ELECTRICAL SPECIFICATIONS ELECTRICAL GENERAL NOTES ABBREVIATIONS AND DESCRIPTIONS
<br />rr"ca ni
<br />1. CONTRACTOR SHALL PERFORM ALL WORK AS TO CONFORM TO
<br />LOCAL, STATE AND NATIONAL CODES AND THE REQUIREMENTS OF
<br />LOCAL AUTHORITIES HAVING JURISDICTION.
<br />2. CONTRACTOR TO EXAMINE THE SITE TO DETERMINE THE EXACT
<br />CONDITIONS AFFECTING THE ELECTRICAL WORK.
<br />3. DRAWNGS INDICATE THE GENERAL SCHEME OF THE INSTALLATION
<br />AND ARE DIAGRAMMATIC IN SCOPE THE ENGINEER RESERVES THE
<br />RIGHT i0 CHANGE THE LOCATION OF OUTLETS, CONDUIT,
<br />EQ UIPMENT APPARATUS ETC. TO A REASONABLE EXTENT AS THE
<br />BUILDING CONDITIONS MAY DICTATE PRIOR TO THEIR INSTALLATION
<br />WITHOUT EXTRA COST TO THE OWNER. THE EXACT LOCATION AND
<br />ARRANGEMENT OF ALL EQUIPMENT AND PARTS SHALL BE
<br />DETERMINED AS THE WORK PROGRESSES,
<br />4. DETAILS OF CONSTRUCTION AND OF WORKMANSHIP WHERE NOT
<br />SPECIFICALLY DESCRIBED HEREIN OR INDICATED ON THE DRAWINGS
<br />SHALL BE SUBJECT TO THE ENGINEER'S APPROVAL. IT IS THE
<br />INTENT OF THESE SPECIFICATIONS TO PROVIDE COMPLETE
<br />SYSTEMS, LEFT IN GOOD WORKING ORDER, READY FOR OPERATION,
<br />5. SCRAP AND DEBRIS, EXCEPT AS OTHERWISE SPECIFIED. SHALL BE
<br />REMOVED FROM THE SITE AND DISPOSED OF BY THIS
<br />CONTRACTOR,
<br />6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR START-UP OF ALL
<br />SYSTEMS.
<br />7. ALL WORK SHALL BE DONE WITH A MINIMUM OF DUST AND DIRT.
<br />PROVIDE SUFFICIENT FIREPROOF TARPAULINS AND COVER ALL
<br />EQUIPMENT IN WORK AREA WITH SAME DURING WORK OPERATIONS.
<br />6. CONTRACTOR SHALL FURNISH SHOP DRAWINGS AND EQUIPMENT
<br />CUTS TO THE ARCHITECT FOR APPROVAL.
<br />9. CONTRACTOR SHALL FILE. SECURE AND PAY FOR ANY NECESSARY
<br />APPROVALS, PERMITS AND INSPECTIONS.
<br />10. ALL WORK SHALL BE GUARANTEED TO BE FREE FROM DEFECT FOR
<br />ONE YEAR AFTER ACCEPTANCE OF WORK.
<br />11. ALL WORK BE IN STRICT CONFORMANCE WITH THE LATEST VERSION
<br />OF THE STATE OF CALIFORNIA FIRE CODE, THE CALIFORNIA
<br />EIECIRIC CODE, THE CALIFORNIA GREEN CODE, AND THE
<br />CALIFORNIA BUILDING CODE.
<br />12. CONTRACTOR TO COORDINATE TESTING WITH LOCAL OFFICIALS.
<br />13. CONTRACTOR SHALL BE RESPONSIBLE FOR DISCONNECTING AND
<br />MAKING SAFE ALL ELECTRICAL FACILITIES IN EXISTING STRUCTURE
<br />PRIOR TO DEMOLITION.
<br />14. CONTRACTOR SHALL BE RESPONSIBLE FOR COMMISSIONING OF
<br />SYSTEMS AS REQUIRED BY LOCAL CODE,
<br />15. NO PIPING, DUCTS OR EQUIPMENT FOREIGN TO ELECTRICAL
<br />EQUIPMENT SHALL BE PERMITTED TO BE LOCATED THIN THE
<br />DEDICATED SPACE ABOVE THE ELECTRICAL EQUIPMENT.
<br />16. PROVIDE AND MAINTAIN REQUIRED WORK SPACE, ACCESS TO WORK
<br />SPACE AND HEAD ROOM ABOUT ELECTRICAL EQUIPMENT PER
<br />TABLE 110.26(A)(1).
