PROJECT NAME
<br />SHEET TITLE
<br />SHEET NUMBER
<br />PROJECT TITLE
<br />JOBSITE ADDRESS
<br />SERRANO
<br />RESIDENCE
<br />1 0.800 DC kW
<br />9.930 KW CEC-AC RATING
<br />STRING INVERTER SYSTEM
<br />21 09
<br />WEST FLORA ST
<br />SANTA ANA, CA
<br />92704
<br />CONTRACTOR
<br />TITAN SOLAR POWER CA INC
<br />525 W BASELINE ROAD
<br />MESA, AZ 8521 0
<br />(855) 729-7652
<br />WWW.TITANSOLARPOWER.COM
<br />PROJECT ID# TSP1 47901
<br />DATE DESCRIPTION
<br />REVISION
<br />DATE
<br />DRAWN1 1 -30-22 REVISION
<br />DESIGN BY: RD
<br />CAD
<br />F O R C A L I I N C .
<br />SHELLEY V CALUAG
<br />caGIorcali@Jmail.com
<br />323-698-4207
<br />SP: Green Life Home
<br />Improvement
<br />A0
<br />PROJECT INFO
<br />VICINITY MAP
<br />PV NOTES
<br />VICINITY MAP
<br />PROJECT SITE
<br />OWNER:VELIA SERRANO
<br />ADDRESS:21 09 WEST FLORA ST
<br />SANTA ANA, CA 92704
<br />PHONE:(71 4) 643-0607
<br />EMAIL:velia.serrano@yahoo.com
<br />AHJ:SANTA ANA CITY
<br />APN:41 239705
<br />(ORANGE COUNTY)
<br />AERIAL VIEW
<br />1 0.800 DC kW SOLAR PV STRING INVERTER SYSTEM - ROOF MOUNT
<br />21 09 WEST FLORA ST SANTA ANA, CA 92704
<br />SERRANO RESIDENCE
<br />SHEET INDEX
<br />A0 PROJECT INFO, VICINITY MAP, PV NOTES
<br />A1 SITE PLAN
<br />A2 MOUNTING ROOF PLAN
<br />E1 SINGLE LINE DIAGRAM
<br />E2 ELECTRICAL CALCULATIONS
<br />E3 REQUIRED SIGNAGE
<br />E4 - E4.1 MODULE DATA SHEET & CERTIFICATION
<br />E5 - E5.1 INVERTER DATA SHEET & CERTIFICATION
<br />E6 OPTIMIZER DATA SHEET
<br />S1 STANCHION DATA SHEET
<br />S2 RACKING DATA SHEET
<br />S3 - S3.3 RACKING ENGINEERING
<br />S4 RACKING GROUNDING
<br />S5 RACKING CERTIFICATION
<br />SOLAR PHOTOVOLTAIC SYSTEM NOTES
<br />1 . ALL EQUIPMENT SHALL BE LISTED AND LABELED BY A RECOGNIZED TESTING LABORATORY AND INSTALLED PER THE
<br />LISTING REQUIREMENTS AND THE MANUFACTURER'S INSTRUCTIONS, CEC 1 1 0.2, 1 1 0.3, 690.4(B) AND 690.1 2(D).
<br />2. ALL OUTDOOR EQUIPMENT SHALL BE NEMA 3R RATED, INCLUDING ALL ROOF MOUNTED TRANSITION BOXES AND
<br />SWITCHES.
<br />3. ALL EQUIPMENT SHALL BE PROPERLY GROUNDED AND BONDED IN ACCORDANCE WITH CEC ARTICLE 250.
<br />4. ALL PV CIRCUITS CONNECTED TO MORE THAN ONE SOURCE SHALL HAVE PROTECTION AGAINST OVERCURRENT PER
<br />CEC 690.9.
<br />5. DISCONNECTING MEANS OF THE PV SYSTEM (INCLUDING RAPID SHUTDOWN INITIATION) SHALL BE LOCATED IN READILY
<br />ACCESSIBLE LOCATION NEAR THE EQUIPMENT, CEC 690.1 3, 690.1 5.
<br />6. ENERGY STORAGE SYSTEMS TERMINALS LOCATED MORE THAN 5 FEET AWAY OR ON OPPOSITE SIDE OF WALL FROM
<br />CONNECTED EQUIPMENT MUST HAVE DISCONNECTING MEANS IN ACCORDANCE WITH CEC 706.7(E) AND LABELED PER
<br />706.7(D). A SECOND DISCONNECTING MEANS LOCATED AT THE CONNECTED EQUIPMENT SHALL BE INSTALLED WHERE
<br />THE DISCONNECTING MEANS AT THE ESS END OF THE CIRCUIT IS NOT WITHIN SIGHT.
