1. ENTIRE INSTALLATION SHALL COMPLY WITH ALL LOCAL AND STATE CODES,
<br />INCLUDING ENERGY CODES, AND ALL OTHER AUTHORITIES HAVING JURISDICTION.
<br />2. PROPER FIRE PROTECTION MEASURES, SATISFACTORY TO THE LOCAL FIRE
<br />DEPARTMENT, SHALL BE TAKEN WHEN WELDING OR CUTTING WITH TORCHES OR
<br />ELECTRIC ARC.
<br />3. CONTRACTOR SHALL SECURE AND PAY FOR ALL REQUIRED PERMITS AND
<br />APPROVALS. ALL REQUIRED SPECIAL AND CONTROLLED INSPECTIONS SHALL BE BY
<br />THIS CONTRACTOR.
<br />4. IT SHALL BE THE CONTRACTORS SOLE RESPONSIBILITY TO PROVIDE ALL REQUIRED
<br />DOCUMENTS, PAY ALL FEES AND TO SEPARATELY FILE AND OBTAIN ALL APPROVALS
<br />AND PERMITS REQUIRED FOR ALL WORK INVOLVED IN TEMPORARY HEATING
<br />SYSTEM(S) TO BE USED AT THE SITE. ALL WORK SHALL BE PROVIDED AND INSTALLED
<br />PER THE REQUIREMENTS OF THE NYC BUILDING CODE.
<br />5. PROVIDE SEISMIC BRACING AND ANCHORING OF MECHANICAL EQUIPMENT, PIPING,
<br />AND DUCTWORK IN ACCORDANCE WITH THE GOVERNING CODES. THE STRUCTURAL
<br />DESIGN AND APPLICATION OF SEISMIC RESTRAINTS SHALL MEET THE CODE CRITERIA
<br />LISTED "DESIGN CRITERIA". THE CONTRACTORS SHALL RETAIN AN INDEPENDENT
<br />PROFESSIONAL ENGINEER TO DESIGN SEISMIC RESTRAINTS, PREPARE INSTALLATION
<br />DETAILS, SUPERVISE INSTALLATION, AND CERTIFY THAT THE INSTALLATION MEETS
<br />THE CODE CRITERIA LISTED HEREIN. SIGNED AND SEALED INSTALLATION DETAILS
<br />AND CALCULATIONS SHALL BE SUBMITTED AS SHOP DRAWINGS.
<br />6. ALL SUPPORT SYSTEMS (SUPPORTS, HANGERS, ANCHORS, GUIDES, BRACING,
<br />FASTENERS, WELDS, ETC.) FOR EQUIPMENT AND SYSTEMS INSTALLED OR REVISED
<br />AS PART OF THIS CONTRACT SHALL BE DESIGNED, SELECTED AND INSTALLED BY THE
<br />CONTRACTOR TO RESIST ALL SEISMIC, WIND AND GRAVITY LOADS. UNDER CERTAIN
<br />CONDITIONS, THE APPLICABLE CODES REQUIRE THESE LOADS, OR A COMBINATION
<br />OF THESE LOADS, BE CONSIDERED AS "COINCIDENTAL". THE CONTRACTOR SHALL
<br />ALSO BE RESPONSIBLE FOR CONFIRMING THAT THE COMPONENT OF THE BUILDING
<br />STRUCTURE WHERE THESE SUPPORT SYSTEMS ARE ATTACHED IS ABLE TO RESIST
<br />THE DESIGN LOADS TRANSFERRED TO THIS BUILDING COMPONENT.
<br />7. ALL PENETRATIONS OF FLOORS (WHETHER OR NOT FIRE RESISTANCE RATED) AND
<br />ALL PENETRATIONS OF FIRE RATED WALLS AND FLOORS SHALL BE PROVIDED WITH A
<br />THROUGH-PENETRATION PROTECTION SYSTEM (FIRESTOPPING). EACH THROUGH-
<br />PENETRATION PROTECTION SYSTEM SHALL BE TESTED IN ACCORDANCE WITH ASTM
<br />E814 AND BE LISTED FOR THE TYPE OF FLOOR OR WALL ASSEMBLY PENETRATED AND
<br />THE TYPE OF PROTECTION SYSTEM.
