PLUMBING GENERAL NOTES <br />1. ALL EXISTING PIPING SHOWN ARE BASED ON AVAILABLE DRAWINGS AND ON SITE INVESTIGATION AND ASSUMPTION WHERE <br />NECESSARY, AND MAY NOT REFLECT THE ACTUAL INSTALLED EXISTING CONDITION. CONTRACTOR SHALL BE RESPONSIBLE FOR <br />FIELD VERIFICATION OF ALL EXISTING CONDITIONS INCLUDING DEPTHS, SIZES AND LOCATIONS OF EXISTING PIPING FOR NEW <br />P.O.C'S OR DEMOLITION AND ALTERATIONS AS REQUIRED PRIOR TO START OF WORK, INFORM ARCHITECT OF ANY <br />DISCREPANCIES. <br />2. A STATE LICENSED C-36 QUALIFIED INSTALLER AND WITH CERTIFICATE OF QUALIFICATION PER CURRENT PLUMBING CODE SHALL <br />SUPERVISE (MAX 3 PERSONNEL) OR PERFORM THE LABOR OF ALTERING, INSTALLING OR REPAIRING ANY PLUMBING REGULATED <br />BY THIS CODE. A NON-QUALIFIED INSTALLER SHALL NOT BE ALLOWED. <br />3. FINAL REPORT FOR TESTING AND ADJUSTING OF ALL NEW SYSTEMS SHALL BE COMPLETED BY THE CONTRACTOR AND PROVIDED <br />TO THE CITY FIELD INSPECTOR PRIOR TO FINAL APPROVAL OF THE INSTALLED NEW SYSTEM. THE REPORT SHALL BE SIGNED BY <br />THE INDIVIDUAL RESPONSIBLE FOR PERFORMING THESE SERVICES. <br />4. AN OPERATION AND MAINTENANCE MANUAL SHALL BE PROVIDED TO THE FIELD INSPECTOR AT THE TIME OF FINAL INSPECTION. <br />5. CONTRACTOR SHALL BE FULLY RESPONSIBLE FOR MAINTAINING THE CONNECTIVITY AND CONTINUITY OF THE EXISTING <br />PLUMBING SYSTEMS DURING CONSTRUCTION. <br />6. ALL WORK SHALL COMPLY WITH CURRENT PLUMBING CODES, FIRE MARSHALL, BUILDING CODES, GREEN BUILDING STANDARDS <br />CODES, CALIFORNIA ADMINISTRATIVE CODE TITLE 17, 20, 24 AND AUTHORITIES HAVING JURISDICTION'S CODE AMENDMENTS. <br />7. 8-1/2x11 PROJECT MANUALS, INCLUDING SPECIFICATIONS, EQUIPMENT AND FIXTURES AND BUILDING STANDARDS SHALL BE A <br />PART OF THIS WORK. <br />8. ALL WORK/MATERIALS SHOWN ON PLANS SHALL BE NEW UNLESS NOTED OTHERWISE, AND SHALL CONFORM TO ALL LOCAL <br />APPLICABLE CODES AND REGULATIONS. <br />9. BEFORE STARTING ANY WORK, CONTRACTOR SHALL PREPARE COORDINATED SHOP DRAWINGS PER SPECIFICATIONS AND <br />SUBMIT FOR ENGINEER'S REVIEW. THIS INCLUDES EXAMINING THE COMPLETE SET OF DRAWINGS FOR ALL TRADES, INCLUDING <br />ARCHITECTURAL, STRUCTURAL, CIVIL, MECHANICAL, AND ELECTRICAL. VERIFY ALL DIMENSIONS, SPACE REQUIREMENTS, AND <br />POINTS OF CONNECTION TO ALL FIXTURES AND EQUIPMENT. MAKE ANY MINOR ALL REQUIRED ADJUSTMENTS NECESSARY TO <br />AVOID CONFLICTS WITH THE BUILDING STRUCTURE AND THE WORK OF OTHER TRADES AND TO PROVIDE A COMPLETE <br />INSTALLATION. <br />10. BEFORE SUBMITTING PROPOSALS FOR THIS WORK, EACH BIDDER SHALL BECOME FAMILIAR WITH DRAWINGS AND SHALL HAVE <br />EXAMINED THE PREMISES AND BE AWARE OF ALL EXISTING CONDITIONS UNDER WHICH HE WILL BE OBLIGATED TO OPERATE IN <br />PERFORMING HIS CONTRACT. THE CONTRACTOR SHALL NOT BE ENTITLED TO ANY EXTRA COMPENSATION FOR FAILURE TO <br />ALLOW FOR ALL EXISTING CONDITIONS. SUBMITTING OF A BID OR PROPOSAL WILL BE CONSIDERED EVIDENCE OF THE FACT THAT <br />CONTRACTOR IS FULLY AWARE OF THESE CONDITIONS AND IS ABLE TO COMPLETE ALL WORK REQUIRED BY THE DRAWINGS AND <br />SPECIFICATIONS. <br />11. PLUMBING DRAWINGS AND LAYOUTS ARE DIAGRAMMATIC TO SHOW DESIGN INTENT AND FINISHED CONDITIONS. COORDINATE <br />PIPING WITH EXISTING CONDITIONS. IF FIELD CONDITIONS DIFFER SIGNIFICANTLY FROM THOSE SHOWN ON THE DRAWINGS AND <br />AFFECT PLUMBING WORK, INFORM ARCHITECT IMMEDIATELY BEFORE PROCEEDING WITH THE WORK. <br />12. THESE DRAWINGS INDICATE THE FINISHED REQUIREMENTS FOR THE PLUMBING SYSTEMS. DUE TO STRUCTURAL, MECHANICAL <br />DUCT OR PIPING INTERFERENCE, RETAINED EXISTING FACILITIES, OR FOR OTHER REASONS, THE