<br />CONDUCTORS
<br />I. UNLESS OTHERWISE NOTED, CONDUCTOR TYPES SHALL BE AS
<br />INDICATED BELOW:
<br />LOCATION
<br />CONDUCTORS
<br />BRANCH CIRCUITS AND FEEDERS
<br />IN CONDUIT
<br />THHN/THWN
<br />CONCEALED BRANCH CIRCUITS
<br />TYPE "AC' CABLE
<br />UNDERGROUND OUTDOORS
<br />RH W/THW/IHWN
<br />2. ALL WIRE AND CABLE SHALL BE COPPER CONDUCTORS.
<br />CONDUCTORS gtOAWG AND SMALLER MAY BE SOLID
<br />CONDUCTORS LARGER THAN #1OAWG SHALL BE STRANDED.
<br />3. CONDUCTORS 68AWG AND SMALLER MAY BE SPLICED USING
<br />NYLON SELF -INSULATED WIRE NUTS AS MANUFACTURED BY 3M
<br />" SCOTCHLOK", IDEAL "WIRE -NUT' OR APPROVED EQUAL.
<br />4. EXCEPT WHERE EQUIPMENT, SUCH AS MOLDED CASE CIRCUIT
<br />BREAKERS, ARE SUPPLIED WITH FACTORY INSTALLED SET SCREW
<br />LUGS, ALL CONNECTIONS FOR CABLES 4/0 AND LARGER SHALL
<br />BE MADE USING NEMA 2 BOLT COMPRESSION LUGS. LUGS
<br />SHALL BE HYDRAULICALLY APPLIED USING MANUFACTURER'S
<br />TOOLING, DIES AND RECOMMENDED PROCEDURES.
<br />5. UNLESS OTHERWISE INDICATED ON THE DRAWINGS, ALL BRANCH
<br />CIRCUITS AND HOME RUNS SHALL BE #12AWG, QUANTITY AS
<br />NDICATED BY HASH MARKS.
<br />6, ADJUST BRANCH CONDUCTOR SIZES AS REQUIRED FOR VOLTAGE
<br />DROP MAXIMUM BRANCH CIRCUIT LENGTHS SHALL BE AS
<br />FOLLOWSUNLESSOTHERWISE NOTED:
<br />®Il�llla:a
<br />�II�II�I�
<br />THE ABOVE LENGTHS REPRESENT "ONE-WAY" CIRCUIT LENGTH
<br />(NOT WIRE LENGTH) AND INCLUDE ALL VERTICAL RISES AND
<br />DROP,
<br />.
<br />7. CONDUCTOR INSULATIONS SHALL BE COLOR CODED AS FOLLOWS:
<br />-III
<br />WHERE CONDUCTORS ARE NOT AVAILABLE NTH COLOR CODED
<br />INSULATION, COLORED TAPES SHALL BE APPLIED TO THE ENTIRE
<br />EXPOSED LENGTH OF CABLES IN PULL BOXES, SWITCHBOARDS,
<br />EQUIPMENT, ETC,
<br />RACEWAYS
<br />1, UNLESS OTHERWISE NOTED, RACEWAY TYPES SHALL BE AS
<br />INDICATED BELOW
<br />LOCATION
<br />WHERE CONDUCTORS ARE NOT AVAILABLE NTH COLOR CODED
<br />INSULATION, COLORED TAPES SHALL BE APPLIED TO THE ENTIRE
<br />EXPOSED LENGTH OF CABLES IN PULL BOXES, SWITCHBOARDS,
<br />EQUIPMENT, ETC,
<br />RACEWAYS
<br />1, UNLESS OTHERWISE NOTED, RACEWAY TYPES SHALL BE AS
<br />INDICATED BELOW
<br />LOCATION
<br />RACEWAY
<br />OUTDOORS, ABOVE GRADE..
<br />GALVANIZED RICH) STEEL (GRS)
<br />INDOOR FEEDERS AND
<br />SUB FEEDERS NOT EXPOSED
<br />TO PHYSICAL DAMAGE.
<br />ELECTRICAL METALLIC TUBING (EMT)
<br />INDOOR BRANCH CIRCUITS
<br />EXPOSED IN UTILITY
<br />AREAS. .
<br />ELECTRICAL METALLIC TUBING (EMT)
<br />UNDERGROUND...
<br />TYPE "DE", SCHEDULE 40 RIGID (PVC),
<br />NON METALLIC CONDUIT
<br />UNDERGROUND
<br />PENETRATION..
<br />GALVANIZED RIGID STEEL (GRS)
<br />THROUGH GRADE
<br />2. GALVANIZED RIGID STEEL CONDUIT SHALL BE MANUFACTURED IN
<br />ACCORDANCE WITH ANSI #CBOT AND UL S. INSTALLATI ON OF
<br />GALVANIZED RIGID STEEL CONDUIT SHALL BE IN STRICT
<br />CONFORMANCE WITH NEC ARTICLE #344.