<br />7. RAPID SHUTDOWN EQUIPMENT TO COMPLY WITH CEC 690.1 2.
<br />8. THE UTILITY-INTERACTIVE INVERTERS SHALL AUTOMATICALLY DE-ENERGIZE ITS OUTPUT TO THE CONNECTED
<br />ELECTRICAL PRODUCTION AND DISTRIBUTION NETWORK UPON LOSS OF VOLTAGE IN THE SYSTEM AND SHALL REMAIN
<br />IN THAT STATE UNTIL THE ELECTRICAL PRODUCTION AND DISTRIBUTION NETWORK VOLTAGE HAS BEEN RESTORED,
<br />CEC 705.40.
<br />9. ALL CONDUCTORS IN EXPOSED OUTDOOR LOCATIONS SHALL BE LISTED AND IDENTIFIED FOR USE IN DIRECT SUNLIGHT
<br />AND FOR THE APPLICATION. CEC31 0.1 0(D) AND 690.31 (C) THROUGH (F).
<br />1 0. INSULATION OF EXPOSED CONDUCTORS UNDER THE MODULES SHALL BE USE-2 OR PV-WIRE TYPE FOR PV SYSTEMS,
<br />CEC 690.31 (C).
<br />1 1 . FINE-STRANDED CABLE CONNECTIONS MUST BE MADE IN LUGS AND TERMINALS LISTED AND MARKED FOR THE USE,
<br />CEC 1 1 0.1 4.
<br />1 2. ALL PV CIRCUIT CONDUCTORS SHALL BE MARKED ON EACH END AND GROUPED FOR UNIQUE IDENTIFICATION, CEC
<br />690.31 (B).
<br />1 3. ALL GROUNDED, (NEUTRAL), CONDUCTORS' INSULATION SHALL BE SOLID WHITE, GRAY, OR WITH 3-WHITE STRIPES, CEC
<br />200.6, 200.7, & 400.22; AND ALL GROUNDING CONDUCTORS SHALL BE OF BARE WIRE WITHOUT COVERING, OR WITH
<br />INSULATION OF GREEN OR GREEN WITH YELLOW STRIPES, CEC 250.1 1 9 & 400.23. THE COLOR OF UNGROUNDED
<br />CONDUCTORS SHALL BE OTHER THAN FOR GROUNDED, (NEUTRAL), AND GROUNDING CONDUCTORS, CEC 31 0.1 1 0(C).
<br />1 4. MAXIMUM CONDUCTOR LENGTH BETWEEN SUPPLY SIDE CONNECTION AND OVERCURRENT PROTECTION IS 1 0 FEET,
<br />CEC 705.31 .
<br />1 5. CONNECTIONS ON THE LOAD SIDE OF THE SERVICE DISCONNECTING MEANS OF THE OTHER SOURCE(S) AT ANY
<br />DISTRIBUTION EQUIPMENT ON THE PREMISES SHALL MEET THE FOLLOWING, CEC 705.1 2(B).
<br />1 6. DC WIRING INSIDE A BUILDING MUST BE IN METALLIC TYPE RACEWAYS, CONDUITS, ENCLOSURES, OR CABLE
<br />SHEATHINGS, CEC 690.31 (G).
<br />1 7. METALLIC TYPE RACEWAYS, CONDUITS, ENCLOSURES, AND CABLE SHEATHS CONTAINING CIRCUITS OVER 250-VOLTS
<br />TO GROUND MUST BE BONDED IN ACCORDANCE WITH CEC 250.97.
<br />1 8. ALL EXTERIOR CONDUIT, FITTINGS AND BOXES SHALL BE RAIN TIGHT AND APPROVED FOR USE IN WET LOCATIONS, CEC
<br />31 4.1 5
<br />1 9. FLEXIBLE, FINE-STRANDED CABLES SHALL BE TERMINATED ONLY WITH TERMINALS, LUGS, DEVICES OR CONNECTOR
<br />THAT ARE IDENTIFIED AND LISTED FOR SUCH USE, CEC 690.31 (H) & 1 1 0.1 4.
<br />20. CONNECTORS SHALL BE OF LATCHING OR LOCKING TYPE. CONNECTORS THAT ARE READILY ACCESSIBLE AND
<br />OPERATING AT OVER 30 VOLTS SHALL REQUIRE TOOL TO OPEN AND MARKED “DO NOT DISCONNECT UNDER LOAD” OR
<br />“NOT FOR CURRENT INTERRUPTING”, CEC 690.33(C) & (E)(2).
<br />21 . EQUIPMENT GROUNDING CONDUCTOR FOR PV MODULES SMALLER THAN 6 AWG SHALL BE PROTECTED FROM
<br />PHYSICAL DAMAGE BY A RACEWAY OR CABLE ARMOR, CEC 690.46 & 250.1 20(C).