CONTRACTOR MAY DESIRE TO <br />INSTALL THE WORK IN A MANNER DIFFERENT FROM THAT SHOWN. SUCH CHANGES SHALL BE PRESENTED TO THE OWNER'S <br />REPRESENTATIVE FOR APPROVAL BEFORE PROCEEDING, AND THE RECORD DRAWINGS SHALL BE ACCURATELY REVISED TO <br />SHOW THE CHANGES AS COMPLETED. <br />13. IF ANY EQUIPMENT SUBMITTED BY THE CONTRACTOR IS DIFFERENT FROM THAT SPECIFIED, OR REQUIRES CHANGES IN MATERIAL <br />OR LABOR FROM THAT REQUIRED IN THE CONTRACT DOCUMENTS AFFECTING THIS AND/OR OTHER TRADES, SUCH CHANGES <br />SHALL BE SUBMITTED AS SHOP DRAWINGS. SUBMITTALS SHALL INDICATE CREDIT DUE TO OWNER. CONTRACTOR SHALL ALSO BE <br />RESPONSIBLE FOR PAYMENT OF ALL CHARGES RESULTING FROM ADDITIONS OR CHANGES IN THE WORK OF OTHER TRADES <br />NECESSARY TO ACCOMMODATE THE REQUESTED MODIFICATION. ALL CHANGES SHALL BE SHOWN ON CONTRACTOR'S RECORD <br />AND AS-BUILT DRAWINGS. <br />14. PRIOR TO BIDDING, CONTRACTOR TO VISIT SITE AND VERIFY FIELD CONDITIONS, DIMENSIONS, SPACING AND ROUTING OF ALL <br />PLUMBING PIPING. ANY DISCREPANCIES WITH FIELD CONDITIONS AND THESE DOCUMENTS ARE TO BE BROUGHT TO THE <br />ATTENTION OF THE ARCHITECT FOR IMMEDIATE RESOLUTION. COORDINATE WITH OTHER TRADES FOR CLEARANCES AND TIMELY <br />FINISH. <br />15. UNLESS INSTRUCTED OTHERWISE, THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS, LICENSES, AND FEES REQUIRED <br />FOR INSTALLATION OF ALL THE WORK, INCLUDING THE DIVISION OF THE STATE ARCHITECT, LOCAL SUPPLIER OF WATER AND <br />POWER, SOUTHERN CALIFORNIA GAS CO., AND ALL OTHER AGENCIES HAVING JURISDICTION OVER SERVICES TO THIS BUILDING. <br />FURNISH FINAL CERTIFICATE OF INSPECTION INCLUDING WITH THE FIRE MARSHALL, OR WRITTEN EVIDENCE OF ACCEPTANCE BY <br />INSPECTION AUTHORITIES FOR ALL WORK INSTALLED. <br />16. SEE ARCHITECTURAL DRAWINGS FOR EXTENT OF DEMOLITION AND NEW CONSTRUCTION, FOR EXACT PLUMBING FIXTURE <br />LOCATIONS AND QUANTITIES, EQUIPMENT, DEVICES, ETC. <br />17. SUBMIT A COORDINATED SHOP DRAWINGS AND PRODUCT DATA. PROVIDE COMPLETE AND UPDATED AS-BUILT DRAWINGS PRIOR <br />TO COMPLETION OF PROJECT FOR REVIEW BY THE ARCHITECT/ENGINEER. PROVIDE AS-BUILT DRAWINGS VIA ELECTRONIC <br />FORMAT IN AUTOCAD 2018 OR LATEST VERSION. <br />18. PROVIDE A COMPLETE PLUMBING SYSTEM FOR ALL AREAS IN SCOPE OF WORK INCLUDING PLUMBING FIXTURE ROUGH-INS AND <br />ALL UTILITY PIPING. PROVIDE ROUGH-INS, EXTEND ALL PIPING (WASTE, VENT, COLD WATER, HOT WATER, ETC.) TO ALL FIXTURES <br />AND APPLIANCES AS INDICATED ON THE ARCHITECTURAL DRAWINGS. PROVIDE ACCESSIBLE ISOLATION VALVES FOR DCW AND <br />DHW AT EACH INDIVIDUAL PLUMBING FIXTURE (CHROME PLATED ANGLE STOPS) AND EQUIPMENT. <br />19. ALL PLUMBING SYSTEM SHALL BE LISTED FOR ITS INTENDED USE AND SHALL COMPLY WITH THE REQUIREMENTS OF THE <br />AUTHORITIES HAVING JURISDICTION. <br />20. UNLESS OTHERWISE SPECIFIED, ALL PLUMBING ITEMS SHALL BE THE PRODUCT OF MANUFACTURERS REGULARLY ENGAGED IN <br />THEIR MANUFACTURE. ALL ITEMS OF A GIVEN TYPE SHALL BE THE PRODUCTS OF THE SAME MANUFACTURER. <br />21. FURNISH EQUIPMENT AND ACCESSORIES NEW AND FREE FROM DEFECTS. <br />22. SUPPLY NEW EQUIPMENT COMPLETE WITH ALL ACCESSORIES FOR OPTIMUM OPERATION IN ACCORDANCE WITH THE APPLICABLE <br />STANDARDS LISTED AND WITH ALL APPLICABLE NATIONAL, STATE, AND LOCAL CODES. <br />23. PROVIDE SERVICE CLEARANCE FOR ALL VALVES, AND EQUIPMENTS PER MANUFACTURER'S RECOMMENDATIONS. ALL VALVES <br />INCLUDING BEHIND ACCESS DOORS SHALL BE WITHIN 24" REACHABLE DISTANCE. <br />24. BARRIER FREE PLUMBING FIXTURES SHALL BE MOUNTED AT REQUIRED HEIGHTS AND INSTALLED WITH ALL RELATED <br />ACCESSORIES AND