br />1.07 STANDARDS AND MATERIALS <br />A.ALL MATERIALS SHALL CONFORM WITH THE CURRENT APPLICABLE INDUSTRY STANDARDS, NEMA (NATIONAL <br />ELECTRICAL MANUFACTURER'S ASSOCIATION), ANSI (AMERICAN NATIONAL STANDARDS INSTITUTE), IPCEA (INSULATED <br />POWER CABLE ENGINEERS ASSOCIATION), IEEE (INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS), NATIONAL <br />ELECTRICAL SAFETY CODE. <br />B.UNLESS OTHERWISE INDICATED, ALL MATERIALS SHALL BE UNDERWRITERS LABORATORIES LISTED AND LABELED, OR <br />CERTIFIED BY A NATIONALLY RECOGNIZED TESTING LABORATORY. <br />C.WORKMANSHIP AND NEAT APPEARANCE SHALL BE AS IMPORTANT AS THE ELECTRICAL MECHANICAL EFFICIENCY. <br />DEFECTIVE AND DAMAGED MATERIALS SHALL BE REPLACED OR REPAIRED PRIOR TO FINAL APPROVAL AND <br />ACCEPTANCE. THE DRAWINGS AND SPECIFICATIONS TAKE PRECEDENCE WHEN THEY ARE MORE STRINGENT THAN <br />CODES, STATUTES, OR ORDINANCES IN EFFECT. APPLICABLE CODES, STANDARDS, ORDINANCES, AND STATUTES TAKE <br />PRECEDENCE WHEN THEY ARE MORE STRINGENT OR CONFLICT WITH THE DRAWINGS OR SPECIFICATIONS. <br />1.08 DELIVERY AND STORAGE OF MATERIALS <br />A.THE CONTRACTOR SHALL INVESTIGATE EACH SPACE IN THE BUILDING THROUGH WHICH EQUIPMENT MUST PASS TO <br />REACH ITS FINAL LOCATIONS. IF NECESSARY, THE MANUFACTURER SHALL BE REQUIRED TO SHIP HIS MATERIAL IN <br />SECTIONS, SIZED TO PERMIT PASSING THROUGH SUCH RESTRICTED AREAS IN THE BUILDING. <br />B.THE CONTRACTOR SHALL RETAIN IN HIS POSSESSION AND SHALL BE RESPONSIBLE FOR ALL PORTABLE AND <br />DETACHABLE PARTS OF PORTIONS OF INSTALLATIONS SUCH AS FUSES, KEY LOCKS, ADAPTERS, BLOCKING CLIPS, AND <br />INSERTS UNTIL FINAL COMPLETION OF WORK. THESE PARTS SHALL BE DELIVERED TO THE OWNER UPON COMPLETION <br />OF THE WORK. <br />PART 2 PRODUCTS <br />2.01 EQUIPMENT AND MATERIALS <br />A.ALL MATERIALS FURNISHED AND INSTALLED UNDER THIS CONTRACT SHALL BE NEW, FREE FROM DEFECTS, AND <br />SHALL BE GUARANTEED FOR A PERIOD OF ONE (1) YEAR FROM DATE OF ACCEPTANCE OF THE WORK. SHOULD ANY <br />TROUBLE DEVELOP DURING THEIR PERIOD DUE TO DEFECTIVE MATERIALS OR FAULTY WORKMANSHIP, THE <br />CONTRACTOR SHALL FURNISH ALL NECESSARY MATERIALS AND LABOR TO CORRECT THE TROUBLE WITHOUT ANY <br />COST TO THE OWNER. ANY DEFECTIVE MATERIAL OR INFERIOR WORKMANSHIP NOTED AT THE TIME OF INSTALLATION <br />SHALL BE CORRECTED IMMEDIATELY TO THE SATISFACTION OF THE OWNER. <br />B.ALL MAJOR EQUIPMENT COMPONENTS SHALL HAVE THE MANUFACTURER'S NAME, ADDRESS, MODEL NUMBER, AND <br />SERIAL NUMBER PERMANENTLY ATTACHED IN A CONSPICUOUS MANNER. <br />2.02 CONDUIT <br />A.PROVIDE RACEWAYS AS INDICATED ON THE DRAWINGS AND AS HEREIN SPECIFIED. CONDUITS SHALL BE RIGID STEEL <br />"GRC" (THICK WALL) GALVANIZED; ELECTRICAL METALLIC TUBING "EMT" (THIN WALL); FLEXIBLE STEEL, GALVANIZED; <br />LIQUID-TIGHT, FLEXIBLE STEEL CONDUIT WITH GROUND BOND; ALUMINUM CONDUIT; OR SCHEDULE 40 PVC. <br />B.ALL EMPTY CONDUITS (CO) SHALL BE SCHEDULE 40 PVC UNLESS OTHERWISE INDICATED ON THE DRAWING. <br />C.WHERE CONDUIT CROSSES AN EXPANSION JOINT, PROVIDE APPROVED FITTINGS WHICH ALLOW DEFLECTIONS <br />EQUIVALENT TO TWICE THE MOVEMENT ALLOWED BY THE DESIGN. <br />2.03 CONDUCTORS <br />A.PROVIDE A COMPLETE SYSTEM OF CONDUCTORS IN RACEWAY SYSTEMS AS SHOWN ON THE DRAWINGS AND THEN <br />HEREIN SPECIFIED. <br />B.LIGHTING AND POWER CONDUCTORS SHALL BE COPPER, 600 VOLT, TYPE THWN/THHN, NO. 12 MINIMUM UNLESS <br />OTHERWISE NOTED. <br />C.CONTROL CONDUCTORS SHALL BE 600V, TYPE THWN/THHN, NO.14 MINIMUM SIZE UNLESS OTHERWISE NOTED. <br />2.04 FITTINGS <br />A.CONNECTOR, COUPLING, LOCKNUT, BUSHINGS AND CAPS USED WITH RIGID CONDUIT SHALL BE STEEL, THREADED <br />AND GALVANIZED. BUSHINGS SHALL BE INSULATED. <br />B.EMT FITTINGS, CONNECTORS AND COUPLINGS SHALL BE STEEL, ZINC, OR CADMIUM PLATED, COMPRESSION TYPE, <br />WITH INSULATED THROAT. <br />C.FLEXIBLE STEEL CONDUIT CONNECTORS SHALL BE TWIST-IN-TYPE WITH INSULATED THROAT. THE FINISH SHALL BE <br />ZINC OR CADMIUM PLATING. <br />D.EMT CONDUIT FITTINGS SHALL BE THE COMPRESSION TYPE; SET SCREW FITTINGS SHALL NOT BE USED. <br />2.05 JUNCTION AND PULL BOXES <br />A.FOR INTERIOR DRY LOCATIONS, BOXES SHALL BE GALVANIZED ONE-PIECE DRAWN STEEL, KNOCKOUT TYPE WITH <br />REMOVABLE, MACHINE SCREW SECURED COVERS. <br />B.ALL BOXES SHALL BE SIZED FOR THE NUMBER AND SIZES OF CONDUCTORS AND CONDUITS ENTERING THE BOX