<br />3. EMT SHALL BE MANUFACTURED IN ACCORDANCE WITH ANSI
<br />fU80.3 AND UL 797. INSTALLATION OF ELECTRICAL METALLIC
<br />UBING SHALL B IN STRICT CONFORMANCE WITH NEC ARTICLE
<br />1344, BENDING RADIUS SHALL NOT BE LESS THAN NEC TABLE 2,
<br />CHAPTER 9. SUPPORT SPACING SHALL NOT EXCEED 10'-0'.
<br />ALL EMT COUPLINGS AND CONNECTORS SHALL BE OF THE
<br />CONCRETE -TIGHT AND RAIN -TIGHT TYPE. SET SCREW
<br />CONNECTORS SHALL NOT BE USED.
<br />4, EXCEPT FOR SURFACE METAL AND SURFACE NON-METALLIC, ALL
<br />RACEWAYS SHALL BE INSTALLED CONCEALED WITH THE
<br />EXCEPTION OF BOILER ROOMS, UTIUTY ROOMS, GARAGES AND
<br />OTHER AREAS SPECIFICALLY APPROVED BY THE ARCHITECT.
<br />5. SEAL ALL PENETRATIONS THROUGH FIRE RESISTIVE ASSEMBLIES
<br />WITH APPROVED MATERIALS PER SEC. 709.E AND 710, CDC.
<br />SITE SERVICES
<br />1, ALL UNDERGROUND RACEWAYS, SHALL BE TYPE US, SCHEDULE
<br />40 PVC, RIGID NON-METALLIC CONDUIT, AND MANUFACTURED BY
<br />CARTON OR APPROVED EQUAL AND SHALL BE INSTALLED IN
<br />ACCORDANCE WITH NEC ARTICLE #352.
<br />2. NON-METALLIC RIGID CONDUIT SHALL BE MANUFACTURED IN
<br />STRICT CONFORMANCE WITH UL #651 AND NEMA #TC-2.
<br />3. FITTINGS FOR RIGID NON-METALLIC CONDUIT SHALL BE OF THE
<br />SOLVENT CEMENTED TYPE AND SHALL BE MANUFACTURED IN
<br />STRICT CONFORMANCE WITH UL 3514 AND NEMA ATC-3.
<br />SOLVENT CEMENT PROCEDURES SHALL BE IN ACCORDANCE WITH
<br />THE MANUFACTURERS RECOMMENDATIONS.
<br />4. WHEREVER POSSIBLE, RIGID NON-METALLIC CONDUIT ELBOWS,
<br />OFFSETS, ETC. SHALL BE MADE USING 30 DEGREE, 45 DEGREE
<br />AND 90 DEGREE FACTORY ELBOWS. WHERE FACTORY ELBOWS
<br />CANNOT BE ACCOMMODATED, FIELD BENDING SHALL USE HEATING
<br />BOXES, END PLUGS AND FORMING GUIDES AS RECOMMENDED BY
<br />THE MANUFACTURER. CARE SHALL BE EXERCISED TO ENSURE
<br />THAT THE INTERNAL DIAMETER OF CONDUITS IS NOT EFFECTIVELY
<br />REDUCED BY FIELD BENDING.
<br />5, MINIMUM BENDING RADIUS FOR RIGID NON-METALLIC CONDUIT
<br />SHALL NOT BE LESS THAN PERMITTED BY NEC TABLE 2,
<br />CHAPTER 9,
<br />6, ALL PENETRATIONS THROUGH MANHOLES, HANDHOLES,
<br />FOUNDATIONS, ETC. SHALL BE MADE USING HOT -DIPPED
<br />GALVANIZED, RIGID STEEL (GRS) CONDUIT. MAKE TRANSITION
<br />FROM RGID NON-METALLIC TO GRS AT 5'-0" FROM
<br />PENETRATION USING APPROVED TRANSITION COUPLING. PROVIDE
<br />3" CONCRETE ENVELOPE AROUND TRANSITION COUPLING
<br />EXTENDING 3'-C" IN EITHER DIRECTION TO MINIMIZE SHEAR
<br />FORCES AT TRANSITION COUPLING.