<br />8. ALL AIR MOVING DEVICES, INCLUDING BUT NOT LIMITED TO AIR HANDLING UNITS, AIR
<br />CONDITIONING UNITS, AND UNIT VENTILATORS, MUST COMPLY WITH AMCA STANDARD
<br />210 AND ASHRAE STANDARD 62.1-2007.
<br />9. DRAWINGS ARE INTENDED TO SHOW THE PROPER SIZE AND GENERAL LOCATIONS OF
<br />THE EQUIPMENT, PIPING, DUCTWORK, ETC. DRAWINGS ARE DIAGRAMMATIC AND
<br />INDICATE GENERAL ARRANGEMENT OF SYSTEMS AND WORK INCLUDED IN CONTRACT.
<br />DEVIATIONS FROM LAYOUT SHOWN MUST BE APPROVED BY THE ARCHITECT.
<br />10. SHOP DRAWINGS SHALL BE PREPARED WITH COMPLETE DIMENSIONAL INFORMATION,
<br />INCLUDING COORDINATES TO BRANCH DUCT AND DIFFUSERS STUBS. ELEVATIONS TO
<br />THE UNDERSIDE OF DUCTS, SHALL BE CLEARLY INDICATED ON THE DRAWING
<br />SUBMITTED AND SHALL BE CAREFULLY CHECKED FOR CONFORMANCE WITH CEILING
<br />HEIGHT REQUIREMENTS. ALL CONFLICTS MUST BE FLAGGED ON THE SHOP
<br />DRAWINGS.
<br />11. THE SHEET METAL SHOP DRAWINGS SHALL INDICATE ALL HUNG CEILING STARTING
<br />POINTS, ELEVATIONS AND BREAK LINES. WHERE PIPING, LIGHTS AND DUCTWORK
<br />CONFLICTS; DUCTWORK SHALL BE SET UP OR DOWN.
<br />12. SEE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR CONSTRUCTION PHASING
<br />REQUIREMENTS.
<br />13. CONTRACTOR SHALL COORDINATE HIS WORK WITH THE WORK OF ALL OTHER
<br />TRADES.
<br />14. CONTRACTOR SHALL COORDINATE WITH ALL ARCHITECTURAL DRAWINGS.
<br />15. CONTRACTOR IS RESPONSIBLE TO COORDINATE AND INCLUDE IN HIS BID THE
<br />RELOCATION OF ALL PIPING, DUCTWORK, HANGERS, CONDUITS, ETC. REQUIRED TO
<br />INSTALL NEW EQUIPMENT, PIPING, DUCTWORK, ETC.
<br />16. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING OF WALLS,
<br />CEILINGS, ROOFS AND FLOORS REQUIRED AS A RESULT OF HIS WORK.
<br />17. DUCTWORK AND PIPING LAYOUTS ARE SCHEMATIC DIAGRAMS AND ARE INTENDED TO
<br />SHOW GENERAL ARRANGEMENT, SIZE AND CAPACITY AND DO NOT NECESSARILY
<br />INDICATE WHICH PIPE OR DUCT IS ABOVE OR BELOW THE OTHER. ALL OFFSETS ARE
<br />NOT NECESSARILY SHOWN. CONTRACTOR SHALL ARRANGE AND COORDINATE THE
<br />WORK, FURNISH NECESSARY OFFSETS, VALVES, VENTS AND FITTINGS TO AVOID
<br />CONFLICT WITH OTHER MECHANICAL AND ELECTRICAL SERVICES AND STRUCTURAL
<br />AND ARCHITECTURAL ELEMENTS WITHOUT ADDITIONAL COST TO THE OWNER. IF
<br />AREAS OF CONFLICT ARE ENCOUNTERED, THE ARCHITECT SHALL BE NOTIFIED AND
<br />CONTRACTOR'S RECOMMENDATIONS SHALL BE SUBMITTED TO THE ARCHITECT FOR
<br />APPROVAL BEFORE WORK HAS BEGUN.
<br />18. CONTRACTOR SHALL PROVIDE ALL NECESSARY MISCELLANEOUS STEEL FOR THE
<br />SUPPORT OF ALL EQUIPMENT, PIPING, CONDUIT AND DUCTWORK. SUSPENDED
<br />FROM SLAB, STEEL, WALL, OR TRUSSWORK.