AND <br />EQUIPPED WITH PLASTER RINGS WHERE REQUIRED. <br />2.06 OUTLET BOXES <br />A.FOR FIXTURES, BOXES SHALL BE GALVANIZED, ONE-PIECE DRAWN STEEL, KNOCKOUT TYPE EQUIPPED WITH 3/8" <br />FIXTURE STUDS AND PLASTER RINGS WHERE REQUIRED. <br />B.FOR CONVENIENCE OUTLETS, WALL SWITCHES, OR OTHER DEVICES, OUTLET BOXES SHALL BE GALVANIZED <br />ONE-PIECE DRAWN STEEL, KNOCKOUT TYPE 4"X4"X1-1/2" MINIMUM. <br />C.FOR LOCATIONS WHERE STANDARD BOXES ARE NOT SUITABLE, SPECIAL BOXES SHALL BE DESIGNED TO FIT SPACE OR <br />MEET OTHER REQUIREMENTS AND SUBMITTED FOR APPROVAL. <br />2.07 SWITCHES <br />A.ALL DEVICES SHALL CONFORM TO NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION (NEMA) STANDARDS AND <br />SHALL BE UNDERWRITERS' LABORATORIES, INC., (UL) LISTED AND LABELED AND SHALL BE "SPECIFICATION GRADE," <br />MEETING THE REQUIREMENTS OF FEDERAL SPECIFICATION WS-896-E, FOR SWITCHES. <br />1.WALL SWITCHES SHALL BE SPECIFICATION COMMERCIAL GRADE (MINIMUM), FULLY ENCLOSED, QUIET-TYPE TUMBLER <br />SWITCHES RATED 20 AMPERES, 120/277-VOLT, BAKELITE OR COMPOSITION, BACK AND SIDE WIRED, BUMPER PAD, FULL <br />RATING FOR INDUCTIVE OR NON-INDUCTIVE LOADS AND INCANDESCENT OR FLUORESCENT LIGHTING LOADS. <br />2.SINGLE POLE SWITCHES: G.E. 59511, HUBBELL #1221, ARROW #1991 OR PASS & SEYMOUR 20AC1. <br />3.THREE-WAY QUIET SWITCHES: G.E. 59531, HUBBELL #1223, ARROW #1993 OR PASS& SEYMOUR 20AC3. <br />4.WALL SWITCH AND PILOT LIGHTS SHALL BE FLUSH MOUNTED COMBINATION WALL TYPE WITH SWITCH AND PILOT LIGHT <br />EQUIPPED WITH A 6-WATT, 125-VOLT CANDELABRA BASE LAMP. THE PILOT LIGHT SHALL HAVE A GREEN JEWEL WITH <br />BRASS RIM FLUSH MOUNTED IN THE WALL PLATE. <br />5.ALL SWITCHES SHALL BE OF THE SAME MANUFACTURE. <br />6.NORMAL SWITCH COLOR IS WHITE APPROVED BY ARCHITECT/OWNER. SWITCHES CONTROLLING CIRCUITS CONNECTED <br />TO EMERGENCY POWER SOURCE SHALL BE RED. <br />7.30 AMP MOTOR RATED SNAP SWITCHES SHALL BE LEVITON MS302-DS. PROVIDED IN NEMA 1 OR 3R ENCLOSURE AS <br />SHOWN ON DRAWING. <br />B.SENSOR SWITCH (MOTION SENSOR) <br />1.WALL SENSOR SWITCH SHALL BE WATT STOPPER DUAL TECHNOLOGY OCCUPANCY SENSOR LEVITON MODEL <br />#OSSMT-GD (FOR SINGLE POLE SWITCHING) & LEVITON MODEL #OSSMD-GD FOR (DUAL SWITCHING). <br />2.CEILING SENSOR SWITCH SHALL BE WATT STOPPER DUAL-TECHNOLOGY MODE. <br />3.PROVIDE 120/277V CEILING SENSOR POWER PACK INSTALLED IN J-BOX NEXT TO LIGHTING CIRCUIT. <br />2.08 RECEPTACLES <br />A.DUPLEX RECEPTACLES SHALL BE SPECIFICATION GRADE, 20 AMPS, 125 VOLTS, 3-WIRE, SIDE-WIRED WITH BINDING <br />SCREWS, PARALLEL SLOTS, U-GROUND, PLASTER EARS AND CAPTIVE MOUNTING SCREWS. BODY SHALL BE <br />PHENOLIC, PLASTIC, OR BAKELITE. RECEPTACLES SHALL BE HEAVY-DUTY, 3-BLADE CURRENT CARRYING CONTACT <br />AND DOUBLEWIDE FLAT BLADE GROUND CONTACTS. PROVIDE ARROW HART 5242-I HUBBELL 5242-I OR LEVITON <br />5242-I. <br />B.SINGLE RECEPTACLES SHALL BE SPECIFICATION GRADE, GROUNDING TYPE, SIDE-WIRED, WITH BINDING SCREWS, AND <br />SHALL HAVE STANDARD SIZE IVORY BAKELITE BASE. FOR CIRCUITS CONSISTING OF ONE SINGLE RECEPTACLE ONLY, <br />AMPERE RATING OF RECEPTACLE SHALL BE THE SAME AS CIRCUIT BREAKER OF FUSE. FOR RECEPTACLES RATED 15 <br />AMPS/125 VOLTS, PROVIDE NEMA 5-15R, ARROW-HART 5251-I. FOR RECEPTACLES RATED 20 AMPS / 125 VOLTS, <br />PROVIDE NEMA 5-20R, ARROW-HART 5721-I, OR EQUAL. <br />2.09 DEVICE PLATES <br />1.PROVIDE PLATES FOR ALL SWITCHES, RECEPTACLES, JUNCTION BOXES, TELEPHONE AND OTHER OUTLETS. <br />2.PROVIDE ENGRAVED OR ETCHED PLATES FOR ALL LOCK SWITCHES, PILOT SWITCHES, SWITCHES FROM WHICH <br />EQUIPMENT OR CIRCUIT CONTROLLED CANNOT BE READILY SEEN, THREE OR MORE SWITCHES UNDER A COMMON <br />PLATE AND FOR SWITCHES AS INDICATED. <br />3.STAINLESS STEEL PLATES SHALL BE AMERICAN IRON AND STEEL INSTITUTE (AISI) TYPE 302, WITH BEVELED EDGES, <br />0.040" THICK WITH SATIN SMOOTH FINISH. "SMOOTHIE," HUBBELL #97071 SERIES. <br />4.PLASTIC COVER PLATE SHALL BE HIGH IMPACT THERMOPLASTIC, HIGH STRENGTH, SCRATCH-RESISTANT, SMOOTH <br />AND SELF-EXTINGUISHING, HUBBELL "PI" SERIES OR PASS & SEYMOUR RP SERIES. <br />5.WHERE OUTLETS ARE INDICATED TO BE WEATHERPROOF, PROVIDE AN AISI TYPE 302 STAINLESS WITH DOUBLE HINGED <br />COVERS, PASS & SEYMOUR #WPD-8. <br />6.GALVANIZED STEEL PLATES SHALL BE SQUARE OR RECTANGULAR AND HOT DIPPED GALVANIZED OR SHERARDIZED, <br />BEVELED EDGES AND 