<br />CIRCUIT BRE
<br />1, EQUIPMENT INTERRUPTING RATINGS SHOWN ON SCHEDULES ARE
<br />BASED ON UL USTED FULL RATING FOR 65,000A AVAILABLE
<br />SHORT CIRCUIT CURRENT AT THE SERVICE. CONTRACTOR SHALL
<br />INCREASE INTERRUPTING RATINGS AS REQUIRED FOR FULLY RATED
<br />EQUIPMENT
<br />BoxES
<br />1. BOXES FOR BRANCH CIRCUIT WIRING DEVICES AND BRANCH
<br />CIRCUIT SPLICES SHALL BE AS INDICATED BELOW:
<br />FLUSH WIRING DEVICES
<br />ON METAL STUDS
<br />RACO #172/173/174
<br />(4" SQUARE)
<br />FLUSH WIRING DEVICES
<br />ON WQOD STUDS
<br />RACO #504/565
<br />GANGABLE
<br />FLUSH WIRING DEVICES
<br />IN MASONRY WALLS
<br />RACO #690
<br />N GANG)
<br />GANG BOXES
<br />RACO #951/953/953/954/955
<br />SURFACE WIRING DEVICES
<br />(DRY AREAS)
<br />RACO #192
<br />4" SQUARE)
<br />SURFACE WIRING DEVCES
<br />(WET ARES, 1 GANG)
<br />BELL 270-L/Z73-L
<br />F.S. TYPE)
<br />SURFACE WIRING DEVICES
<br />(WET AREAS, 2 GANG)
<br />BELL 276-4L/ 277-4L
<br />(ES. TYPE)
<br />THE ABOVE MODEL NUMBERS ARE TYPICAL OF THE PRODUCTS
<br />REQUIRED. CONTRACTOR SHALL ADJUST MODEL NUMBERS AS
<br />REQUIRED TO SUIT JOB CONDITIONS, WALL THICKNESS, DEVICE
<br />REQUIREMENTS, ETC,
<br />2, PULL AND JUNCTION BOXES SHALL BE CODE GAUGE ENAMELED
<br />STEEL, NEMA "1" WITH SCREW FASTENED COVERS WHEN USED IN
<br />INDOOR, DRY AREAS STEEL GAUGE SHALL BE IN ACCORDANCE
<br />WITH NEC ARTICLE #314.40.
<br />3. PULL AND JUNCTION BOXES UTILIZED IN INDOOR AREAS WHICH
<br />CONNECTIONS TO UNDERGROUND RACEWAYS, ETC.) SHALL BE
<br />GALVANIZED TYPE NEMA "1".
<br />4. PULL AND JUNCTION BOXES FOR USE OUTDOORS SHALL BE
<br />GALVANIZED AND OF NEMA "3R" CONSTRUCTION.
<br />5. ALL PULL BOXES FASTENED TO EXTERIOR BLOCKS OR MAS01
<br />WALLS SHALL BE PROVIDED WITH 1 1/2" CHANNEL FRAMING
<br />SPACERS ORIENTED VERTICALLY AT REAR OF ENCLOSURE TO
<br />SHALL BE SIZED IN ACCORDANCE WITH NEC ARTICLE
<br />'314.16-#31430.
<br />7. PULLSOXES AND LARGER JUNCTION BOXES SHALL BE SIZED IN
<br />A
<br />CCORDANCE TH NEC ARTICLE #314.28.
<br />8. MERE USE OF KNOCKOUTS IS DISCONTINUED BY CHANGES IN THE
<br />WORK, INSTALL PROPERLY SIZED KNOCKOUT SEALS BY THOMAS
<br />AND BETTS. RACOR, APPLETON OR EQUAL.
<br />caourl0wc
<br />1. GROUNDING ELECTRODE CONDUCTORS SHALL BE SIZED IN
<br />ACCORDANCE WITH NEC TABLE #250.66 AND NEC ARTICLE
<br />#25D. 102(C).
<br />2, GROUNDING OF ELECTRICAL EQUIPMENT AND ENCLOSURES
<br />DOWNSTREAM OF THE SERVICE DISCONNECT SHALL BE BY
<br />INSULATED GROUNDING CONDUCTOR. INCLUDE WITH ALL FEEDERS
<br />AND BRANCH CIRCUITS.
<br />3. RECEPTACLE MOUNTING YOKE SHALL NOT BE USED FOR
<br />GROUNDING PURPOSES WITH RECESSED OUTLET BOXES PROVIDE
<br />INSULATED GROUNDING JUMPER FROM OUTLET BOXES TO
<br />RECEPTACLE GROUNDING TERMINAL.
<br />RATINGS AS SHOWN ON THE DRAWINGS.
<br />2. ALL SWITCHES SHALL BE QUICK -MAKE. OUICK-BREAK OPERATION
<br />SUITABLE FOR USE IN THE LOCATION SHOWN, SWITCHES SHALL BE
<br />AS MANUFACTURED BY SQUARE D, GENERAL ELECTRIC,
<br />WESTINGHOUSE OR EQUAL.
<br />1. CONTRACTOR SHALL PERFORM ALL WORK AS
<br />NATIONALRM CODES ANCD LtH ET REQUIREMENTS OF
<br />LOCAL AUTHORITIES HAVING JURISDICTION.