<br />19. UNLESS OTHERWISE NOTED ON THE DRAWINGS, ALL MECHANICAL EQUIPMENT
<br />SHALL BE MOUNTED ON VIBRATION ISOLATORS TO PREVENT THE TRANSMISSION
<br />OF SOUND TO THE BUILDING STRUCTURE. VIBRATION ISOLATORS SHALL BE IN
<br />ACCORDANCE WITH THE SPECIFICATIONS AND SHALL BE BASED ON ACTUAL
<br />WEIGHT DISTRIBUTION OF THE EQUIPMENT FURNISHED. DEFLECTIONS SHALL BE
<br />AS NOTED ON THE EQUIPMENT SHOP DRAWING SUBMITTALS.
<br />20. CONTRACTOR SHALL ENSURE THAT ALL MECHANICAL DEVICES ARE INSTALLED IN
<br />A LOCATION WHICH AFFORDS ACCESSIBILITY FOR MAINTENANCE AND REPAIR.
<br />COORDINATE INSTALLATION AMONG ALL TRADES TO AVOID INTERFERENCES, AND
<br />LOCATE EQUIPMENT TO PROVIDE CLEARANCES WHICH EXCEED THOSE
<br />RECOMMENDED BY THE EQUIPMENT MANUFACTURER. PRIOR TO PROJECT
<br />COMPLETION, REPRESENTATIVES OF THE OWNER WILL REVIEW EACH
<br />INSTALLATION AND WILL DIRECT CHANGES WHENEVER ACCESS OR
<br />SERVICEABILITY IS, IN THEIR OPINION, UNACCEPTABLE.
<br />21. ALL MECHANICAL CONTROLS (THERMOSTATS, SENSORS, ETC.) SHALL BE
<br />INSTALLED AT A HEIGHT OF 5'-0" ABOVE FLOOR. COORDINATE EXACT LOCATION
<br />AND MOUNTING HEIGHT WITH ARCHITECT PRIOR TO INSTALLATION.
<br />22. OWNER PROVIDED EQUIPMENT SHALL BE RECEIVED AND INSTALLED BY THE
<br />MECHANICAL CONTRACTOR. ALL COST ASSOCIATED WITH RIGGING, RECEIVING
<br />AND STORAGE SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.
<br />23. ALL ACCESS DOORS IN FINISHED WALLS AND CEILINGS SHALL BE SUPPLIED BY
<br />THIS CONTRACTOR AND SHALL BE FRAMELESS TYPE SUITABLE FOR THE
<br />CONSTRUCTION TYPE INDICATED ON THE ARCHITECTURAL DRAWINGS.
<br />COORDINATE ALL LOCATIONS OF ACCESS DOORS WITH ARCHITECTURAL
<br />DRAWINGS. LOCATE VALVES SO AS TO BE WITHIN ONE (1) FOOT OF AN ACCESS
<br />DOOR.
<br />24. EXACT LOCATION OF DIFFUSERS, GRILLES AND REGISTERS TO BE COORDINATED
<br />WITH ARCHITECTURAL PLANS.
<br />25. CONTRACTOR SHALL BE RESPONSIBLE FOR BALANCING OF AIR QUANTITIES AT
<br />ALL AIR CONDITIONING OUTLETS AND INLETS.
<br />26. HVAC CONTRACTOR SHALL CHANGE FILTERS IN ALL AIR HANDLING UNITS PRIOR
<br />TO DELIVERY OF SYSTEM TO OWNER.
<br />27. DUCT-MOUNTED SMOKE DETECTORS SHALL BE PROVIDED IN THE SUPPLY AND
<br />RETURN DUCTS OF ALL AIR HANDLING UNITS WITH A CAPACITY GREATER THAN
<br />2,000 CFM. WHERE A RETURN AIR PLENUM IS SHARED BETWEEN MULTIPLE AIR
<br />HANDLING UNITS TOTALING GREATER THAN 2,000 CFM, A DUCT SMOKE DETECTOR
<br />SHALL BE PROVIDED IN THE RETURN DUCT OF EACH AIR HANDLING UNIT.