0.040" THICK. GALVANIZED STEEL PLATES SHALL BE USED IN UTILITY AREA. <br />7.PROVIDE PLATES EQUIPPED WITH CLOSE FITTING OPENINGS FOR THE EXACT DEVICE TO BE USED. PROVIDE PLATES <br />FOR TELEPHONE OUTLETS EQUIPPED WITH BUSHED OPENINGS. <br />8.REFER TO SECTION 3.08 FOR LABELING OF PLATES. <br />9.COVER PLATES ON PRESSED STEEL OUTLET BOXES IN FURRED AREAS, ATTICS, ETC., OR EXPOSED IN MECHANICAL <br />EQUIPMENT ROOMS SHALL BE OF THE SAME MATERIAL AS THE OUTLET BOX. <br />10.COVER PLATES IN LOCATIONS CONCEALED FROM PUBLIC VIEW SHALL HAVE THE CIRCUIT NUMBERS AND SOURCE <br />FEED POINT HAND LABELED WITH MARKING BLACK PEN (PERMANENT MARKER). SEE SECTION 3.08 FOR LABELING. <br />11.PROVIDE PLASTIC COVER PLATES UNLESS NOTED OTHERWISE <br />2.10 PANELBOARDS <br />A.FURNISH AND INSTALL ALL BRANCH CIRCUIT PANELBOARDS AS HEREINAFTER SPECIFIED AND AS SHOWN ON THE <br />DRAWINGS. PANELBOARDS SHALL BE OF THE DEAD FRONT SAFETY TYPE EQUIPPED WITH THE THERMAL MAGNETIC <br />40°C CIRCUIT BREAKERS. <br />B.CIRCUIT BREAKERS SHALL BE RATED MINIMUM 10,000 AMPS RMS SYMMETRICAL INTERRUPTING CAPACITY AND SHALL <br />BE THE NUMBER OF POLES AND CURRENT CAPACITY AS INDICATED ON THE PANEL SCHEDULE. BRANCH CIRCUIT <br />PANELBOARDS SHALL BE SQUARE-D OR EATON/CUTLER HAMMER WITH LUGS UL LISTED FOR USE WITH 75°C WIRE. <br />C.DOOR SHALL HAVE A PLASTIC COVERED DIRECTORY FRAME WITH A TYPED IDENTIFICATION CARD OR ALL CIRCUIT <br />AND PANEL NUMBERS FOR BRANCH CIRCUIT PANELBOARDS. <br />D.PROVIDE NAMEPLATE FOR ALL PANELBOARDS, ENGRAVED WHITE LETTERS ON BLACK BACKGROUND INSTALL NAME <br />PLATES ON THE TRIM ABOVE DOOR. <br />E.ALL WIRING SHALL BE NEATLY ARRANGED AND LACED TOGETHER. <br />F.ALL CIRCUIT BREAKERS USED FOR HVAC LOADS SHALL BE RATED "HACR". <br />G.BUS BARS SHALL BE RECTANGULAR IN CROSS SECTION CONSTRUCTED OF COPPER. NEUTRAL AND GROUND BUSES <br />SHALL BE FULL SIZE. <br />2.11 INTERIOR LIGHTING FIXTURES <br />A.FURNISH, INSTALL AND WIRE LIGHTING FIXTURES SCHEDULED OR INDICATED BY TYPE DESIGNATION ON THE <br />DRAWINGS. IF TYPE DESIGNATION IS OMITTED, FIXTURES SHALL BE OF THE SAME TYPE AS SHOWN FOR ROOMS OF <br />SIMILAR USAGE. VERIFY BEFORE PURCHASE AND INSTALLATION. NO ALTERNATIVE FIXTURES WILL BE ACCEPTED. <br />B.LOCATIONS OF FIXTURES ON ELECTRICAL DRAWINGS ARE DIAGRAMMATIC. VERIFY LOCATION AND SPACING WITH <br />ARCHITECTURAL REFLECTED CEILING PLANS AND OTHER REFERENCE DATA BEFORE PURCHASING. COORDINATE <br />SPACE CONDITIONS, INCLUDING HEADROOM CLEARANCES AND INTERFERENCES WITH CEILING COMPONENTS SUCH <br />AS DUCTS, OPENINGS, BEAMS AND PIPING PRIOR TO INSTALLATION. <br />C.CHECK THE ARCHITECTURAL FINISHES AND, REGARDLESS OF THE CATALOG PREFIXES AND SUFFIXES SHOWN, <br />FURNISH FIXTURES WITH THE PROPER TRIM, FRAMES, SUPPORTS, HANGERS AND OTHER MISCELLANEOUS <br />APPURTENANCES OR PROPERLY COORDINATE WITH SAID FINISHES. WHERE REQUIRED, FURNISH REINFORCING FOR <br />CEILING CONSTRUCTION TO SUPPORT THE WEIGHT OF THE FIXTURES. <br />D.FIXTURES SHALL BE FREE OF LIGHT LEAKS AND DESIGNED TO PROVIDE SUFFICIENT VENTILATION OF LAMPS AND <br />BALLASTS, INCLUDING VENT HOLES WHERE REQUIRED. OUTDOOR FIXTURES WITH VENT HOLES SHALL HAVE WIRE <br />MESH SCREENS IN THE VENT HOLES. <br />E.REPLACE BLEMISHED, DAMAGED OR UNSATISFACTORY FIXTURES AT NO ADDITIONAL COST TO THE OWNER AND IN A <br />MANNER SATISFACTORY TO THE ARCHITECT. <br />F.LAMPS <br />1.LAMPS SHALL BE NEW AND OF WATTAGE AND TYPE INDICATED OR AS REQUIRED FOR THE PARTICULAR FIXTURE <br />INSTALLED. <br />2.UNLESS OTHERWISE NOTED, LAMPS DESCRIBED IN FIXTURE SCHEDULE, ANSI NOMENCLATURE, MANUFACTURED BY <br />GENERAL ELECTRIC, SYLVANIA, PHILLIPS, OR EQUAL. <br />3.PROVIDE INCANDESCENT LAMPS AND TUNGSTEN-HALOGEN LAMPS AS 130 VOLT RATED WHENEVER SUCH DESIGNS <br />ARE AVAILABLE. <br />4.PROVIDE FLUORESCENT LAMPS AS INDICATED ON THE DRAWINGS. ALL LINEAR FLUORESCENT LAMPS ARE TO BE <br />INSTALLED WITH THE LABEL FACING THE SAME DIRECTION. <br />5.PROVIDE HIGH INTENSITY DISCHARGE (H.I.D.) LAMPS OF TYPE AND WATTAGE AS SHOWN ON THE DRAWINGS. LAMPS <br />SHALL BE COMPATIBLE WITH FIXTURE BALLAST. MANUFACTURERS: G.E. CO., PHILLIPS, SYLVANIA, OR EQUAL. <br />G.FLUORESCENT BALLASTS <br />1.PROVIDE BALLASTS ONLY BY MANUFACTURERS PRODUCING EQUIPMENT FOR AT LEAST FOUR YEARS. <br />2.PROVIDE BALLASTS WITH OPERATION AT INPUT FREQUENCY OF 60 HZ AND INPUT VOLTAGE