1. ENTIRE INSTALLATION SHALL COMPLY WITH ALL LOCAL AND STATE CODES, <br />INCLUDING ENERGY CODES, AND ALL OTHER AUTHORITIES HAVING JURISDICTION. <br />2. PROPER FIRE PROTECTION MEASURES, SATISFACTORY TO THE LOCAL FIRE <br />DEPARTMENT, SHALL BE TAKEN WHEN WELDING OR CUTTING WITH TORCHES OR <br />ELECTRIC ARC. <br />3. CONTRACTOR SHALL SECURE AND PAY FOR ALL REQUIRED PERMITS AND <br />APPROVALS. ALL REQUIRED SPECIAL AND CONTROLLED INSPECTIONS SHALL BE BY <br />THIS CONTRACTOR. <br />4. IT SHALL BE THE CONTRACTORS SOLE RESPONSIBILITY TO PROVIDE ALL REQUIRED <br />DOCUMENTS, PAY ALL FEES AND TO SEPARATELY FILE AND OBTAIN ALL APPROVALS <br />AND PERMITS REQUIRED FOR ALL WORK INVOLVED IN TEMPORARY HEATING <br />SYSTEM(S) TO BE USED AT THE SITE. ALL WORK SHALL BE PROVIDED AND INSTALLED <br />PER THE REQUIREMENTS OF THE NYC BUILDING CODE. <br />5. PROVIDE SEISMIC BRACING AND ANCHORING OF MECHANICAL EQUIPMENT, PIPING, <br />AND DUCTWORK IN ACCORDANCE WITH THE GOVERNING CODES. THE STRUCTURAL <br />DESIGN AND APPLICATION OF SEISMIC RESTRAINTS SHALL MEET THE CODE CRITERIA <br />LISTED "DESIGN CRITERIA". THE CONTRACTORS SHALL RETAIN AN INDEPENDENT <br />PROFESSIONAL ENGINEER TO DESIGN SEISMIC RESTRAINTS, PREPARE INSTALLATION <br />DETAILS, SUPERVISE INSTALLATION, AND CERTIFY THAT THE INSTALLATION MEETS <br />THE CODE CRITERIA LISTED HEREIN. SIGNED AND SEALED INSTALLATION DETAILS <br />AND CALCULATIONS SHALL BE SUBMITTED AS SHOP DRAWINGS. <br />6. ALL SUPPORT SYSTEMS (SUPPORTS, HANGERS, ANCHORS, GUIDES, BRACING, <br />FASTENERS, WELDS, ETC.) FOR EQUIPMENT AND SYSTEMS INSTALLED OR REVISED <br />AS PART OF THIS CONTRACT SHALL BE DESIGNED, SELECTED AND INSTALLED BY THE <br />CONTRACTOR TO RESIST ALL SEISMIC, WIND AND GRAVITY LOADS. UNDER CERTAIN <br />CONDITIONS, THE APPLICABLE CODES REQUIRE THESE LOADS, OR A COMBINATION <br />OF THESE LOADS, BE CONSIDERED AS "COINCIDENTAL". THE CONTRACTOR SHALL <br />ALSO BE RESPONSIBLE FOR CONFIRMING THAT THE COMPONENT OF THE BUILDING <br />STRUCTURE WHERE THESE SUPPORT SYSTEMS ARE ATTACHED IS ABLE TO RESIST <br />THE DESIGN LOADS TRANSFERRED TO THIS BUILDING COMPONENT. <br />7. ALL PENETRATIONS OF FLOORS (WHETHER OR NOT FIRE RESISTANCE RATED) AND <br />ALL PENETRATIONS OF FIRE RATED WALLS AND FLOORS SHALL BE PROVIDED WITH A <br />THROUGH-PENETRATION PROTECTION SYSTEM (FIRESTOPPING). EACH THROUGH- <br />PENETRATION PROTECTION SYSTEM SHALL BE TESTED IN ACCORDANCE WITH ASTM <br />E814 AND BE LISTED FOR THE TYPE OF FLOOR OR WALL ASSEMBLY PENETRATED AND <br />THE TYPE OF PROTECTION SYSTEM. <br />8. ALL AIR MOVING DEVICES, INCLUDING