FLOOR AND GROUND SURFACES
<br />1.FLOOR AND GROUND SURFACES SHALL BE STABLE, FIRM, AND SLIP RESISTANT.
<br />2.CARPET OR CARPET TILE SHALL BE SECURELY ATTACHED AND SHALL HAVE A FIRM CUSHION, PAD, OR
<br />BACKING OR NO CUSHION OR PAD. CARPET OR CARPET TILE SHALL HAVE A LEVEL LOOP, TEXTURED LOOP,
<br />LEVEL CUT PILE, OR LEVEL CUT/UNCUT PILE TEXTURE. PILE HEIGHT SHALL BE ½ INCH MAXIMUM.
<br />CHANGES IN LEVEL
<br />3.VERTICAL CHANGES IN LEVEL FOR FLOOR OR GROUND SURFACES MAY BE ¼ INCH HIGH MAXIMUM AND
<br />WITHOUT EDGE TREATMENT. CHANGES IN LEVEL GREATER THAN ¼ INCH AND NOT EXCEEDING ½ INCH IN
<br />HEIGHT SHALL BE BEVELED WITH A SLOPE NOT STEEPER THAN 1:2.
<br />4.CHANGES IN LEVEL GREATER THAN ½ INCH IN HEIGHT SHALL BE RAMPED AND SHALL COMPLY WITH THE
<br />REQUIREMENTS OF 11B-405 RAMPS OR 11B-406 CURB RAMPS AS APPLICABLE.
<br />5.ABRUPT CHANGES IN LEVEL EXCEEDING 4 INCHES IN A VERTICAL DIMENSION BETWEEN WALKS, SIDEWALKS
<br />OR OTHER PEDESTRIAN WAYS AND ADJACENT SURFACES OR FEATURES SHALL BE IDENTIFIED BY WARNING
<br />CURBS AT LEAST 6 INCHES IN HEIGHT ABOVE THE WALK OR SIDEWALK SURFACE OR BY GUARDS OR
<br />HANDRAILS WITH A GUIDE RAIL CENTERED 2 INCHES MINIMUM AND 4 INCHES MAXIMUM ABOVE THE
<br />SURFACE OF THE WALK OR SIDEWALK. THESE REQUIREMENTS DO NOT APPLY BETWEEN A WALK OR
<br />SIDEWALK AND AN ADJACENT STREET OR DRIVEWAY.
<br />TURNING SPACE
<br />6.CIRCULAR TURNING SPACES SHALL BE A SPACE OF 60 INCHES DIAMETER MINIMUM AND MAY INCLUDE KNEE
<br />AND TOE CLEARANCE COMPLYING WITH 11B-306 KNEE AND TOE CLEARANCE.
<br />7.T-SHAPED TURNING SPACES SHALL BE A T-SHAPED SPACE WITHIN A 60 INCH SQUARE MINIMUM WITH ARMS
<br />AND BASE 36 INCHES WIDE MINIMUM. EACH ARM OF THE T SHALL BE CLEAR OF OBSTRUCTIONS 12 INCHES
<br />MINIMUM IN EACH DIRECTION AND THE BASE SHALL BE CLEAR OF OBSTRUCTIONS 24 INCHES MINIMUM.
<br />KNEE AND TOE CLEARANCE
<br />8.FOR LAVATORIES AND BUILT-IN DINING AND WORK SURFACES REQUIRED TO BE ACCESSIBLE, TOE
<br />CLEARANCE SHALL BE PROVIDED THAT IS 30 INCHES IN WIDTH AND 9 INCHES IN HEIGHT ABOVE THE FINISH
<br />FLOOR OR GROUND FOR A DEPTH OF 19 INCHES MINIMUM.
<br />9.TOE CLEARANCE SHALL EXTEND 19 INCHES MAXIMUM UNDER LAVATORIES FOR TOILET AND BATHING
<br />FACILITIES AND 25 INCHES MAXIMUM UNDER OTHER ELEMENTS.
<br />10.AT LAVATORIES IN TOILET AND BATHING FACILITIES, KNEE CLEARANCE SHALL BE PROVIDED THAT IS 30
<br />INCHES IN WIDTH FOR A DEPTH OF 11 INCHES AT 9 INCHES ABOVE THE FINISH FLOOR OR GROUND AND
<br />FOR A DEPTH OF 8 INCHES AT 27 INCHES ABOVE THE FINISH FLOOR OR GROUND INCREASING TO 29
<br />INCHES HIGH MINIMUM ABOVE THE FINISH FLOOR OR GROUND AT THE FRONT EDGE OF A COUNTER
<br />WITH A BUILT-IN LAVATORY OR AT THE FRONT EDGE OF A WALL-MOUNTED LAVATORY FIXTURE.
<br />11.AT DINING AND WORK SURFACES REQUIRED TO BE ACCESSIBLE, KNEE CLEARANCE SHALL BE PROVIDED
<br />THAT IS 30 INCHES IN WIDTH AT 27 INCHES ABOVE THE FINISH FLOOR OR GROUND FOR A DEPTH OF AT
<br />LEAST 19 INCHES.
<br />PROTRUDING OBJECTS
<br />12.EXCEPT FOR HANDRAILS, OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES AND LESS THAN 80
<br />INCHES ABOVE THE FINISH FLOOR OR GROUND SHALL PROTRUDE NO MORE THAN 4 INCHES
<br />HORIZONTALLY INTO THE CIRCULATION PATH. HANDRAILS MAY PROTRUDE 4½ INCHES MAXIMUM.
<br />13.FREESTANDING OBJECTS MOUNTED ON POSTS OR PYLONS SHALL OVERHANG CIRCULATION PATHS NO
<br />MORE THAN 12 INCHES WHEN LOCATED FROM 27 TO 80 INCHES ABOVE THE FINISH FLOOR OR GROUND.
<br />14.PROTRUDING OBJECTS SHALL NOT REDUCE THE CLEAR WIDTH REQUIRED FOR ACCESSIBLE ROUTES.
<br />15.LOWEST EDGE OF A SIGN OR OTHER OBSTRUCTION, WHEN MOUNTED BETWEEN POSTS OR PYLONS
<br />SEPARATED WITH A CLEAR DISTANCE GREATER THAN 12 INCHES, SHALL BE LESS THAN 27 INCHES OR MORE
<br />THAN 80 INCHES ABOVE THE FINISH FLOOR OR GROUND.
<br />16.VERTICAL CLEARANCE SHALL BE AT LEAST 80 INCHES HIGH ON CIRCULATION PATHS EXCEPT AT DOOR
<br />CLOSERS AND DOOR STOPS, WHICH MAY BE 78 INCHES MINIMUM ABOVE THE FINISH FLOOR OR
<br />GROUND.
<br />17.GUARDRAILS OR OTHER BARRIERS WITH A LEADING EDGE LOCATED 27 INCHES MAXIMUM ABOVE THE
<br />FINISH FLOOR OR GROUND SHALL BE PROVIDED WHERE THE VERTICAL CLEARANCE ON CIRCULATION
<br />PATHS IS LESS THAN 80 INCHES HIGH.