BETWEEN 100 AND 135 <br />VOLTS FOR 120 VOLT SYSTEMS OR BETWEEN 250 AND 310 VOLTS FOR 277 VOLT SYSTEMS. <br />3.PROVIDE NON-DIMMING ELECTRONIC BALLAST FOR T-8 FLUORESCENT LAMPS AS SHOWN ON DRAWING. THE BALLAST <br />SHALL BE UL LISTED CLASS P, AND SOUND LEVEL A OR BETTER. THE BALLAST WITH LAMP OPERATING FREQUENCY <br />BETWEEN 25 TO 35 KHZ. WITH NO FLICKERING. THE BALLAST SHALL HAVE LOWEST HARMONIC CONTENT AND TOTAL <br />HARMONIC DISTORTION (NOT TO EXCEED 15% ON TOTAL HARMONIC AND 10% ON THIRD HARMONIC CONTENT). <br />BALLAST SHALL BE ADVANCE MARK V OR EQUAL. <br />4.PROVIDE DIMMING ELECTRONIC BALLAST FOR FOUR FEET RAPID START LAMP, SAME CHARACTERISTICS AS SPECIFIED <br />FOR NON-DIMMING WITH DIMMING CAPABILITIES FROM 100% TO 5% OF FULL LIGHT OUTPUT. MANUFACTURED BY ETTA <br />OR LUTRON (15% TOTAL HARMONIC AND 10% THIRD HARMONIC CONTENT). <br />5.BALLASTS FOR EXTERIOR FIXTURES SHALL BE LOW TEMPERATURE TYPE FOR OPERATING AT +20 DEGREES F. <br />6.PROVIDE HIGH POWER FACTOR BALLASTS (90 PERCENT OR HIGHER) UL LISTED AND CONTAINING NO PCB. BALLAST <br />SHALL MEET FCC RULES REPORT 18 AND IEEE 587 FOR WITHSTANDING LINE TRANSIENTS. <br />7.PROVIDE STEEL ENCASED, FULLY POTTED BALLASTS CAPABLE OF STARTING LAMPS AT 0 DEGREES F. <br />8.BALLAST SHALL MEET FOLLOWING CHARACTERISTICS: <br />A.BALLAST FACTOR: 80 TO 100% <br />B.LAMP CURRENT CREST FACTOR: LESS THAN 1.7. <br />C.FILAMENT VOLTAGE: 2.5 TO 3.6 VOLTS. <br />D.FLICKER: LESS THAN 1%. <br />9.PROVIDE BALLASTS WITH BUILT-IN LINE RFI SUPPRESSION AND HAVE SURGE AND TRANSIENT PROTECTED TO 6000 <br />VOLTS. <br />10.PROVIDE BALLASTS WITH OPERATING TEMPERATURES NOT EXCEEDING 80 DEGREES C. AT ANY POINT ON THE CASE <br />DURING NORMAL OPERATION. <br />11.(3) LAMP BALLASTS ARE NOT ACCEPTABLE. <br />H.HIGH INTENSITY DISCHARGE LAMP BALLASTS <br />1.PROVIDE HIGH INTENSITY DISCHARGE LAMP BALLASTS AS HIGH POWER FACTOR REGULATING TYPE, CONFORMING TO <br />APPLICABLE NEMA STANDARDS. INPUT VOLTAGE AND WATTAGES ARE LISTED IN THE FIXTURE SCHEDULE. <br />2.MINIMUM STARTING TEMPERATURE: MINUS 20 DEGREES F. <br />3.PROVIDE HIGH INTENSITY DISCHARGE BALLASTS OF THE ENCAPSULATED TYPE WITH LOWEST SOUND RATING <br />AVAILABLE. <br />I. EXIT SIGNS LIGHTS SHALL BE LED TYPE AND PROVIDED WITH AN INTEGRAL EMERGENCY BATTERY PACK. <br />J.LED LIGHT FIXTURES <br />A.GENERAL: <br />1.LED LIGHT FIXTURES SHALL BE IN ACCORDANCE WITH IES, NFPA, UL, AS SHOWN ON THE DRAWINGS, AND AS <br />SPECIFIED. <br />2.LED LIGHT FIXTURES SHALL BE REDUCTION OF HAZARDOUS SUBSTANCES (ROHS)-COMPLIANT. <br />3.LED DRIVERS SHALL INCLUDE THE FOLLOWING FEATURES UNLESS OTHERWISE INDICATED: <br />a.MINIMUM EFFICIENCY: 85% AT FULL LOAD. <br />b.MINIMUM OPERATING AMBIENT TEMPERATURE: -20 DEG C. (-4 DEG F.) <br />c.INPUT VOLTAGE: 120 - 277V (±10%) AT 60 HZ. <br />d.INTEGRAL SHORT CIRCUIT, OPEN CIRCUIT, AND OVERLOAD PROTECTION. <br />e.POWER FACTOR: >=0.95. <br />f.TOTAL HARMONIC DISTORTION: <=20%. <br />g.COMPLY WITH FCC 47 CFR PART 15. <br />4.LED MODULES SHALL INCLUDE THE FOLLOWING FEATURES UNLESS OTHERWISE INDICATED: <br />a.COMPLY WITH IES LM-79 AND LM-80 REQUIREMENTS. <br />b.MINIMUM CRI 80 AND COLOR TEMPERATURE 4000K UNLESS OTHERWISE SPECIFIED IN LUMINAIRE SCHEDULE. <br />c.MINIMUM RATED LIFE: 50,000 HOURS PER IES L70. <br />d.LIGHT OUTPUT LUMENS AS INDICATED IN THE LUMINAIRE SCHEDULE. <br />B.LED DOWNLIGHTS: <br />1.HOUSING, LED DRIVER, AND LED MODULE SHALL BE PRODUCTS OF THE SAME MANUFACTURER. <br />C.LED TROFFERS: <br />1.LED DRIVERS, MODULES, AND REFLECTOR SHALL BE ACCESSIBLE, SERVICEABLE, AND REPLACEABLE FROM BELOW <br />THE CEILING. <br />2.HOUSING, LED DRIVER, AND LED MODULE SHALL BE PRODUCTS OF THE SAME MANUFACTURER. <br />2.12 LOW VOLTAGE SWITCHGEAR - N/A <br />2.13 CIRCUIT AND MOTOR DISCONNECTS <br />A.DISCONNECT (SAFETY) SWITCHES SHALL BE FUSED, HEAVY DUTY TYPE SWITCHES MEETING NEMA SPECIFICATIONS. <br />SWITCHES SHALL BE PROVIDED WITH REJECTION TYPE FUSE BLOCKS. PROVIDE SWITCHES WITH THE NUMBER OF <br />POLES, THE VOLTAGE, CURRENT AND HORSEPOWER RATINGS AS REQUIRED. PROVIDE EXTERNALLY OPERABLE <br />QUICK-MAKE, QUICK-BREAK TYPE MECHANISM WITH COVER INTERLOCK AND PADLOCKABLE IN EITHER THE OPEN OR <br />CLOSED POSITION. <br />B.SWITCHES SHALL BE NEMA 3R (RAIN TIGHT ENCLOSURE) WHERE INDICATED TO BE OUTDOORS WEATHERPROOF. <br />C.PROVIDE NAMEPLATE INDICATING EQUIPMENT SERVED. ALL