<br />28. ALL ROTATING HVAC EQUIPMENT SHALL BE SUPPORTED OR SUSPENDED ON
<br />VIBRATION ISOLATORS. PROVIDE FLEXIBLE CONNECTORS AT ALL DUCT AND PIPE
<br />CONNECTIONS TO ROTATING EQUIPMENT.
<br />29. DUCT SIZES SHOWN ARE CLEAR INSIDE DIMENSIONS.
<br />30. PROVIDE DOUBLE THICKNESS TURNING VANES IN ALL SQUARE ELBOWS.
<br />31. PROVIDE VOLUME DAMPER ON EACH BRANCH TAKE OFF FROM DUCT MAIN, AND
<br />ON EACH DIFFUSER TAKE OFF FROM BRANCH DUCT OR MAIN.
<br />32. PROVIDE AND INSTALL COMBINATION FIRE AND SMOKE DAMPERS AND ACCESS
<br />DOORS IN ALL DUCTWORK PENETRATING FIRE RATED WALLS (2 HOURS OR MORE).
<br />FIRE DAMPERS AND ACCESS DOORS SHALL BE PROVIDED AND INSTALLED IN ALL
<br />DUCTWORK PENETRATING FIRE RATED WALLS 1-1/2 HOUR OR LESS. ALL ACCESS
<br />DOORS SHALL BE A MINIMUM OF 12"X 12" UNLESS OTHERWISE NOTED.
<br />33. WHERE PIPING CONNECTIONS FOR THE EQUIPMENT SUCH AS PUMPS, AC UNITS,
<br />COILS ETC. DIFFER FROM THE LINE SIZE, IT SHALL BE THE RESPONSIBILITY OF
<br />THE MECHANICAL CONTRACTOR TO FURNISH AND INSTALL THE NECESSARY
<br />REDUCERS OR EXPANDER FITTING TO ENABLE CONNECTION BETWEEN THE
<br />PIPING SYSTEM AND THE EQUIPMENT.
<br />34. PROVIDE CAPPED MANUAL AIR VENTS AT ALL HYDRONIC SYSTEM HIGH POINTS,
<br />AND BEFORE ALL VERTICAL DROPS IN DIRECTION OF FLOW, PROVIDE CAPPED
<br />HOSE DRAINS AT ALL SYSTEM LOW POINTS, SO AS TO ENABLE THE COMPLETE
<br />DOWN-DRAIN OF THE SYSTEM.
<br />35. ALL CONDENSATE DRAIN LINES SHALL COMPLY WITH N.S.P.C. 9.9.2 (AIR
<br />CONDITIONING CONDENSATE POINT OF DISCHARGE). NO PLASTIC PIPING SHALL
<br />BE INSTALLED IN PLENUM CEILING.
<br />36. MINIMUM SIZE OF ALL CONDENSATE DRAIN PIPING SHALL BE 3/4" UNLESS
<br />OTHERWISE NOTED. ALL DRAIN PIPING SHALL BE PITCHED IN THE DIRECTION OF
<br />FLOW, MIN. 1" IN 40 FT.
<br />37. PROVIDE SHUT-OFF VALVES AT ALL BRANCH PIPING CONNECTIONS TO MAINS.
<br />38. INSTALL ALL DIELECTRIC UNIONS IN A MANNER WHICH MAKES THEM READILY
<br />ACCESSIBLE FOR FUTURE REPAIR OR REPLACEMENT. BRASS VALVES, FITTINGS,
<br />ETC. ARE NOT ACCEPTABLE IN LIEU OF DIELECTRIC UNIONS.