<br />18.WHERE A GUY SUPPORT IS USED WITHIN EITHER THE WIDTH OF A CIRCULATION PATH OR 24 INCHES
<br />MAXIMUM OUTSIDE OF A CIRCULATION PATH, A VERTICAL GUY BRACE, SIDEWALK GUY OR SIMILAR DEVICE
<br />SHALL BE USED TO PREVENT A HAZARD OR AN OVERHEAD OBSTRUCTION.
<br />REACH RANGES
<br />19.ELECTRICAL CONTROLS AND SWITCHES INTENDED TO BE USED BY THE OCCUPANT OF A ROOM OR AREA
<br />TO CONTROL LIGHTING AND RECEPTACLE OUTLETS, APPLIANCES OR COOLING, HEATING AND
<br />VENTILATING EQUIPMENT SHALL BE LOCATED WITHIN ALLOWABLE REACH RANGES. LOW REACH SHALL BE
<br />MEASURED TO THE BOTTOM OF THE OUTLET BOX AND HIGH REACH SHALL BE MEASURED TO THE TOP OF
<br />THE OUTLET BOX.
<br />20.ELECTRICAL RECEPTACLE OUTLETS ON BRANCH CIRCUITS OF 30 AMPERES OR LESS AND COMMUNICATION
<br />SYSTEM RECEPTACLES SHALL BE LOCATED WITHIN ALLOWABLE REACH RANGES. LOW REACH SHALL BE
<br />MEASURED TO THE BOTTOM OF THE OUTLET BOX AND HIGH REACH SHALL BE MEASURED TO THE TOP OF
<br />THE OUTLET BOX.
<br />21.HIGH FORWARD REACH THAT IS UNOBSTRUCTED SHALL BE 48 INCHES MAXIMUM AND THE LOW FORWARD
<br />REACH SHALL BE 15 INCHES MINIMUM ABOVE THE FINISH FLOOR OR GROUND.
<br />22.HIGH FORWARD REACH SHALL BE 48 INCHES MAXIMUM WHERE THE REACH DEPTH IS 20 INCHES OR LESS
<br />AND 44 INCHES MAXIMUM WHERE THE REACH DEPTH EXCEEDS 20 INCHES. HIGH FORWARD REACH SHALL
<br />NOT EXCEED 25 INCHES IN DEPTH.
<br />23.HIGH SIDE REACH SHALL BE 48 INCHES MAXIMUM AND THE LOW SIDE REACH SHALL BE 15 INCHES
<br />MINIMUM ABOVE THE FINISH FLOOR WHERE THE SIDE REACH IS UNOBSTRUCTED OR THE DEPTH OF ANY
<br />OBSTRUCTION DOES NOT EXCEED 10 INCHES.
<br />24.HIGH SIDE REACH SHALL BE 46 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND WHERE THE
<br />HIGH SIDE REACH IS OVER AN OBSTRUCTION MORE THAN 10 INCHES BUT NOT MORE THAN 24 INCHES IN
<br />DEPTH.
<br />25.OBSTRUCTIONS FOR HIGH SIDE REACH SHALL NOT EXCEED 34 INCHES IN HEIGHT AND 24 INCHES IN
<br />DEPTH.
<br />26.OBSTRUCTED HIGH SIDE REACH FOR THE TOP OF WASHING MACHINES AND CLOTHES DRYERS SHALL BE
<br />PERMITTED TO BE 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR.
<br />27.OBSTRUCTED HIGH SIDE REACH FOR THE OPERABLE PARTS OF FUEL DISPENSERS SHALL BE PERMITTED TO BE
<br />54 INCHES MAXIMUM MEASURED FROM THE SURFACE OF THE VEHICULAR WAY WHERE FUEL DISPENSERS
<br />ARE INSTALLED ON EXISTING CURBS.
<br />OPERABLE PARTS
<br />28.OPERABLE PARTS SHALL BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING,
<br />PINCHING, OR TWISTING OF THE WRIST. FORCE REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5
<br />POUNDS MAXIMUM.
<br />DETECTABLE WARNINGS AND DETECTABLE DIRECTIONAL TEXTURE
<br />29.DETECTABLE WARNING SURFACES SHALL BE YELLOW AND APPROXIMATE FS 33538 OF FEDERAL STANDARD
<br />595C.
<br />30.DETECTABLE WARNING SURFACES SHALL PROVIDE A 70 PERCENT MINIMUM VISUAL CONTRAST WITH
<br />ADJACENT WALKING SURFACES. CONTRAST IN PERCENT SHALL BE DETERMINED BY:
<br />CONTRAST PERCENT = [(B1-B2)/B1] X 100 WHERE
<br />B1 = LIGHT REFLECTANCE VALUE (LRV) OF THE LIGHTER AREA AND
<br />B2 = LIGHT REFLECTANCE VALUE (LRV) OF THE DARKER AREA
<br />DOORS, DOORWAYS, AND GATES
<br />31.DOORS, DOORWAYS, AND GATES PROVIDING USER PASSAGE SHALL BE PROVIDED IN ACCORDANCE WITH
<br />11B-206.5 DOORS, DOORWAYS, AND GATES.
<br />32.DOORS, DOORWAYS AND GATES THAT ARE PART OF AN ACCESSIBLE ROUTE SHALL COMPLY WITH 11B-404
<br />DOORS, DOORWAYS, AND GATES.
<br />33.DOOR OPENINGS SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES MINIMUM. CLEAR OPENINGS OF
<br />DOORWAYS WITH SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF THE DOOR AND THE
<br />STOP, WITH THE DOOR OPEN 90 DEGREES. OPENINGS MORE THAN 24 INCHES DEEP SHALL PROVIDE A
<br />CLEAR OPENING OF 36 INCHES MINIMUM. THERE SHALL BE NO PROJECTIONS INTO THE REQUIRED CLEAR
<br />OPENING WIDTH LOWER THAN 34 INCHES ABOVE THE FINISH FLOOR OR GROUND. PROJECTIONS INTO
<br />THE CLEAR OPENING WIDTH BETWEEN 34 INCHES AND 80 INCHES ABOVE THE FINISH FLOOR OR GROUND
<br />SHALL NOT EXCEED 4 INCHES.
<br />34.SWINGING DOORS AND GATES SHALL HAVE MANEUVERING CLEARANCES COMPLYING WITH TABLE
<br />11B-404.2.4.1.
<br />35.DOORWAYS LESS THAN 36 INCHES WIDE WITHOUT DOORS OR GATES, SLIDING DOORS, OR FOLDING
<br />DOORS SHALL HAVE MANEUVERING CLEARANCES COMPLYING WITH TABLE 11B-404.2.4.2.
<br />36.MANEUVERING CLEARANCES FOR FORWARD APPROACH SHALL BE PROVIDED WHEN ANY OBSTRUCTION
<br />WITHIN 18 INCHES OF THE LATCH SIDE AN INTERIOR DOORWAY, OR WITHIN 24 INCHES OF THE LATCH
<br />SIDE OF AN EXTERIOR DOORWAY, PROJECTS MORE THAN 8 INCHES BEYOND THE FACE OF THE DOOR,
<br />MEASURED PERPENDICULAR TO THE FACE OF THE DOOR OR GATE.