GENERAL SNAP SWITCHES OPERATING MOTOR LOADS <br />SHALL BE HORSEPOWER RATED OR BE RATED AT LEAST 125% OF THE FULL LOAD CURRENT. <br />2.15 ELECTRICAL CONNECTIONS <br />A.UNLESS OTHERWISE NOTED, ALL WIRING FOR MOTORS, STARTERS, CONTROLS, AND EQUIPMENT SHALL BE PROVIDED <br />BY THE ELECTRICAL CONTRACTOR. WHERE MOTORS FOR MECHANICAL EQUIPMENT ARE FURNISHED BY OTHER <br />DIVISIONS, WIRING SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR, EXCEPT WHERE WIRED <br />INTEGRALLY WITH THE EQUIPMENT. <br />B.CONNECTION AND CONTROL DIAGRAMS FOR ALL MECHANICAL AND CONTROL EQUIPMENT SHALL BE FURNISHED <br />UNDER OTHER DIVISIONS, AND BE APPROVED BY THE OWNER FOR CONNECTION BY THE ELECTRICAL CONTRACTOR. <br />2.16 SUPPORTING DEVICES <br />A.ALL EQUIPMENT CONDUITS SHALL BE SUPPORTED, ANCHORED AND BRACED IN ACCORDANCE WITH THE MOST <br />STRINGENT CODES AND REQUIREMENTS. COMPLY WITH CHAPTER 23 OF THE LATEST CBC (CALIFORNIA BUILDING <br />CODE). <br />PART 3 EXECUTION <br />3.01 WORKMANSHIP AND COMPLETION OF INSTALLATION <br />A.WORKMANSHIP AND NEAT APPEARANCE SHALL BE AS IMPORTANT AS THE ELECTRICAL AND MECHANICAL EFFICIENCY. <br />DEFECTIVE AND DAMAGED MATERIALS SHALL BE REPLACED OR REPAIRED PRIOR TO FINAL INTERPRETATIONS <br />INCLUDED. ANY DEFICIENCY PERTAINING TO EITHER WORKMANSHIP OR MATERIALS FOUND BY THE INSPECTOR SHALL <br />BE CORRECTED WITHOUT ADDITIONAL COST TO THE OWNER. <br />B.THE CONTRACTOR SHALL MAINTAIN ON JOB SITE A SET OF THE WORKING DRAWINGS WHICH SHALL BE UPDATED DAILY <br />IN DETAIL FOR WORK ACCOMPLISHED. UPON COMPLETION OF THE WORK, A SET OF REPRODUCIBLE CONTRACT <br />DRAWINGS SHALL BE OBTAINED FROM THE GENERAL CONTRACTOR AND ALL CHANGES AS NOTED ON THE RECORD <br />SET OF PRINTS SHALL BE INCORPORATED THEREON WITH RED INK IN A NEAT, LEGIBLE, UNDERSTANDABLE AND <br />PROFESSIONAL MANNER. <br />C.ALL EQUIPMENT AND MATERIAL CONNECTED WITH THIS PROJECT SHALL BE INSTALLED COMPLETE, THOROUGHLY <br />CLEANED, AND ALL RESIDUE REMOVED FROM INSIDE SURFACES. EXTERIOR SURFACES OF ALL MATERIAL AND <br />EQUIPMENT SHALL BE CLEANED AND DELIVERED IN A PERFECT, UNBLEMISHED CONDITION. <br />D.UPON COMPLETION OF THE INSTALLATION AND AS A CONDITION OF ITS ACCEPTANCE FURNISH ONE COPY OF THE <br />FINAL INSPECTION CERTIFICATE TO THE OWNER. <br />3.02 PREPARATION COORDINATION. <br />A.THE CONTRACTOR SHALL COORDINATE THIS WORK WITH ALL OTHER CONTRACTORS FURNISHING LABOR, MATERIALS <br />AND WORK, SO THAT THE WORK AS WHOLE SHALL BE EXECUTED AND COMPLETED WITHOUT CONFLICT OR DELAY. <br />B.EXAMINE THE DRAWINGS AND SPECIFICATIONS AND DETERMINE THE WORK TO BE PERFORMED BY THE ELECTRICAL, <br />MECHANICAL AND OTHER TRADES. PROVIDE THE TYPE AND AMOUNT OF ELECTRICAL MATERIALS AND EQUIPMENT <br />NECESSARY TO PLACE THIS WORK IN PROPER OPERATION, COMPLETELY WIRED TESTED AND READY FOR USE. THIS <br />SHALL INCLUDE ALL CONDUIT, WIRE, DISCONNECTS, RELAYS, AND OTHER DEVICES FOR THE REQUIRED OPERATION <br />SEQUENCE OF ALL ELECTRICAL, MECHANICAL, AND OTHER SYSTEMS OR EQUIPMENT. <br />C.PERFORM ALL WORK IN A MANNER WHICH WILL NOT CAUSE UNNECESSARY INCONVENIENCE OR DANGER TO THE <br />OCCUPANTS, NOR INTERFERE WITH THE ACTIVITIES IN THE BUILDING. <br />D.THE CONTRACTOR SHALL COORDINATE AND SCHEDULE EACH POWER INTERRUPTION WITH OWNER, AND SHALL <br />PROVIDE AT LEAST TWO WEEKS NOTICE OF PROPOSED INTERRUPTION AND WORK TO BE ACCOMPLISHED. <br />3.04 CORE CUTTING, DRILLING, AND PATCHING <br />A.NO HOLES WILL BE ALLOWED IN ANY STRUCTURAL MEMBERS WITHOUT THE WRITTEN APPROVAL OF THE ARCHITECT <br />OR STRUCTURAL ENGINEER AND GENERAL CONTRACTOR. <br />3.05 INSTALLATION <br />A.WORKMANSHIP IS TO BE NEAT, BY EXPERIENCED WORKMEN WITH ADEQUATE SUPERVISION, AND IN LINE WITH <br />NORMAL INDUSTRY WORK PRACTICES. <br />B.MAINTAIN WORKING CLEARANCE AROUND ELECTRICAL EQUIPMENT, IN ACCORDANCE WITH CODE REQUIREMENTS AS A <br />MINIMUM. <br />C.WHERE LIGHTING FIXTURES AND OTHER ELECTRICAL ITEMS ARE SHOWN IN CONFLICT WITH LOCATIONS OF <br />STRUCTURAL MEMBERS AND MECHANICAL OR OTHER EQUIPMENT, FURNISH AND INSTALL ALL REQUIRED SUPPORTS <br />AND WIRING TO CLEAR THE ENCROACHMENT. <br />D.VERIFY LOCATION OF EACH OUTLET FOR POWER, SIGNAL, TELEPHONE/DATA, AND EACH LIGHTING FIXTURE WITH <br />ARCHITECT PRIOR TO ROUGH-IN. INCLUDE IN BID COST OF RELOCATING EACH ITEM WITHIN TEN-FEET RADIUS OF ITS <br />INDICATED LOCATION. <br />E.ALL CONDUIT TO BE RUN CONCEALED UNLESS OTHERWISE NOTED. ALL CONDUITS SHALL BE ROUTED OVERHEAD IN <br />CEILING SPACES. NO CONDUITS SHALL BE PERMITTED IN CONCRETE SLAB, MASONRY WALLS UNLESS SPECIFICALLY <br />SO INDICATED. CONDUIT SHALL BE RUN SO AS NOT TO INTERFERE WITH OTHER PIPING FIXTURES OR EQUIPMENT. <br />F.WHERE ALLOWED, EXPOSED CONDUIT RUNS SHALL BE INSTALLED PARALLEL OR PERPENDICULAR TO WALLS, <br />STRUCTURAL MEMBERS, OR INTERSECTION OF VERTICAL PLANES AND CEILINGS. <br />G.ALL ELECTRICAL CONDUITS AND OTHER ELECTRICAL RACEWAYS PASSING THROUGH FIRE RATED CEILINGS, SLABS, <br />CABLE TRAYS, WALLS AND PARTITIONS SHALL BE SEALED TO PREVENT THE SPREAD OF FIRE, SMOKE, AND GASSES. <br />USE A UL LISTED AND APPROVED FIRE-STOP MATERIAL EQUAL TO RATING OF A WALL OR A FLOOR SLAB PENETRATED; <br />INSTALLATION OF FIRE-STOP MATERIAL SHALL BE IN ACCORDANCE WITH MANUFACTURERS INSTRUCTIONS. <br />H.UNLESS WRITTEN PERMISSION IS GRANTED BY THE ARCHITECT, NO MATERIAL SHALL BE MOUNTED ON THE EXTERIOR <br />WALLS OR PARAPET TOP OF THE BUILDING. <br />I.ALL ROTATING ELECTRICAL EQUIPMENT SHALL BE SUPPLIED WITH A FLEXIBLE, LIQUID-TIGHT CONDUIT WITH <br />APPROPRIATE SLACK AND SHALL NOT EXCEED THIRTY-SIX (36) INCHES. <br />J.ALL POWER WIRING SHALL BE INSTALLED IN CONDUIT. <br />K.TELEPHONE WIRES SHALL BE PLENUM RATED CABLE FOR MOUNTING IN CEILING SPACES WITHOUT CONDUIT UNLESS <br />OTHERWISE NOTED. <br />L.ALL WIRES FOR ALL SYSTEMS SHALL BE CONTINUOUS FROM SWITCH TO TERMINAL OR FURTHEST OUTLET. NO JOINTS <br />SHALL BE MADE EXCEPT IN PULL, JUNCTION OR OUTLET BOXES, OR IN PANEL OR SWITCHBOARD GUTTERS. <br />M.ALL RECEPTACLE, CONTROL DEVICE, AND SWITCH MOUNTING HEIGHTS SHALL BE COORDINATED WITH <br />ARCHITECTURAL ELEVATIONS PRIOR TO ROUGH-IN. <br />3.06 GROUNDING <br />A.ALL EQUIPMENT SHALL BE PROPERLY GROUNDED AS INDICATED ON DRAWINGS AND AS REQUIRED BY THE LATEST <br />EDITION OF APPLICABLE CODES. <br />B.FURNISH AND INSTALL ALL GROUNDING CONDUCTORS, CONDUIT AND CLAMPS. THE SIZE OF THE GROUNDING <br />CONDUCTORS SHALL BE NOT LESS THAN THAT SPECIFIED IN THE NEC. <br />C.BUILDING GROUNDING SYSTEM RESISTANCE TO GROUND SHALL NOT EXCEED 25 OHMS. <br />D.EACH BRANCH CIRCUIT SHALL BE EQUIPPED WITH CODE SIZE GREEN GROUND, EQUIPMENT WIRE (PER NEC 250-95) <br />(NOT INDICATED ON DRAWINGS) WITHIN THE SAME CONDUIT FOR ALL CIRCUITS OF PANELBOARDS. <br />3.07 BRANCH CIRCUITS <br />A.NO MORE THAN THREE BRANCH CIRCUITS PERMITTED IN ONE CONDUIT UNLESS INDICATED OTHERWISE <br />3.08 IDENTIFICATION <br />A.THE FOLLOWING ITEMS SHALL BE EQUIPPED WITH NAMEPLATES: <br />1.ALL MOTORS, MOTOR STARTERS, CONTROL PANELS, MOTORS CONTROL REMOTE STATIONS. <br />2.ALL DISCONNECT AND SAFETY SWITCHES, MAIN DISTRIBUTION PANEL FEEDER OVERCURRENT DEVICES AND SPARES, <br />CIRCUIT EQUIPMENT IN SEPARATE ENCLOSURES. <br />3.SPECIAL ELECTRICAL SYSTEMS SHALL BE PROPERLY IDENTIFIED AT JUNCTION AND PULL BOXES <br />4.ALL BRANCH CIRCUIT PANEL BOARDS SHALL HAVE IDENTIFYING ENGRAVED PLASTIC NAMEPLATES. ALSO, PROVIDE A <br />TYPED DIRECTORY CARD FOR EACH BRANCH CIRCUIT PANELBOARD. THE CARD IS TO BE PLACED ON THE INTERIOR <br />SIDE OF THE PANELBOARD DOOR BEHIND A CLEAR PLASTIC SHIELD. THE CARD SHALL IDENTIFY EACH CIRCUIT BY <br />NUMBER, LOAD, AND LOCATION. <br />5.IN GENERAL, EQUIPMENT SHALL BE IDENTIFIED AS DESIGNATED ON THE ELECTRICAL DRAWINGS. NAMEPLATES FOR <br />PANELBOARDS AND SWITCHBOARDS SHALL INCLUDE THE PANEL DESIGNATION, VOLTAGE AND PHASE OF THE SUPPLY. <br />THE NAME OF THE MACHINE SHALL BE THE SAME AS THE NAME USED ON ALL MOTOR STARTERS, DISCONNECTS, AND <br />P.B STATION NAMEPLATES FOR THAT MACHINE. <br />B.NAMEPLATES SHALL BE FABRICATED AS FOLLOWS: <br />1.NAMEPLATE MATERIALS SHALL CONSIST OF 3-PLY, 1/16" LAMINATED PLASTIC WITH WHITE CORE FOR LETTERING AND <br />BLACK BACKGROUND. <br />2.CAPITAL LETTERS SHALL BE USED. <br />3.NAMEPLATES SHALL BE FASTENED WITH CADMIUM-PLATED SELF-TAPPING NO. 6 SCREWS 1/4" LONG <br />4.THE MINIMUM SIZE OF ALL NAME PLATES AND LETTERING SHALL BE 3/4" HIGH BY 2" LONG WITH 1/4" LETTERS. <br />3.09 PROTECTION <br />A.USE ALL MEANS NECESSARY TO PROTECT THE WORK AND MATERIALS FROM LOSS DURING AND AFTER INSTALLATION, <br />AND PROVIDE ADEQUATE AND PROPER STORAGE FACILITIES DURING THE PROGRESS OF THE WORK. PROVIDE FOR <br />THE SAFETY AND GOOD CONDITION OF ALL WORK UNTIL FINAL ACCEPTANCE