PART 1 GENERAL
<br />1.01 SCOPE OF WORK
<br />A.WORK COVERED BY THIS SECTION CONSISTS OF FURNISHING ALL LABOR, EQUIPMENT, SUPPLIES, AND MATERIALS,
<br />UNLESS OTHERWISE SPECIFIED, AND IN PERFORMING ALL OPERATIONS NECESSARY FOR THE INSTALLATION OF A
<br />COMPLETE AND OPERABLE ELECTRICAL SYSTEM AS REQUIRED BY THESE SPECIFICATIONS AND AS INDICATED ON THE
<br />DRAWINGS.
<br />B.THE CONTRACTOR SHALL EXAMINE ALL DRAWINGS AND SPECIFICATIONS IN A MANNER TO BE FULLY COGNIZANT OF
<br />ALL WORK REQUIRED UNDER THIS SECTION.
<br />C.THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL REQUIRED PERMITS UNLESS OTHERWISE ARRANGED AND
<br />SCHEDULE ALL REQUIRED INSPECTIONS FOR THE EXECUTION OF THE WORK UNDER THIS CONTRACT.
<br />1.02 GENERAL REQUIREMENTS
<br />A.WORK DONE UNDER THIS SECTION SHALL COMPLY WITH THE LATEST EDITION OF THE CALIFORNIA ELECTRICAL CODE,
<br />NEC (NATIONAL ELECTRICAL CODE), THE STATE OF CALIFORNIA TITLE 24, THE STATE BUILDING STANDARDS, (OSHA)
<br />OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION, AND TO ANY APPLICABLE LOCAL JURISDICTIONAL
<br />REQUIREMENTS. IN CASE OF CONFLICT BETWEEN REQUIREMENT, THE MOST RESTRICTIVE SHALL APPLY.
<br />1.03 ELECTRICAL CONTRACTOR'S RESPONSIBILITY
<br />A.IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO OBTAIN A COMPLETE SET OF DRAWINGS AND SPECIFICATIONS.
<br />CONTRACTOR SHALL CHECK THE DRAWINGS OF THE OTHER TRADES AND SHALL CAREFULLY READ THE ENTIRE
<br />SPECIFICATIONS AND DETERMINE HIS RESPONSIBILITIES.
<br />B.BEFORE SUBMITTING THE BID, THE ELECTRICAL CONTRACTOR SHALL VISIT THE JOB SITE AND FULLY ACQUAINT
<br />HIMSELF WITH EXISTING CONDITIONS. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO INSTALL THE EQUIPMENT
<br />AND ASSOCIATED WIRING IN SUCH A MANNER AS TO CONFORM WITH THE EXISTING STRUCTURE OF THE BUILDING,
<br />AVOID OBSTRUCTIONS, AND MEET APPLICABLE CODE REQUIREMENTS.
<br />C.THE INTENT OF THESE DRAWINGS IS TO DESCRIBE A COMPLETE AND OPERABLE SYSTEM. WHERE EXISTING
<br />CONDITIONS DIFFER FROM DRAWINGS, ADJUSTMENT SHALL BE MADE AND ALLOWANCES INCLUDED FOR ALL
<br />NECESSARY EQUIPMENT TO COMPLETE ALL PARTS OF THE DRAWINGS AND SPECIFICATIONS. BRING ANY QUESTIONS
<br />TO THE ARCHITECT OR ENGINEER'S ATTENTION PRIOR TO BIDDING.
<br />D.WHEREVER A DISCREPANCY IN QUANTITY OR SIZE OF CONDUIT, WIRE, EQUIPMENT, DEVICES, CIRCUIT BREAKERS,
<br />ETC., ARISES ON THE DRAWING AND/OR SPECIFICATION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING
<br />AND INSTALLING ALL MATERIAL AND SERVICES REQUIRED BY THE STRICTEST CONDITION NOTED ON DRAWINGS
<br />AND/OR IN SPECIFICATIONS TO ENSURE COMPLETE AND OPERABLE SYSTEMS AS REQUIRED BY THE OWNER AND
<br />ENGINEER.
<br />1.04 WORK NOT INCLUDED
<br />A.CERTAIN LABOR, MATERIALS, OR EQUIPMENT MAY BE FURNISHED UNDER OTHER CONTRACTS BY THE OWNER. WHEN
<br />SUCH IS THE CASE, THE EXTENT, SOURCE, AND DESCRIPTION OF THESE ITEMS WILL BE INDICATED ON THE DRAWINGS
<br />OR DESCRIBED IN THE SPECIFICATIONS. UNLESS OTHERWISE NOTED, ALL LABOR, MATERIALS AND EQUIPMENT FOR
<br />THE COMPLETE INSTALLATION OF THE ELECTRICAL WORK SHALL BE PROVIDED UNDER THIS SECTION OF THESE
<br />SPECIFICATIONS.
<br />1.05 SPECIAL REQUIREMENTS
<br />A.THE DRAWINGS INDICATE GENERAL ARRANGEMENT OF CIRCUITS, OUTLETS, LOCATIONS OF MOTOR CONTROLLERS
<br />WITH DISCONNECTS, PANELBOARDS, CONDUIT ROUTING, AND OTHER WORK. INFORMATION SHOWN ON THE
<br />DRAWINGS IS ESSENTIALLY DIAGRAMMATIC; HOWEVER, RECIRCUITING OR RELOCATING ELECTRICAL EQUIPMENT WILL
<br />NOT BE PERMITTED WITHOUT SPECIFIC WRITTEN APPROVAL OF THE ENGINEER.
<br />1.06 SUBMITTALS
<br />A.AFTER AWARD OF THE CONTRACT AND BEFORE ANY MATERIALS ARE DELIVERED TO THE JOB SITE, A COMPLETE LIST
<br />OF ALL MATERIALS PROPOSED TO BE FURNISHED AND INSTALLED UNDER THIS SECTION MUST BE PROVIDED.
<br />B.SUBMIT TO THE ENGINEER FOR APPROVAL ONE PRINT AND ONE REPRODUCIBLE OF ALL LIGHTING FIXTURES,
<br />SWITCHGEAR, PANELBOARDS, MOTOR CONTROL CENTERS, TRANSFORMERS, AND MOTOR STARTERS. SHOP
<br />DRAWINGS SHALL INCLUDE MANUFACTURER'S PRINTED INFORMATION FOR EACH OF THESE ITEMS IDENTIFIED ON THE
<br />DRAWINGS. THE INFORMATION SHALL INCLUDE, AS MINIMUM, OVERALL DIMENSIONS, WEIGHT, PHASE, VOLTAGE
<br />RATINGS, WIRING DIAGRAMS, AND NAMEPLATE DATA.
<br />1.07 STANDARDS AND MATERIALS
<br />A.ALL MATERIALS SHALL CONFORM WITH THE CURRENT APPLICABLE INDUSTRY STANDARDS, NEMA (NATIONAL
<br />ELECTRICAL MANUFACTURER'S ASSOCIATION), ANSI (AMERICAN NATIONAL STANDARDS INSTITUTE), IPCEA (INSULATED
<br />POWER CABLE ENGINEERS ASSOCIATION), IEEE (INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS), NATIONAL
<br />ELECTRICAL SAFETY CODE.
<br />B.UNLESS OTHERWISE INDICATED, ALL MATERIALS SHALL BE UNDERWRITERS LABORATORIES LISTED AND LABELED, OR
<br />CERTIFIED BY A NATIONALLY RECOGNIZED TESTING LABORATORY.
<br />C.WORKMANSHIP AND NEAT APPEARANCE SHALL BE AS IMPORTANT AS THE ELECTRICAL MECHANICAL EFFICIENCY.
<br />DEFECTIVE AND DAMAGED MATERIALS SHALL BE REPLACED OR REPAIRED PRIOR TO FINAL APPROVAL AND
<br />ACCEPTANCE. THE DRAWINGS AND SPECIFICATIONS TAKE PRECEDENCE WHEN THEY ARE MORE STRINGENT THAN
<br />CODES, STATUTES, OR ORDINANCES IN EFFECT. APPLICABLE CODES, STANDARDS, ORDINANCES, AND STATUTES TAKE
<br />PRECEDENCE WHEN THEY ARE MORE STRINGENT OR CONFLICT WITH THE DRAWINGS OR SPECIFICATIONS.