BUT NOT LIMITED TO AIR HANDLING UNITS, AIR <br />CONDITIONING UNITS, AND UNIT VENTILATORS, MUST COMPLY WITH AMCA STANDARD <br />210 AND ASHRAE STANDARD 62.1-2007. <br />9. DRAWINGS ARE INTENDED TO SHOW THE PROPER SIZE AND GENERAL LOCATIONS OF <br />THE EQUIPMENT, PIPING, DUCTWORK, ETC. DRAWINGS ARE DIAGRAMMATIC AND <br />INDICATE GENERAL ARRANGEMENT OF SYSTEMS AND WORK INCLUDED IN CONTRACT. <br />DEVIATIONS FROM LAYOUT SHOWN MUST BE APPROVED BY THE ARCHITECT. <br />10. SHOP DRAWINGS SHALL BE PREPARED WITH COMPLETE DIMENSIONAL INFORMATION, <br />INCLUDING COORDINATES TO BRANCH DUCT AND DIFFUSERS STUBS. ELEVATIONS TO <br />THE UNDERSIDE OF DUCTS, SHALL BE CLEARLY INDICATED ON THE DRAWING <br />SUBMITTED AND SHALL BE CAREFULLY CHECKED FOR CONFORMANCE WITH CEILING <br />HEIGHT REQUIREMENTS. ALL CONFLICTS MUST BE FLAGGED ON THE SHOP <br />DRAWINGS. <br />11. THE SHEET METAL SHOP DRAWINGS SHALL INDICATE ALL HUNG CEILING STARTING <br />POINTS, ELEVATIONS AND BREAK LINES. WHERE PIPING, LIGHTS AND DUCTWORK <br />CONFLICTS; DUCTWORK SHALL BE SET UP OR DOWN. <br />12. SEE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR CONSTRUCTION PHASING <br />REQUIREMENTS. <br />13. CONTRACTOR SHALL COORDINATE HIS WORK WITH THE WORK OF ALL OTHER <br />TRADES. <br />14. CONTRACTOR SHALL COORDINATE WITH ALL ARCHITECTURAL DRAWINGS. <br />15. CONTRACTOR IS RESPONSIBLE TO COORDINATE AND INCLUDE IN HIS BID THE <br />RELOCATION OF ALL PIPING, DUCTWORK, HANGERS, CONDUITS, ETC. REQUIRED TO <br />INSTALL NEW EQUIPMENT, PIPING, DUCTWORK, ETC. <br />16. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING OF WALLS, <br />CEILINGS, ROOFS AND FLOORS REQUIRED AS A RESULT OF HIS WORK. <br />17. DUCTWORK AND PIPING LAYOUTS ARE SCHEMATIC DIAGRAMS AND ARE INTENDED TO <br />SHOW GENERAL ARRANGEMENT, SIZE AND CAPACITY AND DO NOT NECESSARILY <br />INDICATE WHICH PIPE OR DUCT IS ABOVE OR BELOW THE OTHER. ALL OFFSETS ARE <br />NOT NECESSARILY SHOWN. CONTRACTOR SHALL ARRANGE AND COORDINATE THE <br />WORK, FURNISH NECESSARY OFFSETS, VALVES, VENTS AND FITTINGS TO AVOID <br />CONFLICT WITH OTHER MECHANICAL AND ELECTRICAL SERVICES AND STRUCTURAL <br />AND ARCHITECTURAL ELEMENTS WITHOUT ADDITIONAL COST TO THE OWNER. IF <br />AREAS OF CONFLICT ARE ENCOUNTERED, THE ARCHITECT SHALL BE NOTIFIED AND <br />CONTRACTOR'S RECOMMENDATIONS SHALL BE SUBMITTED TO THE ARCHITECT FOR <br />APPROVAL BEFORE WORK HAS BEGUN. <br />18. CONTRACTOR SHALL PROVIDE ALL NECESSARY MISCELLANEOUS STEEL FOR THE <br />SUPPORT OF ALL EQUIPMENT, PIPING, CONDUIT AND DUCTWORK. SUSPENDED <br />FROM SLAB, STEEL, WALL, OR