<br />37.THRESHOLDS, IF PROVIDED AT DOORWAYS, SHALL BE ½ INCH HIGH MAXIMUM. RAISED THRESHOLDS AND
<br />CHANGES IN LEVEL AT DOORWAYS SHALL COMPLY WITH 11B-302 FLOOR OR GROUND SURFACES AND
<br />11B-303 CHANGES IN LEVEL.
<br />38.HANDLES, PULLS, LATCHES, LOCKS, AND OTHER OPERABLE PARTS ON DOORS AND GATES SHALL COMPLY
<br />WITH 11B-309.4 OPERATION. OPERABLE PARTS OF SUCH HARDWARE SHALL BE 34 INCHES MINIMUM AND
<br />44 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. WHERE SLIDING DOORS ARE IN THE FULLY
<br />OPEN POSITION, OPERATING HARDWARE SHALL BE EXPOSED AND USABLE FROM BOTH SIDES.
<br />39.THE FORCE FOR PUSHING OR PULLING OPEN A DOOR OR GATE OTHER THAN FIRE DOORS SHALL BE AS
<br />FOLLOWS:
<br />a.INTERIOR HINGED DOORS AND GATES: 5 POUNDS MAXIMUM.
<br />b.SLIDING OR FOLDING DOORS: 5 POUNDS MAXIMUM.
<br />c.REQUIRED FIRE DOORS: THE MINIMUM OPENING FORCE ALLOWABLE BY THE APPROPRIATE
<br />ADMINISTRATIVE AUTHORITY, NOT TO EXCEED 15 POUNDS.
<br />d.EXTERIOR HINGED DOORS: 5 POUNDS MAXIMUM.
<br />40.SWINGING DOOR AND GATE SURFACES WITHIN 10 INCHES OF THE FINISH FLOOR OR GROUND
<br />MEASURED VERTICALLY SHALL HAVE A SMOOTH SURFACE ON THE PUSH SIDE EXTENDING THE FULL WIDTH
<br />OF THE DOOR OR GATE. PARTS CREATING HORIZONTAL OR VERTICAL JOINTS IN THESE SURFACES SHALL BE
<br />WITHIN 1/16 INCH OF THE SAME PLANE AS THE OTHER AND BE FREE OF SHARP OR ABRASIVE EDGES.
<br />CAVITIES CREATED BY ADDED KICK PLATES SHALL BE CAPPED.
<br />RAMPS
<br />41.RAMP RUNS SHALL HAVE A RUNNING SLOPE NOT STEEPER THAN 1:12 (8.33%).
<br />42.CROSS SLOPE OF RAMP RUNS SHALL NOT BE STEEPER THAN 1:48 (2.083%).
<br />43.FLOOR OR GROUND SURFACES OF RAMP RUNS SHALL COMPLY WITH 11B-302 FLOOR OR GROUND
<br />SURFACES. CHANGES IN LEVEL OTHER THAN THE RUNNING SLOPE AND CROSS SLOPE ARE NOT PERMITTED
<br />ON RAMP RUNS.
<br />44.THE CLEAR WIDTH OF A RAMP RUN SHALL BE 48 INCHES MINIMUM.
<br />45.THE RISE FOR ANY RAMP RUN SHALL BE 30 INCHES MAXIMUM.
<br />46.RAMPS SHALL HAVE LANDINGS AT THE TOP AND THE BOTTOM OF EACH RAMP RUN.
<br />47.LANDINGS SHALL COMPLY WITH 11B-302 FLOOR OR GROUND SURFACES. CHANGES IN LEVEL ARE NOT
<br />PERMITTED.
<br />48.THE LANDING CLEAR WIDTH SHALL BE AT LEAST AS WIDE AS THE WIDEST RAMP RUN LEADING TO THE
<br />LANDING.
<br />49.TOP LANDINGS SHALL BE 60 INCHES WIDE MINIMUM.
<br />50.THE LANDING CLEAR LENGTH SHALL BE 60 INCHES LONG MINIMUM.
<br />51.BOTTOM LANDINGS SHALL EXTEND 72 INCHES MINIMUM IN THE DIRECTION OF RAMP RUN.
<br />52.RAMPS THAT CHANGE DIRECTION BETWEEN RUNS AT LANDINGS SHALL HAVE A CLEAR LANDING 60 INCHES
<br />MINIMUM BY 72 INCHES MINIMUM IN THE DIRECTION OF DOWNWARD TRAVEL FROM THE UPPER RAMP
<br />RUN.
<br />53.WHERE DOORWAYS ARE LOCATED ADJACENT TO A RAMP LANDING, MANEUVERING CLEARANCES REQUIRED
<br />BY 11B-404.2.4 AND 11B-404.3.2 SHALL BE PERMITTED TO OVERLAP THE REQUIRED LANDING AREA. DOORS,
<br />WHEN FULLY OPEN, SHALL NOT REDUCE THE REQUIRED RAMP LANDING WIDTH BY MORE THAN 3 INCHES.
<br />DOORS, IN ANY POSITION, SHALL NOT REDUCE THE MINIMUM DIMENSION OF THE RAMP LANDING TO
<br />LESS THAN 42 INCHES.
<br />54.RAMP RUNS SHALL HAVE COMPLIANT HANDRAILS PER 11B-505 HANDRAILS.
<br />55.EDGE PROTECTION COMPLYING WITH 11B-405.9.2 CURB OR BARRIER SHALL BE PROVIDED ON EACH SIDE
<br />OF RAMP RUNS AND AT EACH SIDE OF RAMP LANDINGS. (SEE EXCEPTIONS)
<br />56.A CURB OR BARRIER SHALL BE PROVIDED THAT PREVENTS THE PASSAGE OF A 4 INCH DIAMETER SPHERE,
<br />WHERE ANY PORTION OF THE SPHERE IS WITHIN 4 INCHES OF THE FINISH FLOOR OR GROUND SURFACE.
<br />TO PREVENT WHEEL ENTRAPMENT, THE CURB OR BARRIER SHALL PROVIDE A CONTINUOUS AND
<br />UNINTERRUPTED BARRIER ALONG THE LENGTH OF THE RAMP.
<br />57.LANDINGS SUBJECT TO WET CONDITIONS SHALL BE DESIGNED TO PREVENT THE ACCUMULATION OF
<br />WATER.
<br />HANDRAILS
<br />58.HANDRAILS SHALL BE PROVIDED ON BOTH SIDES OF STAIRS AND RAMPS.
<br />59.HANDRAILS SHALL BE CONTINUOUS WITHIN THE FULL LENGTH OF EACH STAIR FLIGHT OR RAMP RUN.
<br />INSIDE HANDRAILS ON SWITCHBACK OR DOGLEG STAIRS AND RAMPS SHALL BE CONTINUOUS BETWEEN
<br />FLIGHTS OR RUNS.
<br />60.TOP OF GRIPPING SURFACES OF HANDRAILS SHALL BE 34 INCHES MINIMUM AND 38 INCHES MAXIMUM
<br />VERTICALLY ABOVE WALKING SURFACES, STAIR NOSINGS, AND RAMP SURFACES. HANDRAILS SHALL BE AT A
<br />CONSISTENT HEIGHT ABOVE WALKING SURFACES, STAIR NOSINGS, AND RAMP SURFACES.
