SEE POWER SYSTEMS STUDY SPECIFICATION FOR ADDITIONAL REQUIREMENTS. ALL REQUIRED POWER SYSTEMS <br />STUDIES MUST BE COMPLETED AND SUBMITTED WITH ELECTRICAL POWER DISTRIBUTION EQUIPMENT SUBMITTAL. <br />FAILURE TO DO SO WILL PREVENT THE ENGINEER FROM EFFECTIVELY EVALUATING THE SUBMITTAL AND SHALL RESULT <br />IN REJECTION OF THE ELECTRICAL POWER DISTRIBUTION EQUIPMENT SUBMITTAL AS INCOMPLETE. <br />CONTRACTOR SHALL SUBMIT SHOP DRAWINGS PER THE SPECIFICATIONS FOR SWITCHBOARDS, DISTRIBUTION BOARDS, <br />TRANSFORMERS, PANEL BOARDS, AND ALL OTHER DEVICES SHOWN ON THE SINGLE LINE, PRIOR TO FABRICATION. <br />CONTRACTOR SHALL SUBMIT SWITCHBOARD SHOP DRAWINGS TO THE SERVING UTILITY FOR APPROVAL PRIOR TO <br />FABRICATION. CONTRACTOR SHALL SECURE CONFIRMATION THAT THE PROPOSED SWITCHBOARD COMPLIES WITH <br />ELECTRIC UTILITY COMPANY REGULATIONS. <br />LUGS SUITABLE FOR USE WITH COPPER OR ALUMINUM CONDUCTORS LISTED FOR USE WITH 75 DEGREE CELSIUS <br />AMPACITY CONDUCTORS. <br />TIN-PLATED ALUMINUM BUSSING WITH RECTANGULAR CROSS SECTION. HORIZONTAL AND VERTICAL BUSSING SHALL <br />BE FULL LENGTH AND SHALL HAVE PROVISIONS FOR FUTURE EXTENSIONS. ALL BUSSING SHALL HAVE MINIMUM <br />WITHSTAND RATING EQUAL TO THE AVAILABLE FAULT CURRENT INDICATED. ALL VERTICAL AND HORIZONTAL <br />BUSSING SHALL BE RATED AT FULL CAPACITY IN ALL SWITCHBOARD AND DISTRIBUTION BOARD SECTIONS. PROVIDE <br />100% NEUTRAL BUSSING MINIMUM UNLESS OTHERWISE NOTED. PROVIDE FULL LENGTH GROUND BUS AND, WHERE <br />INDICATED ON PLANS, ISOLATED GROUND BUSSING. PROVIDE REAR WIRE WAY IN ALL SWITCHBOARD SECTIONS. <br />ALL TERMINATIONS AND ENCLOSURES SHALL BE RATED FOR USE WITH 75 DEGREE CELSIUS CONDUCTORS. <br />SERIES RATED DEVICES SHALL HAVE BEEN INVESTIGATED BY U.L. IN COMBINATION WITH THE END USE EQUIPMENT AND <br />IN THE EQUIPMENT IN WHICH THESE DEVICES ARE USED AND SHALL BE MARKED WITH A SERIES RATING. ALL EQUIPMENT <br />SHALL BE MARKED IN ACCORDANCE WITH NEC (OR CEC-WHERE ADOPTED) REQUIREMENTS. SEE SPECIFICATIONS FOR <br />MORE INFORMATION. WHERE SERIES RATINGS ARE ALLOWED, THE EQUIPMENT SHALL BE LEGIBLY MARKED IN THE FIELD <br />TO INDICATE A SERIES COMBINATION RATING WHICH SHALL BE READILY VISIBLE. <br />ALL OVERCURRENT DEVICES IN AN INDIVIDUAL PIECE OF EQUIPMENT SHALL HAVE AN AIC RATING EQUAL TO THE <br />OVERALL RATING OF THE EQUIPMENT. SERIES-RATING OF DEVICES WITHIN A PIECE OF EQUIPMENT IS NOT ALLOWED. <br />SEE SPECIFICATIONS FOR MORE INFORMATION. <br />ALL ITEMS DEPICTED ON THE SINGLE LINE DRAWINGS SHALL BE ASSUMED AS NEW U.O.N. <br />ALL SWITCHGEAR SHALL BE SQUARE D OR EQUAL BY CUTLER-HAMMER, G.E., SIEMENS, IEM, OR Z-POWER AND <br />DISTRIBUTION. <br />PROVIDE GROUNDING PER NEC, OR