<br />GENERAL MECHANICAL NOTES
<br />AD
<br />POSITIVE PRESSURE DUCT (SUPPLY) UP
<br />POSITIVE PRESSURE DUCT (SUPPLY) DOWN
<br />SLOPING RISE IN DUCTWORK
<br />SLOPING DROP IN DUCTWORK
<br />ACCESS DOOR IN DUCT
<br />18x12
<br />18x12
<br />18"ø
<br />18"ø
<br />FC
<br />FC
<br />DUCT SIZE (CLEAR INSIDE DIMENSION)
<br />FIRST FIGURE INDICATES PLAN DIMENSION
<br />ROUND DUCT DIAMETER SIZE
<br />ACOUSTIC LINING IN DUCT
<br />(SIZE NOTED INDICATES INSIDE DIMENSION)
<br />FLEXIBLE CONNECTION
<br />VOLUME DAMPER
<br />DUCTWORK SYMBOLS
<br />R
<br />D
<br />D
<br />SQUARE DUCT ELBOW WITH TURNING VANE
<br />RADIUS ELBOW
<br />DUCT SPLIT
<br />BRANCH TAKE-OFF WITH VOLUME DAMPER
<br />DUCT SMOKE DETECTOR
<br />SUPPLY AIR CEILING DIFFUSER
<br />4 WAY, 3 WAY, 2 WAY, 1 WAY
<br />NEGATIVE PRESSURE DUCT (RETURN OR EXHAUST)
<br />UP
<br />NEGATIVE PRESSURE DUCT (RETURN OR EXHAUST)
<br />DOWN
<br />ADJUSTABLE SETPOINT CONTROLLER
<br />'BUTTON SENSOR' TEMPERATURE SENSORS
<br />T
<br />MISCELLANEOUS SYMBOLS
<br />X X X X
<br />EXISTING WORK TO BE REMOVED
<br />EXISTING WORK TO REMAIN
<br />NEW WORK
<br />CONNECT NEW WORK TO EXISTING
<br />DISCONNECT EXISTING WORK
<br />REVISION NUMBER?
<br />MECHANICAL ABBREVIATIONS
<br />°C DEGREES CELSIUS
<br />°F DEGREES FAHRENHEIT
<br />A AMPERES
<br />AC AIR CONDITIONING
<br />ACCU AIR CONDITIONING CONDENSING UNIT
<br />AD ACCESS DOOR
<br />AFF ABOVE FINISED FLOOR
<br />AHU AIR HANDLING UNIT
<br />AL ACOUSTIC LINING
<br />AP ACCESS PANEL
<br />ATC AUTOMATIC TEMPERATURE CONTROL
<br />B BOILER
<br />BG BOTTOM GRILLE
<br />BHP BRAKE HORSEPOWER
<br />BMS BUILDING MONITORING SYSTEM
<br />BR BOTTOM REGISTER
<br />BTU BRITISH THERMAL UNIT
<br />BTUH BTU PER HOUR
<br />CD CEILING DIFFUSER
<br />CFM CUBIC FEET PER MINUTE
<br />CG CEILING GRILLE
<br />CLG CEILING
<br />CO CLEAN OUT OR CARBON MONOXIDE
<br />COD CABLE OPERATED DAMPER
<br />COMPR COMPRESSOR
<br />COND CONDENSATE
<br />CR CEILING REGISTER
<br />CU IN CUBIC INCHES
<br />CU FT CUBIC FEET
<br />CV CONSTANT VOLUME
<br />D DROP
<br />DB DRY BULB
<br />DDC DIRECT DIGITAL CONTROL
<br />DN DOWN
<br />DWG DRAWING
<br />DX DIRECT EXPANSION
<br />EA EXHAUST AIR
<br />EAT ENTERING AIR TEMPERATURE
<br />EDB ENTERING DRY BULB
<br />EF EXHAUST FAN
<br />EL ELEVATION
<br />ELEC ELECTRIC
<br />EQ EQUAL
<br />ER EXISTING TO BE RELOCATED
<br />EWB ENTERING WET BULB
<br />EWT ENTERING WATER TEMPERATURE
<br />EXH EXHAUST
<br />EXP EXPANSION
<br />F FILTER
<br />FA FREE AREA (SQ.FT.)