TRUSSWORK. <br />19. UNLESS OTHERWISE NOTED ON THE DRAWINGS, ALL MECHANICAL EQUIPMENT <br />SHALL BE MOUNTED ON VIBRATION ISOLATORS TO PREVENT THE TRANSMISSION <br />OF SOUND TO THE BUILDING STRUCTURE. VIBRATION ISOLATORS SHALL BE IN <br />ACCORDANCE WITH THE SPECIFICATIONS AND SHALL BE BASED ON ACTUAL <br />WEIGHT DISTRIBUTION OF THE EQUIPMENT FURNISHED. DEFLECTIONS SHALL BE <br />AS NOTED ON THE EQUIPMENT SHOP DRAWING SUBMITTALS. <br />20. CONTRACTOR SHALL ENSURE THAT ALL MECHANICAL DEVICES ARE INSTALLED IN <br />A LOCATION WHICH AFFORDS ACCESSIBILITY FOR MAINTENANCE AND REPAIR. <br />COORDINATE INSTALLATION AMONG ALL TRADES TO AVOID INTERFERENCES, AND <br />LOCATE EQUIPMENT TO PROVIDE CLEARANCES WHICH EXCEED THOSE <br />RECOMMENDED BY THE EQUIPMENT MANUFACTURER. PRIOR TO PROJECT <br />COMPLETION, REPRESENTATIVES OF THE OWNER WILL REVIEW EACH <br />INSTALLATION AND WILL DIRECT CHANGES WHENEVER ACCESS OR <br />SERVICEABILITY IS, IN THEIR OPINION, UNACCEPTABLE. <br />21. ALL MECHANICAL CONTROLS (THERMOSTATS, SENSORS, ETC.) SHALL BE <br />INSTALLED AT A HEIGHT OF 5'-0" ABOVE FLOOR. COORDINATE EXACT LOCATION <br />AND MOUNTING HEIGHT WITH ARCHITECT PRIOR TO INSTALLATION. <br />22. OWNER PROVIDED EQUIPMENT SHALL BE RECEIVED AND INSTALLED BY THE <br />MECHANICAL CONTRACTOR. ALL COST ASSOCIATED WITH RIGGING, RECEIVING <br />AND STORAGE SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. <br />23. ALL ACCESS DOORS IN FINISHED WALLS AND CEILINGS SHALL BE SUPPLIED BY <br />THIS CONTRACTOR AND SHALL BE FRAMELESS TYPE SUITABLE FOR THE <br />CONSTRUCTION TYPE INDICATED ON THE ARCHITECTURAL DRAWINGS. <br />COORDINATE ALL LOCATIONS OF ACCESS DOORS WITH ARCHITECTURAL <br />DRAWINGS. LOCATE VALVES SO AS TO BE WITHIN ONE (1) FOOT OF AN ACCESS <br />DOOR. <br />24. EXACT LOCATION OF DIFFUSERS, GRILLES AND REGISTERS TO BE COORDINATED <br />WITH ARCHITECTURAL PLANS. <br />25. CONTRACTOR SHALL BE RESPONSIBLE FOR BALANCING OF AIR QUANTITIES AT <br />ALL AIR CONDITIONING OUTLETS AND INLETS. <br />26. HVAC CONTRACTOR SHALL CHANGE FILTERS IN ALL AIR HANDLING UNITS PRIOR <br />TO DELIVERY OF SYSTEM TO OWNER. <br />27. DUCT-MOUNTED SMOKE DETECTORS SHALL BE PROVIDED IN THE SUPPLY AND <br />RETURN DUCTS OF ALL AIR HANDLING UNITS WITH A CAPACITY GREATER THAN <br />2,000 CFM. WHERE A RETURN AIR PLENUM IS SHARED BETWEEN MULTIPLE AIR <br />HANDLING UNITS TOTALING GREATER THAN 2,000 CFM, A DUCT SMOKE DETECTOR <br />SHALL BE PROVIDED IN THE RETURN DUCT OF EACH AIR HANDLING UNIT. <br />28. ALL ROTATING HVAC EQUIPMENT SHALL BE SUPPORTED OR SUSPENDED ON <br />VIBRATION ISOLATORS. PROVIDE