<br />1.08 DELIVERY AND STORAGE OF MATERIALS
<br />A.THE CONTRACTOR SHALL INVESTIGATE EACH SPACE IN THE BUILDING THROUGH WHICH EQUIPMENT MUST PASS TO
<br />REACH ITS FINAL LOCATIONS. IF NECESSARY, THE MANUFACTURER SHALL BE REQUIRED TO SHIP HIS MATERIAL IN
<br />SECTIONS, SIZED TO PERMIT PASSING THROUGH SUCH RESTRICTED AREAS IN THE BUILDING.
<br />B.THE CONTRACTOR SHALL RETAIN IN HIS POSSESSION AND SHALL BE RESPONSIBLE FOR ALL PORTABLE AND
<br />DETACHABLE PARTS OF PORTIONS OF INSTALLATIONS SUCH AS FUSES, KEY LOCKS, ADAPTERS, BLOCKING CLIPS, AND
<br />INSERTS UNTIL FINAL COMPLETION OF WORK. THESE PARTS SHALL BE DELIVERED TO THE OWNER UPON COMPLETION
<br />OF THE WORK.
<br />PART 2 PRODUCTS
<br />2.01 EQUIPMENT AND MATERIALS
<br />A.ALL MATERIALS FURNISHED AND INSTALLED UNDER THIS CONTRACT SHALL BE NEW, FREE FROM DEFECTS, AND
<br />SHALL BE GUARANTEED FOR A PERIOD OF ONE (1) YEAR FROM DATE OF ACCEPTANCE OF THE WORK. SHOULD ANY
<br />TROUBLE DEVELOP DURING THEIR PERIOD DUE TO DEFECTIVE MATERIALS OR FAULTY WORKMANSHIP, THE
<br />CONTRACTOR SHALL FURNISH ALL NECESSARY MATERIALS AND LABOR TO CORRECT THE TROUBLE WITHOUT ANY
<br />COST TO THE OWNER. ANY DEFECTIVE MATERIAL OR INFERIOR WORKMANSHIP NOTED AT THE TIME OF INSTALLATION
<br />SHALL BE CORRECTED IMMEDIATELY TO THE SATISFACTION OF THE OWNER.
<br />B.ALL MAJOR EQUIPMENT COMPONENTS SHALL HAVE THE MANUFACTURER'S NAME, ADDRESS, MODEL NUMBER, AND
<br />SERIAL NUMBER PERMANENTLY ATTACHED IN A CONSPICUOUS MANNER.
<br />2.02 CONDUIT
<br />A.PROVIDE RACEWAYS AS INDICATED ON THE DRAWINGS AND AS HEREIN SPECIFIED. CONDUITS SHALL BE RIGID STEEL
<br />"GRC" (THICK WALL) GALVANIZED; ELECTRICAL METALLIC TUBING "EMT" (THIN WALL); FLEXIBLE STEEL, GALVANIZED;
<br />LIQUID-TIGHT, FLEXIBLE STEEL CONDUIT WITH GROUND BOND; ALUMINUM CONDUIT; OR SCHEDULE 40 PVC.
<br />B.ALL EMPTY CONDUITS (CO) SHALL BE SCHEDULE 40 PVC UNLESS OTHERWISE INDICATED ON THE DRAWING.
<br />C.WHERE CONDUIT CROSSES AN EXPANSION JOINT, PROVIDE APPROVED FITTINGS WHICH ALLOW DEFLECTIONS
<br />EQUIVALENT TO TWICE THE MOVEMENT ALLOWED BY THE DESIGN.
<br />2.03 CONDUCTORS
<br />A.PROVIDE A COMPLETE SYSTEM OF CONDUCTORS IN RACEWAY SYSTEMS AS SHOWN ON THE DRAWINGS AND THEN
<br />HEREIN SPECIFIED.
<br />B.LIGHTING AND POWER CONDUCTORS SHALL BE COPPER, 600 VOLT, TYPE THWN/THHN, NO. 12 MINIMUM UNLESS
<br />OTHERWISE NOTED.
<br />C.CONTROL CONDUCTORS SHALL BE 600V, TYPE THWN/THHN, NO.14 MINIMUM SIZE UNLESS OTHERWISE NOTED.
<br />2.04 FITTINGS
<br />A.CONNECTOR, COUPLING, LOCKNUT, BUSHINGS AND CAPS USED WITH RIGID CONDUIT SHALL BE STEEL, THREADED
<br />AND GALVANIZED. BUSHINGS SHALL BE INSULATED.
<br />B.EMT FITTINGS, CONNECTORS AND COUPLINGS SHALL BE STEEL, ZINC, OR CADMIUM PLATED, COMPRESSION TYPE,
<br />WITH INSULATED THROAT.
<br />C.FLEXIBLE STEEL CONDUIT CONNECTORS SHALL BE TWIST-IN-TYPE WITH INSULATED THROAT. THE FINISH SHALL BE
<br />ZINC OR CADMIUM PLATING.
<br />D.EMT CONDUIT FITTINGS SHALL BE THE COMPRESSION TYPE; SET SCREW FITTINGS SHALL NOT BE USED.
<br />2.05 JUNCTION AND PULL BOXES
<br />A.FOR INTERIOR DRY LOCATIONS, BOXES SHALL BE GALVANIZED ONE-PIECE DRAWN STEEL, KNOCKOUT TYPE WITH
<br />REMOVABLE, MACHINE SCREW SECURED COVERS.
<br />B.ALL BOXES SHALL BE SIZED FOR THE NUMBER AND SIZES OF CONDUCTORS AND CONDUITS ENTERING THE BOX AND
<br />EQUIPPED WITH PLASTER RINGS WHERE REQUIRED.
<br />2.06 OUTLET BOXES
<br />A.FOR FIXTURES, BOXES SHALL BE GALVANIZED, ONE-PIECE DRAWN STEEL, KNOCKOUT TYPE EQUIPPED WITH 3/8"
<br />FIXTURE STUDS AND PLASTER RINGS WHERE REQUIRED.
<br />B.FOR CONVENIENCE OUTLETS, WALL SWITCHES, OR OTHER DEVICES, OUTLET BOXES SHALL BE GALVANIZED
<br />ONE-PIECE DRAWN STEEL, KNOCKOUT TYPE 4"X4"X1-1/2" MINIMUM.
<br />C.FOR LOCATIONS WHERE STANDARD BOXES ARE NOT SUITABLE, SPECIAL BOXES SHALL BE DESIGNED TO FIT SPACE OR
<br />MEET OTHER REQUIREMENTS AND SUBMITTED FOR APPROVAL.
<br />2.07 SWITCHES
<br />A.ALL DEVICES SHALL CONFORM TO NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION (NEMA) STANDARDS AND
<br />SHALL BE UNDERWRITERS' LABORATORIES, INC., (UL) LISTED AND LABELED AND SHALL BE "SPECIFICATION GRADE,"
<br />MEETING THE REQUIREMENTS OF FEDERAL SPECIFICATION WS-896-E, FOR SWITCHES.
<br />1.WALL SWITCHES SHALL BE SPECIFICATION COMMERCIAL GRADE (MINIMUM), FULLY ENCLOSED, QUIET-TYPE TUMBLER
<br />SWITCHES RATED 20 AMPERES, 120/277-VOLT, BAKELITE OR COMPOSITION, BACK AND SIDE WIRED, BUMPER PAD, FULL
<br />RATING FOR INDUCTIVE OR NON-INDUCTIVE LOADS AND INCANDESCENT OR FLUORESCENT LIGHTING LOADS.
<br />2.SINGLE POLE SWITCHES: G.E. 59511, HUBBELL #1221, ARROW #1991 OR PASS & SEYMOUR 20AC1.
<br />3.THREE-WAY QUIET SWITCHES: G.E. 59531, HUBBELL #1223, ARROW #1993 OR PASS& SEYMOUR 20AC3.
