Laserfiche WebLink
ELECTRICAL SPECIFICATIONS ELECTRICAL GENERAL NOTES ABBREVIATIONS AND DESCRIPTIONS <br />rr"ca ni <br />1. CONTRACTOR SHALL PERFORM ALL WORK AS TO CONFORM TO <br />LOCAL, STATE AND NATIONAL CODES AND THE REQUIREMENTS OF <br />LOCAL AUTHORITIES HAVING JURISDICTION. <br />2. CONTRACTOR TO EXAMINE THE SITE TO DETERMINE THE EXACT <br />CONDITIONS AFFECTING THE ELECTRICAL WORK. <br />3. DRAWNGS INDICATE THE GENERAL SCHEME OF THE INSTALLATION <br />AND ARE DIAGRAMMATIC IN SCOPE THE ENGINEER RESERVES THE <br />RIGHT i0 CHANGE THE LOCATION OF OUTLETS, CONDUIT, <br />EQ UIPMENT APPARATUS ETC. TO A REASONABLE EXTENT AS THE <br />BUILDING CONDITIONS MAY DICTATE PRIOR TO THEIR INSTALLATION <br />WITHOUT EXTRA COST TO THE OWNER. THE EXACT LOCATION AND <br />ARRANGEMENT OF ALL EQUIPMENT AND PARTS SHALL BE <br />DETERMINED AS THE WORK PROGRESSES, <br />4. DETAILS OF CONSTRUCTION AND OF WORKMANSHIP WHERE NOT <br />SPECIFICALLY DESCRIBED HEREIN OR INDICATED ON THE DRAWINGS <br />SHALL BE SUBJECT TO THE ENGINEER'S APPROVAL. IT IS THE <br />INTENT OF THESE SPECIFICATIONS TO PROVIDE COMPLETE <br />SYSTEMS, LEFT IN GOOD WORKING ORDER, READY FOR OPERATION, <br />5. SCRAP AND DEBRIS, EXCEPT AS OTHERWISE SPECIFIED. SHALL BE <br />REMOVED FROM THE SITE AND DISPOSED OF BY THIS <br />CONTRACTOR, <br />6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR START-UP OF ALL <br />SYSTEMS. <br />7. ALL WORK SHALL BE DONE WITH A MINIMUM OF DUST AND DIRT. <br />PROVIDE SUFFICIENT FIREPROOF TARPAULINS AND COVER ALL <br />EQUIPMENT IN WORK AREA WITH SAME DURING WORK OPERATIONS. <br />6. CONTRACTOR SHALL FURNISH SHOP DRAWINGS AND EQUIPMENT <br />CUTS TO THE ARCHITECT FOR APPROVAL. <br />9. CONTRACTOR SHALL FILE. SECURE AND PAY FOR ANY NECESSARY <br />APPROVALS, PERMITS AND INSPECTIONS. <br />10. ALL WORK SHALL BE GUARANTEED TO BE FREE FROM DEFECT FOR <br />ONE YEAR AFTER ACCEPTANCE OF WORK. <br />11. ALL WORK BE IN STRICT CONFORMANCE WITH THE LATEST VERSION <br />OF THE STATE OF CALIFORNIA FIRE CODE, THE CALIFORNIA <br />EIECIRIC CODE, THE CALIFORNIA GREEN CODE, AND THE <br />CALIFORNIA BUILDING CODE. <br />12. CONTRACTOR TO COORDINATE TESTING WITH LOCAL OFFICIALS. <br />13. CONTRACTOR SHALL BE RESPONSIBLE FOR DISCONNECTING AND <br />MAKING SAFE ALL ELECTRICAL FACILITIES IN EXISTING STRUCTURE <br />PRIOR TO DEMOLITION. <br />14. CONTRACTOR SHALL BE RESPONSIBLE FOR COMMISSIONING OF <br />SYSTEMS AS REQUIRED BY LOCAL CODE, <br />15. NO PIPING, DUCTS OR EQUIPMENT FOREIGN TO ELECTRICAL <br />EQUIPMENT SHALL BE PERMITTED TO BE LOCATED THIN THE <br />DEDICATED SPACE ABOVE THE ELECTRICAL EQUIPMENT. <br />16. PROVIDE AND MAINTAIN REQUIRED WORK SPACE, ACCESS TO WORK <br />SPACE AND HEAD ROOM ABOUT ELECTRICAL EQUIPMENT PER <br />TABLE 110.26(A)(1). <br />CONDUCTORS <br />I. UNLESS