Laserfiche WebLink
F. Hubs for threaded attachment of steel conduit to sheet metal enclosures, where <br />required, shall be similar to Appleton Type HUB, equivalent types such as <br />manufactured by T & B, Efcor, Myers Scrutite, or approved equal. <br />G. Transition fittings to mate steel to PVC conduit, and PVC access fitting, shall be as <br />furnished or recommended by the manufacturer of the PVC conduit. <br />H. Sealing fittings are required in conduit runs entering corrosive areas and elsewhere as <br />shown. Sealing fittings shall be Appleton Type EYS, O-Z Type FSK, or approved equal. <br />Sealing compound shall not be poured in place until electrical installation has been <br />otherwise accepted. <br />I. Expansion fittings shall be installed wherever a raceway crosses a structural expansion <br />joint. Such fittings shall be expansion and deflection type and shall accommodate <br />lateral and transverse movement. Fittings shall be O-Z/Gedney Type "DX," Crouse <br />Hinds "XD," or approved equal. These fittings are required in metallic and non-metallic <br />raceway installations. When the installation is in a non-metallic run, a 3-ft length of rigid <br />conduit shall be used to connect the non-metallic conduit to the fitting. <br />PART 3 — EXECUTION <br />3.1 INSTALLATION <br />A. UNDERGROUND DUCTS <br />General: Where an underground distribution system is required, it shall be <br />comprised of multiple runs of single bore non-metallic ducts, concrete encased, <br />with steel reinforcing bars. When non-metallic ducts are required, they shall be <br />rigid Schedule 40 PVC for concrete encasement. Trenching and patching shall be <br />performed by the CONTRACTOR. The original surface shall be repaired similar <br />to its original condition. <br />3.2 RACEWAYS <br />A. General: Raceways shall be installed as shown, however, conduit routings shown are <br />diagrammatic. Raceway systems shall be electrically and mechanically complete <br />before conductors are installed. Bends and offsets shall be smooth and symmetrical, <br />and shall be accomplished with tools designed for the purpose intended. Factory <br />elbows shall be used for all 3/4-inch conduit. Bends in larger sizes of metallic conduit <br />shall be accomplished by field bending or by the use of factory elbows. All installations <br />shall be in accordance with the latest edition of the National Electrical Code. <br />B. Raceways shall be installed in accordance with the following schedule: <br />Low Voltage Raceway (control, power, and data hi -way and communications): <br />a. Rigid Schedule 40 PVC shall be used for concrete encased duct on earth. <br />b. PVC -coated galvanized rigid steel raceways shall be used on exposed <br />locations in corrosive areas. <br />City of Santa Ana Conduit <br />Security Management System Project Page 16111-4 <br />SantaAna_SMS_16111 <br />