<br />61.CLEARANCE BETWEEN HANDRAIL GRIPPING SURFACES AND ADJACENT SURFACES SHALL BE 1½ INCHES
<br />MINIMUM. HANDRAILS MAY BE LOCATED IN A RECESS IF THE RECESS IS 3 INCHES MAXIMUM DEEP AND 18
<br />INCHES MINIMUM CLEAR ABOVE THE TOP OF THE HANDRAIL.
<br />62.HANDRAIL GRIPPING SURFACES SHALL BE CONTINUOUS ALONG THEIR LENGTH AND SHALL NOT BE
<br />OBSTRUCTED ALONG THEIR TOPS OR SIDES. THE BOTTOMS OF HANDRAIL GRIPPING SURFACES SHALL NOT
<br />BE OBSTRUCTED FOR MORE THAN 20 PERCENT OF THEIR LENGTHS. WHERE PROVIDED, HORIZONTAL
<br />PROJECTIONS SHALL OCCUR 1½ INCHES MINIMUM BELOW THE BOTTOM OF THE HANDRAIL-GRIPPING
<br />SURFACE.
<br />63.HANDRAIL GRIPPING SURFACES WITH A CIRCULAR CROSS SECTION SHALL HAVE AN OUTSIDE DIAMETER OF
<br />1¼ INCHES MINIMUM AND 2 INCHES MAXIMUM.
<br />64.HANDRAIL GRIPPING SURFACES WITH A NON-CIRCULAR CROSS SECTION SHALL HAVE A PERIMETER
<br />DIMENSION OF 4 INCHES MINIMUM AND 6¼ INCHES MAXIMUM, AND A CROSS-SECTION DIMENSION OF
<br />2¼ INCHES MAXIMUM.
<br />65.HANDRAIL GRIPPING SURFACES SHALL EXTEND BEYOND AND IN THE SAME DIRECTION OF STAIR FLIGHTS
<br />AND RAMP RUNS IN ACCORDANCE WITH SECTION 11B-505.10 HANDRAIL EXTENSIONS.
<br />66.RAMP HANDRAILS SHALL EXTEND HORIZONTALLY ABOVE THE LANDING FOR 12 INCHES MINIMUM BEYOND
<br />THE TOP AND BOTTOM OF RAMP RUNS. EXTENSIONS SHALL RETURN TO A WALL, GUARD, OR THE LANDING
<br />SURFACE, OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN ADJACENT RAMP RUN.
<br />67.AT THE TOP OF A STAIR FLIGHT, HANDRAILS SHALL EXTEND HORIZONTALLY ABOVE THE LANDING FOR 12
<br />INCHES MINIMUM BEGINNING DIRECTLY ABOVE THE FIRST RISER NOSING. EXTENSIONS SHALL RETURN TO A
<br />WALL, GUARD, OR THE LANDING SURFACE, OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN
<br />ADJACENT STAIR FLIGHT.
<br />68.AT THE BOTTOM OF A STAIR FLIGHT, HANDRAILS SHALL EXTEND AT THE SLOPE OF THE STAIR FLIGHT FOR A
<br />HORIZONTAL DISTANCE EQUAL TO ONE TREAD DEPTH BEYOND THE LAST RISER NOSING. THE HORIZONTAL
<br />EXTENSION OF A HANDRAIL SHALL BE 12 INCHES LONG MINIMUM AND A HEIGHT EQUAL TO THAT OF THE
<br />SLOPING PORTION OF THE HANDRAIL AS MEASURED ABOVE THE STAIR NOSINGS. EXTENSION SHALL
<br />RETURN TO A WALL, GUARD, OR THE LANDING SURFACE, OR SHALL BE CONTINUOUS TO THE HANDRAIL OF
<br />AN ADJACENT STAIR FLIGHT.
<br />STAIRWAYS
<br />69.A STAIR IS DEFINED AS A CHANGE IN ELEVATION, CONSISTING OF ONE OR MORE RISERS.
<br />70.ALL STEPS ON A FLIGHT OF STAIRS SHALL HAVE UNIFORM RISER HEIGHTS AND UNIFORM TREAD DEPTHS.
<br />RISERS SHALL BE 4 INCHES HIGH MINIMUM AND 7 INCHES HIGH MAXIMUM. TREADS SHALL BE 11 INCHES
<br />DEEP MINIMUM. CURVED STAIRWAYS WITH WINDER TREADS ARE PERMITTED AT STAIRS WHICH ARE NOT PART
<br />OF A REQUIRED MEANS OF EGRESS. (SEE EXCEPTION)
<br />71.OPEN RISERS ARE NOT PERMITTED. (SEE EXCEPTIONS)
<br />72.INTERIOR STAIRS SHALL HAVE THE UPPER APPROACH AND LOWER TREAD MARKED BY A STRIPE PROVIDING
<br />CLEAR VISUAL CONTRAST. EXTERIOR STAIRS SHALL HAVE THE UPPER APPROACH AND ALL TREADS MARKED BY
<br />A STRIPE PROVIDING CLEAR VISUAL CONTRAST. THE STRIPE SHALL BE A MINIMUM OF 2 INCHES WIDE TO A
<br />MAXIMUM OF 4 INCHES WIDE PLACED PARALLEL TO, AND NOT MORE THAN 1 INCH FROM, THE NOSE OF
<br />THE STEP OR UPPER APPROACH. THE STRIPE SHALL EXTEND THE FULL WIDTH OF THE STEP OR UPPER
<br />APPROACH AND SHALL BE OF MATERIAL THAT IS AT LEAST AS SLIP RESISTANT AS THE OTHER TREADS OF THE
<br />STAIR. A PAINTED STRIPE SHALL BE ACCEPTABLE. GROOVES SHALL NOT BE USED TO SATISFY THIS
<br />REQUIREMENT.
<br />73.THE RADIUS OF CURVATURE AT THE LEADING EDGE OF THE TREAD SHALL BE ½ INCH MAXIMUM. NOSINGS
<br />THAT PROJECT BEYOND RISERS SHALL HAVE THE UNDERSIDE OF THE LEADING EDGE CURVED OR BEVELED.
<br />RISERS SHALL BE PERMITTED TO SLOPE UNDER THE TREAD AT AN ANGLE OF 30 DEGREES MAXIMUM FROM
<br />VERTICAL. THE PERMITTED PROJECTION OF THE NOSING SHALL EXTEND 1¼ INCHES MAXIMUM OVER THE
<br />TREAD BELOW. (SEE EXCEPTION FOR EXISTING BUILDINGS)
<br />74.STAIRS SHALL HAVE HANDRAILS COMPLYING WITH SECTION 11B-505 HANDRAILS.
<br />75.STAIR TREADS AND LANDINGS SUBJECT TO WET CONDITIONS SHALL BE DESIGNED TO PREVENT THE
<br />ACCUMULATION OF WATER.