<br />2. CONTRACTOR TO EXAMINE THE SITE TO
<br />DETERMINE THE EXACT CONDITIONS
<br />AFFECTING THE ELECTRICAL WORK.
<br />3. DRAWINGS INDICATE THE GENERAL SCHEME
<br />OF THE INSTALLATION AND ARE
<br />DIAGRAMMATIC IN SCOPE. THE ENGINEER
<br />RESERVES THE RIGHT TO CHANGE THE
<br />LOCATION OF OUTLETS, CONDUIT, EQUIPMENT
<br />APPARATUS, ETC. TO A REASONABLE EXTENT
<br />AS THE BUILDING CONDITIONS MAY DICTATE
<br />PRIOR TO THEIR INSTALLATION WITHOUT
<br />EXTRA COST TO THE OWNER. THE EXACT
<br />LOCATION AND ARRANGEMENT OF ALL
<br />EQUIPMENT AND PARTS SHALL BE
<br />DETERMINED AS THE WORK PROGRESSES.
<br />4. DETAILS OF CONSTRUCTION AND OF
<br />WORKMANSHIP WHERE NOT SPECIFICALLY
<br />DESCRIBED HEREIN OR INDICATED ON THE
<br />DRAWINGS SHALL BE SUBJECT TO THE
<br />ENGINEER'S APPROVAL. IT IS THE INTENT OF
<br />THESE SPECIFICATIONS TO PROVIDE COMPLETE
<br />SYSTEMS. LEFT IN GOOD WORKING ORDER,
<br />REAY FOR OPERATION.
<br />5. SCRAP AND DEBRIS EXCEPT AS OTHERWISE
<br />SPECIFIED, SHALL BE REMOVED FROM THE
<br />SITE AND DISPOSED OF BY THIS
<br />CONTRACTOR.
<br />6. THE CONTRACTOR SHALL BE RESPONSIBLE
<br />FOR START-UP OF ALL SYSTEMS.
<br />7. ALL WORK SHALL BE DONE WITH A MINIMUM
<br />OF DUST AND DIRT. PROVIDE SUFFICIENT
<br />FIREPROOF TARPAULINS AND COVER ALL
<br />EQUIPMENT IN WORK AREA WITH SAME
<br />DURING WORK OPERATIONS.
<br />8, CONTRACTOR SHALL FURNISH SHOP
<br />DRAWINGS AND EQUIPMENT CUTS TO THE
<br />ARCHITECT FOR APPROVAL (MINIMUM (5)
<br />COPIES).
<br />X COORDINATE NEW SERVICE CONNECTIONS WITH
<br />LOCAL UTILITY COMPANY(S).
<br />10. FOR TANY TOR SHALL
<br />PERMITSY
<br />AND INSPECTIONS.
<br />11. ALL WORK SHALL BE GUARANTEED TO BE
<br />FREE FROM DEFECT FOR ONE YEAR AFTER
<br />ACCEPTANCE OF WORK.
<br />12. CONTRACTOR TO COORDINATE TESTING WITH
<br />LOCAL OFFICIALS.
<br />13. ALL WORK BE IN STRICT CONFORMANCE WITH
<br />THE LATEST VERSION OF THE STATE OF
<br />CALIFORNIA FIRE CODE, THE CALIFORNIA
<br />CODE, AND CODE, CALIFORNIA BUILDINGECODE.
<br />14. PRIOR TO TESTING, CONTRACTOR SHALL
<br />MAKE ALL SYSTEM ADJUSTMENTS REQUIRED
<br />FOR PROPER OPERATION. ADJUSTMENTS
<br />SHALL INCLUDE TRANSFORMER TAPS, CIRCUIT
<br />BREAKER MAGNETIC SETTINGS, GROUND
<br />FAULT RELAY TRIP SETTINGS. BALLAST TAP
<br />SETTINGS, ETC.
<br />15. CONTRACTOR SHALL BE RESPONSIBLE FOR
<br />DISCONNECTING AND MAKING SAFE ALL
<br />ELECTRICAL FACILITIES IN EXISTING
<br />STRUCTURE PRIOR TO DEMOLITION.
<br />16. CONTRACTOR SHALL BE RESPONSIBLE FOR
<br />COMMISSIONING OF SYSTEMS AS REQUIRED
<br />BY LOCAL CODE.
<br />17. ALL EQUIPMENT SHALL BE LISTED BY A CITY
<br />OF SANTA ANA RECOGNIZED ELECTRICAL
<br />TESTING LAB (IE U.L.) OR APPROVED BY THE
<br />DEPARTMENT.
<br />18. COMPLY WITH CITY OF SANTA ANA
<br />AMENDMENTS TO 2019 CEC.