CEC WHERE ADOPTED, 250.30. SEE TRANSFORMER SCHEDULE FOR GEC/BJ <br />SIZING INFORMATION. SEE SEPARATELY DERIVED SYSTEM GROUNDING DETAIL A, SHEET E2-2, FOR MORE <br />INFORMATION. <br />b. <br />ALL SWITCHBOARDS AND DISTRIBUTION BOARDS SHALL HAVE:9. <br />6. <br />1. <br />2. <br />3. <br />5. <br />7. <br />a. <br />GENERAL SINGLE LINE DIAGRAM NOTES: <br />10. <br />SPECIFIC SINGLE LINE NOTES: <br />ALLOWABLE DIMENSIONS IN MAIN ELECTRICAL ROOM ARE A CRITICAL COORDINATION ITEM. CONTRACTOR SHALL <br />PROVIDE 1/4"= 1'-0" SCALE DRAWINGS WITH SWITCHGEAR SUBMITTALS SHOWING THAT ALL PROPOSED EQUIPMENT WILL <br />FIT IN THE SPACE PROVIDED. SUBMITTALS WITHOUT THIS DRAWING SHALL BE REJECTED AS INCOMPLETE. <br />PROVIDE NEW OVERCURRENT PROTECTIVE DEVICE(S) COMPATIBLE WITH EXISTING ELECTRICAL DISTRIBUTION <br />EQUIPMENT. AIC AND WITHSTAND RATINGS MATCHING EXISTING OCPD RATINGS OR DISTRIBUTION EQUIPMENT <br />WITHSTAND RATINGS - WHICHEVER IS HIGHER. <br />UNLESS SPECIFICALLY SHOWN AS (E), (R), (ER), (D), EXISTING OR NON-BOLD, ALL ELECTRICAL DEVICES SHOWN ARE NEW. <br />WHERE REQUIRED BY THE LOCAL AUTHORITY HAVING JURISDICTION OR WHERE A NEW GROUND FAULT PROTECTIVE <br />DEVICE IS BEING INSTALLED, A GROUND FAULT SYSTEM TEST SHALL BE CONDUCTED BY AN INDEPENDENT TESTING <br />AGENCY PER NEC (OR CEC-WHERE ADOPTED) 230.95(C). THE GROUND FAULT SYSTEM TEST SHALL BE PERFORMED IN <br />THE PRESENCE OF THE LOCAL AUTHORITY HAVING JURISDICTION. VERIFICATION OF DEVICE SETTINGS PER THE POWER <br />SYSTEMS STUDY SPECIFICATION SHALL BE PERFORMED BY THE SAME INDEPENDENT TESTING AGENCY. THE GROUND <br />FAULT TEST RESULTS SHALL BE DELIVERED TO THE ENGINEER OF RECORD. DURING THE CONSTRUCTION PHASE OF THE <br />PROJECT, ALL NEW GROUND FAULT RELAYS SHALL BE SET AT THE LOWEST AVAILABLE TIME DELAY AND PICK-UP <br />SETTINGS. <br />1 <br />2 <br />c.PERMANENT PLACARD(S) MARKED PER THE SPECIFICATIONS AND PER NEC (OR CEC-WHERE ADOPTED) SECTIONS <br />225.37, 230.2(E), 690.56, 692.56, 700.7, 701.7, 702.7, AND 705.10 AND IFC (OR CFC - WHERE ADOPTED) SECTION 608.2.6.1. <br />DENOTING THE PRESENCE OF ADDITIONAL SERVICES, PHOTOVOLTAIC SYSTEMS, FUEL CELLS, EMERGENCY, <br />STATIONARY BATTERY STORAGE SYSTEMS, OR STAND-BY POWER SOURCES AS APPLICABLE. <br />ALL SERVICE ENTRANCE EQUIPMENT RATED AT 400A OR GREATER SHALL BE PROVIDED WITH A BACKFEED-RATED, SOLID <br />STATE MAIN OVERCURRENT DEVICE AND BUSSING RATED AT 100% OPERATION (1000A/sq.in. FOR CU, 750A/sq.in. FOR AL). <br />NO HEAT RISE RATED BUSSING ALLOWED. NON-SERVICE ENTRANCE SWITCHBOARDS AND DISTRIBUTION BOARDS <br />LARGER THAN 600A SHALL BE PROVIDED WITH BUSSING RATED FOR 100% OPERATION - SEE SPECIFICATION FOR CIRCUIT <br />BREAKER