<br />76.FLOOR IDENTIFICATION SIGNS REQUIRED BY CHAPTER 10, SECTION 1022.9 COMPLYING WITH SECTIONS
<br />11B-703.1 SIGNS GENERAL, 11B-703.2 RAISED CHARACTERS, 11B-703.3 BRAILLE AND 11B-703.5 VISUAL
<br />CHARACTERS SHALL BE LOCATED AT THE LANDING OF EACH FLOOR LEVEL, PLACED ADJACENT TO THE
<br />DOOR ON THE LATCH SIDE, IN ALL ENCLOSED STAIRWAYS IN BUILDINGS TWO OR MORE STORIES IN
<br />HEIGHT TO IDENTIFY THE FLOOR LEVEL. AT THE EXIT DISCHARGE LEVEL, THE SIGN SHALL INCLUDE A RAISED
<br />FIVE POINTED STAR LOCATED TO THE LEFT OF THE IDENTIFYING FLOOR LEVEL. THE OUTSIDE DIAMETER OF
<br />THE STAR SHALL BE THE SAME AS THE HEIGHT OF THE RAISED CHARACTERS.
<br />CURB RAMPS, BLENDED TRANSITIONS AND ISLANDS
<br />77.PERPENDICULAR RAMP RUNS SHALL HAVE A RUNNING SLOPE NOT STEEPER THAN 1:12 (8.33%).
<br />78.FOR PERPENDICULAR RAMPS, WHERE PROVIDED, CURB RAMP FLARES SHALL NOT BE STEEPER THAN 1:10.
<br />79.THE RUNNING SLOPE OF THE CURB RAMP SEGMENTS SHALL BE IN-LINE WITH THE DIRECTION OF SIDEWALK
<br />TRAVEL. RAMP RUNS SHALL HAVE A RUNNING SLOPE NOT STEEPER THAN 1:12 (8.33%).
<br />80.A TURNING SPACE 48 INCHES MINIMUM BY 48 INCHES MINIMUM SHALL BE PROVIDED AT THE BOTTOM OF
<br />THE CURB RAMP. THE SLOPE OF THE TURNING SPACE IN ALL DIRECTIONS SHALL BE 1:48 MAXIMUM (2.083%).
<br />81.BLENDED TRANSITION RAMPS HALL HAVE A RUNNING SLOPE NOT STEEPER THAN 1:20 (5%).
<br />82.CURB RAMPS AND THE FLARED SIDES OF CURB RAMPS SHALL BE LOCATED SO THAT THEY DO NOT PROJECT
<br />INTO VEHICULAR TRAFFIC LANES, PARKING SPACES, OR PARKING ACCESS AISLES. CURB RAMPS AT MARKED
<br />CROSSINGS SHALL BE WHOLLY CONTAINED WITHIN THE MARKINGS, EXCLUDING ANY FLARED SIDES.
<br />83.THE CLEAR WIDTH OF CURB RAMP RUNS (EXCLUDING ANY FLARED SIDES), BLENDED TRANSITIONS, AND
<br />TURNING SPACES SHALL BE 48 INCHES MINIMUM.
<br />84.LANDINGS SHALL BE PROVIDED AT THE TOPS OF CURB RAMPS AND BLENDED TRANSITIONS (PARALLEL CURB
<br />RAMPS SHALL NOT BE REQUIRED TO COMPLY). THE LANDING CLEAR LENGTH SHALL BE 48 INCHES
<br />MINIMUM. THE LANDING CLEAR WIDTH SHALL BE AT LEAST AS WIDE AS THE CURB RAMP, EXCLUDING ANY
<br />FLARED SIDES, OR THE BLENDED TRANSITION LEADING TO THE LANDING. THE SLOPE OF THE LANDING IN
<br />ALL DIRECTIONS SHALL BE 1:48 (2.083%) MAXIMUM.
<br />85.GRADE BREAKS AT THE TOP AND BOTTOM OF CURB RAMP RUNS SHALL BE PERPENDICULAR TO THE
<br />DIRECTION OF THE RAMP RUN. GRADE BREAKS SHALL NOT BE PERMITTED ON THE SURFACE OF RAMP RUNS
<br />AND TURNING SPACES. SURFACE SLOPES THAT MEET AT GRADE BREAKS SHALL BE FLUSH.
<br />86.THE CROSS SLOPE OF CURB RAMPS AND BLENDED TRANSITIONS SHALL BE 1:48 (2.083%) MAXIMUM.
<br />87.COUNTER SLOPES OF ADJOINING GUTTERS AND ROAD SURFACES IMMEDIATELY ADJACENT TO AND
<br />WITHIN 24 INCHES OF THE CURB RAMP SHALL NOT BE STEEPER THAN 1:20 (5%). THE ADJACENT SURFACES
<br />AT TRANSITIONS AT CURB RAMPS TO WALKS, GUTTERS, AND STREETS SHALL BE AT THE SAME LEVEL.
<br />88.THE BOTTOM OF DIAGONAL CURB RAMPS SHALL HAVE A CLEAR SPACE 48 INCHES MINIMUM OUTSIDE
<br />ACTIVE TRAFFIC LANES OF THE ROADWAY. DIAGONAL CURB RAMPS PROVIDED AT MARKED CROSSINGS
<br />SHALL PROVIDE THE 48 INCHES MINIMUM CLEAR SPACE WITHIN THE MARKINGS.
<br />89.CURB RAMPS AND BLENDED TRANSITIONS SHALL HAVE DETECTABLE WARNINGS COMPLYING WITH 11B-705
<br />DETECTABLE WARNINGS.
<br />90.RAISED ISLANDS IN CROSSINGS SHALL BE CUT THROUGH LEVEL WITH THE STREET OR HAVE CURB RAMPS AT
<br />BOTH SIDES. THE CLEAR WIDTH OF THE ACCESSIBLE ROUTE AT ISLANDS SHALL BE 60 INCHES WIDE
<br />MINIMUM. WHERE CURB RAMPS ARE PROVIDED, THEY SHALL COMPLY WITH 11B-406 CURB RAMPS, BLENDED
<br />TRANSITIONS AND ISLANDS. LANDINGS COMPLYING WITH 11B-406.5.3 LANDINGS AND THE ACCESSIBLE
<br />ROUTE SHALL BE PERMITTED TO OVERLAP. ISLANDS SHALL HAVE DETECTABLE WARNINGS COMPLYING WITH
<br />11B-705 DETECTABLE WARNINGS AND DETECTABLE DIRECTIONAL TEXTURE.
<br />GENERAL SITE AND BUILDING ELEMENTS
<br />91.WHERE PARKING SPACES ARE PROVIDED, ACCESSIBLE PARKING SPACES SHALL BE PROVIDED IN NUMBER AND
<br />KIND REQUIRED PER SECTION 11B-208 PARKING SPACES.
<br />92.WHERE PASSENGER LOADING ZONES, DROP-OFF ZONES, AND/OR BUS STOPS ARE PROVIDED, ACCESSIBLE
<br />PASSENGER LOADING ZONES, DROP-OFF ZONES, AND/OR BUS STOPS ARE REQUIRED.
<br />93.WHERE ELECTRIC VEHICLE CHARGING STATIONS (EVCS) ARE PROVIDED, THEY SHALL COMPLY WITH SECTION
<br />11B-812 AS REQUIRED BY SECTION 11B-228.3.