<br />19. USE RIGID METAL CONDUIT IN ALL AREAS
<br />EXPOSED TO WEATHER USE GROUND WIRE
<br />INSIDE ALL FLEXIBLE METAL CONDUITS.
<br />METAL CONDUIT SHALL NOT BE INSTALLED IN
<br />CONTACT WITH EARTH.
<br />20. SCREENING SHALL BE PROVIDED SO THAT
<br />MATERIALS STORED IN ANY OUTDOOR
<br />STORAGE AREA AND/OR EQUIPMENT AT
<br />GRADE OR ON THE ROOF ARE SCREENED
<br />FROM VIEW FROM ALL ADJACENT STREETS,
<br />PROPERTIES A E THE SAME HGRADEAND ALL
<br />21. ALL UNDERGROUND RACEWAYS, SHALL BE
<br />INOEETALUCE CONDUIT AND RIGID
<br />BY CARTON OR APPROVED EQUAL AND
<br />SHALL BE INSTALLED IN ACCORDANCE WITH
<br />NEC ARTICLE #352.
<br />22. NON-METALLIC RIGID CONDUIT SHALL BE
<br />MANUFACTURED IN STRICT CONFORMANCE
<br />WITH UL #651 AND NEMA #TC-2.
<br />23. ALL GROUND CONDUCTORS SHALL BE
<br />INSULATED COPPER.
<br />24, FITTINGS FOR RIGID NON-METALLIC CONDUIT
<br />SHALL BE OF THE SOLVENT CEMENTED TYPE
<br />AND SHALL BE MANUFACTURED IN STRICT
<br />CONFORMANCE WITH UL 3514 AND NEMA
<br />#TC-3. SOLVENT CEMENT PROCEDURES
<br />SHALL BE IN ACCORDANCE WITH THE
<br />MANUFACTURERS RECOMMENDATIONS.
<br />25. CONDUITS ELBOWSB 0 STETS, ETC SHALLLIBE
<br />MADE USING 30 DEGREE, 45 DEGREE AND 90
<br />DEGREE FACTORY ELBOWS. WHERE FACTORY
<br />ELBOWS CANNOT BE ACCOMMODATED, FIELD
<br />BENDING SHALL USE HEATING BOXES. END
<br />PLUGS AND FORMING GUIDES AS
<br />RECOMMENDED BY THE MANUFACTURER. CARE
<br />SHALL BE EXERCISED TO ENSURE THAT THE
<br />INTERNAL DIAMETER OF CONDUITS IS NOT
<br />EFFECTIVELY REDUCED BY FIELD BENDING.
<br />26. MINIMUM BENDING RADIUS FOR RIGID
<br />NON-METALLIC CONDUIT SHALL NOT BE LESS
<br />THAN PERMITTED BY NEC TABLE 2, CHAPTER
<br />9.
<br />27. MINIMUM BURIAL DEPTH FOR UNDERGROUND
<br />RIGID NON-METALLIC RACEWAY SHALL BE 36"
<br />BELOW FINISHED GRADE. WHERE LESSER
<br />DEPTHS ARE REQUIRED DUE TO SUBSURFACE
<br />OBSTACLES, ENCASE RACEWAYS IN MINIMUM
<br />3", 3000 PSI CONCRETE ENVELOPE.
<br />28 HANDHOLES PENETRATIONS
<br />DATIOTHRNSGETC
<br />CAN SHALE BE
<br />MADE USING` HOT -DIPPED GALVANIZED RIGID
<br />STEEL (GRS) CONDUIT. MAKE TRANSITION
<br />FROM RIGID NON-METALLIC TO GRS AT 5'-0"
<br />FROM PENETRATION USING APPROVED
<br />TRANSITION COUPLING. PROVIDE 3"
<br />CONCRETE ENVELOPE AROUND TRANSITION
<br />COUPLING EXTENDING S-O" IN EITHER
<br />DIRECTION TO MINIMIZE SHEAR FORCES AT
<br />TRANSITION COUPLING.
<br />29. RISERS AT UTILITY POLES SHALL CONSISTS
<br />OF GRS ELBOWSS) AND CONDUCT TO 10,-0
<br />'
<br />ABOVE FIN ISHE AND
<br />FOR ELECTRICAL
<br />SUPPLIES. SPARE ELECTRICAL DUCTS SHALL
<br />BE CAPPED AT 6" ABOVE FINISHED GRADE.
<br />30. PROVIDE WEATHERPROOF (NEMA 3R1
<br />JUNCTION BOXES, CONDUIT FITTING SS AND
<br />ENCLOSURES AT ALL EXTERIOR LOCATIONS
<br />AND ALL WET OR DAMP INTERIOR LOCATIONS.