OTHERWISE NOTED, CONDUCTOR TYPES SHALL BE AS <br />INDICATED BELOW: <br />LOCATION <br />CONDUCTORS <br />BRANCH CIRCUITS AND FEEDERS <br />IN CONDUIT <br />THHN/THWN <br />CONCEALED BRANCH CIRCUITS <br />TYPE "AC' CABLE <br />UNDERGROUND OUTDOORS <br />RH W/THW/IHWN <br />2. ALL WIRE AND CABLE SHALL BE COPPER CONDUCTORS. <br />CONDUCTORS gtOAWG AND SMALLER MAY BE SOLID <br />CONDUCTORS LARGER THAN #1OAWG SHALL BE STRANDED. <br />3. CONDUCTORS 68AWG AND SMALLER MAY BE SPLICED USING <br />NYLON SELF -INSULATED WIRE NUTS AS MANUFACTURED BY 3M <br />" SCOTCHLOK", IDEAL "WIRE -NUT' OR APPROVED EQUAL. <br />4. EXCEPT WHERE EQUIPMENT, SUCH AS MOLDED CASE CIRCUIT <br />BREAKERS, ARE SUPPLIED WITH FACTORY INSTALLED SET SCREW <br />LUGS, ALL CONNECTIONS FOR CABLES 4/0 AND LARGER SHALL <br />BE MADE USING NEMA 2 BOLT COMPRESSION LUGS. LUGS <br />SHALL BE HYDRAULICALLY APPLIED USING MANUFACTURER'S <br />TOOLING, DIES AND RECOMMENDED PROCEDURES. <br />5. UNLESS OTHERWISE INDICATED ON THE DRAWINGS, ALL BRANCH <br />CIRCUITS AND HOME RUNS SHALL BE #12AWG, QUANTITY AS <br />NDICATED BY HASH MARKS. <br />6, ADJUST BRANCH CONDUCTOR SIZES AS REQUIRED FOR VOLTAGE <br />DROP MAXIMUM BRANCH CIRCUIT LENGTHS SHALL BE AS <br />FOLLOWSUNLESSOTHERWISE NOTED: <br />®Il�llla:a <br />�II�II�I� <br />THE ABOVE LENGTHS REPRESENT "ONE-WAY" CIRCUIT LENGTH <br />(NOT WIRE LENGTH) AND INCLUDE ALL VERTICAL RISES AND <br />DROP, <br />. <br />7. CONDUCTOR INSULATIONS SHALL BE COLOR CODED AS FOLLOWS: <br />-III <br />WHERE CONDUCTORS ARE NOT AVAILABLE NTH COLOR CODED <br />INSULATION, COLORED TAPES SHALL BE APPLIED TO THE ENTIRE <br />EXPOSED LENGTH OF CABLES IN PULL BOXES, SWITCHBOARDS, <br />EQUIPMENT, ETC, <br />RACEWAYS <br />1, UNLESS OTHERWISE NOTED, RACEWAY TYPES SHALL BE AS <br />INDICATED BELOW <br />LOCATION <br />WHERE CONDUCTORS ARE NOT AVAILABLE NTH COLOR CODED <br />INSULATION, COLORED TAPES SHALL BE APPLIED TO THE ENTIRE <br />EXPOSED LENGTH OF CABLES IN PULL BOXES, SWITCHBOARDS, <br />EQUIPMENT, ETC, <br />RACEWAYS <br />1, UNLESS OTHERWISE NOTED, RACEWAY TYPES SHALL BE AS <br />INDICATED BELOW <br />LOCATION <br />RACEWAY <br />OUTDOORS, ABOVE GRADE.. <br />GALVANIZED RICH) STEEL (GRS) <br />INDOOR FEEDERS AND <br />SUB FEEDERS NOT EXPOSED <br />TO PHYSICAL DAMAGE. <br />ELECTRICAL METALLIC TUBING (EMT) <br />INDOOR BRANCH CIRCUITS <br />EXPOSED IN UTILITY <br />AREAS. . <br />ELECTRICAL METALLIC TUBING (EMT) <br />UNDERGROUND... <br />TYPE "DE", SCHEDULE 40 RIGID (PVC), <br />NON METALLIC CONDUIT <br />UNDERGROUND <br />PENETRATION.. <br />GALVANIZED RIGID STEEL (GRS) <br />THROUGH GRADE <br />2. GALVANIZED RIGID STEEL CONDUIT SHALL BE MANUFACTURED IN <br />ACCORDANCE WITH ANSI #CBOT AND UL S. INSTALLATI ON OF <br />GALVANIZED RIGID STEEL CONDUIT SHALL BE IN STRICT <br />CONFORMANCE