<br />4.WALL SWITCH AND PILOT LIGHTS SHALL BE FLUSH MOUNTED COMBINATION WALL TYPE WITH SWITCH AND PILOT LIGHT
<br />EQUIPPED WITH A 6-WATT, 125-VOLT CANDELABRA BASE LAMP. THE PILOT LIGHT SHALL HAVE A GREEN JEWEL WITH
<br />BRASS RIM FLUSH MOUNTED IN THE WALL PLATE.
<br />5.ALL SWITCHES SHALL BE OF THE SAME MANUFACTURE.
<br />6.NORMAL SWITCH COLOR IS WHITE APPROVED BY ARCHITECT/OWNER. SWITCHES CONTROLLING CIRCUITS CONNECTED
<br />TO EMERGENCY POWER SOURCE SHALL BE RED.
<br />7.30 AMP MOTOR RATED SNAP SWITCHES SHALL BE LEVITON MS302-DS. PROVIDED IN NEMA 1 OR 3R ENCLOSURE AS
<br />SHOWN ON DRAWING.
<br />B.SENSOR SWITCH (MOTION SENSOR)
<br />1.WALL SENSOR SWITCH SHALL BE WATT STOPPER DUAL TECHNOLOGY OCCUPANCY SENSOR LEVITON MODEL
<br />#OSSMT-GD (FOR SINGLE POLE SWITCHING) & LEVITON MODEL #OSSMD-GD FOR (DUAL SWITCHING).
<br />2.CEILING SENSOR SWITCH SHALL BE WATT STOPPER DUAL-TECHNOLOGY MODE.
<br />3.PROVIDE 120/277V CEILING SENSOR POWER PACK INSTALLED IN J-BOX NEXT TO LIGHTING CIRCUIT.
<br />2.08 RECEPTACLES
<br />A.DUPLEX RECEPTACLES SHALL BE SPECIFICATION GRADE, 20 AMPS, 125 VOLTS, 3-WIRE, SIDE-WIRED WITH BINDING
<br />SCREWS, PARALLEL SLOTS, U-GROUND, PLASTER EARS AND CAPTIVE MOUNTING SCREWS. BODY SHALL BE
<br />PHENOLIC, PLASTIC, OR BAKELITE. RECEPTACLES SHALL BE HEAVY-DUTY, 3-BLADE CURRENT CARRYING CONTACT
<br />AND DOUBLEWIDE FLAT BLADE GROUND CONTACTS. PROVIDE ARROW HART 5242-I HUBBELL 5242-I OR LEVITON
<br />5242-I.
<br />B.SINGLE RECEPTACLES SHALL BE SPECIFICATION GRADE, GROUNDING TYPE, SIDE-WIRED, WITH BINDING SCREWS, AND
<br />SHALL HAVE STANDARD SIZE IVORY BAKELITE BASE. FOR CIRCUITS CONSISTING OF ONE SINGLE RECEPTACLE ONLY,
<br />AMPERE RATING OF RECEPTACLE SHALL BE THE SAME AS CIRCUIT BREAKER OF FUSE. FOR RECEPTACLES RATED 15
<br />AMPS/125 VOLTS, PROVIDE NEMA 5-15R, ARROW-HART 5251-I. FOR RECEPTACLES RATED 20 AMPS / 125 VOLTS,
<br />PROVIDE NEMA 5-20R, ARROW-HART 5721-I, OR EQUAL.
<br />2.09 DEVICE PLATES
<br />1.PROVIDE PLATES FOR ALL SWITCHES, RECEPTACLES, JUNCTION BOXES, TELEPHONE AND OTHER OUTLETS.
<br />2.PROVIDE ENGRAVED OR ETCHED PLATES FOR ALL LOCK SWITCHES, PILOT SWITCHES, SWITCHES FROM WHICH
<br />EQUIPMENT OR CIRCUIT CONTROLLED CANNOT BE READILY SEEN, THREE OR MORE SWITCHES UNDER A COMMON
<br />PLATE AND FOR SWITCHES AS INDICATED.
<br />3.STAINLESS STEEL PLATES SHALL BE AMERICAN IRON AND STEEL INSTITUTE (AISI) TYPE 302, WITH BEVELED EDGES,
<br />0.040" THICK WITH SATIN SMOOTH FINISH. "SMOOTHIE," HUBBELL #97071 SERIES.
<br />4.PLASTIC COVER PLATE SHALL BE HIGH IMPACT THERMOPLASTIC, HIGH STRENGTH, SCRATCH-RESISTANT, SMOOTH
<br />AND SELF-EXTINGUISHING, HUBBELL "PI" SERIES OR PASS & SEYMOUR RP SERIES.
<br />5.WHERE OUTLETS ARE INDICATED TO BE WEATHERPROOF, PROVIDE AN AISI TYPE 302 STAINLESS WITH DOUBLE HINGED
<br />COVERS, PASS & SEYMOUR #WPD-8.
<br />6.GALVANIZED STEEL PLATES SHALL BE SQUARE OR RECTANGULAR AND HOT DIPPED GALVANIZED OR SHERARDIZED,
<br />BEVELED EDGES AND 0.040" THICK. GALVANIZED STEEL PLATES SHALL BE USED IN UTILITY AREA.
<br />7.PROVIDE PLATES EQUIPPED WITH CLOSE FITTING OPENINGS FOR THE EXACT DEVICE TO BE USED. PROVIDE PLATES
<br />FOR TELEPHONE OUTLETS EQUIPPED WITH BUSHED OPENINGS.
<br />8.REFER TO SECTION 3.08 FOR LABELING OF PLATES.
<br />9.COVER PLATES ON PRESSED STEEL OUTLET BOXES IN FURRED AREAS, ATTICS, ETC., OR EXPOSED IN MECHANICAL
<br />EQUIPMENT ROOMS SHALL BE OF THE SAME MATERIAL AS THE OUTLET BOX.
<br />10.COVER PLATES IN LOCATIONS CONCEALED FROM PUBLIC VIEW SHALL HAVE THE CIRCUIT NUMBERS AND SOURCE
<br />FEED POINT HAND LABELED WITH MARKING BLACK PEN (PERMANENT MARKER). SEE SECTION 3.08 FOR LABELING.
<br />11.PROVIDE PLASTIC COVER PLATES UNLESS NOTED OTHERWISE
<br />2.10 PANELBOARDS
<br />A.FURNISH AND INSTALL ALL BRANCH CIRCUIT PANELBOARDS AS HEREINAFTER SPECIFIED AND AS SHOWN ON THE
<br />DRAWINGS. PANELBOARDS SHALL BE OF THE DEAD FRONT SAFETY TYPE EQUIPPED WITH THE THERMAL MAGNETIC
<br />40°C CIRCUIT BREAKERS.
<br />B.CIRCUIT BREAKERS SHALL BE RATED MINIMUM 10,000 AMPS RMS SYMMETRICAL INTERRUPTING CAPACITY AND SHALL
<br />BE THE NUMBER OF POLES AND CURRENT CAPACITY AS INDICATED ON THE PANEL SCHEDULE. BRANCH CIRCUIT
<br />PANELBOARDS SHALL BE SQUARE-D OR EATON/CUTLER HAMMER WITH LUGS UL LISTED FOR USE WITH 75°C WIRE.
<br />C.DOOR SHALL HAVE A PLASTIC COVERED DIRECTORY FRAME WITH A TYPED IDENTIFICATION CARD OR ALL CIRCUIT
<br />AND PANEL NUMBERS FOR BRANCH CIRCUIT PANELBOARDS.
<br />D.PROVIDE NAMEPLATE FOR ALL PANELBOARDS, ENGRAVED WHITE LETTERS ON BLACK BACKGROUND INSTALL NAME
<br />PLATES ON THE TRIM ABOVE DOOR.
<br />E.ALL WIRING SHALL BE NEATLY ARRANGED AND LACED TOGETHER.
<br />F.ALL CIRCUIT BREAKERS USED FOR HVAC LOADS SHALL BE RATED "HACR".