<br />31, ALL AMPACITIES ARE BASED UPON TABLE
<br />31015lB116 OF THE 2019 CALIFORNIA
<br />ELECTTRRICCAL CODE,
<br />APPLICABLE CODES
<br />2019 CALIFORNIA BUILDING CODE (CBC)
<br />2019 CALIFORNIA ELECTRICAL CODE (CEC)
<br />2019 CALIFORNIA ENERGY CODE
<br />2019 CALIFORNIA FIRE CODE.
<br />2019 CALIFORNIA BUILDING ENERGY EFFICIENCY STANDARDS
<br />2019 CALIFORNIA GREEN BUILDING STANDARDS CODE
<br />A
<br />AMPERES
<br />AC
<br />ALTERNATING CURRENT
<br />AID
<br />AFC
<br />AMPERES INTERRUPTING CAPACITY
<br />AVAILABLE FAULT CURRENT
<br />AFF
<br />ABOVE FINISHED FLOOR
<br />AEG
<br />ABOVE FINISHED GRADE
<br />AF
<br />AMP FRAME/AMP FUSE
<br />AL
<br />ALUMINUM
<br />AS
<br />AT
<br />AMP SWITCH
<br />AMP TRIP
<br />ATE
<br />AUTOMATIC TRANSFER SWITCH
<br />AWG
<br />AMERICAN WIRE GAUGE
<br />CAN
<br />CABLE TELEVISION
<br />CCTV
<br />CLOSED CIRCUIT TELEVISION
<br />CB
<br />CIRCUIT BREAKER
<br />CO
<br />CONDUIT ONLY WITH NYLON PULLCORD
<br />CO AS
<br />CU
<br />COAXIAL CABLE
<br />COPPER
<br />CT
<br />CURRENT TRANSFORMER
<br />DC
<br />DIRECT CURRENT
<br />DIST
<br />DISTRIBUTION
<br />DB
<br />DISTRIBUTION SWITCHBOARD
<br />DWGS
<br />DRAWINGS
<br />OF
<br />EXHAUST FAN
<br />ELECT
<br />ELECTRICAL
<br />ELEV
<br />ELEVATION/ELEVATOR
<br />EM ER,EM
<br />EMERGENCY
<br />EMT
<br />ELECTRO-METALLIC TUBING
<br />EQUIP
<br />EXIST,EX
<br />EQUIPMENT
<br />EXISTING
<br />F
<br />DEGREES FAHRENHEIT
<br />FA
<br />FIRE ALARM
<br />FF
<br />FURNITURE FEED, FINISHED FLOOR
<br />G
<br />GROUND BUS OR WIRE
<br />GD
<br />GARBAGE DISPOSAL
<br />GFCI
<br />GROUND FAULT CIRCUIT INTERRUPTER
<br />GND
<br />GROUND
<br />H
<br />HORIZONTAL
<br />HP
<br />HORSEPOWER
<br />HOA
<br />HAND -OFF -AUTOMATIC
<br />HE
<br />HERTZ
<br />IS
<br />ISOLATED GROUND
<br />IMC
<br />INTERMEDIATE METAL CONDUIT
<br />J-BOX
<br />JUNCTION BOX
<br />KCM
<br />KILO -CIRCULAR -MIL
<br />KVA
<br />KILO-VOLTAMPERE
<br />KW
<br />KILO -WATT
<br />UPS
<br />POUNDS
<br />LV
<br />LOW VOLTAGE
<br />SCOPE OF WORK
<br />EXISTING IRRIGATION CONTROLLER WITHIN ELECTRICAL ROOM TO BE DISCONNECTED
<br />AND REMOVED AND A NEW PEDESTAL MOUNTED IRRIGATION CONTROLLER IN AND
<br />EXTERIOR PLANTER AREA TO BE INSTALLED. EXISTING CIRCUITRY SHALL BE REUSED
<br />FOR CONNECTION OF NEW CONTROLLER.
