Laserfiche WebLink
A, Hardwired Functions <br />i, I "roaidc I�ilrrt IihC t �tispl�iy t]ie Fc7ltowua� p�nixip stt�rfeastsatns siatiuls: <br />at. pump CALL <br />b. Pump IN HAND <br />c. Pump RUN <br />d. Pump HIGH DISCHARGE PRESSURE <br />c. Pump LOW SUCTION PRESSURE <br />f. Motor HIGH TEMPERATURE <br />g, WD /SS'T FAIT, <br />i. Provide a RESET pushbutton for resetting latched alarm conditions. <br />1, Provide a LOCK-OFF-STOP pushbutton adjacent to the pump interlocked with the pump <br />starter, to prevent operation when in the OPF position. <br />4. Provide a RUN command to the pump starter when the 110A switch 'is in dw, HAND <br />p(sifion. <br />S. Clufput an OPEN command to the SST pump discharge valve when the pump is started, The <br />4''FD discharge valve shall OPEN when the pump is started and a minimum discharge <br />pressure Is obtained in the r"pectivc VFF) discharge piping. <br />6. Provide pump control and protection as indicated on the electrical schematics included with <br />the project draw[ngs, <br />7. Provide Pump Running and Drive Motor Foult indicating lights on the VFD or SST. The <br />DrivelMotor fault to indicate if any motor temperahire alarm or SS]"'WI) fault is detected. <br />B. PLC FLInCtions <br />t. l�oa- esch Lruml7 monitor the following fiend signals; <br />a. lt7 Remote <br />b, In Hand <br />c. Disidiarge pressure High alarm <br />d. Suction pressure "Low" alarni <br />city or Sonia Ana RFP 77,05 <br />2 5°f' SM. <br />