WITH NEC ARTICLE #344. <br />3. EMT SHALL BE MANUFACTURED IN ACCORDANCE WITH ANSI <br />fU80.3 AND UL 797. INSTALLATION OF ELECTRICAL METALLIC <br />UBING SHALL B IN STRICT CONFORMANCE WITH NEC ARTICLE <br />1344, BENDING RADIUS SHALL NOT BE LESS THAN NEC TABLE 2, <br />CHAPTER 9. SUPPORT SPACING SHALL NOT EXCEED 10'-0'. <br />ALL EMT COUPLINGS AND CONNECTORS SHALL BE OF THE <br />CONCRETE -TIGHT AND RAIN -TIGHT TYPE. SET SCREW <br />CONNECTORS SHALL NOT BE USED. <br />4, EXCEPT FOR SURFACE METAL AND SURFACE NON-METALLIC, ALL <br />RACEWAYS SHALL BE INSTALLED CONCEALED WITH THE <br />EXCEPTION OF BOILER ROOMS, UTIUTY ROOMS, GARAGES AND <br />OTHER AREAS SPECIFICALLY APPROVED BY THE ARCHITECT. <br />5. SEAL ALL PENETRATIONS THROUGH FIRE RESISTIVE ASSEMBLIES <br />WITH APPROVED MATERIALS PER SEC. 709.E AND 710, CDC. <br />SITE SERVICES <br />1, ALL UNDERGROUND RACEWAYS, SHALL BE TYPE US, SCHEDULE <br />40 PVC, RIGID NON-METALLIC CONDUIT, AND MANUFACTURED BY <br />CARTON OR APPROVED EQUAL AND SHALL BE INSTALLED IN <br />ACCORDANCE WITH NEC ARTICLE #352. <br />2. NON-METALLIC RIGID CONDUIT SHALL BE MANUFACTURED IN <br />STRICT CONFORMANCE WITH UL #651 AND NEMA #TC-2. <br />3. FITTINGS FOR RIGID NON-METALLIC CONDUIT SHALL BE OF THE <br />SOLVENT CEMENTED TYPE AND SHALL BE MANUFACTURED IN <br />STRICT CONFORMANCE WITH UL 3514 AND NEMA ATC-3. <br />SOLVENT CEMENT PROCEDURES SHALL BE IN ACCORDANCE WITH <br />THE MANUFACTURERS RECOMMENDATIONS. <br />4. WHEREVER POSSIBLE, RIGID NON-METALLIC CONDUIT ELBOWS, <br />OFFSETS, ETC. SHALL BE MADE USING 30 DEGREE, 45 DEGREE <br />AND 90 DEGREE FACTORY ELBOWS. WHERE FACTORY ELBOWS <br />CANNOT BE ACCOMMODATED, FIELD BENDING SHALL USE HEATING <br />BOXES, END PLUGS AND FORMING GUIDES AS RECOMMENDED BY <br />THE MANUFACTURER. CARE SHALL BE EXERCISED TO ENSURE <br />THAT THE INTERNAL DIAMETER OF CONDUITS IS NOT EFFECTIVELY <br />REDUCED BY FIELD BENDING. <br />5, MINIMUM BENDING RADIUS FOR RIGID NON-METALLIC CONDUIT <br />SHALL NOT BE LESS THAN PERMITTED BY NEC TABLE 2, <br />CHAPTER 9, <br />6, ALL PENETRATIONS THROUGH MANHOLES, HANDHOLES, <br />FOUNDATIONS, ETC. SHALL BE MADE USING HOT -DIPPED <br />GALVANIZED, RIGID STEEL (GRS) CONDUIT. MAKE TRANSITION <br />FROM RGID NON-METALLIC TO GRS AT 5'-0" FROM <br />PENETRATION USING APPROVED TRANSITION COUPLING. PROVIDE <br />3" CONCRETE ENVELOPE AROUND TRANSITION COUPLING <br />EXTENDING 3'-C" IN EITHER DIRECTION TO MINIMIZE SHEAR <br />FORCES AT TRANSITION COUPLING. <br />CIRCUIT BRE <br />1, EQUIPMENT INTERRUPTING RATINGS SHOWN ON SCHEDULES ARE <br />BASED ON UL USTED FULL RATING FOR 65,000A AVAILABLE <br />SHORT CIRCUIT CURRENT AT THE SERVICE. CONTRACTOR SHALL <br />INCREASE INTERRUPTING RATINGS AS REQUIRED FOR FULLY RATED <br />EQUIPMENT <br />BoxES <br />1. BOXES FOR BRANCH