Section 7.3.1.1 is hereby is deleted in its entirety and replaced as follows: <br />7.3.1.1 Class I and III Standpipe hose connections shall be unobstructed <br />and shall be located not less than 18 inches or more than 24 inches above <br />the finished floor. Class II Standpipe hose connections shall be <br />unobstructed and shall be located not less than 3 feet or more than 5 feet <br />above the finished floor. <br />NFPA 24, 2016 Edition, Standard for the Installation of Private Fire Service <br />Mains and Their Appurtenances is hereby amended as follows: <br />Section 6.2.8.1 is hereby added as follows: <br />6.2.8.1 All indicating valves controlling fire suppression water <br />supplies shall be painted OSHA red. <br />Exceptions: <br />1. Brass or bronze valves on sprinkler risers mounted to the exterior <br />of the building may be left unpainted. <br />2. Where OS&Y valves on the detector check assembly are the only <br />control valves, at least one OS&Y valve shall be painted red. <br />Section 6.2.9 is hereby amended as follows: <br />All connections to private fire service mains for fire protection systems shall be <br />arranged in accordance with one of the following so that they can be isolated: <br />(1) A post indicator valve installed not less than 40 ft (12 m) from the <br />building <br />(a) For buildings less than 40 ft (12 m) in height, a post <br />indicator valve shall be permitted to be installed closer than 40 ft <br />(12 m) but at least as far from the building as the height of the wall <br />facing the post indicator valve. <br />(2) A wall post indicator valve <br />(3) An indicating valve in a pit, installed in accordance with Section 6.4 <br />(4) A backflow preventer with at least one indicating valve not less than <br />40 ft (12 m) from the building <br />(a) For buildings less than 40 ft (12 m) in height, a backflow <br />preventer with at least one indicating valve shall be permitted to be <br />Ordinance No. NS-2981 <br />Page 29 of 33 <br />