SPACES AS REQUIRED BY THE CALIFORNIA OFFICE OF THE STATE ARCHITECT AND AMERICANS WITH <br />DISABILITIES ACT (ADA). ALL FIXTURE TRAPS, PIPING AND VALVES UNDER THE FIXTURE SHALL BE INSULATED WITH A FACTORY <br />PREFORMED INSULATION IN COMPLIANCE WITH ASTM E 84 AND IAPMO PS 94-2012. <br />25. PLUMBING SYSTEM COMPONENTS AND EQUIPMENTS SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE MANUFACTURERS' <br />INSTRUCTIONS, RECOMMENDATIONS AND APPLICABLE CODES. PROVIDE ALL FITTINGS, TRANSITIONS, VALVES, AND ALL <br />ACCESSORIES AND DEVICES REQUIRED FOR A COMPLETE WORKABLE INSTALLATION <br />26. PROVIDE PIPING ISOLATION ON STUD WALL USING 1/4" FELT OR NEOPRENE ISOLATION, OR APPROVED SMWF ISOLATOR. <br />27. COORDINATE ALL SHUT-DOWN OF THE DOMESTIC WATER SYSTEMS WITH THE BUILDING ENGINEER PRIOR TO START OF WORK. <br />28. PROTECT IN PLACE ALL USED AND ACTIVE PIPING BELOW AND ABOVE CEILING, AND BELOW SLAB. <br />29. KEEP ALL PIPING CLEAR FROM LOAD BEARING FOOTINGS. COORDINATE WITH STRUCTURAL ENGINEER FOR UNDERGROUND PIPE <br />ROUTING. <br />30. ALL EXISTING ABANDONED SAN. & VENT PIPING AND STUBOUTS FROM DEMOLISHED PLUMBING FIXTURES SHALL BE REMOVED, <br />AND EXISTING PIPING SHALL BE CAPPED WHERE THEY ARE OUT OF SIGHT. SLAB SHALL BE FINISHED TO MATCH EXISTING. <br />CONCRETE FILL OF STUBOUTS ARE NOT ACCEPTABLE AND SHALL NOT BE PERMITTED. <br />31. NEW OR REPAIRED POTABLE WATER SYSTEMS SHALL BE DISINFECTED PRIOR TO USE ACCORDING TO THE METHOD SET IN <br />DIVISION 22 SPECIFICATIONS OR CURRENT PLUMBING CODE, WHICHEVER IS MORE STRINGENT. IF NO METHOD WAS MANDATED <br />BY THE SPECIFICATION AND BY THE LOCAL HEALTH AUTHORITY, DISINFECT ACCORDING TO CURRENT PLUMBING CODE. <br />32. ALL VENTS THRU ROOF SHALL BE MINIMUM OF THREE FEET VERTICALLY AND TEN FEET HORIZONTALLY FROM AIR CONDITIONING <br />EQUIPMENT FRESH AIR INTAKES, WINDOWS, DOORS OR OTHER OPENINGS, AND SHALL COMPLY WITH CURRENT PLUMBING CODE. <br />33. PROVIDE PIPE SLEEVES TO ALL PIPING PASSING THROUGH NEW MASONRY, CONCRETE, STRUCTURAL WALL. PROVIDE FIRE <br />RATED CAULKING OF SAME RATING AS THE WALL AND SHALL BE OF APPROVED MATERIALS. <br />34. A MINIMUM 1/2" CLEARANCE SHALL BE PROVIDED AROUND PIPES AT ALL PENETRATIONS THROUGH WALLS AND ROOF. THE GAP <br />SHALL BE PACKED TIGHTLY WITH LOOSE, LIGHTWEIGHT INSULATION THROUGH NON RATED WALLS, AND APPROVED U.L. LISTED <br />FIRE SAFING MATERIAL THROUGH RATED WALLS TO MATCH WALL RATING. <br />PLUMBING GENERAL NOTES (CONT.) <br />VALVES <br />CLEANOUT <br />ELBOW DOWN <br />ELBOW DOWN TO TEE <br />ELBOW UP <br />END CAP <br />TEE DOWN <br />TEE UP <br />UNION <br />P-TRAP <br />TEE SIDE OUTLET DOWN <br />VENT THROUGH ROOF <br />FITTINGS <br />SYMBOLS LEGEND <br />DETAIL REFERENCE <br />DETAIL NO. 1 <br />FOUND IN P3.0 <br />PLAN TITLE NO. -1 <br />SECTION MARK <br />SECTION NO. 1 <br />FOUND IN P4.0 <br />DETAIL/FLOOR PLAN <br />BOUNDARY NO. 1 <br />FOUND IN P2.0 <br />SHEET KEYNOTE <br />REVISION CLOUD <br />(DELTA 1) <br />EQUIPMENT TAG <br />DESIGNATION WH <br />DESIGNATION NUMBER 1 <br />POINT OF CONNECTION <br />POINT OF DISCONNECTION <br />PLUMBING LINES <br />ANNOTATION <br />1 VIEW TITLE <br />SCALE <br />35. ROOF CONTRACTOR TO PROVIDE WATER TIGHT SEAL AROUND ALL NEW PENETRATIONS THRU ROOF. REFER TO ARCHITECTURAL <br />DWGS. FOR DETAILS OF PIPE PENETRATIONS THRU ROOF. <br />36. PROVIDE AND INSTALL WATER HAMMER ARRESTORS WITH ACCESS PANELS OF REQUIRED SIZE AT ALL QUICK CLOSING VALVES, <br />MANUFACTURER AND MODEL NUMBER SHALL BE PER SPECIFICATIONS AND SIZES PER MANUFACTURER REQUIREMENTS. <br />37. ALL CLEANOUTS SHALL BE ACCESSIBLE. CLEANOUTS