<br />G.BUS BARS SHALL BE RECTANGULAR IN CROSS SECTION CONSTRUCTED OF COPPER. NEUTRAL AND GROUND BUSES
<br />SHALL BE FULL SIZE.
<br />2.11 INTERIOR LIGHTING FIXTURES
<br />A.FURNISH, INSTALL AND WIRE LIGHTING FIXTURES SCHEDULED OR INDICATED BY TYPE DESIGNATION ON THE
<br />DRAWINGS. IF TYPE DESIGNATION IS OMITTED, FIXTURES SHALL BE OF THE SAME TYPE AS SHOWN FOR ROOMS OF
<br />SIMILAR USAGE. VERIFY BEFORE PURCHASE AND INSTALLATION. NO ALTERNATIVE FIXTURES WILL BE ACCEPTED.
<br />B.LOCATIONS OF FIXTURES ON ELECTRICAL DRAWINGS ARE DIAGRAMMATIC. VERIFY LOCATION AND SPACING WITH
<br />ARCHITECTURAL REFLECTED CEILING PLANS AND OTHER REFERENCE DATA BEFORE PURCHASING. COORDINATE
<br />SPACE CONDITIONS, INCLUDING HEADROOM CLEARANCES AND INTERFERENCES WITH CEILING COMPONENTS SUCH
<br />AS DUCTS, OPENINGS, BEAMS AND PIPING PRIOR TO INSTALLATION.
<br />C.CHECK THE ARCHITECTURAL FINISHES AND, REGARDLESS OF THE CATALOG PREFIXES AND SUFFIXES SHOWN,
<br />FURNISH FIXTURES WITH THE PROPER TRIM, FRAMES, SUPPORTS, HANGERS AND OTHER MISCELLANEOUS
<br />APPURTENANCES OR PROPERLY COORDINATE WITH SAID FINISHES. WHERE REQUIRED, FURNISH REINFORCING FOR
<br />CEILING CONSTRUCTION TO SUPPORT THE WEIGHT OF THE FIXTURES.
<br />D.FIXTURES SHALL BE FREE OF LIGHT LEAKS AND DESIGNED TO PROVIDE SUFFICIENT VENTILATION OF LAMPS AND
<br />BALLASTS, INCLUDING VENT HOLES WHERE REQUIRED. OUTDOOR FIXTURES WITH VENT HOLES SHALL HAVE WIRE
<br />MESH SCREENS IN THE VENT HOLES.
<br />E.REPLACE BLEMISHED, DAMAGED OR UNSATISFACTORY FIXTURES AT NO ADDITIONAL COST TO THE OWNER AND IN A
<br />MANNER SATISFACTORY TO THE ARCHITECT.
<br />F.LAMPS
<br />1.LAMPS SHALL BE NEW AND OF WATTAGE AND TYPE INDICATED OR AS REQUIRED FOR THE PARTICULAR FIXTURE
<br />INSTALLED.
<br />2.UNLESS OTHERWISE NOTED, LAMPS DESCRIBED IN FIXTURE SCHEDULE, ANSI NOMENCLATURE, MANUFACTURED BY
<br />GENERAL ELECTRIC, SYLVANIA, PHILLIPS, OR EQUAL.
<br />3.PROVIDE INCANDESCENT LAMPS AND TUNGSTEN-HALOGEN LAMPS AS 130 VOLT RATED WHENEVER SUCH DESIGNS
<br />ARE AVAILABLE.
<br />4.PROVIDE FLUORESCENT LAMPS AS INDICATED ON THE DRAWINGS. ALL LINEAR FLUORESCENT LAMPS ARE TO BE
<br />INSTALLED WITH THE LABEL FACING THE SAME DIRECTION.
<br />5.PROVIDE HIGH INTENSITY DISCHARGE (H.I.D.) LAMPS OF TYPE AND WATTAGE AS SHOWN ON THE DRAWINGS. LAMPS
<br />SHALL BE COMPATIBLE WITH FIXTURE BALLAST. MANUFACTURERS: G.E. CO., PHILLIPS, SYLVANIA, OR EQUAL.
<br />G.FLUORESCENT BALLASTS
<br />1.PROVIDE BALLASTS ONLY BY MANUFACTURERS PRODUCING EQUIPMENT FOR AT LEAST FOUR YEARS.
<br />2.PROVIDE BALLASTS WITH OPERATION AT INPUT FREQUENCY OF 60 HZ AND INPUT VOLTAGE BETWEEN 100 AND 135
<br />VOLTS FOR 120 VOLT SYSTEMS OR BETWEEN 250 AND 310 VOLTS FOR 277 VOLT SYSTEMS.
<br />3.PROVIDE NON-DIMMING ELECTRONIC BALLAST FOR T-8 FLUORESCENT LAMPS AS SHOWN ON DRAWING. THE BALLAST
<br />SHALL BE UL LISTED CLASS P, AND SOUND LEVEL A OR BETTER. THE BALLAST WITH LAMP OPERATING FREQUENCY
<br />BETWEEN 25 TO 35 KHZ. WITH NO FLICKERING. THE BALLAST SHALL HAVE LOWEST HARMONIC CONTENT AND TOTAL
<br />HARMONIC DISTORTION (NOT TO EXCEED 15% ON TOTAL HARMONIC AND 10% ON THIRD HARMONIC CONTENT).
<br />BALLAST SHALL BE ADVANCE MARK V OR EQUAL.
<br />4.PROVIDE DIMMING ELECTRONIC BALLAST FOR FOUR FEET RAPID START LAMP, SAME CHARACTERISTICS AS SPECIFIED
<br />FOR NON-DIMMING WITH DIMMING CAPABILITIES FROM 100% TO 5% OF FULL LIGHT OUTPUT. MANUFACTURED BY ETTA
<br />OR LUTRON (15% TOTAL HARMONIC AND 10% THIRD HARMONIC CONTENT).
<br />5.BALLASTS FOR EXTERIOR FIXTURES SHALL BE LOW TEMPERATURE TYPE FOR OPERATING AT +20 DEGREES F.
<br />6.PROVIDE HIGH POWER FACTOR BALLASTS (90 PERCENT OR HIGHER) UL LISTED AND CONTAINING NO PCB. BALLAST
<br />SHALL MEET FCC RULES REPORT 18 AND IEEE 587 FOR WITHSTANDING LINE TRANSIENTS.
<br />7.PROVIDE STEEL ENCASED, FULLY POTTED BALLASTS CAPABLE OF STARTING LAMPS AT 0 DEGREES F.
<br />8.BALLAST SHALL MEET FOLLOWING CHARACTERISTICS:
<br />A.BALLAST FACTOR: 80 TO 100%
<br />B.LAMP CURRENT CREST FACTOR: LESS THAN 1.7.
<br />C.FILAMENT VOLTAGE: 2.5 TO 3.6 VOLTS.
<br />D.FLICKER: LESS THAN 1%.
<br />9.PROVIDE BALLASTS WITH BUILT-IN LINE RFI SUPPRESSION AND HAVE SURGE AND TRANSIENT PROTECTED TO 6000
<br />VOLTS.
<br />10.PROVIDE BALLASTS WITH OPERATING TEMPERATURES NOT EXCEEDING 80 DEGREES C. AT ANY POINT ON THE CASE
<br />DURING NORMAL OPERATION.
<br />11.(3) LAMP BALLASTS ARE NOT ACCEPTABLE.
<br />H.HIGH INTENSITY DISCHARGE LAMP BALLASTS
<br />1.PROVIDE HIGH INTENSITY DISCHARGE LAMP BALLASTS AS HIGH POWER FACTOR REGULATING TYPE, CONFORMING TO
<br />APPLICABLE NEMA STANDARDS. INPUT VOLTAGE AND WATTAGES ARE LISTED IN THE FIXTURE SCHEDULE.
<br />2.MINIMUM STARTING TEMPERATURE: MINUS 20 DEGREES F.
<br />3.PROVIDE HIGH INTENSITY DISCHARGE BALLASTS OF THE ENCAPSULATED TYPE WITH LOWEST SOUND RATING
<br />AVAILABLE.