<br />FC FLEXIBLE CONNECTION
<br />FD FIRE DAMPER
<br />FF FINAL FILTER
<br />FLA FULL LOAD AMPERES
<br />FPM FEET PER MINUTE
<br />FPS FEET PER SECOND
<br />FT FEET
<br />FV FACE VELOCITY
<br />ABBREVIATION DESCRIPTION
<br />VFD VARIABLE FREQUENCY DRIVE
<br />VENT VENTILATION AIR
<br />W/WITH
<br />W/O WITHOUT
<br />W WIDTH
<br />WB WET BULB
<br />WMS WIRE MESH SCREEN
<br />ABBREVIATION DESCRIPTION
<br />HP HORSEPOWER
<br />HR HOUR
<br />HZ FREQUENCY IN HERTZ
<br />IN INCH OR INCHES
<br />KW KILOWATT
<br />L LENGTH
<br />LAT LEAVING AIR TEMPERATURE
<br />LBS POUNDS
<br />LDB LEAVING DRY BULB TEMPERATURE
<br />L. FT. LINEAR FOOT
<br />LWB LEAVING WET BULB TEMPERTAURE
<br />MAX MAXIMUM
<br />MBH THOUSAND BTU PER HOUR
<br />MHP MOTOR HORSEPOWER
<br />MIN MINIMUM
<br />N NECK
<br />N.C. NORMALLY CLOSED
<br />NIC NOT IN CONTRACT
<br />N.O. NORMALLY OPEN
<br />NO. NUMBERS
<br />NTS NOT TO SCALE
<br />OA OUTSIDE AIR
<br />OAI OUTSIDE AIR INTAKE
<br />OBD OPPOSED BLADE DAMPER
<br />OD OUTSIDE DIAMETER
<br />OV OUTLET VELOCITY
<br />PD PRESSUDE DROP
<br />PHC PREHEAT COIL
<br />PSI POUNDS PER SQUARE INCH
<br />PSIA PSI ABSOLUTE
<br />PSIG PSI GAUGE
<br />R RISE
<br />RA RETURN AIR
<br />RAD RADIATION
<br />RE RELOCATE EXISTING
<br />REFR REFRIGERANT
<br />RM ROOM
<br />RPM REVOLUTIONS PER MINUTE
<br />RR RETURN REGISTER
<br />SA SUPPLY AIR
<br />SF SUPPLY FAN
<br />SG SUPPLY GRILLE
<br />SP STATIC PRESSURE
<br />SPEC SPECIFICATION
<br />SS STAINLESS STEEL
<br />TD TRANSFER DUCT
<br />TEMP TEMPERATURE
<br />TF TRANSFER FAN
<br />TG TOP GRILLE
<br />TR TOP REGISTER
<br />TS TIP SPEED
<br />TV TURNING VANES
<br />TX TOILET EXHAUST
<br />TYP TYPICAL
<br />UON UNLESS OTHERWISE NOTED
<br />V VOLTS
<br />VAV VARIABLE AIR VOLUME
<br />RF RETURN FAN
<br />RH RELATIVE HUMIDITY
<br />ABBREVIATION DESCRIPTION
<br />1. CONTRACTOR TO PROVIDE COMPLETE SEISMIC ANCHORAGE AND BRACING FOR ALL
<br />MECHANICAL EQUIPMENT THAT IS DIRECTLY MOUNTED ON THE FLOOR OR ROOF AND ALL
<br />MECHANICAL EQUIPMENT THAT IS SUSPENDED FROM THE FLOOR, WALL OR SUPPORTED
<br />BY VIBRATION ISOLATORS TO RESIST A HORIZONTAL FORCE ACTING IN ANY DIRECTION
<br />USING THE CRITERIA OUTLINED IN THE 2022 CALIFORNIA BUILDING CODE. PROVIDE
<br />ANCHORAGE CALCULATION AND DETAILS CERTIFIED BY A STRUCTURAL ENGINEER
<br />REGISTERED IN THE STATE OF CALIFORNIA. THE INSTALLATION SHALL BE SUBJECT TO
<br />THE APPROVAL OF THE STRUCTURAL ENGINEER AND THE CITY OF SAN FRANCISCO
<br />BUILDING AND FIRE DEPARTMENTS.
<br />2. ALL PIPING, DUCTWORK AND CONDUIT CROSSING BUILDING SEISMIC SEPARATIONS SHALL
<br />BE PROVIDED WITH APPROVED FLEXIBLE CONNECTORS.