<br />94.EVCS COMPLYING WITH SECTION 11B-812 THAT SERVE A PARTICULAR BUILDING OR FACILITY SHALL BE
<br />LOCATED ON AN ACCESSIBLE ROUTE TO AN ENTRANCE COMPLYING WITH SECTION 11B-206.4. WHERE
<br />EVCS DO NOT SERVE A PARTICULAR BUILDING OR FACILITY, EVCS COMPLYING WITH SECTION 11B-812
<br />SHALL BE LOCATED ON AN ACCESSIBLE ROUTE TO AN ACCESSIBLE PEDESTRIAN ENTRANCE OF THE EV
<br />CHARGING FACILITY.
<br />TOILET AND BATHING ROOM CLEARANCES
<br />95.DOORS TO UNISEX TOILET ROOMS AND UNISEX BATHING ROOMS SHALL HAVE PRIVACY LATCHES.
<br />96.MIRRORS LOCATED ABOVE THE LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITHIN THE BOTTOM
<br />EDGE OF THE REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
<br />MIRRORS NOT LOCATED ABOVE THE LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE
<br />BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
<br />GROUND.
<br />97.COAT HOOKS SHALL BE LOCATED WITHIN ONE OF THE REACH RANGES SPECIFIED IN SECTION 11B-308.
<br />SHELVES SHALL BE LOCATED 40 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH FLOOR.
<br />MEDICINE CABINETS SHALL BE LOCATED WITH A USABLE SHELF NO HIGHER THAN 44 INCHES MAXIMUM
<br />ABOVE THE FINISH FLOOR.
<br />98.WHERE TOWEL OR SANITARY NAPKIN DISPENSERS, WASTE RECEPTACLES, OR OTHER ACCESSORIES ARE
<br />PROVIDED IN TOILET FACILITIES, AT LEAST ONE OF EACH TYPE SHALL BE LOCATED ON AN ACCESSIBLE
<br />ROUTE. ALL OPERABLE PARTS, INCLUDING COIN SLOTS, SHALL BE 40 INCHES MAXIMUM ABOVE THE FINISH
<br />FLOOR. BABY CHANGING STATIONS ARE NOT REQUIRED TO COMPLY WITH SECTION 11B-603.5 (SEE
<br />EXCEPTION)
<br />WATER CLOSETS AND TOILET COMPARTMENTS
<br />99.FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC. HAND OPERATED FLUSH CONTROLS SHALL
<br />COMPLY WITH SECTION 11B-309.4 OPERATION EXCEPT THEY SHALL BE LOCATED 44 INCHES MAXIMUM
<br />ABOVE THE FLOOR. FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE WATER CLOSET
<br />EXCEPT IN AMBULATORY ACCESSIBLE COMPARTMENTS COMPLYING WITH SECTION 11B-604.8.2
<br />AMBULATORY ACCESSIBLE COMPARTMENTS.
<br />100.TOILET PAPER DISPENSERS SHALL COMPLY WITH SECTION 11B-309.4 OPERATION AND SHALL BE 7 INCHES
<br />MINIMUM AND 9 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF
<br />THE DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE BELOW THE GRAB BAR, 19 INCHES MINIMUM
<br />ABOVE THE FINISH FLOOR AND SHALL NOT BE LOCATED BEHIND THE GRAB BARS. DISPENSERS SHALL NOT
<br />BE OF A TYPE THAT CONTROL DELIVERY OR THAT DOES NOT ALLOW CONTINUOUS PAPER FLOW.
<br />101.SANITARY NAPKIN DISPOSAL UNITS, IF PROVIDED, SHALL COMPLY WITH SECTION 11B-309.4 AND SHALL BE
<br />WALL MOUNTED AND LOCATED ON THE SIDEWALL BETWEEN THE REAR WALL OF THE TOILET AND THE
<br />TOILET PAPER DISPENSER, ADJACENT TO THE TOILET PAPER DISPENSER. THE DISPOSAL UNIT SHALL BE
<br />LOCATED BELOW THE GRAB BAR WITH THE OPENING OF THE DISPOSAL UNIT 19 INCHES MINIMUM (483
<br />MM) ABOVE THE FINISH FLOOR.
<br />102.URINALS SHALL BE THE STALL-TYPE OR THE WALL-HUNG TYPE WITH THE RIM 17 INCHES MAXIMUM ABOVE
<br />THE FINISH FLOOR OR GROUND. URINALS SHALL BE 13½ INCHES DEEP MINIMUM MEASURED FROM THE
<br />OUTER FACE OF THE URINAL RIM TO THE BACK OF THE FIXTURE.
<br />103.FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC. HAND OPERATED FLUSH CONTROLS SHALL
<br />COMPLY WITH SECTION 11B-309 OPERABLE PARTS EXCEPT THAT THE FLUSH CONTROL SHALL BE MOUNTED
<br />AT A MAXIMUM HEIGHT OF 44 INCHES ABOVE THE FINISH FLOOR.
<br />104.FOR LAVATORIES AND SINKS, A CLEAR FLOOR SPACE COMPLYING WITH SECTION 11B-305 CLEAR FLOOR
<br />OR GROUND SURFACES, POSITIONED FOR A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE
<br />COMPLYING WITH SECTION 11B-306 KNEE AND TOE CLEARANCE SHALL BE PROVIDED.
<br />105.LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER
<br />SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
<br />SIGNS RELATED TO TOILETS AND BATHING FACILITIES
<br />106.ENTRANCES LEADING TO TOILET ROOMS AND BATHING ROOMS COMPLYING WITH 11B-603 TOILET AND
<br />BATHING ROOMS SHALL BE IDENTIFIED BY A GEOMETRIC SYMBOL COMPLYING WITH 11B-703.7.2.6 TOILET
<br />AND BATHING ROOM GEOMETRIC SYMBOLS. WHERE EXISTING TOILET ROOMS OR BATHING ROOMS DO
<br />NOT COMPLY WITH 11B-603 TOILET AND BATHING ROOMS, DIRECTIONAL SIGNS INDICATING THE
<br />LOCATION OF THE NEAREST COMPLIANT TOILET ROOM OR BATHING ROOM WITHIN THE FACILITY SHALL BE
<br />PROVIDED. SIGNS SHALL COMPLY WITH 11B-703.5 VISUAL CHARACTERS AND SHALL INCLUDE THE
<br />INTERNATIONAL SYMBOL OF ACCESSIBILITY COMPLYING WITH 11B-703.7.2.1 ISA. WHERE EXISTING TOILET
<br />ROOMS OR BATHING ROOMS DO NOT COMPLY WITH 11B-603 TOILET AND BATHING ROOMS, THE TOILET
<br />ROOMS OR BATHING ROOMS COMPLYING WITH 11B-603 TOILET AND BATHING ROOMS SHALL BE
<br />IDENTIFIED BY THE INTERNATIONAL SYMBOL OF ACCESSIBILITY COMPLYING WITH 11B-703.7.2.1 ISA.
