Laserfiche WebLink
I. Allow the. hoostel• Ixrrnpas to he started and :stopped from the PLC when tic: Local"Remote <br />switch Im the pump is in the 1.0('A1, position. <br />2. Providc pilot light to display tic following ptunp starter status signals: <br />a. Pump CALL <br />b. Pump IN IIAND <br />c. Pump RUIN <br />d. Ptunp HIGH DISCTHAROE PRESSURE. <br />c. Pump LOW DISCHARGE PRESSURE <br />l: Nfotor HI0I-1 TEMPERATURF <br />g. SST FAIL <br />3. Provide n RFSE "l" pu4tibutton 14 resetting latched alarm conditions. <br />4. Provide a LOCK -OIT -STOP pushbutton adjacent to the pump interlocked with the punip <br />starter, to present operation when in the OFF position. <br />S. Provide a RUN command to the pump snarter when the HOA switcli is in the HAND <br />posi Lion. <br />G. Provide pump control and protcetion as indicated on the pump electrical scltcniatics included <br />with the project drawings, <br />B. PLC' Functions <br />1. For ca h pump rrionitor the following Field fsiguils: <br />a, IN REMOTE <br />h, IN HAND <br />c. Discharge pressure High alarm <br />d. Discharge pressure "Low" alarm <br />c. RUN <br />C Motor High Temperature <br />g. SST FML <br />City tit Sant_ An�a��FA 15.1 ©5 <br />