Laserfiche WebLink
(1) A post indicator valve installed not less than 40 ft (12 m) from the <br />building <br />(a) For buildings less than 40 ft (12 m) in height, a post indicator valve <br />shall be permitted to be installed closer than 40 ft (12 m) but at least as <br />far from the building as the height of the wall facing the post indicator <br />valve. <br />(2) A wall post indicator valve <br />(3) An indicating valve in a pit, installed in accordance with Section 6.4 <br />(4) A backflow preventer with at least one indicating valve not less than <br />40 ft (12 m) from the building <br />(a) For buildings less than 40 ft (12 m) in height, a backflow preventer <br />with at least one indicating valve shall be permitted to be installed <br />closer than 40 ft (12 m) but at least as far from the building as the <br />height of the wall facing the backflow preventer. <br />(5) Control valves installed in a fire -rated room accessible from the exterior. <br />(6) Control valves in a fire -rated stair enclosure accessible from the <br />exterior. <br />Section 10.1.5 is hereby added as follows: <br />10.1.5 All ferrous pipe and joints shall be polyethylene encased per AWWA <br />C150, Method A, B, or C. All fittings shall be protected with a loose 8- <br />mil polyethylene tube or sheet. The ends of the tube or sheet shall <br />extend past the joint by a minimum of 12 inches and be sealed with 2 <br />inch wide tape approved for underground use. Galvanizing does not <br />meet the requirements of this section. <br />Exception: 304 or 316 Stainless Steel pipe and fittings <br />Section 10.4.1.1 is hereby revised as follows: <br />10.4.1.1 All bolted joint accessories shall be cleaned and thoroughly coated <br />with asphalt or other corrosion -retarding material after installation. <br />Ordinance No. NS-XXXX <br />Page 26 of 29 11 B-26 <br />