REQUIREMENTS. ALL NON-SERVICE ENTRANCE SWITCHBOARDS AND DISTRIBUTION BOARD MAIN <br />OVERCURRENT DEVICES SHALL BE BACKFEED-RATED. BACKFEED RATINGS SHALL COMPLY WITH NEC, OR CEC WHERE <br />ADOPTED, 710.15 (E) AND 705.12(B)(4). SEE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS REGARDING CIRCUIT <br />BREAKERS. <br />8.PROVIDE CIRCUIT BREAKER ARC ENERGY REDUCTION MAINTENANCE SWITCHING PER NEC, OR CEC WHERE ADPOPTED, <br />240.87(B)(3) FOR ANY CIRCUIT BREAKER, 1200A FRAME AND LARGER. SEE SPECIFICATIONS FOR ADDITIONAL <br />REQUIREMENTS. <br />4.ALL SWITCHBOARDS, SWITCHGEAR, AND PANELBOARDS SHALL HAVE A SHORT-CIRCUIT CURRENT RATING NOT LESS <br />THAN THE AVAILABLE FAULT CURRENT. THE AVAILABLE FAULT CURRENT AND THE DATE THE CALCULATION WAS <br />PERFORMED SHALL BE FIELD MARKED ON THE ENCLOSURE AT THE POINT OF SUPPLY. <br />11. <br />12. <br />13. <br />14. <br />15. <br />U.G.P.S. <br />3,000A <br />3P <br />EX <br />110A <br />3P <br />PARTIAL EXISTING SERVICE ENTRANCE EQUIPMENT "MSB3" <br />3,000A, (100% RATED) 277/480V- 3~ - 4W <br />AVAILABLE FAULT CURRENT PER SCE = 40,000A <br />CONNECTED LOAD = <br />GROUNDING <br />EXISTING <br />B <br />E-2.2 <br />1 <br />TD <br />1 <br />TD1 <br />2 <br />DP1 <br />DP <br />1 <br />NOTESV.D.LOADFEEDERCONDUIT AND CONDUCTORS (%) <br />AVAIL.FAULT <br />CURRENT (A)(A) <br />DISTANCE <br />(FT) <br />SCALE: NONE <br />CB <br />D <br />1 <br />---2"C., 3#1 + 1#6 GRD.CBD1 <br />W.P. <br />W.P. <br />ENCLOSED CIRCUIT BREAKER <br />"CBD1" <br />600V, 110A-3P <br />NEMA 3R <br />75KVA <br />---2"C., 3#1 + 1#6 GRD.TD1 <br />---3"C., 4#4/0 + 1#4 GRD.DP1 <br />AVAILABLE FAULT CURRENT VALUE AT THE END OF THE FEEDER INDICATED. CALCULATIONS ARE BASED UPON INITIAL <br />VALUES RECEIVED FROM THE SERVING UTILITY AND THE LENGTH AND IMPEDANCE OF THE FEEDER. THE SHORT <br />CIRCUIT CURRENT RATING, EQUIPMENT BUS BRACING, AND/OR AMP INTERRUPTING CURRENT OF EQUIPMENT <br />CONNECTED ON THE LOAD SIDE OF THE FEEDER SHALL BE GREATER THAN THE AVAILABLE FAULT CURRENT. <br />VOLTAGE DROP VALUE INDICATED IS AT THE END OF THE FEEDER. <br />DISTANCE SHOWN IS FOR DESIGN PURPOSES ONLY. IT IS NOT A MATERIAL TAKEOFF. <br />LOADS INDICATED WITH " ( ) " REPRESENT WORST CASE LOAD IN AMPS. <br />ALL FEEDERS SHOWN, UNLESS SPECIFICALLY NOTED OTHERWISE, ARE PRESUMED TO BE ROUTED IN METAL <br />RACEWAYS. IF P.V.C. CONDUITS ARE UTILIZED, THE CONTRACTOR SHALL PROVIDE AN EQUIPMENT GROUND PER NEC, <br />OR CEC WHERE ADOPTED, TABLE 250.122 OR, WHERE REQUIRED, PROVIDE A MAIN BONDING JUMPER PER TABLE <br />250.66 AND INCREASE THE CONDUIT SIZE ACCORDINGLY. <br />5. <br />4. <br />3. <br />2. <br />1. <br />GENERAL FEEDER SCHEDULE NOTES: <br />PANELS SHALL