SHALL BE INSTALLED PER CURRENT PLUMBING CODE REQUIREMENTS. <br />PROVIDE WALL CLEANOUT ACCESS COVERS SIMILAR TO JR SMITH 4700 SERIES. COORDINATE COLOR AND FINISH WITH <br />ARCHITECT. PROVIDE A CLEANOUT FOR EVERY FIXTURE IN RESTROOM, AT EACH URINAL VENT ABOVE SANITARY TEE <br />CONNECTION, AT END OF SANITARY SEWER RUN, AT EACH END OF SANITARY LINE SERVING PLUMBING FIXTURES. ON THE <br />HORIZONTAL RUN OF WASTE PIPING THAT IS MORE THAN 75 FEET IN TOTAL DEVELOPED LENGTH, PROVIDE CLEANOUTS AT EVERY <br />75 FEET, OR FRACTION THEROF. <br />38. SLOPE OF BUILDING SEWERS SHALL NOT BE LESS THAN 2% UNLESS OTHERWISE APPROVED BY THE AUTHORITY HAVING <br />JURISDICTION. <br />39. ALL PIPING AND EQUIPMENT SUPPORT AND SEISMIC BRACING IS A CONTRACTOR DESIGN AND BUILD RESPONSIBILITY IN <br />ACCORDANCE TO GUIDELINES FOR SEISMIC RESTRAINTS OF PLUMBING SYSTEMS PER SMACNA CURRENT EDITION; CHAPTER 6 OF <br />CBC-2022; CHAPTER 3 OF CPC-2022; AND OSHPD PRE-APPROVED NO. R0010. PROVIDE PIPE SUPPORT TO ALL UNDER-SLAB ABOVE <br />GROUND P-TRAPS. <br />40. ALL FLOOR DRAINS SHALL BE PROVIDED WITH CODE-APPROVED ACCESSIBLE TRAP PRIMERS. CONCEALED TRAP PRIMER VALVES <br />SHALL BE PROVIDED WITH ACCESS PANELS. <br />41. EXISTING FLOOR REQUIRING CORING OR SAWCUTTING SHALL BE PATCHED FOR INSTALLATION OF NEW FIXTURES AND PIPING AS <br />REQUIRED TO MATCH EXISTING SLAB RATING. <br />42. GET APPROVAL FROM THE STRUCTURAL ENGINEER IN CORE DRILLING EXISTING CONCRETE FLOOR AND WALL SLAB. USE CARE <br />AND CAUTION IN CORING EXISTING REINFORCED CONCRETE SLAB. USE X-RAY TO VERIFY EXISTING REINFORCED BARS TO AVOID <br />CUTTING OR DAMAGING THEM. COORDINATE ALL STRUCTURAL CUTTING, DRILLING, PATCHING AND REINFORCING REQUIRED FOR <br />PLUMBING WORK WITH THE GENERAL CONTRACTOR AND REQUIREMENTS OF STRUCTURAL ENGINEER. <br />43. LAVATORIES SHALL HAVE ASSE 1070 CONTROLS TO LIMIT THE WATER TEMPERATURE TO 105 DEG. F. OR LESS AS DIRECTED IN <br />SCHEDULE. <br />44. PENETRATIONS INTO OR THROUGH THE EXIT PASSAGEWAY ARE PROHIBITED PER CURRENT BUILDING CODE THAT IS APPLICABLE <br />TO THIS PROJECT, EXCEPT FOR THOSE SERVING THE EXIT PASSAGEWAY SUCH AS FIRE SPRINKLER PIPING, AND STANDPIPES IN <br />ACCORDANCE WITH NFPA STANDARDS. <br />45. ALL BACKFLOW DEVICES SHALL BE TESTED BY A CERTIFIED BACKFLOW TESTING TECHNICIAN WITH THE RESULTS DOCUMENTED <br />ON FORMS PROVIDED BY THE DEPT. OF HEALTH SERVICES CROSS CONNECTION CONTROL DIVISION. THE FORMS SHALL BE <br />REGISTERED WITH THE ABOVE AGENCY AND COPIES OF THE FORMS SHALL BE PRESENTED TO THE INSPECTOR PRIOR TO FINAL <br />APPROVAL. <br />46. ALL PIPING SHALL BE PROVIDED WITH SEISMIC JOINTS OR SEISMIC LOOP CONNECTIONS WHERE STRUCTURAL SEISMIC JOINT <br />OCCURS. SEISMIC JOINTS SHALL BE ICBO LISTED AND OR APPROVED BY 3RD PARTY TESTING LABS. REFER TO STRUCTURAL <br />DRAWINGS FOR ALLOWABLE MOVEMENT FOR EACH JOINT. <br />47. ALL PLUMBING SYSTEMS IN WATER UTILITY DISTRIBUTION PIPING WITHIN THE SCOPE OF WORK INCLUDING PIPE, FITTING, VALVE, <br />SOLDER AND FLUX, FIXTURE AND FAUCET INTENDED TO CONVEY OR DISPENSE WATER FOR HUMAN CONSUMPTION THROUGH <br />DRINKING OR COOKING (WITH LAVATORY, SINK, DRINKING FOUNTAIN, WATER DISPENSER, ETC.) SHALL MEET THE NSF/ANSI <br />STANDARD 61 ANNEX F, NSF/ANSI 372, SAFE DRINKING WATER ACT (SDWA), AND CALIFORNIA HEALTH SAFETY CODE SECTION <br />116875 (LEAD FREE) REQUIREMENTS. <br />48. ALL BRANCH LINES FOR DOMESTIC HOT AND COLD WATER SHALL BE PROVIDED WITH LINE SIZED ISOLATION VALVE WITH ACCESS <br />DOOR. <br />49. ALL SOV SHALL BE FULL-PORT BALL VALVE APPROVED BY LOCAL AHJ. BUTTERFLY VALVE SHALL