CIRCUIT WIRING DEVICES AND BRANCH <br />CIRCUIT SPLICES SHALL BE AS INDICATED BELOW: <br />FLUSH WIRING DEVICES <br />ON METAL STUDS <br />RACO #172/173/174 <br />(4" SQUARE) <br />FLUSH WIRING DEVICES <br />ON WQOD STUDS <br />RACO #504/565 <br />GANGABLE <br />FLUSH WIRING DEVICES <br />IN MASONRY WALLS <br />RACO #690 <br />N GANG) <br />GANG BOXES <br />RACO #951/953/953/954/955 <br />SURFACE WIRING DEVICES <br />(DRY AREAS) <br />RACO #192 <br />4" SQUARE) <br />SURFACE WIRING DEVCES <br />(WET ARES, 1 GANG) <br />BELL 270-L/Z73-L <br />F.S. TYPE) <br />SURFACE WIRING DEVICES <br />(WET AREAS, 2 GANG) <br />BELL 276-4L/ 277-4L <br />(ES. TYPE) <br />THE ABOVE MODEL NUMBERS ARE TYPICAL OF THE PRODUCTS <br />REQUIRED. CONTRACTOR SHALL ADJUST MODEL NUMBERS AS <br />REQUIRED TO SUIT JOB CONDITIONS, WALL THICKNESS, DEVICE <br />REQUIREMENTS, ETC, <br />2, PULL AND JUNCTION BOXES SHALL BE CODE GAUGE ENAMELED <br />STEEL, NEMA "1" WITH SCREW FASTENED COVERS WHEN USED IN <br />INDOOR, DRY AREAS STEEL GAUGE SHALL BE IN ACCORDANCE <br />WITH NEC ARTICLE #314.40. <br />3. PULL AND JUNCTION BOXES UTILIZED IN INDOOR AREAS WHICH <br />CONNECTIONS TO UNDERGROUND RACEWAYS, ETC.) SHALL BE <br />GALVANIZED TYPE NEMA "1". <br />4. PULL AND JUNCTION BOXES FOR USE OUTDOORS SHALL BE <br />GALVANIZED AND OF NEMA "3R" CONSTRUCTION. <br />5. ALL PULL BOXES FASTENED TO EXTERIOR BLOCKS OR MAS01 <br />WALLS SHALL BE PROVIDED WITH 1 1/2" CHANNEL FRAMING <br />SPACERS ORIENTED VERTICALLY AT REAR OF ENCLOSURE TO <br />SHALL BE SIZED IN ACCORDANCE WITH NEC ARTICLE <br />'314.16-#31430. <br />7. PULLSOXES AND LARGER JUNCTION BOXES SHALL BE SIZED IN <br />A <br />CCORDANCE TH NEC ARTICLE #314.28. <br />8. MERE USE OF KNOCKOUTS IS DISCONTINUED BY CHANGES IN THE <br />WORK, INSTALL PROPERLY SIZED KNOCKOUT SEALS BY THOMAS <br />AND BETTS. RACOR, APPLETON OR EQUAL. <br />caourl0wc <br />1. GROUNDING ELECTRODE CONDUCTORS SHALL BE SIZED IN <br />ACCORDANCE WITH NEC TABLE #250.66 AND NEC ARTICLE <br />#25D. 102(C). <br />2, GROUNDING OF ELECTRICAL EQUIPMENT AND ENCLOSURES <br />DOWNSTREAM OF THE SERVICE DISCONNECT SHALL BE BY <br />INSULATED GROUNDING CONDUCTOR. INCLUDE WITH ALL FEEDERS <br />AND BRANCH CIRCUITS. <br />3. RECEPTACLE MOUNTING YOKE SHALL NOT BE USED FOR <br />GROUNDING PURPOSES WITH RECESSED OUTLET BOXES PROVIDE <br />INSULATED GROUNDING JUMPER FROM OUTLET BOXES TO <br />RECEPTACLE GROUNDING TERMINAL. <br />RATINGS AS SHOWN ON THE DRAWINGS. <br />2. ALL SWITCHES SHALL BE QUICK -MAKE. OUICK-BREAK OPERATION <br />SUITABLE FOR USE IN THE LOCATION SHOWN, SWITCHES SHALL BE <br />AS MANUFACTURED BY SQUARE D, GENERAL ELECTRIC, <br />WESTINGHOUSE OR EQUAL. <br />1. CONTRACTOR SHALL PERFORM ALL WORK AS <br />NATIONALRM CODES ANCD LtH ET REQUIREMENTS OF <br />LOCAL AUTHORITIES HAVING