OF THE WORK BY THE OWNER. REPLACE <br />ALL DAMAGE OR DEFECTIVE WORK, MATERIAL, AND EQUIPMENT AT NO EXPENSE TO THE OWNER BEFORE <br />REQUESTING FINAL ACCEPTANCE. <br />3.10 CLEANING OF EQUIPMENT, MATERIAL, AND PREMISES <br />A.SITE SHALL BE LEFT BROOM CLEAN AFTER COMPLETION OF WORK EACH DAY. UPON COMPLETION OF THE WORK, <br />LEAVE THE PREMISES CLEAN OF ALL DIRT AND DEBRIS. <br />B.ALL EQUIPMENT AND MATERIAL CONNECTED WITH THIS PROJECT SHALL BE INSTALLED COMPLETE, THOROUGHLY <br />CLEANED, AND ALL RESIDUE REMOVED FROM INSIDE SURFACES. EXTERIOR SURFACES OF ALL MATERIAL AND <br />EQUIPMENT SHALL BE CLEANED AND DELIVERED IN A PERFECT, UNBLEMISHED CONDITION. <br />3.11 HANDLING OF WIRE AND CABLE <br />A.HANDLE WIRE AND CABLE SO AS TO AVOID DAMAGE TO CONDUCTORS AND TAKE EVERY PRECAUTION TO AVOID SHARP <br />BENDING OR SCORING OF THE CABLE. CABLE SHALL NOT BE LAID NOR DRAGGED UPON THE GROUND. <br />B.THE CONTRACTOR SHALL BE REQUIRED TO REMOVE AND REPLACE AT HIS OWN EXPENSE ALL WIRE AND CABLE <br />DAMAGED DUE TO IMPROPER HANDLING, AND SHALL PAY FOR THE NEW WIRE OR CABLE. <br />3.12 TESTING AND INSPECTIONS <br />A.THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL REQUIRED PERMITS AND ARRANGE ALL REQUIRED INSPECTIONS <br />FOR THE EXECUTION OF THE WORK UNDER THIS CONTRACT. <br />B.THE CONTRACTOR SHALL REPLACE ALL DAMAGED OR DEFECTIVE EQUIPMENT OR WORK. <br />C.ALL CIRCUITS SHALL BE TESTED FOR CONTINUITY AND CIRCUIT INTEGRITY BY THE CONTRACTOR. ADJUSTMENTS <br />SHALL BE MADE FOR CIRCUITS NOT COMPLYING WITH TESTING CRITERIA. <br />D.THE CONTRACTOR SHALL FURNISH ALL INSTRUMENTS AND PERFORM ANY ADDITIONAL TESTS REQUIRED BY THE <br />AUTHORITY HAVING JURISDICTION. CONTRACTOR SHALL ALSO CORRECT ALL FAILURES AND REPLACE ANY DAMAGED <br />PORTIONS OF THE WORK RESULTING FROM THOSE TESTS. THE COST OF THE FOREGOING ITEMS SHALL BE PAID BY <br />THE CONTRACTOR. <br />E.THE CONTRACTOR SHALL FURNISH THE OWNER CERTIFICATES OF INSPECTION AND APPROVAL BY THE ELECTRICAL <br />INSPECTION AUTHORITY ON ALL WORK COMPETED AS REQUIRED. <br />F.TITLE 24 REQUIRES THE COMPLETION OF ALL APPLICABLE CERTIFICATES OF INSTALLATION AND CERTIFICATES OF <br />ACCEPTANCE FOR LIGHTING SYSTEMS. THIS SHALL INCLUDE INDOOR AND OUTDOOR LIGHTING SYSTEMS. <br />G.CONTRACT DRAWINGS AND SPECIFICATIONS, GENERAL PROVISIONS OF THE CONTRACT, INCLUDING GENERAL AND <br />SUPPLEMENTARY CONDITIONS, ELECTRICAL PROVISIONS AND DIVISION-1 SPECIFICATION SECTIONS APPLY TO WORK <br />OF THIS SECTION. <br />H.COMPLETE ALL TITLE 24 REQUIRED CERTIFICATE(S) OF INSTALLATION (NRCI) AND CERTIFICATE(S) OF ACCEPTANCE <br />(NRCA) TO BE COMPLETED PER THE CONTRACT DOCUMENTS. <br />I.RESPONSIBILITIES OF INSTALLING CONTRACTORS <br />A.A.GENERAL CONTRACTOR (GC) <br />a.ENSURE THAT ALL CONTRACTORS IDENTIFIED AS THE CONTRACTOR RESPONSIBLE FOR ACCEPTANCE TESTING <br />AND COMPLETION OF THE TITLE 24 CERTIFICATE(S) OF ACCEPTANCE ARE CERTIFIED BY THE STATE OF <br />CALIFORNIA OR ITS DESIGNATED BODY TO CONDUCT EACH RESPECTIVE TEST. <br />A.A.ELECTRICAL CONTRACTOR (EC) <br />a.VERIFY PROPER INSTALLATION AND PERFORMANCE OF ALL ELECTRICAL SERVICES PROVIDED. <br />b.COMPLETE TITLE 24 CERTIFICATE(S) OF INSTALLATION AND MANUFACTURER'S PRE-START CHECKLISTS PRIOR <br />TO SCHEDULING STARTUP/PROGRAMMING OF LIGHTING CONTROL EQUIPMENT. <br />i.RETAIN CERTIFICATE(S) OF INSTALLATION IN A 3-RING BINDER IN AN ORGANIZED FASHION. BINDER IS TO REMAIN <br />ON THE JOB SITE <br />ii.MAKE CERTIFICATE(S) OF INSTALLATION AVAILABLE FOR BUILDING INSPECTOR'S REVIEW. <br />iii.RETAIN CALIBRATION RECORDS FOR EQUIPMENT PROVIDED WITH MANUFACTURER CALIBRATED SENSORS IN <br />THE CERTIFICATE(S) OF INSTALLATION BINDER. <br />iv.CORRECT LABELING OF ALL CIRCUITS WITH CONNECTED EQUIPMENT. <br />c.COMPLETE THE CERTIFICATE(S) OF ACCEPTANCE PER THE CONTRACT DOCUMENTS. <br />i.THE COMPANY INSTALLING THE LIGHTING SYSTEMS MUST BE AN AUTHORIZED LIGHTING CONTROLS <br />ACCEPTANCE TEST EMPLOYER CERTIFIED BY A LIGHTING CONTROLS ACCEPTANCE TEST TECHNICIAN <br />CERTIFICATION PROVIDER OR INCLUDE IN THEIR BID THE COST OF RETAINING AND OVERSEEING A CONTRACTOR <br />WHO IS AN AUTHORIZED LIGHTING CONTROLS ACCEPTANCE TEST EMPLOYER TO COMPLETE THE ACCEPTANCE <br />TESTING. <br />ii.ALL REQUIRED ACCEPTANCE TESTING MUST BE COMPLETED BY A LIGHTING CONTROLS ACCEPTANCE TEST <br />TECHNICIAN EMPLOYED BY