<br />MAX
<br />MAXIMUM
<br />MCC
<br />MOTOR CONTROL CENTER
<br />MCP
<br />MECH
<br />MOTOR CIRCUIT PROTECTION
<br />MECHANICAL
<br />MIN
<br />MINIMUM
<br />MILD
<br />MAIN LUGS ONLY
<br />MT D
<br />MTG
<br />MOUNTED
<br />MOUNTING
<br />N
<br />NEU RAL
<br />NO
<br />NORMALLY CLOSED
<br />NEC
<br />NATIONAL ELECTRICAL CODE
<br />NIC
<br />NOT IN CONTRACT
<br />NTS
<br />NO
<br />NOT TO SCALE
<br />NORMALLY OPEN
<br />OF CI
<br />OWNER FURNISHED CONTRACTOR INSTALLE[
<br />OFOI
<br />OWNER FURNISHED OWNER INSTALLED
<br />PB
<br />PULLBOX
<br />PC
<br />PHOTOCELL CONTROL
<br />PH
<br />PHASE
<br />PLBG
<br />PLUMBING
<br />PUT
<br />PVC
<br />PANEL
<br />POLYVINYL CHLORIDE
<br />PP
<br />POWER POLE
<br />PS
<br />POWER SENTRY EMERGENCY BATTERY UNIT
<br />STY
<br />QUANTITY
<br />RECEPT
<br />RECEPTACLE
<br />REF
<br />REFRIGERATOR
<br />RGS
<br />RIGID GALVANIZED STEEL
<br />RM
<br />ROOM
<br />SB
<br />STANDBY
<br />SD
<br />SMOKE DETECTOR
<br />SPEC
<br />SPECIFICATION
<br />SQFT
<br />SQUARE FEET OR SQUARE FOOT
<br />SWBD
<br />SWGR
<br />SWITCHBOARD
<br />SW TCHGEAR
<br />TEMP
<br />TEMPERATURE OR TEMPORARY
<br />TV
<br />TELEVISION
<br />TYP
<br />TYPICAL
<br />LOPS
<br />UNDERGROUND PULL SECTION
<br />UL
<br />UNDERWRITERS LABORATORIES
<br />LINO
<br />UNLESS NOTED OTHERWISE
<br />V
<br />VOLTS
<br />VA
<br />VOLTAMPERE
<br />VFD
<br />VARIABLE FREQUENCE DRIVE
<br />W/
<br />WITH
<br />WP
<br />WEATHERPROOF
<br />WT
<br />WEIGHT
<br />X
<br />EXISTING
<br />XFMR
<br />TRANSFORMER
<br />I SYMBOLS LIST
<br />BRANCH CIRCUIT HOMERUN
<br />1 3/4" CONDUIT MINIMUM - 1#2 HOT, 1#12
<br />NEUTRAL AND 1#12 GROUND. TYPICAL
<br />UNLESS NOTED OTHERWISE.
<br />NEUTRAL
<br />BRANCH CIRCUIT WIRING WITH TICK
<br />MARKS
<br />GND HOT(S)
<br />ELECTRICAL PANELBOARD
<br />Sheet List Table
<br />Sheet
<br />Sheet Title
<br />Number
<br />EN01
<br />ELECTRICAL LEAD SHEET
<br />EA01
<br />PARTIAL SITE ELECTRICAL PLAN
<br />Underground Service Alert
<br />of Southern California le
<br />TWO WORKING DAYS
<br />BEFORE YOU DIG
<br />KDow Ibaf below.
<br />COlbefore you dig. w DigAI,u.orq
<br />NOTICE TO CONTRACTOR
<br />PURSUANT TO ASSEMBLY BILL 4218 NO EXCAVATION PERMIT
<br />IS VALID UNLESS THE CONTRACTOR CONTACTS AND OBTAINS
<br />A DIG ALERT TICKET NUMBER. CALL 811 AT LEAST TWO
<br />WORKING DAYS PRIOR TO COMMENCING EXCAVATION.
<br />Robert J. Hatch, P.E.
<br />A
<br />LE1PRpFE55/p.
<br />,p� J. y4r"�9
<br />-
<br />LtNWC 1)
<br />ENCINEEWNC IHC
<br />-
<br />16
<br />f
<br />...«�....,.-
<br />sTq� OF CALIF
<br />MR.12/31/23
<br />FILE No.:
<br />REVISIONS
<br />REFERENCES
<br />THEHSUPERVISOH
<br />DATE
<br />ELECTRICAL LEAD SHEET EN01
<br />CT^�
<br />NUMBER
<br />DATE
<br />INITIALS
<br />DESCRIPTION
<br />APPROVED
<br />INSTALLED
<br />BENCHMARK NO.: XX-XXX-XX ELEV.: NNN.NN' NAVDYY
<br />OF:
<br />10/2021
<br />C A B R ILL O PARK IRRIGATION RENOVATION
<br />SENIOR LANDSCAPE ARCHITECT
<br />%_
<br />JAMES BRECK
<br />DESIGNED: ML DRAWN: AT CHECKED: ME
<br />�J
<br />REVIEWED FOR
<br />CABRLLO PARK - CORNER OF CABRLLO PARK DR. & FRUIT ST.
<br />4G
<br />CONSTRUCTABIUTY
<br />AND RECOMMENDED
<br />FOR CONSTRUCTION:
<br />PUBLIC WORKS AGENCY
<br />CONSTRUCTION COMPLETED:
<br />JASON GABRIEL
<br />XX/YYYY
<br />CITY OF SANTA ANA SHEET 11 OF 12
<br />PRINCIPAL CIVIL ENGINEER RCE NO.: 62968
<br />
|