<br />WHERE CLUSTERED SINGLE USER TOILET ROOMS OR BATHING FACILITIES ARE PERMITTED TO USE
<br />EXCEPTIONS TO 11B-213.2 TOILET AND BATHING ROOMS, TOILET ROOMS OR BATHING FACILITIES
<br />COMPLYING WITH 11B-603 TOILET AND BATHING ROOMS SHALL BE IDENTIFIED BY THE INTERNATIONAL
<br />SYMBOL OF ACCESSIBILITY COMPLYING WITH 11B-703.7.2.1 ISA UNLESS ALL TOILET ROOMS AND BATHING
<br />FACILITIES COMPLY WITH 11B-603 TOILET AND BATHING ROOMS. EXISTING BUILDINGS THAT HAVE BEEN
<br />REMODELED TO PROVIDE SPECIFIC TOILET ROOMS OR BATHING ROOMS FOR PUBLIC USE THAT COMPLY
<br />WITH THESE BUILDING STANDARDS SHALL HAVE THE LOCATION OF AND THE DIRECTIONS TO THESE
<br />ROOMS POSTED IN OR NEAR THE BUILDING LOBBY OR ENTRANCE ON A SIGN COMPLYING WITH
<br />11B-703.5 VISUAL CHARACTERS, INCLUDING THE INTERNATIONAL SYMBOL OF ACCESSIBILITY COMPLYING
<br />WITH 11B-703.7.2.1 ISA.
<br />107.PICTOGRAMS SHALL COMPLY WITH THE FOLLOWING:
<br />a.PICTOGRAMS SHALL HAVE A FIELD HEIGHT OF 6 INCHES MINIMUM. CHARACTERS AND BRAILLE SHALL
<br />NOT BE LOCATED IN THE PICTOGRAM FIELD.
<br />b.PICTOGRAMS AND THEIR FIELD SHALL HAVE A NON-GLARE FINISH. PICTOGRAMS SHALL CONTRAST WITH
<br />THEIR FIELD WITH EITHER A LIGHT PICTOGRAM ON A DARK FIELD OR A DARK PICTOGRAM ON A LIGHT
<br />FIELD.
<br />c.PICTOGRAMS SHALL HAVE TEXT DESCRIPTORS LOCATED DIRECTLY BELOW THE PICTOGRAM FIELD. TEXT
<br />DESCRIPTORS SHALL COMPLY WITH 11B-703.2 RAISED CHARACTERS, 11B-703.3 BRAILLE AND 11B-703.4
<br />INSTALLATION HEIGHT AND LOCATION.
<br />d.THE INSTALLATION HEIGHT AND LOCATION OF PICTOGRAM SIGNS SHALL BE PER 11B-703.4.1.
<br />116.SYMBOLS SHALL COMPLY WITH THE FOLLOWING:
<br />a.DOORWAYS LEADING TO TOILET ROOMS AND BATHING ROOMS SHALL BE IDENTIFIED BY A GEOMETRIC
<br />SYMBOL COMPLYING WITH 11B-703.7.2.6 TOILET AND BATHING FACILITIES GEOMETRIC SYMBOLS. THE
<br />SYMBOL SHALL BE MOUNTED AT 58 INCHES MINIMUM AND 60 INCHES MAXIMUM ABOVE THE FINISH
<br />FLOOR OR GROUND SURFACE MEASURED FROM THE CENTERLINE OF THE SYMBOL. WHERE A DOOR IS
<br />PROVIDED, THE SYMBOL SHALL BE MOUNTED WITHIN 1 INCH OF THE VERTICAL CENTERLINE OF THE
<br />DOOR. 11B-703.7.2.6 (SEE EXCEPTION)
<br />b.A TRIANGLE SYMBOL SHALL BE LOCATED AT ENTRANCES TO MEN’S TOILET AND BATHING FACILITIES
<br />AND IT SHALL BE IDENTIFIED BY AN EQUILATERAL TRIANGLE, ¼ INCH THICK WITH EDGES 12 INCHES
<br />LONG AND A VERTEX POINTING UPWARD. THE TRIANGLE SYMBOL SHALL CONTRAST WITH THE DOOR,
<br />EITHER LIGHT ON A DARK BACKGROUND OR DARK ON A LIGHT BACKGROUND.
<br />c.A CIRCLE SYMBOL SHALL BE LOCATED AT ENTRANCES TO WOMEN’S TOILET AND BATHING FACILITIES
<br />AND IT SHALL BE IDENTIFIED BY A CIRCLE, ¼ INCH THICK AND 12 INCHES IN DIAMETER. THE CIRCLE
<br />SYMBOL SHALL CONTRAST WITH THE DOOR, EITHER LIGHT ON A DARK BACKGROUND OR DARK ON A
<br />LIGHT BACKGROUND.
<br />d.A COMBINED CIRCLE AND TRIANGLE SYMBOL SHALL BE LOCATED AT ENTRANCES TO UNISEX TOILET AND
<br />BATHING FACILITIES AND IT SHALL BE SHALL BE IDENTIFIED BY A CIRCLE, ¼ INCH THICK AND 12 INCHES
<br />IN DIAMETER WITH A ¼ INCH THICK TRIANGLE WITH A VERTEX POINTING UPWARD SUPERIMPOSED ON
<br />THE CIRCLE AND WITHIN THE 12-INCH DIAMETER. THE TRIANGLE SYMBOL SHALL CONTRAST WITH THE
<br />CIRCLE SYMBOL, EITHER LIGHT ON A DARK BACKGROUND OR DARK ON A LIGHT BACKGROUND. THE
<br />CIRCLE SYMBOL SHALL CONTRAST WITH THE DOOR, EITHER LIGHT ON A DARK BACKGROUND OR DARK
<br />ON A LIGHT BACKGROUND.
<br />FIRE ALARM SYSTEMS
<br />117.WHERE FIRE ALARM SYSTEMS AND CARBON MONOXIDE ALARM SYSTEMS PROVIDE AUDIBLE ALARM
<br />COVERAGE, ALARMS SHALL COMPLY WITH 11B-215 FIRE ALARM SYSTEMS. §11B-215.1 (SEE EXCEPTION)
<br />118.ALARMS IN PUBLIC USE AREAS AND COMMON USE AREAS SHALL COMPLY WITH 702 CHAPTER 9, SECTION
<br />907.5.2.3.1.
<br />119.WHERE EMPLOYEE WORK AREAS HAVE AUDIBLE ALARM COVERAGE, THE WIRING SYSTEM SHALL BE DESIGNED
<br />SO THAT VISIBLE ALARMS COMPLYING WITH 702 CHAPTER 9, SECTION 907.5.2.3.2 CAN BE INTEGRATED
<br />INTO THE ALARM SYSTEM.
<br />120.FIRE ALARM SYSTEMS SHALL HAVE PERMANENTLY INSTALLED AUDIBLE AND VISIBLE ALARMS COMPLYING WITH
<br />NFPA 72 (1999 OR 2002 EDITION) (INCORPORATED BY REFERENCE, SEE “REFERENCED STANDARDS” IN
<br />CHAPTER 1), EXCEPT THAT THE MAXIMUM ALLOWABLE SOUND LEVEL OF AUDIBLE NOTIFICATION
<br />APPLIANCES COMPLYING WITH SECTION 4-3.2.1 OF NFPA 72 (1999 EDITION) SHALL HAVE A SOUND LEVEL
<br />NO MORE THAN 110 DB AT THE MINIMUM HEARING DISTANCE FROM THE AUDIBLE APPLIANCE. IN
<br />ADDITION, ALARMS IN GUEST ROOMS REQUIRED TO PROVIDE COMMUNICATION FEATURES SHALL COMPLY
<br />WITH SECTIONS 4-3 AND 4-4 OF NFPA 72 (1999 EDITION) OR SECTIONS 7.4 AND 7.5 OF NFPA 72 (2002
<br />EDITION), AND CHAPTER 9, SECTIONS 907.5.2.1 AND 907.5.2.3.