<br />GENERAL SEISMIC NOTES
<br />ALL WORK SHALL COMPLY WITH THE REQUIREMENTS OF THE FOLLOWING:
<br />PART 1 -2022 CALIFORNIA STANDARDS ADMINISTRATIVE CODE, TITLE 24 C.C.R
<br />PART 2 -2022 CALIFORNIA BUILDING CODE (CBC)
<br />PART 3 -2022 CALIFORNIA ELECTRICAL CODE, TITLE 24, C.C.R (WITH
<br />NATIONAL ELECTRICAL CODE AND NATIONAL FIRE PROTECTION ASSOCIATION)
<br />PART 4 -2022 CALIFORNIA MECHANICAL CODE
<br />PART 5 -2022 CALIFORNIA PLUMBING CODE
<br />PART 6 -2022 CALIFORNIA ENERGY CODE, TITLE 24 C.C.R
<br />PART 11 -2022 CALIFORNIA GREEN BUILDING STANDARDS CODE
<br />APPLICABLE CODES
<br />PERIODIC SPECIAL INSPECTION IS REQUIRED FOR CONCRETE EXPANSION
<br />ANCHORS, (IF APPLICABLE TO THE PROJECT). THE SPECIAL INSPECTOR SHALL
<br />VERIFY ANCHOR TYPE, DIMENSIONS, HOLE DIMENSIONS, ANCHOR EMBEDMENT,
<br />TIGHTENING TORQUE AND ADHERENCE TO THE MANUFACTURER'S PRINTED
<br />INSTALLATION INSTRUCTIONS.
<br />SPECIAL INSPECTION
<br />1. NO CHANGES ARE BEING MADE TO THE BUILDING ENVELOPE.
<br />2. NO ADDITIONAL COOLING/HEATING LOADS ARE BEING ADDED TO THE BUILDING HVAC
<br />SYSTEMS.
<br />3. ALL HVAC SYSTEMS SHALL MEET THE CONTROL REQUIREMENTS PER SECTION 110.2,
<br />120.2 AND 140.4 OF THE 2022 E.E.S.
<br />4. ALL PIPING AND DUCTWORK SHALL BE INSULATED CONSISTENT WITH THE
<br />REQUIREMENTS OF SECTIONS 120.3, 120.4 AND 120.7 TITLE 24 ENERGY STANDARDS AND
<br />CHAPTER 6 OF CMC.
<br />5. ALL MECHANICAL CERTIFICATE OF ACCEPTANCE FORMS AND ALL RELATED
<br />ACCEPTANCE DOCUMENTS SHALL BE SUBMITTED TO THE FIELD INSPECTOR DURING
<br />CONSTRUCTION. CERTIFICATE OF OCCUPANCY WILL NOT BE ISSUED UNTIL THESE
<br />FORMS ARE REVIEWED AND APPROVED.
<br />6. INSULATION AND FLEXIBLE DUCT SHALL COMPLY WITH STATE FIRE MARSHAL CRITERIA
<br />AND SHALL NOT EXCEED FLAME SPREAD OF 25 AND SMOKE DEVELOPED IF 50 PER
<br />ASTM-84, NFPA-225 AND UL-723.
<br />7. OUTSIDE AIR VENTILATION AND FILTRATION REQUIREMENTS SHALL BE PROVIDED PER
<br />120.1(c) OF THE 2022 E.E.S.
<br />8. DUCTWORK AND PLENUMS SHALL BE TO SEALED TO CLASS A. SEE 2022 CEC 120.4(B).
<br />9. DUCT LEAKAGE TESTING SHALL BE PROVIDED PER 2022 CEC120.4(G)
<br />10. OCCUPANT SENSOR VENTIALTION CONTROL DEVICES SHALL BE PROVIDED AS
<br />REQUIRED BY 2022 CEC 120.1(d)5
<br />TITLE 24 NOTES
<br />I VERIFY AS THE DESIGNER OF RECORD THE DRAWINGS UNDER MY CHARGE
<br />DO NOT ADVERSELY IMPACT THE EXISTING BUILDING'S LIFE SAFETY SYSTEMS
<br />NON-INFRINGEMENT STATEMENT
<br />NRCC-MCH-E
<br />2022 BUILDING ENERGY EFFICIENCY STANDARDS
<br />TITLE 24 -APPLICABLE MECHANICAL FORMS
<br />NEW ROOFTOP AC UNIT (RTU-1) AND NEW SPLIT SYSTEM HEAT PUMP UNIT (FCU-1
<br />/ HP-1) AND ASSOCIATED DUCTWORK DISTRIBUTION AND AIR OUTLETS ARE
<br />BEING PROVIDED TO ACCOMMODATE THE NEW ARCHITECTURAL LAYOUT FOR
<br />THE SPACE. A DUCTLESS SPLIT SYSTEM AC UNIT (CRU-1 AND ACCU-1) ARE ALSO
<br />BEING PROVIDED FOR THE TELCO ROOM.