FLEXIBLE CONNECTORS AT ALL DUCT AND PIPE <br />CONNECTIONS TO ROTATING EQUIPMENT. <br />29. DUCT SIZES SHOWN ARE CLEAR INSIDE DIMENSIONS. <br />30. PROVIDE DOUBLE THICKNESS TURNING VANES IN ALL SQUARE ELBOWS. <br />31. PROVIDE VOLUME DAMPER ON EACH BRANCH TAKE OFF FROM DUCT MAIN, AND <br />ON EACH DIFFUSER TAKE OFF FROM BRANCH DUCT OR MAIN. <br />32. PROVIDE AND INSTALL COMBINATION FIRE AND SMOKE DAMPERS AND ACCESS <br />DOORS IN ALL DUCTWORK PENETRATING FIRE RATED WALLS (2 HOURS OR MORE). <br />FIRE DAMPERS AND ACCESS DOORS SHALL BE PROVIDED AND INSTALLED IN ALL <br />DUCTWORK PENETRATING FIRE RATED WALLS 1-1/2 HOUR OR LESS. ALL ACCESS <br />DOORS SHALL BE A MINIMUM OF 12"X 12" UNLESS OTHERWISE NOTED. <br />33. WHERE PIPING CONNECTIONS FOR THE EQUIPMENT SUCH AS PUMPS, AC UNITS, <br />COILS ETC. DIFFER FROM THE LINE SIZE, IT SHALL BE THE RESPONSIBILITY OF <br />THE MECHANICAL CONTRACTOR TO FURNISH AND INSTALL THE NECESSARY <br />REDUCERS OR EXPANDER FITTING TO ENABLE CONNECTION BETWEEN THE <br />PIPING SYSTEM AND THE EQUIPMENT. <br />34. PROVIDE CAPPED MANUAL AIR VENTS AT ALL HYDRONIC SYSTEM HIGH POINTS, <br />AND BEFORE ALL VERTICAL DROPS IN DIRECTION OF FLOW, PROVIDE CAPPED <br />HOSE DRAINS AT ALL SYSTEM LOW POINTS, SO AS TO ENABLE THE COMPLETE <br />DOWN-DRAIN OF THE SYSTEM. <br />35. ALL CONDENSATE DRAIN LINES SHALL COMPLY WITH N.S.P.C. 9.9.2 (AIR <br />CONDITIONING CONDENSATE POINT OF DISCHARGE). NO PLASTIC PIPING SHALL <br />BE INSTALLED IN PLENUM CEILING. <br />36. MINIMUM SIZE OF ALL CONDENSATE DRAIN PIPING SHALL BE 3/4" UNLESS <br />OTHERWISE NOTED. ALL DRAIN PIPING SHALL BE PITCHED IN THE DIRECTION OF <br />FLOW, MIN. 1" IN 40 FT. <br />37. PROVIDE SHUT-OFF VALVES AT ALL BRANCH PIPING CONNECTIONS TO MAINS. <br />38. INSTALL ALL DIELECTRIC UNIONS IN A MANNER WHICH MAKES THEM READILY <br />ACCESSIBLE FOR FUTURE REPAIR OR REPLACEMENT. BRASS VALVES, FITTINGS, <br />ETC. ARE NOT ACCEPTABLE IN LIEU OF DIELECTRIC UNIONS. <br />GENERAL MECHANICAL NOTES <br />AD <br />POSITIVE PRESSURE DUCT (SUPPLY) UP <br />POSITIVE PRESSURE DUCT (SUPPLY) DOWN <br />SLOPING RISE IN DUCTWORK <br />SLOPING DROP IN DUCTWORK <br />ACCESS DOOR IN DUCT <br />18x12 <br />18x12 <br />18"ø <br />18"ø <br />FC <br />FC <br />DUCT SIZE (CLEAR INSIDE DIMENSION) <br />FIRST FIGURE INDICATES PLAN DIMENSION <br />ROUND DUCT DIAMETER SIZE <br />ACOUSTIC LINING IN DUCT <br />(SIZE NOTED INDICATES INSIDE DIMENSION) <br />FLEXIBLE CONNECTION <br />VOLUME DAMPER <br />DUCTWORK SYMBOLS <br />R <br />D <br />D <br />SQUARE DUCT ELBOW WITH TURNING VANE <br />RADIUS ELBOW <br />DUCT SPLIT <br />BRANCH TAKE-OFF WITH VOLUME DAMPER <br />DUCT SMOKE DETECTOR <br />SUPPLY AIR CEILING DIFFUSER <br />4 WAY, 3 WAY, 2 WAY, 1 WAY <br />NEGATIVE PRESSURE DUCT (RETURN OR EXHAUST) <br />UP <br />NEGATIVE PRESSURE DUCT (RETURN OR EXHAUST) <br />DOWN <br />ADJUSTABLE SETPOINT CONTROLLER <br />'BUTTON SENSOR' TEMPERATURE SENSORS <br />T <br />MISCELLANEOUS SYMBOLS <br />X X X X <br />EXISTING WORK TO BE REMOVED <br />EXISTING WORK TO REMAIN <br />NEW WORK <br />CONNECT NEW WORK TO EXISTING <br />DISCONNECT EXISTING WORK <br />REVISION NUMBER? <br />MECHANICAL ABBREVIATIONS <br />°C DEGREES CELSIUS <br />°F DEGREES FAHRENHEIT <br />A AMPERES <br />AC AIR CONDITIONING <br />ACCU AIR CONDITIONING CONDENSING UNIT <br />AD ACCESS DOOR <br />AFF ABOVE FINISED FLOOR <br />AHU AIR HANDLING UNIT <br />AL ACOUSTIC LINING <br />AP ACCESS PANEL <br />ATC AUTOMATIC TEMPERATURE CONTROL <br />B BOILER <br />BG BOTTOM GRILLE <br />BHP BRAKE HORSEPOWER <br />BMS BUILDING MONITORING SYSTEM <br />BR BOTTOM REGISTER <br />BTU BRITISH THERMAL UNIT <br />BTUH BTU PER HOUR <br />CD CEILING DIFFUSER <br />CFM CUBIC FEET PER MINUTE <br />CG CEILING GRILLE <br />CLG CEILING <br />CO CLEAN OUT OR CARBON MONOXIDE <br />COD CABLE OPERATED DAMPER <br />COMPR COMPRESSOR <br />COND CONDENSATE <br />CR CEILING REGISTER <br />CU IN CUBIC INCHES <br />CU FT CUBIC FEET <br />CV CONSTANT VOLUME <br />D DROP <br />DB DRY BULB <br />DDC DIRECT DIGITAL CONTROL <br />DN DOWN <br />DWG DRAWING <br />DX DIRECT EXPANSION <br />EA EXHAUST AIR <br />EAT ENTERING AIR TEMPERATURE <br />EDB ENTERING DRY BULB <br />EF EXHAUST FAN <br />EL ELEVATION <br />ELEC ELECTRIC <br />EQ EQUAL <br />ER EXISTING TO BE RELOCATED <br />EWB ENTERING WET BULB <br />EWT ENTERING WATER TEMPERATURE <br />EXH EXHAUST <br />EXP EXPANSION <br />F FILTER <br />FA FREE AREA (SQ.FT.) <br />FC FLEXIBLE CONNECTION <br />FD FIRE DAMPER <br />FF FINAL FILTER <br />FLA FULL LOAD AMPERES <br />FPM FEET PER MINUTE <br />FPS FEET PER SECOND <br />FT FEET <br />FV FACE VELOCITY <br />ABBREVIATION DESCRIPTION <br />VFD VARIABLE FREQUENCY DRIVE <br />VENT VENTILATION AIR <br />W/WITH <br />W/O WITHOUT <br />W WIDTH <br />WB WET BULB <br />WMS WIRE MESH SCREEN <br />ABBREVIATION DESCRIPTION <br />HP HORSEPOWER <br />HR HOUR <br />HZ FREQUENCY IN HERTZ <br />IN INCH OR INCHES <br />KW KILOWATT <br />L LENGTH <br />LAT LEAVING AIR TEMPERATURE <br />LBS POUNDS <br />LDB LEAVING DRY BULB TEMPERATURE <br />L. FT. LINEAR FOOT <br />LWB LEAVING WET BULB TEMPERTAURE <br />MAX MAXIMUM <br />MBH THOUSAND BTU PER HOUR <br />MHP