JURISDICTION. <br />2. CONTRACTOR TO EXAMINE THE SITE TO <br />DETERMINE THE EXACT CONDITIONS <br />AFFECTING THE ELECTRICAL WORK. <br />3. DRAWINGS INDICATE THE GENERAL SCHEME <br />OF THE INSTALLATION AND ARE <br />DIAGRAMMATIC IN SCOPE. THE ENGINEER <br />RESERVES THE RIGHT TO CHANGE THE <br />LOCATION OF OUTLETS, CONDUIT, EQUIPMENT <br />APPARATUS, ETC. TO A REASONABLE EXTENT <br />AS THE BUILDING CONDITIONS MAY DICTATE <br />PRIOR TO THEIR INSTALLATION WITHOUT <br />EXTRA COST TO THE OWNER. THE EXACT <br />LOCATION AND ARRANGEMENT OF ALL <br />EQUIPMENT AND PARTS SHALL BE <br />DETERMINED AS THE WORK PROGRESSES. <br />4. DETAILS OF CONSTRUCTION AND OF <br />WORKMANSHIP WHERE NOT SPECIFICALLY <br />DESCRIBED HEREIN OR INDICATED ON THE <br />DRAWINGS SHALL BE SUBJECT TO THE <br />ENGINEER'S APPROVAL. IT IS THE INTENT OF <br />THESE SPECIFICATIONS TO PROVIDE COMPLETE <br />SYSTEMS. LEFT IN GOOD WORKING ORDER, <br />REAY FOR OPERATION. <br />5. SCRAP AND DEBRIS EXCEPT AS OTHERWISE <br />SPECIFIED, SHALL BE REMOVED FROM THE <br />SITE AND DISPOSED OF BY THIS <br />CONTRACTOR. <br />6. THE CONTRACTOR SHALL BE RESPONSIBLE <br />FOR START-UP OF ALL SYSTEMS. <br />7. ALL WORK SHALL BE DONE WITH A MINIMUM <br />OF DUST AND DIRT. PROVIDE SUFFICIENT <br />FIREPROOF TARPAULINS AND COVER ALL <br />EQUIPMENT IN WORK AREA WITH SAME <br />DURING WORK OPERATIONS. <br />8, CONTRACTOR SHALL FURNISH SHOP <br />DRAWINGS AND EQUIPMENT CUTS TO THE <br />ARCHITECT FOR APPROVAL (MINIMUM (5) <br />COPIES). <br />X COORDINATE NEW SERVICE CONNECTIONS WITH <br />LOCAL UTILITY COMPANY(S). <br />10. FOR TANY TOR SHALL <br />PERMITSY <br />AND INSPECTIONS. <br />11. ALL WORK SHALL BE GUARANTEED TO BE <br />FREE FROM DEFECT FOR ONE YEAR AFTER <br />ACCEPTANCE OF WORK. <br />12. CONTRACTOR TO COORDINATE TESTING WITH <br />LOCAL OFFICIALS. <br />13. ALL WORK BE IN STRICT CONFORMANCE WITH <br />THE LATEST VERSION OF THE STATE OF <br />CALIFORNIA FIRE CODE, THE CALIFORNIA <br />CODE, AND CODE, CALIFORNIA BUILDINGECODE. <br />14. PRIOR TO TESTING, CONTRACTOR SHALL <br />MAKE ALL SYSTEM ADJUSTMENTS REQUIRED <br />FOR PROPER OPERATION. ADJUSTMENTS <br />SHALL INCLUDE TRANSFORMER TAPS, CIRCUIT <br />BREAKER MAGNETIC SETTINGS, GROUND <br />FAULT RELAY TRIP SETTINGS. BALLAST TAP <br />SETTINGS, ETC. <br />15. CONTRACTOR SHALL BE RESPONSIBLE FOR <br />DISCONNECTING AND MAKING SAFE ALL <br />ELECTRICAL FACILITIES IN EXISTING <br />STRUCTURE PRIOR TO DEMOLITION. <br />16. CONTRACTOR SHALL BE RESPONSIBLE FOR <br />COMMISSIONING OF SYSTEMS AS REQUIRED <br />BY LOCAL CODE. <br />17. ALL EQUIPMENT SHALL BE LISTED BY A CITY <br />OF SANTA ANA RECOGNIZED ELECTRICAL <br />TESTING LAB (IE U.L.) OR APPROVED BY THE <br />DEPARTMENT. <br />18. COMPLY WITH CITY OF SANTA ANA <br />AMENDMENTS TO 2019 CEC. <br />19. USE RIGID METAL CONDUIT IN ALL AREAS <br />EXPOSED TO WEATHER USE GROUND WIRE <br />INSIDE ALL FLEXIBLE METAL CONDUITS. <br />METAL CONDUIT SHALL NOT BE INSTALLED IN <br />CONTACT WITH EARTH. <br />20. SCREENING SHALL BE PROVIDED SO THAT <br />MATERIALS STORED IN ANY OUTDOOR <br />STORAGE AREA AND/OR EQUIPMENT AT <br />GRADE OR ON THE ROOF ARE SCREENED <br />FROM VIEW FROM ALL ADJACENT STREETS, <br />PROPERTIES A E THE SAME HGRADEAND ALL <br />21. ALL UNDERGROUND RACEWAYS, SHALL BE <br />INOEETALUCE CONDUIT AND RIGID <br />BY CARTON OR APPROVED EQUAL AND <br />SHALL BE INSTALLED IN ACCORDANCE WITH <br />NEC ARTICLE #352. <br />22. NON-METALLIC RIGID CONDUIT SHALL BE <br />MANUFACTURED IN STRICT CONFORMANCE <br />WITH UL #651 AND NEMA #TC-2. <br />23. ALL GROUND CONDUCTORS SHALL BE <br />INSULATED COPPER. <br />24, FITTINGS FOR RIGID NON-METALLIC CONDUIT <br />SHALL BE OF THE SOLVENT CEMENTED TYPE <br />AND SHALL BE MANUFACTURED IN STRICT <br />CONFORMANCE WITH UL 3514 AND NEMA <br />#TC-3. SOLVENT CEMENT PROCEDURES <br />SHALL BE IN ACCORDANCE WITH THE <br />MANUFACTURERS RECOMMENDATIONS. <br />25. CONDUITS ELBOWSB 0 STETS, ETC SHALLLIBE <br />MADE USING 30 DEGREE, 45 DEGREE AND 90 <br />DEGREE FACTORY ELBOWS. WHERE FACTORY <br />ELBOWS CANNOT BE ACCOMMODATED, FIELD <br />BENDING SHALL USE HEATING BOXES. END <br />PLUGS AND FORMING GUIDES AS <br />RECOMMENDED BY THE MANUFACTURER. CARE <br />SHALL BE EXERCISED TO ENSURE THAT THE <br />INTERNAL DIAMETER OF CONDUITS IS NOT <br />EFFECTIVELY REDUCED BY FIELD BENDING. <br />26. MINIMUM BENDING RADIUS FOR RIGID <br />NON-METALLIC CONDUIT SHALL NOT BE LESS <br />THAN PERMITTED BY NEC TABLE 2, CHAPTER <br />9. <br />27. MINIMUM BURIAL DEPTH FOR UNDERGROUND <br />RIGID NON-METALLIC RACEWAY SHALL BE 36" <br />BELOW FINISHED GRADE. WHERE LESSER <br />DEPTHS ARE REQUIRED DUE TO SUBSURFACE <br />OBSTACLES, ENCASE RACEWAYS IN MINIMUM <br />3", 3000 PSI CONCRETE ENVELOPE. <br />28 HANDHOLES PENETRATIONS <br />DATIOTHRNSGETC <br />CAN SHALE BE <br />MADE USING` HOT -DIPPED GALVANIZED RIGID <br />STEEL (GRS) CONDUIT. MAKE TRANSITION <br />FROM RIGID NON-METALLIC TO GRS AT 5'-0" <br />FROM PENETRATION USING APPROVED <br />TRANSITION COUPLING. PROVIDE 3" <br />CONCRETE ENVELOPE AROUND TRANSITION <br />COUPLING EXTENDING S-O" IN EITHER <br />DIRECTION TO MINIMIZE SHEAR FORCES AT <br />TRANSITION COUPLING. <br />29. RISERS AT UTILITY POLES SHALL CONSISTS <br />OF GRS ELBOWSS) AND CONDUCT TO 10,-0 <br />' <br />ABOVE FIN ISHE AND <br />FOR ELECTRICAL <br />SUPPLIES. SPARE ELECTRICAL DUCTS SHALL <br />BE CAPPED AT 6" ABOVE FINISHED GRADE. <br />30. PROVIDE WEATHERPROOF (NEMA 3R1 <br />JUNCTION BOXES, CONDUIT FITTING SS AND <br />ENCLOSURES AT ALL EXTERIOR LOCATIONS <br />AND ALL WET OR DAMP INTERIOR LOCATIONS. <br />31, ALL