NOT BE ALLOWED. <br />50. ALL LAVATORY FAUCETS SHALL BE SELF-CLOSING OR METERED TYPE AS REQUIRED BY LOCAL AHJ. <br />51. ALL FIXTURES, EQUIPMENT, FITTINGS, AND MATERIALS SHALL BE LISTED. <br />1 <br />P3.0 <br />1 <br />P4.0 <br />1 <br />P2.0 <br />1 <br />1 <br />WH <br />1 <br />TEE SIDE OUTLET UPCOLD WATER <br />HOT WATER <br />VENT LINE <br />WASTE LINE <br />DRAINS <br />FLOOR DRAIN <br />BALL VALVE <br />COLD WATER <br />FIXTURE UNITS <br />FIXTURE COUNT F.U.TOTAL <br />30.5TOTAL FIXTURE UNITS <br />WC 3 5 15 <br />L 2 1 2 <br />U 2 4 8 <br />1ST HB 2.52.51 <br />ADDITIONAL HB 213 <br />WASTE & VENT PIPE SIZING <br />MAXIMUM UNITS DRAINAGE PIPING <br />PIPE SIZE 1 1/4 1 1/2 2 3 4 6 8 10 <br />VERTICAL 1 2 16 48 256 1,380 3,600 5,600 <br />HORIZONTAL 1 1 8 35 216 720 2,640 4,680 <br />MAXIMUM LENGTH DRAINAGE PIPING <br />VERTICAL <br />HORIZONTAL <br />45 65 85 212 300 510 750 - <br />UNLIMITED <br />VENT PIPING HORIZONTAL & VERTICAL <br />MAXIMUM UNITS 1 8 24 84 256 1,380 3,600 - <br />MAXIMUM LENGTH 45 60 120 212 300 510 750 - <br />NOTES: <br />1. BASED ON 1/4" PER FOOT SLOPE. REFER TO CPC TABLE 703.2 FOR <br />ADDITIONAL NOTES. <br />PIPE INSULATION THICKNESS <br />FLUID TEMPERATURE <br />RANGE (°F) <br />NOMINAL PIPE DIAMETER (IN) <br /><1 1 - 1.5 1.5 - 4 4 - 8 >8 <br />105 - 140 INCHES <br />R-VALUE <br />1.0 <br />R-7.7 <br />1.5 <br />R-12.5 <br />1.5 <br />R-11 R-9 R-8 <br />1.5 1.5 <br />FLUID TEMPERATURE <br />RANGE (°F) <br />NOMINAL PIPE DIAMETER (IN) <br /><1 1 - 1.5 1.5 - 4 4 - 8 >8 <br />40 - 60 <br />BELOW 40 <br />INCHES <br />R-VALUE <br />0.5 <br />R-3 <br />INCHES <br />R-VALUE <br />0.5 <br />R-3 <br />1.0 <br />R-7 R-6 R-5 <br />1.0 1.0 <br />1.0 <br />R-8.5 <br />1.5 <br />R-14 <br />1.5 <br />R-12 R-10 R-9 <br />1.5 1.5 <br />DUCT <br />DUCTWORK (NEW) <br />DUCT TRANSITION <br />VANED ELBOW <br />RADIUS ELBOW <br />DUCT FITTING <br />(SEE DETAILS) <br />T <br />VOLUME DAMPER <br />THERMOSTAT <br />DAMPERS AND CONTROLS <br />DIFFUSER <br />SIDEWALL EXHAUST <br />REGISTER <br />PIPE MATERIAL SCHEDULE <br />SERVICE <br />COLD WATER <br />(ABOVE GROUND) <br />PIPE MATERIAL <br />TYPE "L" COPPER <br />JOINT TYPE <br />SOLDERED <br />PRESSURE FITTING <br />MATERIAL <br />CAST BRONZE/ <br />WROUGHT COPPER <br />SHUT-OFF RATING <br />(PSI) <br />125 <br />VALVE <br />BALL <br />GATE <br />CHECK <br />HOT WATER <br />(ABOVE GROUND)TYPE "L" COPPER SOLDERED CAST BRONZE/ <br />WROUGHT COPPER 125 BALL <br />GATE <br />SANITARY WASTE <br />(BELOW GROUND) <br />NO-HUB CAST IRON <br />SCHEDULE 40 ABS <br />(IF APPROVED BY <br />ARCHITECT OR MTN) <br />NO-HUB <br />SOLVENT-WELD <br />N/A <br />ABS N/A N/A <br />VENT N/A N/A <br />SANITARY WASTE <br />(ABOVE GROUND) <br />SCHEDULE 40 ABS SOLVENT-WELD ABS N/A N/ANO-HUB N/ANO-HUB CAST IRON <br />SCHEDULE 40 ABS SOLVENT-WELD ABS <br />NO-HUB N/ANO-HUB CAST IRON <br />AIR DISTRIBUTION SCHEDULE <br />TAG DESCRIPTION FINISHMANUF. / MODEL ACCESSORIES <br />CE KRUEGER <br />S585 <br />EXHAUST SIDEWALL <br />GRILLE STANDARD WHITE - <br />APPLICABLE CODES <br />PROJECT SHALL COMPLY WITH, BUT NOT LIMITED TO THE FOLLOWING CODES: <br />1. 2022 CALIFORNIA BUILDING CODE (CBC) <br />2. 2022 CALIFORNIA MECHANICAL CODE (CMC) <br />3. 2022 CALIFORNIA ELECTRICAL CODE (CEC) <br />4. 2022 CALIFORNIA PLUMBING CODE (CPC) <br />5. 2022 CALIFORNIA FIRE CODE (CFC) <br />6. 2022 CALIFORNIA ENERGY CODE (CEC) <br />7. 