GENERAL PLAN NOTES <br />PLUMBING CODED KEY NOTES <br />MECHANICAL CODED KEY NOTES <br />1.DRAWINGS ARE DIAGRAMMATIC ONLY AND REPRESENT THE GENERAL SCOPE OF THE WORK. PRIOR TO <br />SUBMITTING BID, VISIT THE JOB SITE TO OBSERVE THE EXISTING CONDITIONS OF THE PROJECT. REVIEW <br />GENERAL NOTES. SPECIFICATIONS AND PLANS FOR ADDITIONAL REQUIREMENTS THAT MAY NOT BE <br />SPECIFICALLY CALLED OUT IN THIS PORTION OF THE CONSTRUCTION DOCUMENTS. NOTIFY ARCHITECT OF ANY <br />CONFLICTS OR DISCREPANCIES PRIOR TO SUBMISSION OF BID. <br />INSTALLATION OF EQUIPMENT SHALL COMPLY WITH EQUIPMENT MANUFACTURER'S INSTALLATION AND <br />CLEARANCE REQUIREMENTS TO ALLOW FOR INSPECTION, SERVICE, REPAIR OR REPLACEMENT. <br />CONTRACTOR SHALL COMPLY WITH ALL LANDLORD'S TENANT CRITERIA. COORDINATE AND SCHEDULE ALL <br />WORK WITH LANDLORD'S FIELD REPRESENTATIVE. <br />IDENTIFY ALL ROOF MOUNTED EQUIPMENT WITH STORE NAME AND UNIT NUMBER USING PERMANENT <br />WEATHER PROOF 2" HIGH DIE-CUT LETTERS. <br />ALL ROOFTOP EQUIPMENT SHALL BE SET LEVEL AND PLUMB. <br />ALL NEW ROOF WORK SHALL BE DONE BY LANDLORDS ROOFING CONTRACTOR AT TENANTS EXPENSE. <br />CONTRACTOR SHALL COORDINATE ALL NEW AND EXISTING ROOF WORK TO CONFORM TO LANDLORDS <br />ROOFING STANDARDS AND PER LOCAL CODE REQUIREMENTS. FIELD VERIFY ALL ROOF WORK PRIOR TO BID. <br />2. <br />3. <br />4. <br />5. <br />6. <br />1.COORDINATE EXACT EXHAUST FAN LOCATION FOR OPENING IN THE ROOF. <br />MAINTAIN 10 FOOT CLEARANCE FROM ANY FRESH AIR INTAKE. FIELD VERIFY EXACT REQUIREMENTS PRIOR TO <br />BID AND INSTALLATION. IF EXHAUST FAN FALLS WITHIN 10 FOOT OF ANY FRESH AIR INTAKE, THE EXHAUST <br />DISCHARGE OPENING SHALL BE EXTENDED BY MEANS OF A SHROUD ON UPBLAST FANS AND DUCTWORK ON <br />UTILITY FANS, TO MEET THE 3'-0" VERTICAL CLEARANCE REQUIREMENTS FROM EXHAUST DISCHARGE. SHROUD <br />CAN BE PROVIDED BY CAPTIVEAIRE. FIELD VERIFY EXACT REQUIREMENTS PRIOR TO ORDERING, INSTALLATION <br />AND BID , G C TO COORDINATE WITH CAPTIVEIAIRE. <br />4" EXHAUST DUCT SHALL BE MINIMUM 26 GA GALVANIZED STEEL. PROVIDE RAIN CAP WITH INTEGRAL BIRD <br />SCREEN, BACKDRAFT DAMPER, AND ACCESSORIES AS REQUIRED INCLUDING SPEED CONTROLLER <br />CONCEALED AND ACCESSIBLE. EXHAUST FAN OUTLET SHALL MAINTAIN 10' CLEARANCE FROM ANY OUTSIDE <br />AIR INTAKES. ALL ROOF WORK SHALL BE DONE BY LANDLORD'S ROOFING CONTRACTOR AT TENANT'S EXPENSE <br />UNLESS NOTED OTHERWISE. <br />INTERLOCK HP-1 WITH OVEN EXHAUST FAN SO THAT WHEN THE OVEN IS IN USE THE EXHAUST FAN <br />AND HP-1 WILL RUN TOGETHER. <br />3" CONCENTRIC FLUE/CA VENT KIT DOWN TO WATER HEATER. CONTRACTOR TO VERIFY EXACT SIZE AND <br />ROUTING. SLOPE 1/4 INCH PER FOOT BACK TOWARD WATER HEATER. INSTALL PER MANUFACTURER'S <br />RECOMMENDATIONS. MAINTAIN 10 FOOT CLEARANCE FROM ANY FRESH AIR INTAKE. <br />APPROXIMATE LOCATION OF REFRIGERATION EQUIPMENT CONDENSING UNIT. COORDINATE WITH FOOD <br />SERVICE, ARCHITECTURAL AND ELECTRICAL DRAWINGS. PROVIDE RAILS FOR CONDENSING UNITS. <br />COORDINATE RAIL SYSTEM WITH MANUFACTURERS REQUIREMENTS AND STRUCTURAL ENGINEERS. <br />CONTRACTOR INSTALLING REMOTE CONDENSERS SHALL VERIFY EXACT SIZE OF CONDENSER STAND. <br />2. <br />3. <br />4. <br />5. <br />6. <br />3. CONTRACTOR TO VERIFY TERMINATION OF VTR IS A MINIMUM OF 10'0" FROM ALL OUTSIDE AIR INTAKES. <br />1. 2-1/2" NG LINE TO EXISTING GAS METER. <br />2. 