MOTOR HORSEPOWER <br />MIN MINIMUM <br />N NECK <br />N.C. NORMALLY CLOSED <br />NIC NOT IN CONTRACT <br />N.O. NORMALLY OPEN <br />NO. NUMBERS <br />NTS NOT TO SCALE <br />OA OUTSIDE AIR <br />OAI OUTSIDE AIR INTAKE <br />OBD OPPOSED BLADE DAMPER <br />OD OUTSIDE DIAMETER <br />OV OUTLET VELOCITY <br />PD PRESSUDE DROP <br />PHC PREHEAT COIL <br />PSI POUNDS PER SQUARE INCH <br />PSIA PSI ABSOLUTE <br />PSIG PSI GAUGE <br />R RISE <br />RA RETURN AIR <br />RAD RADIATION <br />RE RELOCATE EXISTING <br />REFR REFRIGERANT <br />RM ROOM <br />RPM REVOLUTIONS PER MINUTE <br />RR RETURN REGISTER <br />SA SUPPLY AIR <br />SF SUPPLY FAN <br />SG SUPPLY GRILLE <br />SP STATIC PRESSURE <br />SPEC SPECIFICATION <br />SS STAINLESS STEEL <br />TD TRANSFER DUCT <br />TEMP TEMPERATURE <br />TF TRANSFER FAN <br />TG TOP GRILLE <br />TR TOP REGISTER <br />TS TIP SPEED <br />TV TURNING VANES <br />TX TOILET EXHAUST <br />TYP TYPICAL <br />UON UNLESS OTHERWISE NOTED <br />V VOLTS <br />VAV VARIABLE AIR VOLUME <br />RF RETURN FAN <br />RH RELATIVE HUMIDITY <br />ABBREVIATION DESCRIPTION <br />1. CONTRACTOR TO PROVIDE COMPLETE SEISMIC ANCHORAGE AND BRACING FOR ALL <br />MECHANICAL EQUIPMENT THAT IS DIRECTLY MOUNTED ON THE FLOOR OR ROOF AND ALL <br />MECHANICAL EQUIPMENT THAT IS SUSPENDED FROM THE FLOOR, WALL OR SUPPORTED <br />BY VIBRATION ISOLATORS TO RESIST A HORIZONTAL FORCE ACTING IN ANY DIRECTION <br />USING THE CRITERIA OUTLINED IN THE 2022 CALIFORNIA BUILDING CODE. PROVIDE <br />ANCHORAGE CALCULATION AND DETAILS CERTIFIED BY A STRUCTURAL ENGINEER <br />REGISTERED IN THE STATE OF CALIFORNIA. THE INSTALLATION SHALL BE SUBJECT TO <br />THE APPROVAL OF THE STRUCTURAL ENGINEER AND THE CITY OF SAN FRANCISCO <br />BUILDING AND FIRE DEPARTMENTS. <br />2. ALL PIPING, DUCTWORK AND CONDUIT CROSSING BUILDING SEISMIC SEPARATIONS SHALL <br />BE PROVIDED WITH APPROVED FLEXIBLE CONNECTORS. <br />GENERAL SEISMIC NOTES <br />ALL WORK SHALL COMPLY WITH THE REQUIREMENTS OF THE FOLLOWING: <br />PART 1 -2022 CALIFORNIA STANDARDS ADMINISTRATIVE CODE, TITLE 24 C.C.R <br />PART 2 -2022 CALIFORNIA BUILDING CODE (CBC) <br />PART 3 -2022 CALIFORNIA ELECTRICAL CODE, TITLE 24, C.C.R (WITH <br />NATIONAL ELECTRICAL CODE AND NATIONAL FIRE PROTECTION ASSOCIATION) <br />PART 4 -2022 CALIFORNIA MECHANICAL CODE <br />PART 5 -2022 CALIFORNIA PLUMBING CODE <br />PART 6 -2022 CALIFORNIA ENERGY CODE, TITLE 24 C.C.R <br />PART 11 -2022 CALIFORNIA GREEN BUILDING STANDARDS CODE <br />APPLICABLE CODES <br />PERIODIC SPECIAL INSPECTION IS REQUIRED FOR CONCRETE EXPANSION <br />ANCHORS, (IF APPLICABLE TO