<br />MECHANICAL SCOPE OF WORK DESCRIPTION
<br />3
<br />Mechanical and Electrical Engineers
<br />Lilker Associates
<br />1001 Avenue of the Americas
<br />New York, NY 10018
<br />tel 212.695.1000
<br />fax 212.695.1299
<br />www.lilker.com
<br />Kenneth A. Gruskin AIA
<br />No. Date Description
<br />Consultant:
<br />Checked By:
<br />Drawn By:
<br />Job Address:
<br />Drawing Title:
<br />Revision Issue:
<br />Professional Seal:
<br />Drawing Number:
<br />2022 Gruskin Architecture + Design, P.C.c
<br />This document and the ideas and designs incorporated
<br />herein, as an instrument of professional service, is the
<br />property of GRUSKIN ARCHITECTURE + DESIGN, P.C.,
<br />and is not to be used in whole or in part for any other
<br />project without the written authorization of GRUSKIN
<br />ARCHITECTURE + DESIGN, P.C.
<br />North
<br />Arrow:
<br />Job Name and Number:
<br />Date Issued For
<br />All Rights Reserved
<br />Client:
<br />Landlord:
<br />Permit:
<br />Bid:
<br />Construction:
<br />0006261
<br />AR91629
<br />5421
<br />9613
<br />39209
<br />10635
<br />2537
<br />11016
<br />5734
<br />ARC 2596
<br />4674
<br />2666
<br />AI 09999
<br />2796
<br />0401 011223
<br />2572
<br />17680
<br />RA-015432-B
<br />025528-1 NY
<br />TX
<br />VA
<br />VT
<br />MA
<br />MT
<br />RI
<br />PA
<br />NY
<br />NJ
<br />NH
<br />MD
<br />LA
<br />ME
<br />KS
<br />FL
<br />DE
<br />CT
<br />AZ
<br />AL
<br />C-1967WY
<br />RA011075GA
<br />AR10400066IN
<br />C-29898CA
<br />NM 004168
<br />ARC-400347CO
<br />HI AR 11489
<br />PR 19965
<br />OR 4899
<br />SC 6834
<br />NC 9961
<br />13761OH
<br />05713IA
<br />WV 3727
<br />IL 001-019152
<br />UT 5881358-0301
<br />ID AR-984459
<br />1301052379MI
<br />ARC100723DC
<br />WI 9900-005MN44326
<br />A-3547NE
<br />3811AR
<br />5967KY 101374TN
<br />MS 3860
<br />1666ND
<br />A-2005029740MO
<br />a4895OK
<br />NV 5521
<br />WA 10344
<br />13167AK
<br />SD 11532
<br />C:
<br />\
<br />R
<br />e
<br />v
<br />i
<br />t
<br />
<br />L
<br />o
<br />c
<br />a
<br />l
<br />
<br />F
<br />i
<br />l
<br />e
<br />s
<br />\
<br />2
<br />4
<br />0
<br />0
<br />1
<br />3
<br />0
<br />8
<br />_
<br />V
<br />E
<br />R
<br />I
<br />Z
<br />O
<br />N
<br />_
<br />S
<br />a
<br />n
<br />t
<br />a
<br />
<br />A
<br />n
<br />a
<br />_
<br />C
<br />A
<br />_
<br />ME
<br />C
<br />H
<br />A
<br />N
<br />I
<br />C
<br />A
<br />L
<br />_
<br />v
<br />2
<br />3
<br />_
<br />r
<br />t
<br />r
<br />o
<br />v
<br />a
<br />t
<br />o
<br />T
<br />7
<br />V
<br />P
<br />K
<br />.
<br />r
<br />v
<br />t
<br />2023-0069
<br />Proposed
<br />Store Design
<br />for: VERIZON
<br />3500 South Bristol Street
<br />Suite 100
<br />Santa Ana, CA 92704
<br />3/15/24
<br />3/15/24
<br />4/5/24
<br />MECHANICAL NOTES,
<br />SYMBOLS &
<br />ABBREVIATIONS
<br />M.0.2
<br />MB
<br />KG
<br />35 OF 81