<br />I. EXIT SIGNS LIGHTS SHALL BE LED TYPE AND PROVIDED WITH AN INTEGRAL EMERGENCY BATTERY PACK.
<br />J.LED LIGHT FIXTURES
<br />A.GENERAL:
<br />1.LED LIGHT FIXTURES SHALL BE IN ACCORDANCE WITH IES, NFPA, UL, AS SHOWN ON THE DRAWINGS, AND AS
<br />SPECIFIED.
<br />2.LED LIGHT FIXTURES SHALL BE REDUCTION OF HAZARDOUS SUBSTANCES (ROHS)-COMPLIANT.
<br />3.LED DRIVERS SHALL INCLUDE THE FOLLOWING FEATURES UNLESS OTHERWISE INDICATED:
<br />a.MINIMUM EFFICIENCY: 85% AT FULL LOAD.
<br />b.MINIMUM OPERATING AMBIENT TEMPERATURE: -20 DEG C. (-4 DEG F.)
<br />c.INPUT VOLTAGE: 120 - 277V (±10%) AT 60 HZ.
<br />d.INTEGRAL SHORT CIRCUIT, OPEN CIRCUIT, AND OVERLOAD PROTECTION.
<br />e.POWER FACTOR: >=0.95.
<br />f.TOTAL HARMONIC DISTORTION: <=20%.
<br />g.COMPLY WITH FCC 47 CFR PART 15.
<br />4.LED MODULES SHALL INCLUDE THE FOLLOWING FEATURES UNLESS OTHERWISE INDICATED:
<br />a.COMPLY WITH IES LM-79 AND LM-80 REQUIREMENTS.
<br />b.MINIMUM CRI 80 AND COLOR TEMPERATURE 4000K UNLESS OTHERWISE SPECIFIED IN LUMINAIRE SCHEDULE.
<br />c.MINIMUM RATED LIFE: 50,000 HOURS PER IES L70.
<br />d.LIGHT OUTPUT LUMENS AS INDICATED IN THE LUMINAIRE SCHEDULE.
<br />B.LED DOWNLIGHTS:
<br />1.HOUSING, LED DRIVER, AND LED MODULE SHALL BE PRODUCTS OF THE SAME MANUFACTURER.
<br />C.LED TROFFERS:
<br />1.LED DRIVERS, MODULES, AND REFLECTOR SHALL BE ACCESSIBLE, SERVICEABLE, AND REPLACEABLE FROM BELOW
<br />THE CEILING.
<br />2.HOUSING, LED DRIVER, AND LED MODULE SHALL BE PRODUCTS OF THE SAME MANUFACTURER.
<br />2.12 LOW VOLTAGE SWITCHGEAR - N/A
<br />2.13 CIRCUIT AND MOTOR DISCONNECTS
<br />A.DISCONNECT (SAFETY) SWITCHES SHALL BE FUSED, HEAVY DUTY TYPE SWITCHES MEETING NEMA SPECIFICATIONS.
<br />SWITCHES SHALL BE PROVIDED WITH REJECTION TYPE FUSE BLOCKS. PROVIDE SWITCHES WITH THE NUMBER OF
<br />POLES, THE VOLTAGE, CURRENT AND HORSEPOWER RATINGS AS REQUIRED. PROVIDE EXTERNALLY OPERABLE
<br />QUICK-MAKE, QUICK-BREAK TYPE MECHANISM WITH COVER INTERLOCK AND PADLOCKABLE IN EITHER THE OPEN OR
<br />CLOSED POSITION.
<br />B.SWITCHES SHALL BE NEMA 3R (RAIN TIGHT ENCLOSURE) WHERE INDICATED TO BE OUTDOORS WEATHERPROOF.
<br />C.PROVIDE NAMEPLATE INDICATING EQUIPMENT SERVED. ALL GENERAL SNAP SWITCHES OPERATING MOTOR LOADS
<br />SHALL BE HORSEPOWER RATED OR BE RATED AT LEAST 125% OF THE FULL LOAD CURRENT.
<br />2.15 ELECTRICAL CONNECTIONS
<br />A.UNLESS OTHERWISE NOTED, ALL WIRING FOR MOTORS, STARTERS, CONTROLS, AND EQUIPMENT SHALL BE PROVIDED
<br />BY THE ELECTRICAL CONTRACTOR. WHERE MOTORS FOR MECHANICAL EQUIPMENT ARE FURNISHED BY OTHER
<br />DIVISIONS, WIRING SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR, EXCEPT WHERE WIRED
<br />INTEGRALLY WITH THE EQUIPMENT.
<br />B.CONNECTION AND CONTROL DIAGRAMS FOR ALL MECHANICAL AND CONTROL EQUIPMENT SHALL BE FURNISHED
<br />UNDER OTHER DIVISIONS, AND BE APPROVED BY THE OWNER FOR CONNECTION BY THE ELECTRICAL CONTRACTOR.
<br />2.16 SUPPORTING DEVICES
<br />A.ALL EQUIPMENT CONDUITS SHALL BE SUPPORTED, ANCHORED AND BRACED IN ACCORDANCE WITH THE MOST
<br />STRINGENT CODES AND REQUIREMENTS. COMPLY WITH CHAPTER 23 OF THE LATEST CBC (CALIFORNIA BUILDING
<br />CODE).
<br />PART 3 EXECUTION
<br />3.01 WORKMANSHIP AND COMPLETION OF INSTALLATION
<br />A.WORKMANSHIP AND NEAT APPEARANCE SHALL BE AS IMPORTANT AS THE ELECTRICAL AND MECHANICAL EFFICIENCY.
<br />DEFECTIVE AND DAMAGED MATERIALS SHALL BE REPLACED OR REPAIRED PRIOR TO FINAL INTERPRETATIONS
<br />INCLUDED. ANY DEFICIENCY PERTAINING TO EITHER WORKMANSHIP OR MATERIALS FOUND BY THE INSPECTOR SHALL
<br />BE CORRECTED WITHOUT ADDITIONAL COST TO THE OWNER.
<br />B.THE CONTRACTOR SHALL MAINTAIN ON JOB SITE A SET OF THE WORKING DRAWINGS WHICH SHALL BE UPDATED DAILY
<br />IN DETAIL FOR WORK ACCOMPLISHED. UPON COMPLETION OF THE WORK, A SET OF REPRODUCIBLE CONTRACT
<br />DRAWINGS SHALL BE OBTAINED FROM THE GENERAL CONTRACTOR AND ALL CHANGES AS NOTED ON THE RECORD
<br />SET OF PRINTS SHALL BE INCORPORATED THEREON WITH RED INK IN A NEAT, LEGIBLE, UNDERSTANDABLE AND
<br />PROFESSIONAL MANNER.
<br />C.ALL EQUIPMENT AND MATERIAL CONNECTED WITH THIS PROJECT SHALL BE INSTALLED COMPLETE, THOROUGHLY
<br />CLEANED, AND ALL RESIDUE REMOVED FROM INSIDE SURFACES. EXTERIOR SURFACES OF ALL MATERIAL AND
<br />EQUIPMENT SHALL BE CLEANED AND DELIVERED IN A PERFECT, UNBLEMISHED CONDITION.
<br />D.UPON COMPLETION OF THE INSTALLATION AND AS A CONDITION OF ITS ACCEPTANCE FURNISH ONE COPY OF THE
<br />FINAL INSPECTION CERTIFICATE TO THE OWNER.
<br />3.02 PREPARATION COORDINATION.
<br />A.THE CONTRACTOR SHALL COORDINATE THIS WORK WITH ALL OTHER CONTRACTORS FURNISHING LABOR, MATERIALS
<br />AND WORK, SO THAT THE WORK AS WHOLE SHALL BE EXECUTED AND COMPLETED WITHOUT CONFLICT OR DELAY.