THE PROJECT). THE SPECIAL INSPECTOR SHALL <br />VERIFY ANCHOR TYPE, DIMENSIONS, HOLE DIMENSIONS, ANCHOR EMBEDMENT, <br />TIGHTENING TORQUE AND ADHERENCE TO THE MANUFACTURER'S PRINTED <br />INSTALLATION INSTRUCTIONS. <br />SPECIAL INSPECTION <br />1. NO CHANGES ARE BEING MADE TO THE BUILDING ENVELOPE. <br />2. NO ADDITIONAL COOLING/HEATING LOADS ARE BEING ADDED TO THE BUILDING HVAC <br />SYSTEMS. <br />3. ALL HVAC SYSTEMS SHALL MEET THE CONTROL REQUIREMENTS PER SECTION 110.2, <br />120.2 AND 140.4 OF THE 2022 E.E.S. <br />4. ALL PIPING AND DUCTWORK SHALL BE INSULATED CONSISTENT WITH THE <br />REQUIREMENTS OF SECTIONS 120.3, 120.4 AND 120.7 TITLE 24 ENERGY STANDARDS AND <br />CHAPTER 6 OF CMC. <br />5. ALL MECHANICAL CERTIFICATE OF ACCEPTANCE FORMS AND ALL RELATED <br />ACCEPTANCE DOCUMENTS SHALL BE SUBMITTED TO THE FIELD INSPECTOR DURING <br />CONSTRUCTION. CERTIFICATE OF OCCUPANCY WILL NOT BE ISSUED UNTIL THESE <br />FORMS ARE REVIEWED AND APPROVED. <br />6. INSULATION AND FLEXIBLE DUCT SHALL COMPLY WITH STATE FIRE MARSHAL CRITERIA <br />AND SHALL NOT EXCEED FLAME SPREAD OF 25 AND SMOKE DEVELOPED IF 50 PER <br />ASTM-84, NFPA-225 AND UL-723. <br />7. OUTSIDE AIR VENTILATION AND FILTRATION REQUIREMENTS SHALL BE PROVIDED PER <br />120.1(c) OF THE 2022 E.E.S. <br />8. DUCTWORK AND PLENUMS SHALL BE TO SEALED TO CLASS A. SEE 2022 CEC 120.4(B). <br />9. DUCT LEAKAGE TESTING SHALL BE PROVIDED PER 2022 CEC120.4(G) <br />10. OCCUPANT SENSOR VENTIALTION CONTROL DEVICES SHALL BE PROVIDED AS <br />REQUIRED BY 2022 CEC 120.1(d)5 <br />TITLE 24 NOTES <br />I VERIFY AS THE DESIGNER OF RECORD THE DRAWINGS UNDER MY CHARGE <br />DO NOT ADVERSELY IMPACT THE EXISTING BUILDING'S LIFE SAFETY SYSTEMS <br />NON-INFRINGEMENT STATEMENT <br />NRCC-MCH-E <br />2022 BUILDING ENERGY EFFICIENCY STANDARDS <br />TITLE 24 -APPLICABLE MECHANICAL FORMS <br />NEW ROOFTOP AC UNIT (RTU-1) AND NEW SPLIT SYSTEM HEAT PUMP UNIT (FCU-1 <br />/ HP-1) AND ASSOCIATED DUCTWORK DISTRIBUTION AND AIR OUTLETS ARE <br />BEING PROVIDED TO ACCOMMODATE THE NEW ARCHITECTURAL LAYOUT FOR <br />THE SPACE. A DUCTLESS SPLIT SYSTEM AC UNIT (CRU-1 AND ACCU-1) ARE ALSO <br />BEING PROVIDED FOR THE TELCO ROOM. <br />MECHANICAL SCOPE OF WORK DESCRIPTION <br />3 <br />Mechanical and Electrical Engineers <br />Lilker Associates <br />1001 Avenue of the Americas <br />New York, NY 10018 <br />tel 212.695.1000 <br />fax 212.695.1299 <br />www.lilker.com <br />Kenneth A. Gruskin AIA <br />No. Date Description <br />Consultant: <br />Checked By: <br />Drawn By: <br />Job Address: <br />Drawing Title: <br />Revision