2022 CALIFORNIA GREEN BUILDING CODE (CALGREEN) <br />ENERGY CONSERVATION NOTES <br />1. ALL WATER FAUCETS AND SHOWER HEADS SHALL BE PROVIDED WITH CODE APPROVED FLOW RESTRICTORS. LAVATORY <br />FAUCETS AND SINK FAUCETS (NOT INCLUDING SERVICE SINK FAUCETS) SHALL MEET THE FLOW REQUIREMENTS OUTLINED IN <br />2022 CALIFORNIA GREEN BUILDING STANDARDS, CODE, AND APPLIANCE EFFICIENCY STANDARDS AND SPECIFICATIONS. <br />2. ALL PLUMBING FIXTURES SHALL BE CERTIFIED TO THE CALIFORNIA GREEN BUILDING STANDARDS CODE (CALGREEN) (WATER <br />CLOSET 1.28 GPF, SHOWER HEAD 1.8 GPM, RESIDENTIAL LAVATORY 1.2 GPM, AND KITCHEN FAUCETS 1.8 GPM). <br />1. LOCATION OF DUCTWORK IS APPROXIMATE. ALL DRAWINGS AND LAYOUT ARE DIAGRAMMATIC TO SHOW DESIGN INTENT ONLY. <br />CONTRACTOR TO COORDINATE ALL DUCTWORK AND PIPING WITH ALL OTHER WORK .IF FIELD CONDITIONS DIFFER SIGNIFICANTLY <br />FROM THOSE SHOWN ON THE DRAWINGS AND AFFECT WORK, INFORM ARCHITECT IMMEDIATELY BEFORE PROCEEDING WITH THAT <br />AREA. <br />2. ALL WORK SHALL COMPLY WITH THE STATE OF CALIFORNIA BUILDING CODE, TITLE 24 ENERGY CODE, CALGREEN, [INTERNATIONAL <br />BUILDING CODE, INTERNATIONAL ENERGY EFFICIENCY CODE] AND ALL OTHER GOVERNING CODES AND ORDINANCES. <br />3. CONTRACTOR WILL BE HELD RESPONSIBLE TO HAVE VISITED AND EXAMINED THE PREMISES PRIOR TO SUBMITTING HIS PROPOSAL <br />IN ORDER TO UNDERSTAND THE EXISTING CONDITIONS RELATED TO HIS WORK. <br />4. SUPPORT ALL DUCTWORK FROM BUILDING STRUCTURE AND/OR FRAMING IN AN APPROVED MANNER, WHERE OVERHEAD <br />CONSTRUCTION DOES NOT PERMIT FASTENING OF SUPPORTS FOR EQUIPMENT, FURNISH ADDITIONAL FRAMING. <br />5. UNDER NO CIRCUMSTANCE WILL THIS CONTRACTOR OR HIS WORKMEN BE PERMITTED TO USE ANY PART OF THE BUILDING AS A <br />SHOP EXCEPT PARTS AS DESIGNATED FOR SUCH USE. <br />6. STORE ALL MATERIALS IN DESIGNATED AREAS. <br />7. NEW WORK AND EQUIPMENT SHALL BE THOROUGHLY CLEANED AND MADE READY FOR USE. <br />8. SUBMISSION OF A PROPOSAL SHALL BE EVIDENCE THAT A CAREFUL EXAMINATION OF THE SITE, DRAWINGS & SPECIFICATIONS <br />HAVE BEEN MADE AND THE CONTRACTOR IS FAMILIAR WITH THOSE ITEMS AND AREAS THAT WILL PRESENT DIFFICULTY TO THE <br />PERFORMANCE OF THIS CONTRACT. LATER CLAIMS SHALL NOT BE MADE FOR LABOR, EQUIPMENT, ETC. NECESSARY TO COMPLETE <br />ALL WORK AS A RESULT OF DIFFICULTIES ENCOUNTERED WHICH COULD HAVE BEEN FORESEEN. <br />A. CONTRACTOR TO VERIFY THE EXISTING CONDITIONS BEFORE CONSTRUCTION; CONFIRMING SIZES AND LOCATIONS OF ALL <br />EXISTING PIPING PRIOR TO START OF WORK. <br />B. ALL DIMENSIONS AND EXISTING CONDITIONS SHALL BE CHECKED AND VERIFIED BY THE CONTRACTOR AT THE SITE BEFORE <br />PROCEEDING WITH ANY WORK. <br />C. PRIOR TO STARTING DEMOLITION, DETERMINE LOCATIONS AND EXISTING CONDITIONS. <br />9. PROVIDE ALL REQUIRED LABOR, MATERIALS, EQUIPMENT, AND SERVICES NECESSARY FOR A COMPLETE AND SAFE INSTALLATION <br />OF MECHANICAL IN FULL CONFORMITY WITH REQUIREMENTS OF ALL AUTHORITIES HAVING JURISDICTION; ALL AS INDICATED ON <br />DRAWINGS AND/OR HEREIN SPECIFIED FOR THE SYSTEMS INCLUDED. WORK SHALL BE INSTALLED IN A NEAT, WORKMANLIKE <br />MANNER. INCLUDE ALL COSTS FOR PERMITS, LICENSES, CERTIFICATES, FILING AND INSPECTIONS REQUIRED BY AUTHORITIES <br />HAVING JURISDICTION. <br />10. REFER TO ARCHITECTURAL DRAWINGS FOR ADDITIONAL INFORMATION NOT SHOWN ON MECHANICAL DRAWINGS. <br />11. ALL WORK MUST BE COORDINATED AROUND THE OPERATION OF THE FACILITY. <br />12. ALL APPLICABLE CODES, LAWS AND REGULATIONS GOVERNING OR RELATING TO ANY PORTION OF THIS WORK ARE HEREBY <br />INCORPORATED INTO AND MADE A PART OF THESE CONSTRUCTION DOCUMENTS AND THEIR PROVISIONS SHALL BE CARRIED OUT <br />BY THE CONTRACTOR WHO SHALL INFORM THE OWNER, PRIOR TO SUBMITTING A PROPOSAL OF ANY WORK OR MATERIALS WHICH <br />VIOLATE ANY OF THE