<br />B.EXAMINE THE DRAWINGS AND SPECIFICATIONS AND DETERMINE THE WORK TO BE PERFORMED BY THE ELECTRICAL,
<br />MECHANICAL AND OTHER TRADES. PROVIDE THE TYPE AND AMOUNT OF ELECTRICAL MATERIALS AND EQUIPMENT
<br />NECESSARY TO PLACE THIS WORK IN PROPER OPERATION, COMPLETELY WIRED TESTED AND READY FOR USE. THIS
<br />SHALL INCLUDE ALL CONDUIT, WIRE, DISCONNECTS, RELAYS, AND OTHER DEVICES FOR THE REQUIRED OPERATION
<br />SEQUENCE OF ALL ELECTRICAL, MECHANICAL, AND OTHER SYSTEMS OR EQUIPMENT.
<br />C.PERFORM ALL WORK IN A MANNER WHICH WILL NOT CAUSE UNNECESSARY INCONVENIENCE OR DANGER TO THE
<br />OCCUPANTS, NOR INTERFERE WITH THE ACTIVITIES IN THE BUILDING.
<br />D.THE CONTRACTOR SHALL COORDINATE AND SCHEDULE EACH POWER INTERRUPTION WITH OWNER, AND SHALL
<br />PROVIDE AT LEAST TWO WEEKS NOTICE OF PROPOSED INTERRUPTION AND WORK TO BE ACCOMPLISHED.
<br />3.04 CORE CUTTING, DRILLING, AND PATCHING
<br />A.NO HOLES WILL BE ALLOWED IN ANY STRUCTURAL MEMBERS WITHOUT THE WRITTEN APPROVAL OF THE ARCHITECT
<br />OR STRUCTURAL ENGINEER AND GENERAL CONTRACTOR.
<br />3.05 INSTALLATION
<br />A.WORKMANSHIP IS TO BE NEAT, BY EXPERIENCED WORKMEN WITH ADEQUATE SUPERVISION, AND IN LINE WITH
<br />NORMAL INDUSTRY WORK PRACTICES.
<br />B.MAINTAIN WORKING CLEARANCE AROUND ELECTRICAL EQUIPMENT, IN ACCORDANCE WITH CODE REQUIREMENTS AS A
<br />MINIMUM.
<br />C.WHERE LIGHTING FIXTURES AND OTHER ELECTRICAL ITEMS ARE SHOWN IN CONFLICT WITH LOCATIONS OF
<br />STRUCTURAL MEMBERS AND MECHANICAL OR OTHER EQUIPMENT, FURNISH AND INSTALL ALL REQUIRED SUPPORTS
<br />AND WIRING TO CLEAR THE ENCROACHMENT.
<br />D.VERIFY LOCATION OF EACH OUTLET FOR POWER, SIGNAL, TELEPHONE/DATA, AND EACH LIGHTING FIXTURE WITH
<br />ARCHITECT PRIOR TO ROUGH-IN. INCLUDE IN BID COST OF RELOCATING EACH ITEM WITHIN TEN-FEET RADIUS OF ITS
<br />INDICATED LOCATION.
<br />E.ALL CONDUIT TO BE RUN CONCEALED UNLESS OTHERWISE NOTED. ALL CONDUITS SHALL BE ROUTED OVERHEAD IN
<br />CEILING SPACES. NO CONDUITS SHALL BE PERMITTED IN CONCRETE SLAB, MASONRY WALLS UNLESS SPECIFICALLY
<br />SO INDICATED. CONDUIT SHALL BE RUN SO AS NOT TO INTERFERE WITH OTHER PIPING FIXTURES OR EQUIPMENT.
<br />F.WHERE ALLOWED, EXPOSED CONDUIT RUNS SHALL BE INSTALLED PARALLEL OR PERPENDICULAR TO WALLS,
<br />STRUCTURAL MEMBERS, OR INTERSECTION OF VERTICAL PLANES AND CEILINGS.
<br />G.ALL ELECTRICAL CONDUITS AND OTHER ELECTRICAL RACEWAYS PASSING THROUGH FIRE RATED CEILINGS, SLABS,
<br />CABLE TRAYS, WALLS AND PARTITIONS SHALL BE SEALED TO PREVENT THE SPREAD OF FIRE, SMOKE, AND GASSES.
<br />USE A UL LISTED AND APPROVED FIRE-STOP MATERIAL EQUAL TO RATING OF A WALL OR A FLOOR SLAB PENETRATED;
<br />INSTALLATION OF FIRE-STOP MATERIAL SHALL BE IN ACCORDANCE WITH MANUFACTURERS INSTRUCTIONS.
<br />H.UNLESS WRITTEN PERMISSION IS GRANTED BY THE ARCHITECT, NO MATERIAL SHALL BE MOUNTED ON THE EXTERIOR
<br />WALLS OR PARAPET TOP OF THE BUILDING.
<br />I.ALL ROTATING ELECTRICAL EQUIPMENT SHALL BE SUPPLIED WITH A FLEXIBLE, LIQUID-TIGHT CONDUIT WITH
<br />APPROPRIATE SLACK AND SHALL NOT EXCEED THIRTY-SIX (36) INCHES.
<br />J.ALL POWER WIRING SHALL BE INSTALLED IN CONDUIT.
<br />K.TELEPHONE WIRES SHALL BE PLENUM RATED CABLE FOR MOUNTING IN CEILING SPACES WITHOUT CONDUIT UNLESS
<br />OTHERWISE NOTED.
<br />L.ALL WIRES FOR ALL SYSTEMS SHALL BE CONTINUOUS FROM SWITCH TO TERMINAL OR FURTHEST OUTLET. NO JOINTS
<br />SHALL BE MADE EXCEPT IN PULL, JUNCTION OR OUTLET BOXES, OR IN PANEL OR SWITCHBOARD GUTTERS.
<br />M.ALL RECEPTACLE, CONTROL DEVICE, AND SWITCH MOUNTING HEIGHTS SHALL BE COORDINATED WITH
<br />ARCHITECTURAL ELEVATIONS PRIOR TO ROUGH-IN.
<br />3.06 GROUNDING
<br />A.ALL EQUIPMENT SHALL BE PROPERLY GROUNDED AS INDICATED ON DRAWINGS AND AS REQUIRED BY THE LATEST
<br />EDITION OF APPLICABLE CODES.
<br />B.FURNISH AND INSTALL ALL GROUNDING CONDUCTORS, CONDUIT AND CLAMPS. THE SIZE OF THE GROUNDING
<br />CONDUCTORS SHALL BE NOT LESS THAN THAT SPECIFIED IN THE NEC.
<br />C.BUILDING GROUNDING SYSTEM RESISTANCE TO GROUND SHALL NOT EXCEED 25 OHMS.
<br />D.EACH BRANCH CIRCUIT SHALL BE EQUIPPED WITH CODE SIZE GREEN GROUND, EQUIPMENT WIRE (PER NEC 250-95)
<br />(NOT INDICATED ON DRAWINGS) WITHIN THE SAME CONDUIT FOR ALL CIRCUITS OF PANELBOARDS.
<br />3.07 BRANCH CIRCUITS
<br />A.NO MORE THAN THREE BRANCH CIRCUITS PERMITTED IN ONE CONDUIT UNLESS INDICATED OTHERWISE
<br />3.08 IDENTIFICATION
<br />A.THE FOLLOWING ITEMS SHALL BE EQUIPPED WITH NAMEPLATES:
<br />1.ALL MOTORS, MOTOR STARTERS, CONTROL PANELS, MOTORS CONTROL REMOTE STATIONS.
<br />2.ALL DISCONNECT AND SAFETY SWITCHES, MAIN DISTRIBUTION PANEL FEEDER OVERCURRENT DEVICES AND SPARES,
<br />CIRCUIT EQUIPMENT IN SEPARATE ENCLOSURES.
<br />3.SPECIAL ELECTRICAL SYSTEMS SHALL BE PROPERLY IDENTIFIED AT JUNCTION AND PULL BOXES
<br />4.ALL BRANCH CIRCUIT PANEL BOARDS SHALL HAVE IDENTIFYING ENGRAVED PLASTIC NAMEPLATES. ALSO, PROVIDE A
<br />TYPED DIRECTORY CARD FOR EACH BRANCH CIRCUIT PANELBOARD. THE CARD IS TO BE PLACED ON THE INTERIOR
<br />SIDE OF THE PANELBOARD DOOR BEHIND A CLEAR PLASTIC SHIELD. THE CARD SHALL IDENTIFY EACH CIRCUIT BY
<br />NUMBER, LOAD, AND LOCATION.