1-1/4" NG LINE DOWN TO TENANT SPACE. SEE SHEET P1.0 FOR CONTINUATION. <br />ROOFTOP PLAN <br />SCALE: 1/4" = 1' - 0" <br />MECHANICAL ROOF PLAN <br />MP-100 <br />4. NEW WATER HEATER . ROUTE NEW GAS PIPING AS REQUIRED AND CONNECT TO NEW WATER HEATER. <br />79 <br />6 <br /> <br />M <br />e <br />r <br />u <br />s <br /> <br />C <br />o <br />u <br />r <br />t <br />St <br />. <br /> <br />L <br />o <br />u <br />i <br />s <br />, <br /> <br />M <br />O <br /> <br />6 <br />3 <br />0 <br />2 <br />6 <br />T <br />6 <br />3 <br />6 <br />. <br />3 <br />4 <br />9 <br />. <br />1 <br />6 <br />0 <br />0 <br />F <br />6 <br />3 <br />6 <br />. <br />3 <br />4 <br />9 <br />. <br />1 <br />7 <br />3 <br />0 <br />16842136571210911141315 <br />84213657 1210911 1413 15 16 <br />a <br />b <br />c <br />d <br />e <br />f <br />g <br />h <br />j <br />k <br />l <br />m <br />n <br />p <br />r <br />s <br />a <br />b <br />c <br />d <br />e <br />f <br />g <br />h <br />j <br />k <br />l <br />m <br />n <br />p <br />r <br />s <br />Checked by <br />Drawn by <br />Issue Date <br />Project # <br />Scale <br />Client Approval <br />TI <br /> <br />T <br />E <br />M <br />P <br />L <br />A <br />T <br />E <br /> <br />V <br />1 <br />. <br />0 <br />, <br />10 <br />- <br />1 <br />1 <br />- <br />2 <br />0 <br />1 <br />1 <br />SANTA ANA - SOUTH <br />(#0972) <br />3313 S. BRISTOL ST. <br />SANTA ANA, CA 92704 <br />AS INDICATED <br />07/09/2025 <br />69325-CA03 <br />ISSUED FOR <br />PERMIT <br /># Description Date <br />These drawings/specifications are the property of Oculus Inc. They are <br />furnished as contract documents only. The seal(s) and signature(s) apply <br />only to the document to which they are affixed, and expressly disclaim <br />any responsibility for all other plans, specifications, estimates, reports or <br />other documents or instruments relating to or intended to be used for any <br />part or parts of the architectural or engineering project. Additionally these <br />drawings and seal(s) shall in no way convey or imply any type of warranty <br />or certification relating to the performance of products and materials <br />beyond those provided by their respective manufacturer. <br />© 2025 Oculus Inc. <br />03/10/2026 <br />Matthew R. Case, Engineer <br />CA # M41121 <br />10'0" MIN CLEARANCE FROM ANY <br />FRESH AIR INTAKE <br />10'0" MIN CLEARANCE FROM ANY <br />FRESH AIR INTAKE <br />10'0" MIN CLEARANCE FROM ANY <br />FRESH AIR INTAKE <br />10'0" MIN CLEARANCE FROM ANY <br />FRESH AIR INTAKE <br />1-1/4"(290) <br />1-1/4"(199 MBH) <br />1 <br />1-1/2" (290 CFH) <br />1-1/2" (290 CFH) <br />1-1/2" (489 CFH) <br />1-1/4" (199 CFH)TOTAL GAS DEMAND LOAD <br />PLUMBING SUB-TOTAL 489 <br />SIZE <br />CONN. <br />(MBH/EA) <br />INPUT <br />DESCRIPTION (MBH) <br />TOTAL <br />NO.QTY. <br />NOTE(S): <br />1.GAS PIPING SIZE IS BASED ON LONGEST RUN METHOD. <br />2.THE GAS SYSTEM SIZED FOR THE RTUS, OVEN AND WATER HEATER IS SIZED FOR A TOTAL <br />DEVELOPED LENGTH OF MAXIMUM 200'-0" FROM THE GAS METER. <br />3.PIPE SIZES SHOWN ON THE RISER DIAGRAM ARE BASED ON 2022 CALIFORNIA PLUMBING <br />CODE. VERIFY FIELD CONDITIONS FOR ACTUAL DEVELOPED LENGTH AND POSSIBLE <br />ADJUSTMENTS TO PIPE SIZES. <br />GAS DEMAND TOTAL <br />HVAC SUB-TOTAL - <br />1 WATER HEATER 1-1/4"1 199 199 <br />2 OVEN 1-1/4"1 290 290 <br />489 <br />4 <br />2 <br />1