<br />ASSISTED LISTENING SYSTEMS
<br />121.ASSISTIVE LISTENING SYSTEMS SHALL BE PROVIDED IN ASSEMBLY AREAS, INCLUDING CONFERENCE AND
<br />MEETING ROOMS, USED FOR THE PURPOSE OF ENTERTAINMENT, EDUCATIONAL OR CIVIC GATHERINGS,
<br />OR SIMILAR PURPOSES.
<br />NOTE: ASSEMBLY AREAS INCLUDE, BUT ARE NOT LIMITED TO, CLASSROOMS, LECTURE HALLS,
<br />COURTROOMS, PUBLIC MEETING ROOMS, PUBLIC HEARING ROOMS, LEGISLATIVE CHAMBERS, MOTION
<br />PICTURE HOUSES, AUDITORIA, THEATERS, PLAYHOUSES, DINNER THEATERS, CONCERT HALLS, CENTERS FOR
<br />THE PERFORMING ARTS, AMPHITHEATERS, ARENAS, STADIUMS, GRANDSTANDS, OR CONVENTION CENTERS.
<br />122.ASSISTIVE LISTENING SYSTEM SHALL PROVIDE AN AMPLIFICATION SYSTEM UTILIZING TRANSMITTERS,
<br />RECEIVERS, AND COUPLING DEVICES TO BYPASS THE ACOUSTICAL SPACE BETWEEN A SOUND SOURCE AND
<br />A LISTENER BY MEANS OF INDUCTION LOOP, RADIO FREQUENCY, INFRARED, OR DIRECT-WIRED
<br />EQUIPMENT.
<br />123.WHERE A BUILDING CONTAINS MORE THAN ONE ASSEMBLY AREA UNDER ONE MANAGEMENT, THE TOTAL
<br />NUMBER OF REQUIRED RECEIVERS MAY BE CALCULATED USING THE TOTAL NUMBER OF SEATS IN THE
<br />ASSEMBLY AREAS PROVIDED THAT ALL RECEIVERS ARE USABLE WITH ALL SYSTEMS. 11B-219.3 (SEE EXCEPTION)
<br />124.TWENTY-FIVE PERCENT MINIMUM OF RECEIVERS PROVIDED FOR ASSISTIVE LISTENING SYSTEMS, BUT NO
<br />FEWER THAN TWO, SHALL BE HEARING-AID COMPATIBLE EXCEPT WHEN ALL SEATS IN AN ASSEMBLY AREA ARE
<br />SERVED BY MEANS OF AN INDUCTION LOOP.
<br />125.WHEN ASSISTIVE-LISTENING SYSTEMS ARE LIMITED TO SPECIFIC AREAS OR SEATS, SUCH AREAS OR SEATS
<br />SHALL BE WITHIN A 50-FOOT VIEWING DISTANCE OF THE STAGE OR PLAYING AREA AND SHALL HAVE A
<br />COMPLETE VIEW OF THE STAGE OR PLAYING AREA.
<br />126.PERMANENTLY INSTALLED ASSISTIVE-LISTENING SYSTEMS ARE REQUIRED IN AREAS IF (1) THEY HAVE FIXED
<br />SEATING AND (2A) THEY ACCOMMODATE AT LEAST 50 PERSONS OR (2B) THEY HAVE AUDIO-AMPLIFICATION
<br />SYSTEMS, EXCEPT THOSE USED EXCLUSIVELY FOR PAGING AND/OR BACKGROUND MUSIC.
<br />127.PORTABLE ASSISTIVE-LISTENING SYSTEMS MAY SERVE MORE THAN ONE CONFERENCE OR MEETING ROOMS
<br />IF AN ADEQUATE NUMBER OF ELECTRICAL OUTLETS OR OTHER SUPPLEMENTARY WIRING IS PROVIDED AND
<br />PERMANENTLY INSTALLED SYSTEMS ARE NOT REQUIRED.
<br />128.RECEIVERS REQUIRED FOR USE WITH AN ASSISTIVE LISTENING SYSTEM SHALL INCLUDE A 1/8 INCH
<br />STANDARD MONO JACK.
<br />129.RECEIVERS REQUIRED TO BE HEARING AID COMPATIBLE SHALL INTERFACE WITH TELECOILS IN HEARING AIDS
<br />THROUGH THE PROVISION OF NECK LOOPS.
<br />130.ASSISTIVE LISTENING SYSTEMS SHALL BE CAPABLE OF PROVIDING A SOUND PRESSURE LEVEL FROM 110 – 118
<br />DB WITH A DYNAMIC RANGE ON THE VOLUME CONTROL OF 50 DB.
<br />131.SIGNAL-TO-NOISE RATIO FOR INTERNALLY GENERATED NOISE IN ASSISTIVE LISTENING SYSTEMS SHALL BE 18
<br />DB MINIMUM.
<br />132.PEAK CLIPPING SHALL NOT EXCEED 18 DB OF CLIPPING RELATIVE TO THE PEAKS OF SPEECH.
<br />Sheet Title:
<br />ISSUE DATE
<br />ISSUE FOR PLANCHECK 12.22.2025
<br />All drawings and written material appearing herein constitute the original and
<br />unpublished work of MAD Studio and the same may not be duplicated, used
<br />or disclosed without the written consent of MAD Studio.
<br />Sheet No.:
<br />ISSUE DESCRIPTION
<br />ENGINEER/CONSULTANT
<br />ARCHITECT/ENGINEER STAMP
<br />30
<br />5
<br />
<br />W
<br />
<br />4
<br />T
<br />H
<br />
<br />S
<br />T
<br />R
<br />E
<br />E
<br />T
<br />,
<br />
<br />S
<br />A
<br />N
<br />T
<br />A
<br />
<br />A
<br />N
<br />A
<br />,
<br />
<br />C
<br />A
<br />
<br />9
<br />2
<br />7
<br />0
<br />1
<br />CA
<br />F
<br />E
<br />OA
<br />S
<br />I
<br />S
<br />CLIENT
<br />www.madstudiola.com
<br />CITY STAMP
<br />Project Director:
<br />Project Designer:
<br />Project Tech:
<br />Project No:25030.300E.M.
<br />E.M.
<br />S.P.
<br />ISSUED FOR MEP 01.13.2026
<br />ISSUED FOR PLAN CHECK COMMENTS- PLANNING DEPT.01.22.2026
<br />ISSUED FOR PRICING 02.17.2026
<br />ISSUED FOR PLAN CHECK COMMENTS - PLANNING DEPT.02.20.2026
<br />ISSUED FOR COUNTY REVIEW 03.24.2026
<br />ISSUED FOR ADDENDUM A 03.27.2026
<br />ISSUED FOR BUILDING DEPT REVIEW 04.08.2026
<br />ISSUED FOR BUILDING DEPT REVIEW - RESUBMITTAL 05.05.2026
<br />ISSUED FOR BUILDING DEPT CORRECTIONS 05.20.2026
<br />ID0.3
<br />ACCESSIBILITY NOTES
|