<br />22. THE INTERCONNECTION POINT SHALL BE ON THE SUPPLY SIDE OF ALL GROUND-FAULT PROTECTION EQUIPMENT, CEC
<br />705.32.
<br />23. CABLES/WIRES THAT ARE SUBJECT TO PHYSICAL DAMAGE, SUCH AS THOSE NOT LOCATED UNDER THE MODULES,
<br />MUST BE PROTECTED, CEC 300.4.
<br />24. PROPOSED LOCATIONS OF ELECTRICAL SERVICE REPLACEMENTS MUST ALSO BE APPROVED BY THE ELECTRICAL
<br />UTILITY COMPANY.
<br />25. FOR ELECTRICAL SERVICE REPLACEMENTS, BONDING TO THE METAL PIPES OF NATURAL GAS, HOT WATER, AND COLD
<br />WATER MUST BE PROVIDE, CEC 250.1 04.
<br />26. GROUNDING ROD ELECTRODES SHALL BE MINIMUM 5/8’’ IN DIAMETER AND INSTALLED 8’ MINIMUM IN CONTACT WITH
<br />SOIL, CEC 250.52(A)(5), 250.53(G).
<br />27. MINIMUM 7/8’’ CLEARANCE FROM ROOF TO BOTTOM OF CONDUIT OR USE A TEMPERATURE ADDER OF 33 DEGREES C.
<br />CEC 31 0.1 5(B)(3)(C)
<br />28. EXISTING PLUMBING VENTS, SKYLIGHTS, EXHAUST OUTLETS, & VENTILATIONS INTAKE AIR OPENINGS SHALL NOT BE
<br />COVERED OR BLOCKED BY THE SOLAR PHOTOVOLTAIC SYSTEM.
<br />29. EXISTING DWV PLUMBING VENT TERMINATIONS THAT ARE HORIZONTALLY LOCATED CLOSER THAN 1 2" FROM THE
<br />PROPOSED MODULES, MUST BE REROUTED, OR MUST BE EXTENDED A MINIMUM OF 6" ABOVE THE SURFACE OF THE
<br />MODULES, CPC 906.1 .
<br />30. EXISTING B-VENT TERMINATIONS, FOR FUEL BURNING APPLIANCES, WHERE ADJACENT TO THE PROPOSED MODULES,
<br />MUST BE EXTENDED 1 2" ABOVE THE MODULES' TOP SURFACE, CMC 802.6.1 (1 ) & CPC 509.6.1 (1 ).
<br />31 . THE MARKINGS, "WARNING: PHOTOVOLTAIC POWER SOURCE", FOR DC RACEWAYS AND CABLE ASSEMBLIES MUST BE
<br />AT 1 0' O.C.; AND BENDS, ABOVE OR BELOW PENETRATIONS OF ROOFS, CEILINGS, WALLS, OR BARRIERS, CEC
<br />690.31 (G)(4).
<br />32. PV COMBINER PANELBOARDS MUST HAVE PERMANENT MARKINGS INDICATING THAT THEY ARE DEDICATED FOR PV
<br />CIRCUITS ONLY NO LOADS ARE TO BE CONNECTED.
<br />33. WORKING CLEARANCES TO BE PROVIDED AT NEW AND EXISTING ELECTRICAL EQUIPMENT, CEC 1 1 0.26.
<br />34. A LADDER MUST BE PROVIDED FOR INSPECTIONS IN ACCORDANCE WITH CAL-OSHA REGULATIONS, SECURED AND
<br />EXTENDING 3' ABOVE THE ROOF.
<br />35. ALL OF THE REQUIRED MARKINGS, SIGNS, AND LABELS MUST BE INSTALLED ON ALL EQUIPMENT PRIOR TO ANY
<br />INSPECTIONS.
<br />36. LABELS SHALL BE REFLECTIVE, AND ALL LETTERS SHALL BE CAPITALIZED AND SHALL BE A MINIMUM HEIGHT OF 3/8'' IN
<br />WHITE ON A RED BACKGROUND. CEC 690.31 (G)(4)
<br />37. IDENTIFICATION OF POWER SOURCE RAPID SHUTDOWN AND LABELING SHALL BE IN ACCORDANCE WITH CEC 690.56(C).
<br />38. WHEN THE MAIN CIRCUIT BREAKER IS DERATED, A PERMANENT MARKING MUST BE PROVIDED ON THE PANELBOARD TO
<br />INDICATE THAT THE MAIN CIRCUIT BREAKER HAS BEEN DOWNSIZED TO _______ AMPS, DO NOT UPSIZE IT.