BE OF THE DEAD FRONT SAFETY TYPE. PANELS SHALL BE <br />MINIMUM 20" WIDE AND 5-3/4" DEEP UNLESS OTHERWISE NOTED ON PLAN. <br />COORDINATE WITH APPLICABLE TRADE TO INSURE RECESSED MOUNTED <br />PANELBOARDS WILL SEAT FLUSH IN THE WALLS PROVIDED. PANEL TRIMS <br />SHALL HAVE CONCEALED DOORS AND FASTENERS WITH FLUSH TYPE <br />COMBINATION LOCK AND CATCH, TWO MILLED TYPE KEYS SUPPLIED WITH <br />EACH PANEL. ALL LOCKS SHALL BE KEYED ALIKE AND EACH DOOR SHALL <br />HAVE A PLASTIC COVERED DIRECTORY FRAME WITH A TYPED IDENTIFICATION <br />CARD OF ALL CIRCUIT AND PANEL NUMBERS FOR BRANCH CIRCUIT <br />PANELBOARDS. <br />ALL CIRCUIT BREAKERS SHALL BE BOLT-ON TYPE AND SHALL BE SUITABLE <br />FOR 75 DEGREE AMPACITY CONDUCTORS. <br />PROVIDE BREAKER INTERLOCK WITH ADJACENT BREAKER(S) FOR ANY <br />MULTI-WIRE BRANCH CIRCUIT. BREAKER INTERLOCK GROUPING SHALL BE <br />BY BRANCH CIRCUIT GROUP (i.e. MULTIPLE CIRCUITS SHARING A COMMON <br />NEUTRAL (NEC, OR CEC WHERE ADOPTED, 210.4(B),) COMMON YOKE (NEC, <br />OR CEC WHERE ADOPTED, 210.7), OR FURNITURE SYSTEM NEC OR CEC <br />WHERE ADOPTED, 605.5 AND 605.7). WHERE AN EXISTING PANEL IS BEING <br />ALTERED OR MODIFIED IN ANY WAY, CONTRACTOR SHALL INCLUDE ALL <br />COSTS IN BASE BID TO ADD BREAKER INTERLOCKS TO EXISTING <br />MULTI-WIRE BRANCH CIRCUITS BASED ON CONTRACTOR'S INVESTIGATION <br />OF EXISTING CONDITIONS. <br />ALL CIRCUIT BREAKERS USED AS SWITCHES SHALL BE UL LISTED AND <br />LABELED "SWD" FOR SWITCHING DUTY. <br />ALL BUSSING SHALL BE TIN PLATED ALUMINUM. <br />WHERE PANEL IS INDICATED AS RECESSED OR FLUSH MOUNTED, PROVIDE <br />SPARE CONDUITS STUBBED UP INTO THE ACCESSIBLE CEILING SPACE. <br />PROVIDE ONE (1) 3/4" CONDUIT ONLY FOR EACH THREE (3) SPARES OR <br />SPACES, MINIMUM OF TWO (2). EACH CONDUIT SHALL BE TAGGED, CAPPED <br />AND MARKED FOR FUTURE USE. <br />WHERE PANEL CIRCUIT BREAKER RATING IS SHOWN AS SERIES RATED, <br />PROVIDE CIRCUIT BREAKERS IN PANELBOARD WHICH ARE SERIES RATED <br />WITH THE UPSTREAM SYSTEM FOR THE AVAILABLE FAULT CURRENT. THE <br />PANELBOARD SHALL BE MARKED WITH THE SERIES CONNECTED RATINGS, <br />AS WELL AS ALL MARKING AS REQUIRED BY THE NEC, OR CEC WHERE <br />ADOPTED, 240.86(B). <br />WHERE PANEL IS INDICATED TO INCLUDE AN I/G BUS, PROVIDE <br />PANELBOARDS WITH AN ISOLATED GROUND BUS, DRILLED AND TAPPED <br />FOR NUMBER OF ISOLATED GROUND CONDUCTORS SHOWN, AS WELL AS <br />FOR ALL SPARES AND SPACES SHOWN ON THE PANELBOARD. <br />WHERE PANEL IS INDICATED TO INCLUDE 200% NEUTRAL, PROVIDE <br />PANELBOARDS UL LISTED AS HAVING NEUTRAL BUSSES RATED TO CARRY <br />200 PERCENT OF THE CURRENT CARRYING CAPACITY OF THE PHASE <br />BUSSING. OTHERWISE, NEUTRAL BUSSING TO BE FULL SIZE