ABOVE LAWS AND REGULATIONS. ANY WORK DONE BY THE CONTRACTOR CAUSING SUCH VIOLATION SHALL <br />BE CORRECTED BY THE CONTRACTOR. <br />13. THE CONTRACTOR SHALL RESTORE ALL AREAS DISTURBED DURING CONSTRUCTION TO THEIR ORIGINAL STATE. <br />14. THE CONTRACTOR SHALL KEEP ALL EQUIPMENT AND MATERIALS, AND ALL PARTS OF THE BUILDING, EXTERIOR SPACES AND <br />ADJACENT STREETS, SIDEWALKS AND PAVEMENTS, FREE FROM MATERIAL AND DEBRIS RESULTING FROM THE EXECUTION OF THIS <br />WORK. EXCESS MATERIALS WILL NOT BE PERMITTED TO ACCUMULATE EITHER ON THE INTERIOR OR THE EXTERIOR. <br />MECHANICAL GENERAL NOTES <br />UP TO 12" DD, SS <br />GAUGEDUCT SIZE TRANSVERSE JOINT <br />26 <br />BRACING <br />NONE <br />DUCT GAUGE SCHEDULE <br />RECTANGULAR <br />NOTE: <br />LOW PRESSURE DUCT: GAUGES, TRANSVERSE JOINTS, SPACING OF JOINTS AND INTERMEDIATE BRACING SHALL BE AS TABULATED <br />ABOVE, IN WHICH TRANSVERSE JOINTS ARE SHOWN SS FOR S-STOP, DS FOR DRIVE SLIP, PS FOR POCKET SLIP, AND BS FOR BAR SLIP, <br />PS AND BS LAPPED AND RIVETED AT CORNERS. INTERMEDIATE BRACING WHERE SHOWN MAY BE OMITTED IF DUCT SECTIONS OF FOUR <br />FEET (4'-0") OR LESS ARE USED. MAXIMUM SPACING OF BRACING - FOUR FEET (4'-0") <br />CLEANOUT TO GRADE / <br />FLOOR CLEANOUT <br />WATER CALCULATIONS <br />(A) PRESSURE AVAILABLE <br />(B) TOTAL FIXTURES <br />(C) WATER DEMAND (40 GPM FROM RR + 25 GPM SPLASH PAD) <br />(D) RESIDUAL PRESSURE REQUIRED <br />(E) PRESSURE LOSS DUE TO HIGHEST FIXTURE <br />(F) PRESSURE LOSS THRU PRV <br />(G) PRESSURE LOSS THRU BP <br />(H) PRESSURE LOSS THRU METER <br />(I) TOTAL SYSTEM PRESSURE LOSS <br />(J) PRESSURE AVAILABLE FOR FRICTION LOSS <br />(K) TOTAL DEVELOPED PIPE LENGTH <br />(L) FRICTION LOSS PER 100 FT OF PIPE <br />76.0 <br />30.5 <br />65 <br />35.0 <br />8.7 <br />2.0 <br />5.0 <br />3.7 <br />54.4 <br />21.6 <br />465 <br />4.6 <br />PSI (FROM CITY) <br />FU <br />GPM <br />PSI <br />PSI <br />PSI <br />PSI <br />PSI <br />PSI (D THRU H) <br />PSI (A MINUS I) <br />FT (+25% INCLUDED <br />FOR FITTINGS) <br />PSI/100FT <br />PRESSURE REDUCING <br />VALVE <br />COLD WATER <br />PIPE SIZING CHART <br />PIPE SIZE <br />(IN.)GPM <br />1/2 <br />FLUSH TANK FLUSH VALVE <br />FLOW <br />VELOCITY <br />(FPS) <br />FIXTURE UNITS <br />3/4 <br />1 <br />2 <br />3 <br />4 <br />1-1/4 <br />1-1/2 <br />2-1/2 <br />2.2 1 02.8 <br />5.8 7 03.8 <br />12 15 04.5 <br />20 30 05.2 <br />33 60 156.0 <br />78 275 1406.8 <br />120 475 3508.0 <br />175 800 7508.0 <br />275 1,550 1,5508.0 <br />NOTES: <br />1. BASED ON PRESSURE DROP OF 4.0 PSI/100FT OF PIPE AND MAX <br />PIPE VELOCITY OF 8 FPS, CPC APPENDIX A CHART 105.1. <br />COLD WATER <br />(BELOW GROUND)TYPE "K" COPPER BRAZED CAST BRONZE/ <br />WROUGHT COPPER 125 BALL <br />GATE <br />UNDERGROUND SERVICE ALERT OF SOUTHERN CALIFORNIA <br />811 <br />ATTENTION IS DIRECTED TO THE POSSIBLE EXISTENCE OF <br />UNDERGROUND FACILITIES NOT KNOWN OR IN A LOCATION <br />DIFFERENT FROM THAT WHICH IS SHOWN ON THE PLANS OR IN <br />THE SPECIAL PROVISIONS. THE CONTRACTOR SHALL TAKE <br />STEPS TO ASCERTAIN THE EXACT LOCATION OF ALL <br />UNDERGROUND FACILITIES PRIOR TO DOING WORK THAT MAY <br />DAMAGE SUCH FACILITIES OR INTERFERE WITH THEIR SERVICE <br />BEFORE EXCAVATING. THE CONTRACTOR SHALL VERIFY THE <br />LOCATION OF UNDERGROUND UTILITIES BY CONTRACTING <br />UNDERGROUND SERVICES ALERT. DIAL 811 <br />H AINROFILACFOETATS <br />REENIGNELANOISSEFORPDERETSIGERNo. 