<br />39. PANELS AND MODULES NOT TO BE INSTALLED ON ROOF BELOW AN EMERGENCY ESCAPE AND RESCUE OPENING. CRC
<br />R324.6.2.2
<br />40. GROUND-MOUNTED PV SYSTEMS MUST HAVE A CLEAR, BRUSH-FREE AREA OF 1 0-FEET AND A FIRE SEPARATION
<br />DISTANCE OF 5-FEET MINIMUM TO OTHER STRUCTURES AND PROPERTY LINES, CRC R324.7 & R302.1 .
<br />41 . PLAN CHECK AND PERMIT FOR PV SYSTEM AND ASSOCIATED EQUIPMENT ONLY.
<br />42. ALL PROJECTS SUBJECT TO FIELD VERIFICATION FOR CODE COMPLIANCE.
<br />43. APPROVED SMOKE AND CARBON MONOXIDE ALARMS ARE REQUIRED WITHIN THE DWELLING UNIT AND SHALL BE
<br />FIELD VERIFIED EITHER THROUGH FINAL BUILDING INSPECTION. SMOKE ALARMS ARE REQUIRED TO BE
<br />INSTALLED IN ALL BEDROOMS, OUTSIDE EACH BEDROOM, AND AT LEAST ONE ON EACH FLOOR OF THE HOUSE.
<br />CARBON MONOXIDE ALARMS ARE REQUIRED OUTSIDE EACH BEDROOM AND AT LEAST ONE ON EACH FLOOR OF
<br />THE HOUSE. R31 4.1 , R31 5.1
<br />44. NOTIFY SERVING UTILITY BEFORE ACTIVATION OF PV SYSTEM.
<br />APPLICABLE CODES
<br />ALL MATERIALS, EQUIPMENT, INSTALLATION AND WORK SHALL
<br />COMPLY WITH THE FOLLOWING APPLICABLE CODES
<br />201 9 CA BUILDING CODES (CBC)
<br />201 9 CA RESIDENTIAL CODES (CRC)
<br />201 9 CA MECHANICAL CODES (CMC)
<br />201 9 CA PLUMBING CODES (CPC)
<br />201 9 CA FIRE CODES (CFC)
<br />201 9 CA ELECTRICAL CODES (CEC)
<br />201 9 CA ENERGY CODES (CEnC)
<br />201 9 CALIFORNIA GREEN BUILDING STANDARDS CODE (CALGreen)
<br />PROJECT SCOPE
<br />INSTALLATION OF ROOF MOUNT SOLAR PV SYSTEM
<br />PV EQUIPMENT QTY MODEL NO AND MANUFACTURER
<br />MODULES:27 Q.PEAK DUO BLK ML-G1 0 400
<br />HANWHA Q CELL MODULES
<br />OPTIMIZERS:27 P401 SOLAREDGE OPTIMIZERS
<br />INVERTER:1 SE10000H-US (240V) >SI1@
<br />SOLAREDGE HD INVERTER
<br />SYSTEM SIZE:10.800 DC kW RATING
<br />9.930 CEC AC RATING
<br />ARRAY AREA:21.14 SQFT x 27 =570.66 SQFT
<br />BUILDING INFO
<br />OCCUPANCY:R3-SFD CONSTRUCTION TYPE:VB
<br /># OF STORIES:1 BLDG AREA (SQFT):1584
<br />SPRINKLERS:NONE ROOF AREA (SQFT):3841
<br />ENGINEERING CRITERIA FOR RACKING
<br />DESIGN WIND SPEED:110 MPH
<br />WIND EXPOSURE CATEGORY:B
<br />GROUND SNOW LOAD:O PSF
<br />PROJECT SITE
<br />MAIN SERVICE PANEL INFORMATION
<br />EXISTING:YES UPGRADE:NO
<br />BUS RATING:(E)100A MAIN BREAKER SIZE:(E)100A
<br />PHASE:1PH MB POSITION:TOP
<br /># OF WIRES:3 DERATE?:NO
<br />VOLTAGE:240V DERATE SIZE:N/A
<br />UTILITY FED:OH
<br />METER#:222013-506053
<br />INTERCONNECTION THRU 200A SUBPANEL
<br />STRUCTURAL ONLY
<br />www.vincise.com
<br />S T R U C T U R A L E N G I N E E R S
<br />12.12.2022
<br />The scope of the plans is for the
<br />installation of the solar photovoltaic
<br />system only and the approval is subject to
<br />compliance with all applicable city and
<br />state codes and regulations regarding
<br />construction. The approval of the plans
<br />does not constitute any certification of the
<br />accuracy, completeness, or building
<br />permit status of the existing buildings and
<br />structures as shown.
<br />Bldg# 101113462
<br />Elec# 20178424
<br />Issued 01/25/23
<br />2109 W Flora St
<br />01/27/23
|