(Fi'st Poi\t Ap.trtnrclts - Shllto <br />^no, <br />O{) <br />Per the requirements of Section 1028.4, the exterior walls of the building will be required to achieve at least a 1- <br />hour tire resislance rating for a distancs o{ lo-feet above th€ lloor of the egress @urt. Openings in this portion <br />of th€ wall should achieve a 4tmlnule fire protection ratjng. The exterior wall at this location ls alroady <br />construclod to achieve a l-hour rating. Unprotecled openings in this wall will be lntilled. The extent of the rating <br />should €xtend as showyl on the attached exhibit. <br />Where a building ls constructed on the adjacent property and wilhln 3.5 feet of th€ property the extorior wall of <br />this building will be required to achieve at least a 1-hour lire resistance rating based on lire separation distance <br />and Table 602. Although lhe exterior wall of the adjacont building may have openings located 1o-feet above the <br />walking surfacs of lhe €gress court, the openings would not noed to b€ rated since lhe egress court serves <br />occupants exiling the Flrst Pointe Apartments and not the adjacent building. lf the future adiacent bulldlng <br />utilizos this same egr6ss court as an exil component then the exterior wall of the adjacent building will need to <br />be rated and have protected openlr -- <br />Sinc€rely, <br />Jensen Hughes <br />lsaac Martinez, PE, cFPS <br />Sr. Fire Protoclion Engineer <br />imartine@.ienssnhughss.com <br />213.412.140o <br />Psge4ol4 I Novernber 25, 2019 I Rev l jensenhugftescant <br />FP,893 <br />tsXF.q,ao