Laserfiche WebLink
Exception: Bolted joint accessories made from 304 or 316 stainless <br />steel. <br />Section 10.4.1.1.1 is hereby added as follows: <br />10.4.1.1.1 All bolts used in pipe -joint assembly shall be 316 stainless steel. <br />Section 10.4.3.2 is hereby deleted and replaced as follows: <br />10.4.3.2 Where approved, private fire service mains supplying systems <br />within the building shall be permitted to extend more than 10 ft. under <br />the building when all of the requirements of 10.4.3.2.1 through <br />10.4.3.2.4 are met. Where fire service mains enter the building adjacent <br />to the foundation, the pipe may run under a building to a maximum of <br />24 inches, as measured from the interior face of the exterior wall to the <br />center of the vertical pipe. The pipe under the building or building <br />foundation shall be 304 or 316 stainless steel and shall not contain <br />mechanical joints or it shall comply with 10.4.3.2.1 through 10.4.3.2.4. <br />SECTION 30: Section 14-47 is hereby amended to read as follows: <br />Sec.14-47. Appendices. <br />Appendix A is deleted in its entirety without amendments. <br />Appendix B is adopted in its entirety with amendments outlined in Guideline B-09. <br />Appendix BB is adopted in its entirety without amendments. <br />Appendix C is adopted in its entirety without amendments. <br />Appendix CC is adopted in its entirety without amendments. <br />Appendix D is deleted in its entirety without amendments. <br />Appendix E is deleted in its entirety without amendments. <br />Appendix F is deleted in its entirety without amendments. <br />Appendix G is deleted in its entirety without amendments. <br />Appendix H is deleted in its entirety without amendments. <br />Appendix I is deleted in its entirety without amendments. <br />Ordinance No. NS-XXXX <br />11 B-27 Page 27 of 29 <br />