37151 <br />EXP. 12-31-2026 <br />BRIAN E .GRAHAM <br />MEC LACINA <br />©2 <br />0 <br />2 <br />5 <br /> <br />M <br />T <br />N <br /> <br />E <br />n <br />g <br />i <br />n <br />e <br />e <br />r <br />i <br />n <br />g <br />. <br /> <br />A <br />l <br />l <br /> <br />R <br />i <br />g <br />h <br />t <br />s <br /> <br />R <br />e <br />s <br />e <br />r <br />v <br />e <br />d <br />. <br /> <br />N <br />o <br /> <br />p <br />a <br />r <br />t <br /> o <br />f <br /> <br />t <br />h <br />i <br />s <br /> <br />d <br />o <br />c <br />u <br />m <br />e <br />n <br />t <br /> <br />m <br />a <br />y <br /> <br />b <br />e <br /> <br />re <br />p <br />r <br />o <br />d <br />u <br />c <br />e <br />d <br /> <br />i <br />n <br /> <br />a <br />n <br />y <br /> <br />f <br />o <br />r <br />m <br /> <br />o <br />f <br /> <br />b <br />y <br /> <br />a <br />n <br />y <br /> <br />m <br />e <br />a <br />n <br />s <br /> <br />w <br />i <br />t <br />h <br />o <br />u <br />t <br /> <br />p <br />e <br />r <br />m <br />is <br />s <br />i <br />o <br />n <br /> <br />f <br />r <br />o <br />m <br /> <br />M <br />T <br />N <br /> <br />E <br />n <br />g <br />i <br />n <br />e <br />e <br />r <br />i <br />n <br />g <br />. <br />DESIGNED:BG LM BG <br />MECHANICAL ENGINEER <br />DRAWN:CHECKED: <br />PORTOLA PARK <br />SPLASH PAD <br />X <br />BENCHMARK DESCRIPTION: <br />OCS BM SA-253-70 <br />FD 3 3/4" OCS ALUMINUM BENCH MARK DISK STAMPED "SA-253-70", SET IN NW'LY CORNER OF A 3.5FT X 16FT <br />CONCRETE CATCH BASIN. MONUMENT IS LOCATED IN THE NE'LY CORNER OF THE INTERSECTION OF GRAND AVE <br />AND SANTA CLARA AVE, 87FT N'LY OF THE CENTERLINE OF SANTA CLARA AVE AND 39FT E'LY OF THE CENTERLINE <br />OF GRAND AVE. MONUMENT IS SET LEVEL WITH THE SIDEWALK <br />PRINCIPAL CIVIL ENGINEER <br />PRINCIPAL CIVIL ENGINEER25-2401 <br />NUMBER DATE INITIALS DESCRIPTION <br />PREPARED UNDER THE <br />SUPERVISION OF: <br />CITY OF SANTA ANA <br />FILE NO.: <br />INSTALLEDAPPROVED <br />CONSTRUCTION COMPLETED: <br />BENCHMARK NO.: SA-253-70 <br />RECOMMENDED FOR <br />CONSTRUCTION: <br />REFERENCES <br />PUBLIC WORKS AGENCY <br />RCE NO.: <br />ELEV.: 176.00 (2010) <br />REVISIONS <br />SHEET OF <br />REVIEWED FOR <br />CONSTRUCTABLITY: <br />RCE NO.: <br />BRIAN GRAHAM <br />1700 E. SANTA CLARA AVENUE, SANTA ANA, CA 92705 <br />Z: <br />\ <br />S <br />h <br />a <br />r <br />e <br />d <br />\ <br />0 <br />2 <br /> <br />- <br /> <br />P <br />r <br />o <br />j <br />e <br />c <br />t <br />s <br />\ <br />2 <br />0 <br />2 <br />5 <br /> <br />P <br />r <br />o <br />j <br />e <br />c <br />t <br />s <br />\ <br />2 <br />5 <br />- <br />0 <br />0 <br />5 <br /> <br />S <br />a <br />n <br />t <br />a <br /> <br />An <br />a <br /> <br />P <br />o <br />r <br />t <br />o <br />l <br />a <br /> <br />P <br />a <br />r <br />k <br /> <br />R <br />e <br />s <br />t <br />r <br />o <br />o <br />m <br />\ <br />0 <br />2 <br /> <br />- <br /> <br />C <br />A <br />D <br /> <br />F <br />i <br />l <br />e <br />s <br />\ <br />S <br />a <br />n <br />t <br />a <br /> <br />A <br />n <br />a <br /> <br />Po <br />r <br />t <br />o <br />l <br />a <br /> <br />P <br />a <br />r <br />k <br /> <br />R <br />e <br />s <br />t <br />r <br />o <br />o <br />m <br />s <br />. <br />r <br />v <br />t <br />MECHANICAL/PLUMBING NOTES & SCHEDULES MP0.0 <br />PO <br />R <br />T <br />O <br />L <br />A <br /> <br />P <br />A <br />R <br />K <br /> <br />S <br />P <br />L <br />A <br />S <br />H <br /> <br />P <br />A <br />D <br /> <br />P <br />R <br />O <br />J <br />E <br />C <br />T <br /> <br />N <br />O <br />. <br /> <br />2 <br />5 <br />- <br />2 <br />4 <br />0 <br />1 <br />SHEET 52 OF 57