AMPACITIES ARE BASED UPON TABLE <br />31015lB116 OF THE 2019 CALIFORNIA <br />ELECTTRRICCAL CODE, <br />APPLICABLE CODES <br />2019 CALIFORNIA BUILDING CODE (CBC) <br />2019 CALIFORNIA ELECTRICAL CODE (CEC) <br />2019 CALIFORNIA ENERGY CODE <br />2019 CALIFORNIA FIRE CODE. <br />2019 CALIFORNIA BUILDING ENERGY EFFICIENCY STANDARDS <br />2019 CALIFORNIA GREEN BUILDING STANDARDS CODE <br />A <br />AMPERES <br />AC <br />ALTERNATING CURRENT <br />AID <br />AFC <br />AMPERES INTERRUPTING CAPACITY <br />AVAILABLE FAULT CURRENT <br />AFF <br />ABOVE FINISHED FLOOR <br />AEG <br />ABOVE FINISHED GRADE <br />AF <br />AMP FRAME/AMP FUSE <br />AL <br />ALUMINUM <br />AS <br />AT <br />AMP SWITCH <br />AMP TRIP <br />ATE <br />AUTOMATIC TRANSFER SWITCH <br />AWG <br />AMERICAN WIRE GAUGE <br />CAN <br />CABLE TELEVISION <br />CCTV <br />CLOSED CIRCUIT TELEVISION <br />CB <br />CIRCUIT BREAKER <br />CO <br />CONDUIT ONLY WITH NYLON PULLCORD <br />CO AS <br />CU <br />COAXIAL CABLE <br />COPPER <br />CT <br />CURRENT TRANSFORMER <br />DC <br />DIRECT CURRENT <br />DIST <br />DISTRIBUTION <br />DB <br />DISTRIBUTION SWITCHBOARD <br />DWGS <br />DRAWINGS <br />OF <br />EXHAUST FAN <br />ELECT <br />ELECTRICAL <br />ELEV <br />ELEVATION/ELEVATOR <br />EM ER,EM <br />EMERGENCY <br />EMT <br />ELECTRO-METALLIC TUBING <br />EQUIP <br />EXIST,EX <br />EQUIPMENT <br />EXISTING <br />F <br />DEGREES FAHRENHEIT <br />FA <br />FIRE ALARM <br />FF <br />FURNITURE FEED, FINISHED FLOOR <br />G <br />GROUND BUS OR WIRE <br />GD <br />GARBAGE DISPOSAL <br />GFCI <br />GROUND FAULT CIRCUIT INTERRUPTER <br />GND <br />GROUND <br />H <br />HORIZONTAL <br />HP <br />HORSEPOWER <br />HOA <br />HAND -OFF -AUTOMATIC <br />HE <br />HERTZ <br />IS <br />ISOLATED GROUND <br />IMC <br />INTERMEDIATE METAL CONDUIT <br />J-BOX <br />JUNCTION BOX <br />KCM <br />KILO -CIRCULAR -MIL <br />KVA <br />KILO-VOLTAMPERE <br />KW <br />KILO -WATT <br />UPS <br />POUNDS <br />LV <br />LOW VOLTAGE <br />SCOPE OF WORK <br />EXISTING IRRIGATION CONTROLLER WITHIN ELECTRICAL ROOM TO BE DISCONNECTED <br />AND REMOVED AND A NEW PEDESTAL MOUNTED IRRIGATION CONTROLLER IN AND <br />EXTERIOR PLANTER AREA TO BE INSTALLED. EXISTING CIRCUITRY SHALL BE REUSED <br />FOR CONNECTION OF NEW CONTROLLER. <br />MAX <br />MAXIMUM <br />MCC <br />MOTOR CONTROL CENTER <br />MCP <br />MECH <br />MOTOR CIRCUIT PROTECTION <br />MECHANICAL <br />MIN <br />MINIMUM <br />MILD <br />MAIN LUGS ONLY <br />MT D <br />MTG <br />MOUNTED <br />MOUNTING <br />N <br />NEU RAL <br />NO <br />NORMALLY CLOSED <br />NEC <br />NATIONAL ELECTRICAL CODE <br />NIC <br />NOT IN CONTRACT <br />NTS <br />NO <br />NOT TO SCALE <br />NORMALLY OPEN <br />OF CI <br />OWNER FURNISHED CONTRACTOR INSTALLE[ <br />OFOI <br />OWNER FURNISHED OWNER INSTALLED <br />PB <br />PULLBOX <br />PC <br />PHOTOCELL CONTROL <br />PH <br />PHASE <br />PLBG <br />PLUMBING <br />PUT <br />PVC <br />PANEL <br />POLYVINYL CHLORIDE <br />PP <br />POWER POLE <br />PS <br />POWER SENTRY EMERGENCY BATTERY UNIT <br />STY <br />QUANTITY <br />RECEPT <br />RECEPTACLE <br />REF <br />REFRIGERATOR <br />RGS <br />RIGID GALVANIZED STEEL <br />RM <br />ROOM <br />SB <br />STANDBY <br />SD <br />SMOKE DETECTOR <br />SPEC <br />SPECIFICATION <br />SQFT <br />SQUARE FEET OR SQUARE FOOT <br />SWBD <br />SWGR <br />SWITCHBOARD <br />SW TCHGEAR <br />TEMP <br />TEMPERATURE OR TEMPORARY <br />TV <br />TELEVISION <br />TYP <br />TYPICAL <br />LOPS <br />UNDERGROUND PULL SECTION <br />UL <br />UNDERWRITERS LABORATORIES <br />LINO <br />UNLESS NOTED OTHERWISE <br />V <br />VOLTS <br />VA <br />VOLTAMPERE <br />VFD <br />VARIABLE FREQUENCE DRIVE <br />W/ <br />WITH <br />WP <br />WEATHERPROOF <br />WT <br />WEIGHT <br />X <br />EXISTING <br />XFMR <br />TRANSFORMER <br />I SYMBOLS LIST <br />BRANCH CIRCUIT HOMERUN <br />1 3/4" CONDUIT MINIMUM - 1#2 HOT, 1#12 <br />NEUTRAL AND 1#12 GROUND. TYPICAL <br />UNLESS NOTED OTHERWISE. <br />NEUTRAL <br />BRANCH CIRCUIT WIRING WITH TICK <br />MARKS <br />GND HOT(S) <br />ELECTRICAL PANELBOARD <br />Sheet List Table <br />Sheet <br />Sheet Title <br />Number <br />EN01 <br />ELECTRICAL LEAD SHEET <br />EA01 <br />PARTIAL SITE ELECTRICAL PLAN <br />Underground Service Alert <br />of Southern California le <br />TWO WORKING DAYS <br />BEFORE YOU DIG <br />KDow Ibaf below. <br />COlbefore you dig. w DigAI,u.orq <br />NOTICE TO CONTRACTOR <br />PURSUANT TO ASSEMBLY BILL 4218 NO EXCAVATION PERMIT <br />IS VALID UNLESS THE CONTRACTOR CONTACTS AND OBTAINS <br />A DIG ALERT TICKET NUMBER. CALL 811 AT LEAST TWO <br />WORKING DAYS PRIOR TO COMMENCING EXCAVATION. <br />Robert J. Hatch, P.E. <br />A <br />LE1PRpFE55/p. <br />,p� J. y4r"�9 <br />- <br />LtNWC 1) <br />ENCINEEWNC IHC <br />- <br />16 <br />f <br />...«�....,.- <br />sTq� OF CALIF <br />MR.12/31/23 <br />FILE No.: <br />REVISIONS <br />REFERENCES <br />THEHSUPERVISOH <br />DATE <br />ELECTRICAL LEAD SHEET EN01 <br />CT^� <br />NUMBER <br />DATE <br />INITIALS <br />DESCRIPTION <br />APPROVED <br />INSTALLED <br />BENCHMARK NO.: XX-XXX-XX ELEV.: NNN.NN' NAVDYY <br />OF: <br />10/2021 <br />C A B R ILL O PARK IRRIGATION RENOVATION <br />SENIOR LANDSCAPE ARCHITECT <br />%_ <br />JAMES BRECK <br />DESIGNED: ML DRAWN: AT CHECKED: ME <br />�J <br />REVIEWED FOR <br />CABRLLO PARK - CORNER OF CABRLLO PARK DR. & FRUIT ST. <br />4G <br />CONSTRUCTABIUTY <br />AND RECOMMENDED <br />FOR CONSTRUCTION: <br />PUBLIC WORKS AGENCY <br />CONSTRUCTION COMPLETED: <br />JASON GABRIEL <br />XX/YYYY <br />CITY OF SANTA ANA SHEET 11 OF 12 <br />PRINCIPAL CIVIL ENGINEER RCE NO.: 62968 <br />