AND <br />RECTANGULAR. <br />WHERE PANEL IS INDICATED TO INCLUDE DOUBLE LUGS, PROVIDE A <br />DOUBLE LUG KIT AT THE SAME END OF THE PANELBOARD AS THE <br />PANELBOARD MAIN LUGS. <br />WHERE PANEL IS INDICATED TO INCLUDE FEED THRU LUGS, PROVIDE FEED <br />THROUGH LUGS AT THE OPPOSITE END OF THE PANELBOARD FROM THE <br />PANELBOARD MAIN LUGS. <br />GENERAL PANEL SCHEDULE NOTES: <br />13. <br />12. <br />11. <br />9. <br />8. <br />6. <br />7. <br />5. <br />4. <br />3. <br />2. <br />1. <br />UPON PROJECT COMPLETION, CONTRACTOR SHALL INSTALL TYPED AS-BUILT <br />PANEL DIRECTORIES IN EACH PANEL WITHIN THE MFGR-PROVIDED DIRECTORY <br />HOLDER. THE DIRECTORY SHALL CLEARLY IDENTIFY EACH CIRCUIT TO ITS <br />CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. EACH CIRCUIT IDENTITY <br />SHALL INCLUDE SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE <br />DISTINGUISHED FROM ALL OTHERS PER NEC, OR CEC WHERE ADOPTED, ART <br />408.1 AND 408.4. HANDWRITTEN DIRECTORIES ARE UNACCEPTABLE. COPIES <br />OF AS-BUILT PANEL SCHEDULES SHALL BE PLACED IN PANEL DIRECTORIES. <br />E.C. TO INCLUDE ALL COSTS REQUIRED FOR LARGER-THAN-STANDARD <br />CUSTOM PANEL DIRECTORY HOLDERS TO ACCOMMODATE COPIES OF <br />AS-BUILT PANEL SCHEDULES. <br />PANELBOARDS SHALL BE MANUFACTURED BY G.E., CUTLER-HAMMER, <br />SIEMENS, OR SQUARE "D". FUSED PANEL BOARDS SHALL BE BY COOPER <br />BUSSMANN. <br />SPECIFIC PANEL SCHEDULE NOTES: <br />"E" <br />"D" <br />"C" <br />"B" <br />"A" <br />15. <br />14. <br />16.PROVIDE SHOP DRAWING SUBMITTAL PER THE ELECTRICAL SPECIFICATION <br />SUBMITTAL REQUIREMENTS FOR EACH PANEL DEPICTING CONFORMANCE <br />WITH THE ABOVE NOTES AND SCHEDULES. <br />PROVIDE LOCK-ON DEVICE. <br />PROVIDE PERMANENT LOCK-OFF DEVICE THAT SHALL REMAIN IN PLACE <br />WITH OR WITHOUT THE LOCK INSTALLED, PER NEC, OR CEC WHERE <br />ADOPTED, SECTION 110.25. <br />PROVIDE SHUNT TRIP DEVICE. <br />PROVIDE GFCI TYPE DEVICE. <br />PROVIDE A RED CIRCUIT BREAKER. <br />PROVIDE BREAKER LOCK OFF DEVICE ON ANY CIRCUIT BREAKER FEEDING <br />A TRANSFORMER AS REQUIRED, PER NEC, OR CEC WHERE ADOPTED, <br />450.14. WHERE AN EXISTING PANEL IS BEING ALTERED OR MODIFIED IN <br />ANY WAY, CONTRACTOR SHALL INCLUDE ALL COSTS IN BASE BID TO ADD <br />BREAKER LOCK-OFF DEVICES TO EXISTING TRANSFORMER CIRCUIT <br />BREAKERS BASED ON CONTRACTOR'S INVESTIGATION OF EXISTING <br />CONDITIONS. <br />10. <br />tk1sc project number: B2305501.000 <br />drawn by:checked by: <br />drawing no.: <br />ar <br />c <br />h <br />i <br />t <br />e <br />c <br />t <br />u <br />r <br />e <br />pl <br />a <br />n <br />n <br />i <br />n <br />g <br />in <br />t <br />e <br />r <br />i <br />o <br />r <br />s <br />tB <br />P <br />/ <br />A <br />r <br />c <br />h <br />i <br />t <br />e <br />c <br />t <br />u <br />r <br />e <br />46 <br />1 <br />1 <br /> <br />T <br />e <br />l <br />l <br />e <br />r <br /> <br />A <br />v <br />e <br />n <br />u <br />e <br />Ne <br />w <br />p <br />o <br />r <br />t <br /> <br />B <br />e <br />a <br />c <br />h <br />, <br /> <br />C <br />A <br /> <br />9 <br />2 <br />6 <br />6 <br />0 <br />ph <br />: <br /> <br />9 <br />4 <br />9 <br />. <br />6 <br />7 <br />3 <br />. <br />0 <br />3 <br />0 <br />0 <br />consultant <br />agency <br />owner <br />date: <br />drawing title: <br />description:date:Rev: <br />tBP project number : <br />architect <br />THIS DRAWING AND THE DESIGNS, DEPICTIONS, IDEAS AND OTHER INFORMATION <br />CONTAINED HEREIN CONSTITUTE UNPUBLISHED WORK OF tBP/ARCHITECTURE AND <br />SHALL REMAIN THE PROPERTY OF tBP/ARCHITECTURE IN PERPETUITY. NO PART <br />THEREOF SHALL BE REPRODUCED, DISCLOSED, DISTRIBUTED, SOLD, PUBLISHED OR <br />OTHERWISE USED IN ANY WAY WITHOUT THE ADVANCED EXPRESS WRITTEN CONSENT <br />OF tBP/ARCHITECTURE. <br />ph: 714.667.2700 <br />SANTA ANA, CA 92701 <br />20 CIVIC CENTER PLAZA <br />SANTA ANA PLANNING AND BUILDING AGENCY <br /># <br />DA <br />N <br />C <br />E <br /> <br />S <br />T <br />U <br />D <br />I <br />O <br />SA <br />N <br />T <br />A <br /> <br />A <br />N <br />A <br />, <br /> <br />C <br />A <br />L <br />I <br />F <br />O <br />R <br />N <br />I <br />A <br /> <br />9 <br />2 <br />7 <br />0 <br />7 <br />12 <br />0 <br />2 <br /> <br />W <br /> <br />E <br />D <br />I <br />N <br />G <br />E <br />R <br /> <br />A <br />V <br />E <br />MA <br />T <br />E <br />R <br /> <br />D <br />E <br />I <br /> <br />H <br />I <br />G <br />H <br /> <br />S <br />C <br />H <br />O <br />O <br />L <br />21125.00 <br />SA <br />N <br />T <br />A <br /> <br />A <br />N <br />A <br />, <br /> <br />C <br />A <br />L <br />I <br />F <br />O <br />R <br />N <br />I <br />A <br /> <br />9 <br />2 <br />7 <br />0 <br />7 <br />12 <br />0 <br />2 <br /> <br />W <br /> <br />E <br />D <br />I <br />N <br />G <br />E <br />R <br /> <br />A <br />V <br />E <br />MA <br />T <br />E <br />R <br /> <br />D <br />E <br />I <br /> <br />H <br />I <br />G <br />H <br /> <br />S <br />C <br />H <br />O <br />O <br />L <br />21125.00 <br />09/06/2023 <br />11870 Pierce Street, Suite 160 <br />Riverside, California 92505 <br />951.299.4160 www.tk1sc.com <br />Project Leader - Bill Voller <br />tk1sc Job #: B2305501.000 <br />Electrical Lead - Marie Rothenberger <br />City Submittal 09/06/23- <br />SINGLE LINE DIAGRAM <br />E2-1 <br />21159.00 <br />1202 W Edinger <br />Ave10/3/2024