Issue: <br />Professional Seal: <br />Drawing Number: <br />2022 Gruskin Architecture + Design, P.C.c <br />This document and the ideas and designs incorporated <br />herein, as an instrument of professional service, is the <br />property of GRUSKIN ARCHITECTURE + DESIGN, P.C., <br />and is not to be used in whole or in part for any other <br />project without the written authorization of GRUSKIN <br />ARCHITECTURE + DESIGN, P.C. <br />North <br />Arrow: <br />Job Name and Number: <br />Date Issued For <br />All Rights Reserved <br />Client: <br />Landlord: <br />Permit: <br />Bid: <br />Construction: <br />0006261 <br />AR91629 <br />5421 <br />9613 <br />39209 <br />10635 <br />2537 <br />11016 <br />5734 <br />ARC 2596 <br />4674 <br />2666 <br />AI 09999 <br />2796 <br />0401 011223 <br />2572 <br />17680 <br />RA-015432-B <br />025528-1 NY <br />TX <br />VA <br />VT <br />MA <br />MT <br />RI <br />PA <br />NY <br />NJ <br />NH <br />MD <br />LA <br />ME <br />KS <br />FL <br />DE <br />CT <br />AZ <br />AL <br />C-1967WY <br />RA011075GA <br />AR10400066IN <br />C-29898CA <br />NM 004168 <br />ARC-400347CO <br />HI AR 11489 <br />PR 19965 <br />OR 4899 <br />SC 6834 <br />NC 9961 <br />13761OH <br />05713IA <br />WV 3727 <br />IL 001-019152 <br />UT 5881358-0301 <br />ID AR-984459 <br />1301052379MI <br />ARC100723DC <br />WI 9900-005MN44326 <br />A-3547NE <br />3811AR <br />5967KY 101374TN <br />MS 3860 <br />1666ND <br />A-2005029740MO <br />a4895OK <br />NV 5521 <br />WA 10344 <br />13167AK <br />SD 11532 <br />C: <br />\ <br />R <br />e <br />v <br />i <br />t <br /> <br />L <br />o <br />c <br />a <br />l <br /> <br />F <br />i <br />l <br />e <br />s <br />\ <br />2 <br />4 <br />0 <br />0 <br />1 <br />3 <br />0 <br />8 <br />_ <br />V <br />E <br />R <br />I <br />Z <br />O <br />N <br />_ <br />S <br />a <br />n <br />t <br />a <br /> <br />A <br />n <br />a <br />_ <br />C <br />A <br />_ <br />ME <br />C <br />H <br />A <br />N <br />I <br />C <br />A <br />L <br />_ <br />v <br />2 <br />3 <br />_ <br />r <br />t <br />r <br />o <br />v <br />a <br />t <br />o <br />T <br />7 <br />V <br />P <br />K <br />. <br />r <br />v <br />t <br />2023-0069 <br />Proposed <br />Store Design <br />for: VERIZON <br />3500 South Bristol Street <br />Suite 100 <br />Santa Ana, CA 92704 <br />3/15/24 <br />3/15/24 <br />4/5/24 <br />MECHANICAL NOTES, <br />SYMBOLS & <br />ABBREVIATIONS <br />M.0.2 <br />MB <br />KG <br />35 OF 81 <br />3 6-3-2024 City Comments <br />3500 S Bristol St Unit# 100 - <br />101119098, 20182666 & <br />401390437/11/2024