<br />5.IN GENERAL, EQUIPMENT SHALL BE IDENTIFIED AS DESIGNATED ON THE ELECTRICAL DRAWINGS. NAMEPLATES FOR
<br />PANELBOARDS AND SWITCHBOARDS SHALL INCLUDE THE PANEL DESIGNATION, VOLTAGE AND PHASE OF THE SUPPLY.
<br />THE NAME OF THE MACHINE SHALL BE THE SAME AS THE NAME USED ON ALL MOTOR STARTERS, DISCONNECTS, AND
<br />P.B STATION NAMEPLATES FOR THAT MACHINE.
<br />B.NAMEPLATES SHALL BE FABRICATED AS FOLLOWS:
<br />1.NAMEPLATE MATERIALS SHALL CONSIST OF 3-PLY, 1/16" LAMINATED PLASTIC WITH WHITE CORE FOR LETTERING AND
<br />BLACK BACKGROUND.
<br />2.CAPITAL LETTERS SHALL BE USED.
<br />3.NAMEPLATES SHALL BE FASTENED WITH CADMIUM-PLATED SELF-TAPPING NO. 6 SCREWS 1/4" LONG
<br />4.THE MINIMUM SIZE OF ALL NAME PLATES AND LETTERING SHALL BE 3/4" HIGH BY 2" LONG WITH 1/4" LETTERS.
<br />3.09 PROTECTION
<br />A.USE ALL MEANS NECESSARY TO PROTECT THE WORK AND MATERIALS FROM LOSS DURING AND AFTER INSTALLATION,
<br />AND PROVIDE ADEQUATE AND PROPER STORAGE FACILITIES DURING THE PROGRESS OF THE WORK. PROVIDE FOR
<br />THE SAFETY AND GOOD CONDITION OF ALL WORK UNTIL FINAL ACCEPTANCE OF THE WORK BY THE OWNER. REPLACE
<br />ALL DAMAGE OR DEFECTIVE WORK, MATERIAL, AND EQUIPMENT AT NO EXPENSE TO THE OWNER BEFORE
<br />REQUESTING FINAL ACCEPTANCE.
<br />3.10 CLEANING OF EQUIPMENT, MATERIAL, AND PREMISES
<br />A.SITE SHALL BE LEFT BROOM CLEAN AFTER COMPLETION OF WORK EACH DAY. UPON COMPLETION OF THE WORK,
<br />LEAVE THE PREMISES CLEAN OF ALL DIRT AND DEBRIS.
<br />B.ALL EQUIPMENT AND MATERIAL CONNECTED WITH THIS PROJECT SHALL BE INSTALLED COMPLETE, THOROUGHLY
<br />CLEANED, AND ALL RESIDUE REMOVED FROM INSIDE SURFACES. EXTERIOR SURFACES OF ALL MATERIAL AND
<br />EQUIPMENT SHALL BE CLEANED AND DELIVERED IN A PERFECT, UNBLEMISHED CONDITION.
<br />3.11 HANDLING OF WIRE AND CABLE
<br />A.HANDLE WIRE AND CABLE SO AS TO AVOID DAMAGE TO CONDUCTORS AND TAKE EVERY PRECAUTION TO AVOID SHARP
<br />BENDING OR SCORING OF THE CABLE. CABLE SHALL NOT BE LAID NOR DRAGGED UPON THE GROUND.
<br />B.THE CONTRACTOR SHALL BE REQUIRED TO REMOVE AND REPLACE AT HIS OWN EXPENSE ALL WIRE AND CABLE
<br />DAMAGED DUE TO IMPROPER HANDLING, AND SHALL PAY FOR THE NEW WIRE OR CABLE.
<br />3.12 TESTING AND INSPECTIONS
<br />A.THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL REQUIRED PERMITS AND ARRANGE ALL REQUIRED INSPECTIONS
<br />FOR THE EXECUTION OF THE WORK UNDER THIS CONTRACT.
<br />B.THE CONTRACTOR SHALL REPLACE ALL DAMAGED OR DEFECTIVE EQUIPMENT OR WORK.
<br />C.ALL CIRCUITS SHALL BE TESTED FOR CONTINUITY AND CIRCUIT INTEGRITY BY THE CONTRACTOR. ADJUSTMENTS
<br />SHALL BE MADE FOR CIRCUITS NOT COMPLYING WITH TESTING CRITERIA.
<br />D.THE CONTRACTOR SHALL FURNISH ALL INSTRUMENTS AND PERFORM ANY ADDITIONAL TESTS REQUIRED BY THE
<br />AUTHORITY HAVING JURISDICTION. CONTRACTOR SHALL ALSO CORRECT ALL FAILURES AND REPLACE ANY DAMAGED
<br />PORTIONS OF THE WORK RESULTING FROM THOSE TESTS. THE COST OF THE FOREGOING ITEMS SHALL BE PAID BY
<br />THE CONTRACTOR.
<br />E.THE CONTRACTOR SHALL FURNISH THE OWNER CERTIFICATES OF INSPECTION AND APPROVAL BY THE ELECTRICAL
<br />INSPECTION AUTHORITY ON ALL WORK COMPETED AS REQUIRED.
<br />F.TITLE 24 REQUIRES THE COMPLETION OF ALL APPLICABLE CERTIFICATES OF INSTALLATION AND CERTIFICATES OF
<br />ACCEPTANCE FOR LIGHTING SYSTEMS. THIS SHALL INCLUDE INDOOR AND OUTDOOR LIGHTING SYSTEMS.
<br />G.CONTRACT DRAWINGS AND SPECIFICATIONS, GENERAL PROVISIONS OF THE CONTRACT, INCLUDING GENERAL AND
<br />SUPPLEMENTARY CONDITIONS, ELECTRICAL PROVISIONS AND DIVISION-1 SPECIFICATION SECTIONS APPLY TO WORK
<br />OF THIS SECTION.
<br />H.COMPLETE ALL TITLE 24 REQUIRED CERTIFICATE(S) OF INSTALLATION (NRCI) AND CERTIFICATE(S) OF ACCEPTANCE
<br />(NRCA) TO BE COMPLETED PER THE CONTRACT DOCUMENTS.
<br />I.RESPONSIBILITIES OF INSTALLING CONTRACTORS
<br />A.A.GENERAL CONTRACTOR (GC)
<br />a.ENSURE THAT ALL CONTRACTORS IDENTIFIED AS THE CONTRACTOR RESPONSIBLE FOR ACCEPTANCE TESTING
<br />AND COMPLETION OF THE TITLE 24 CERTIFICATE(S) OF ACCEPTANCE ARE CERTIFIED BY THE STATE OF
<br />CALIFORNIA OR ITS DESIGNATED BODY TO CONDUCT EACH RESPECTIVE TEST.
<br />A.A.ELECTRICAL CONTRACTOR (EC)
<br />a.VERIFY PROPER INSTALLATION AND PERFORMANCE OF ALL ELECTRICAL SERVICES PROVIDED.
<br />b.COMPLETE TITLE 24 CERTIFICATE(S) OF INSTALLATION AND MANUFACTURER'S PRE-START CHECKLISTS PRIOR
<br />TO SCHEDULING STARTUP/PROGRAMMING OF LIGHTING CONTROL EQUIPMENT.
<br />i.RETAIN CERTIFICATE(S) OF INSTALLATION IN A 3-RING BINDER IN AN ORGANIZED FASHION. BINDER IS TO REMAIN
<br />ON THE JOB SITE
<br />ii.MAKE CERTIFICATE(S) OF INSTALLATION AVAILABLE FOR BUILDING INSPECTOR'S REVIEW.
<br />iii.RETAIN CALIBRATION RECORDS FOR EQUIPMENT PROVIDED WITH MANUFACTURER CALIBRATED SENSORS IN
<br />THE CERTIFICATE(S) OF INSTALLATION BINDER.
<br />iv.CORRECT LABELING OF ALL CIRCUITS WITH CONNECTED EQUIPMENT.