THE LIGHTING CONTROLS ACCEPTANCE TEST EMPLOYER. <br />iii.RETAIN CERTIFICATE(S) OF ACCEPTANCE IN A 3-RING BINDER IN AN ORGANIZED FASHION. BINDER IS TO REMAIN <br />ON THE JOB SITE <br />iv.UPLOAD ALL CERTIFICATE(S) OF ACCEPTANCE TO THE CALIFORNIA TITLE 24 CERTIFICATES OF ACCEPTANCE <br />DATABASE, IF, AT THE TIME OF PROJECT COMPLETION, THE DATABASE IS AVAILABLE TO THE PUBLIC. <br />d.SUCCESSFUL COMPLETION OF THE REQUIRED ACCEPTANCE TESTS IS THE RESPONSIBILITY OF THE INSTALLING <br />CONTRACTOR. ANY COSTS ASSOCIATED WITH MODIFICATIONS NECESSARY TO OBTAIN COMPLIANCE AND <br />RE-TESTING OF SYSTEMS SHALL BE INCLUDED IN THE BASE BID OF THIS PROJECT. <br />3.13 TELEPHONE AND DATA <br />A.PROVIDE AND INSTALL COMPLETE SYSTEM OF CONDUIT WITH PULL LINES, BACKBOARDS, EQUIPMENT RACK, PULL <br />BOXES, JUNCTION BOXES, OUTLET BOXES, AND PLASTER RINGS, FOR TELEPHONE/ DATA SYSTEMS, TO BE INSTALLED <br />AS PART OF THIS BUILDING CONTRACT. <br />B.PROVIDE OVERHEAD CONDUIT CONNECTIONS BETWEEN THE MAIN TELECOM ROOM AND THE NETWORK RACK. <br />301 9TH STREET, SUITE 103 <br />REDLANDS, CA 92374 <br />P: (909) 281-8100 <br />E: svela@velaengineering.biz <br />G: <br />\ <br />P <br />r <br />o <br />j <br />e <br />c <br />t <br /> <br />F <br />i <br />l <br />e <br />s <br />\ <br />3 <br />1 <br />3 <br />9 <br /> <br />S <br />a <br />n <br />t <br />a <br /> <br />A <br />n <br />a <br /> <br />P <br />o <br />r <br />t <br />o <br />l <br />a <br /> <br />P <br />a <br />r <br />k <br /> <br />R <br />e <br />s <br />t <br />o <br />o <br />m <br /> <br />R <br />e <br />n <br />o <br />v <br /> <br />& <br /> <br />A <br />d <br />d <br /> <br />f <br />o <br />r <br /> <br />D <br />V <br />D <br />\ <br />0 <br />1 <br />- <br />D <br />r <br />a <br />w <br />i <br />n <br />g <br />s <br />\ <br />0 <br />1 <br />- <br />R <br />e <br />v <br />i <br />t <br />\ <br />3 <br />- <br />C <br />D <br />\ <br />3 <br />1 <br />3 <br />9 <br /> <br />S <br />a <br />n <br />t <br />a <br /> <br />A <br />n <br />a <br /> <br />P <br />o <br />r <br />t <br />o <br />l <br />a <br /> <br />P <br />a <br />r <br />k <br /> <br />R <br />e <br />s <br />t <br />r <br />o <br />o <br />m <br /> <br />R <br />e <br />n <br />o <br /> <br />& <br /> <br />A <br />d <br />d <br /> <br />C <br />D <br />_ <br /> <br />C <br />A <br />D <br /> <br />B <br />a <br />c <br />k <br />g <br />r <br />o <br />u <br />n <br />d <br />s <br />. <br />r <br />v <br />t <br />NUMBER DATE INITIALS DESCRIPTION <br />PREPARED UNDER THE <br />SUPERVISION OF: <br />CITY OF SANTA ANA <br />FILE NO.: <br />INSTALLEDAPPROVED <br />CONSTRUCTION COMPLETED: <br />BENCHMARK NO.: SA-253-70 <br />RECOMMENDED FOR <br />CONSTRUCTION: <br />REFERENCES <br />PUBLIC WORKS AGENCY <br />XRCE NO.: <br />ELEV.: 176.00 (2010) <br />REVISIONS <br />SHEET OF <br />BENCHMARK DESCRIPTION: <br />OCS BM SA-253-70 <br />FD 3 3/4" OCS ALUMINUM BENCH MARK DISK STAMPED "SA-253-70", SET IN NW'LY CORNER OF A 3.5FT X 16FT <br />CONCRETE CATCH BASIN. MONUMENT IS LOCATED IN THE NE'LY CORNER OF THE INTERSECTION OF GRAND AVE <br />AND SANTA CLARA AVE, 87FT N'LY OF THE CENTERLINE OF SANTA CLARA AVE AND 39FT E'LY OF THE CENTERLINE <br />OF GRAND AVE. MONUMENT IS SET LEVEL WITH THE SIDEWALK <br />PORTOLA PARK <br />SPLASH PADREVIEWED FOR <br />CONSTRUCTABLITY: <br />PRINCIPAL CIVIL ENGINEER <br />DESIGNED: <br />PRINCIPAL CIVIL ENGINEER RCE NO.: <br />RM RM SV <br />ELECTRICAL ENGINEER <br />DRAWN:CHECKED: <br />10 <br />0 <br />% <br /> <br />S <br />U <br />B <br />M <br />I <br />T <br />T <br />A <br />L <br />. <br />PS-25-2401 <br />SAMUEL VELA <br />1700 E. SANTA CLARA AVENUE, SANTA ANA, CA 92705 <br />811 <br />UNDERGROUND SERVICE ALERT. DIAL 811 <br />LOCATION OF UNDERGROUND UTILITIES BY CONTRACTING <br />BEFORE EXCAVATING, THE CONTRACTOR SHALL VERIFY THE <br />DAMAGE SUCH FACILITIES OR INTERFERE WITH THEIR SERVICE. <br />UNDERGROUND FACILITIES PRIOR TO DOING WORK THAT MAY <br />STEPS TO ASCERTAIN THE EXACT LOCATION OF ALL <br />THE SPECIAL PROVISIONS. THE CONTRACTOR SHALL TAKE <br />DIFFERENT FROM THAT WHICH IS SHOWN ON THE PLANS OR IN <br />UNDERGROUND FACILITIES NOT KNOWN OR IN A LOCATION <br />ATTENTION IS DIRECTED TO THE POSSIBLE EXISTENCE OF <br />UNDERGROUND SERVICE ALERT OF SOUTHERN CALIFORNIA <br />SPECIFICATIONS E3.1 <br />52 57