<br />c.COMPLETE THE CERTIFICATE(S) OF ACCEPTANCE PER THE CONTRACT DOCUMENTS.
<br />i.THE COMPANY INSTALLING THE LIGHTING SYSTEMS MUST BE AN AUTHORIZED LIGHTING CONTROLS
<br />ACCEPTANCE TEST EMPLOYER CERTIFIED BY A LIGHTING CONTROLS ACCEPTANCE TEST TECHNICIAN
<br />CERTIFICATION PROVIDER OR INCLUDE IN THEIR BID THE COST OF RETAINING AND OVERSEEING A CONTRACTOR
<br />WHO IS AN AUTHORIZED LIGHTING CONTROLS ACCEPTANCE TEST EMPLOYER TO COMPLETE THE ACCEPTANCE
<br />TESTING.
<br />ii.ALL REQUIRED ACCEPTANCE TESTING MUST BE COMPLETED BY A LIGHTING CONTROLS ACCEPTANCE TEST
<br />TECHNICIAN EMPLOYED BY THE LIGHTING CONTROLS ACCEPTANCE TEST EMPLOYER.
<br />iii.RETAIN CERTIFICATE(S) OF ACCEPTANCE IN A 3-RING BINDER IN AN ORGANIZED FASHION. BINDER IS TO REMAIN
<br />ON THE JOB SITE
<br />iv.UPLOAD ALL CERTIFICATE(S) OF ACCEPTANCE TO THE CALIFORNIA TITLE 24 CERTIFICATES OF ACCEPTANCE
<br />DATABASE, IF, AT THE TIME OF PROJECT COMPLETION, THE DATABASE IS AVAILABLE TO THE PUBLIC.
<br />d.SUCCESSFUL COMPLETION OF THE REQUIRED ACCEPTANCE TESTS IS THE RESPONSIBILITY OF THE INSTALLING
<br />CONTRACTOR. ANY COSTS ASSOCIATED WITH MODIFICATIONS NECESSARY TO OBTAIN COMPLIANCE AND
<br />RE-TESTING OF SYSTEMS SHALL BE INCLUDED IN THE BASE BID OF THIS PROJECT.
<br />3.13 TELEPHONE AND DATA
<br />A.PROVIDE AND INSTALL COMPLETE SYSTEM OF CONDUIT WITH PULL LINES, BACKBOARDS, EQUIPMENT RACK, PULL
<br />BOXES, JUNCTION BOXES, OUTLET BOXES, AND PLASTER RINGS, FOR TELEPHONE/ DATA SYSTEMS, TO BE INSTALLED
<br />AS PART OF THIS BUILDING CONTRACT.
<br />B.PROVIDE OVERHEAD CONDUIT CONNECTIONS BETWEEN THE MAIN TELECOM ROOM AND THE NETWORK RACK.
<br />301 9TH STREET, SUITE 103
<br />REDLANDS, CA 92374
<br />P: (909) 281-8100
<br />E: svela@velaengineering.biz
<br />G:
<br />\
<br />P
<br />r
<br />o
<br />j
<br />e
<br />c
<br />t
<br />
<br />F
<br />i
<br />l
<br />e
<br />s
<br />\
<br />3
<br />1
<br />3
<br />9
<br />
<br />S
<br />a
<br />n
<br />t
<br />a
<br />
<br />A
<br />n
<br />a
<br />
<br />P
<br />o
<br />r
<br />t
<br />o
<br />l
<br />a
<br />
<br />P
<br />a
<br />r
<br />k
<br />
<br />R
<br />e
<br />s
<br />t
<br />o
<br />o
<br />m
<br />
<br />R
<br />e
<br />n
<br />o
<br />v
<br />
<br />&
<br />
<br />A
<br />d
<br />d
<br />
<br />f
<br />o
<br />r
<br />
<br />D
<br />V
<br />D
<br />\
<br />0
<br />1
<br />-
<br />D
<br />r
<br />a
<br />w
<br />i
<br />n
<br />g
<br />s
<br />\
<br />0
<br />1
<br />-
<br />R
<br />e
<br />v
<br />i
<br />t
<br />\
<br />3
<br />-
<br />C
<br />D
<br />\
<br />3
<br />1
<br />3
<br />9
<br />
<br />S
<br />a
<br />n
<br />t
<br />a
<br />
<br />A
<br />n
<br />a
<br />
<br />P
<br />o
<br />r
<br />t
<br />o
<br />l
<br />a
<br />
<br />P
<br />a
<br />r
<br />k
<br />
<br />R
<br />e
<br />s
<br />t
<br />r
<br />o
<br />o
<br />m
<br />
<br />R
<br />e
<br />n
<br />o
<br />
<br />&
<br />
<br />A
<br />d
<br />d
<br />
<br />C
<br />D
<br />_
<br />
<br />C
<br />A
<br />D
<br />
<br />B
<br />a
<br />c
<br />k
<br />g
<br />r
<br />o
<br />u
<br />n
<br />d
<br />s
<br />.
<br />r
<br />v
<br />t
<br />NUMBER DATE INITIALS DESCRIPTION
<br />PREPARED UNDER THE
<br />SUPERVISION OF:
<br />CITY OF SANTA ANA
<br />FILE NO.:
<br />INSTALLEDAPPROVED
<br />CONSTRUCTION COMPLETED:
<br />BENCHMARK NO.: SA-253-70
<br />RECOMMENDED FOR
<br />CONSTRUCTION:
<br />REFERENCES
<br />PUBLIC WORKS AGENCY
<br />XRCE NO.:
<br />ELEV.: 176.00 (2010)
<br />REVISIONS
<br />SHEET OF
<br />BENCHMARK DESCRIPTION:
<br />OCS BM SA-253-70
<br />FD 3 3/4" OCS ALUMINUM BENCH MARK DISK STAMPED "SA-253-70", SET IN NW'LY CORNER OF A 3.5FT X 16FT
<br />CONCRETE CATCH BASIN. MONUMENT IS LOCATED IN THE NE'LY CORNER OF THE INTERSECTION OF GRAND AVE
<br />AND SANTA CLARA AVE, 87FT N'LY OF THE CENTERLINE OF SANTA CLARA AVE AND 39FT E'LY OF THE CENTERLINE
<br />OF GRAND AVE. MONUMENT IS SET LEVEL WITH THE SIDEWALK
<br />PORTOLA PARK
<br />SPLASH PADREVIEWED FOR
<br />CONSTRUCTABLITY:
<br />PRINCIPAL CIVIL ENGINEER
<br />DESIGNED:
<br />PRINCIPAL CIVIL ENGINEER RCE NO.:
<br />RM RM SV
<br />ELECTRICAL ENGINEER
<br />DRAWN:CHECKED:
<br />10
<br />0
<br />%
<br />
<br />S
<br />U
<br />B
<br />M
<br />I
<br />T
<br />T
<br />A
<br />L
<br />.
<br />PS-25-2401
<br />SAMUEL VELA
<br />1700 E. SANTA CLARA AVENUE, SANTA ANA, CA 92705
<br />811
<br />UNDERGROUND SERVICE ALERT. DIAL 811
<br />LOCATION OF UNDERGROUND UTILITIES BY CONTRACTING
<br />BEFORE EXCAVATING, THE CONTRACTOR SHALL VERIFY THE
<br />DAMAGE SUCH FACILITIES OR INTERFERE WITH THEIR SERVICE.
<br />UNDERGROUND FACILITIES PRIOR TO DOING WORK THAT MAY
<br />STEPS TO ASCERTAIN THE EXACT LOCATION OF ALL
<br />THE SPECIAL PROVISIONS. THE CONTRACTOR SHALL TAKE
<br />DIFFERENT FROM THAT WHICH IS SHOWN ON THE PLANS OR IN
<br />UNDERGROUND FACILITIES NOT KNOWN OR IN A LOCATION
<br />ATTENTION IS DIRECTED TO THE POSSIBLE EXISTENCE OF
<br />UNDERGROUND SERVICE ALERT OF SOUTHERN CALIFORNIA
<br />SPECIFICATIONS E3.1
<br />52 57
|